AC EDGE
Specifications
Model AC120V60DF 6/6
P/N 1101-1188
©2016 Transtector. All rights reserved.
1
Table of Contents
Introduction ................................................................................................................................................... 3 Features and Benefits ................................................................................................................................... 3 Grounding...................................................................................................................................................... 3 Specifications ................................................................................................................................................ 4 Dimensions ................................................................................................................................................... 5 Kit Contents ................................................................................................................................................... 6 Electrical Features ........................................................................................................................................ 6 Mechanical Features ..................................................................................................................................... 7 ©2016 Transtector. All rights reserved.
2
Introduction
The AC Edge 120 is a 2RU rack mount AC distribution solution to overcome discrete electrical conduit
and panel challenges. Designed for mission critical electronic storage and backup systems, the AC
power distribution panel is scalable for up to twelve dedicated circuits (1 A to 15 A) using 120 Vac per
phase (60 A maximum) distribution.
Features and Benefits
Designed for demanding usage, the AC Edge offers best in class current handling and surge performance
in a 2RU rack mount environment.

High power, 60 A per phase panel supports demanding loads.

Independent Neutral connections allow for a truly redundant power distribution unit.

Robust metal chassis with passive venting keeps temperature rise to a minimum .

Replaceable silicon avalanche suppression diode (SASD) surge protection modules on each
phase keep loads protected from damaging transient over-voltage conditions.

Wide spacing between outlet connections (L2 only) accommodates oversized pluggable
transformers.

IEC 320-C14 test terminals allow for a quick, low-power connection to reduce overall system test
setup time.
Grounding
Unit shall be properly grounded per the installation instructions. Failure to do so will result in voided
warranty and possible equipment damage.
©2016 Transtector. All rights reserved.
3
Specifications
AC EDGE 120
Part Number
1101-1188
Electrical
Feeds
Maximum Continuous Operating Voltage
Input Rating
Output Positions
Maximum Output Protection Device
Maximum Neutral Current Rating
Surge Protection
Voltage Protection Level (500A/6kV)
Duty Cycle Test
Operating Voltage
Input Terminals
Output Terminals
Test Terminals
Status Indication LEDs (each line)
Remote Status Indication
Alarm Terminals
2, 120 Vac (Independent Neutrals)
138 Vac (per phase)
60 A Max per phase (14.4 kVA total)
6 per phase (12 total, A+B)
Removable 1 A to 15 A, UL489 Listed Circuit Breakers
60 A per phase
3kA/6kV 8/20 µs per phase
<450 V
IEEE C62.41, 6kV/200A, 100 kHz ringwave
110-130 Vac 50/60 Hz
Cage-clamp connection, supports #20 to #2 AWG feeds
12X NEMA 5-15R Outlets
2X IEC 320-C14 Inlets
PWR (GRN = power on), FA (RED = tripped breaker),
SURGE (GRN = normal, RED = replace)
Power, Fuse, and Surge Alarm for each line, Dry Form C
Contact (1 A, 138 Vac/Vdc max rated)
Single 15-socket, high density, D-type connector
Mechanical
Mounting
Material
Finish
Weight
Dimensions (HxWxD)
19” or 23” rack in 2RU with adjustable ears
Cold-rolled steel – 18 gauge
Black powder coated front panel and zinc plated chassis
17lbs (approx.)
3.47” x 19.00” x 13.48” (88mm x 483mm x 342mm)
Environmental
Operating Temperature
Flammability
14ºF to 131ºF (-10ºC to +55ºC)
UL94 V-0
Installation
Mounting
Installation Hardware
Grounding
19” or 23” rack in 2RU with adjustable ears
Provided
2X, 1/4-20 studs on 5/8” centers
Regulatory Compliance
UL Certification
UL/cUL Listed, E211453
Warranty
Warranty
1 year
©2016 Transtector. All rights reserved.
4
Dimensions
©2016 Transtector. All rights reserved.
5
Kit Contents
Part Number
Rack Mount Hardware
Designation Card
Quick Installation Guide
Installation Manual
AC EDGE 120
1101-1188
Yes (19” brackets)
Yes
Yes
PDF download only (visit www.transtector.com)
Electrical Features
AC Edge features independent neutrals for each phase allowing for fully redundant system integration. At
the power source(s), install one, single pole, high inrush circuit breakers per phase (75 A max each,
derated 80%), or a 2-pole breaker with identified handle tie following proper wire sizing and conduit
guidelines (per NFPA 70 2011 Article 220, Chapter 9 and local/national codes).
Refer to installation manual found on www.transtector.com for more detailed information.
©2016 Transtector. All rights reserved.
6
Mechanical Features
Widely spaced outlets yield ample room for oversized power transformers (“wall-warts”) to be placed side
by side.
©2016 Transtector. All rights reserved.
7
Transtector Systems, Inc.
10701 Airport Drive, Hayden ID 83835
(TF) 800.882.9110 | (FX) 208.762.6034
DRAWN
DATE
TREVOR TOLLEFSOL
01/29/2015
CHECKED
DATE
DPM
1/28/2016
ENGRG APPD
DATE
MPD
2/2/2016
PROJ APPD
DATE
DWR
2/2/2016
APPROVED
DATE
DLR
2/2/2016
Notice:
The information and design in this document is the property of Transtector
Systems. All rights reserved.
1101-1188-C REV C
©2016 Transtector. All rights reserved.
8