4.5 kWMax. 9.0 kWMax.

advertisement
5 kVA
Highly Reliable Online UPS
Input / Output AC [Single-phase 2-wire]
V
Output capacity
5
200, 208, 220, 230, 240
A11J
kVA (kW)
(9.0)
Battery backup time
Load power factor = 0.8
Only 5 kVA type (A11J502A002TU) is UL certified and CE marking.
5
Network Support
ネットワーク対応
19インチラック
対応
常時インバータ
給電
19-inch Rack Mountable
ネットワーク対応
19インチラック
対応
常時インバータ
給電
Mounting examples
Vertical mounting or 19-inch rack mounting.
Optional rack support rails are available.
The orientation of the front LCD display panel
is changeable.
10
(4.5)
10 kVA
min.
3U size
(130 mm)
Battery selection options *
15 25 35 45
min.
min.
min.
min.
30 60 180
min.
min.
min.
* There are some restrictions on the combination with the installation method and output capacity.
1 High Reliability
The compact 3U size of the 5 kVA UPS unit
allows to mount it in an EIA 19-inch rack.
2 High Power Factor
Periodically performs battery self-tests, ensuring it maintains
0.9 load power factor enables the unit to supply power to high
the ability to operate in outages.
power factor devices such as servers.
Battery tests do not cause momentary power outages.
* You can select the frequency of the battery test.
Start operation test
Normal operation
Periodic
check
Check battery power supply
Output capacity of
5 kVA
10 kVA
4.5 kW Max.
9.0 kW Max.
3 Wide Input Voltage Range
When the load factor is less than 70%, it can operate with -40%
to +15% of the nominal.
Return to normal operation
It reduces the use of batteries. Results in longer battery life
and high reliability.
4 Easy Maintenance
Maintenance can be easily performed by replacing the
battery or inverter from the front.
Battery can be replaced even during operation.
External View
5 kVA front
10 kVA back
InverterON / STAND BY Switch
Input LED
Optional Card Interface
Unit-to-Unit Interface
Backup LED
PC Interface
Warning LED
Input LED
INPUT
UIF A1
UIF A2
UIF A1
UIF A2
UIF B1
UIF B2
UIF B1
UIF B2
PC I/F
CARD I/F
OUTPUT
ALARM
LCD
Contact
Signal
Interface
Output LED
Alarm LED
MAIN
MCCB
Menu Operation Switch
Output LED
SIGNAL I/F
REMOTE/EPO
OPTION CARD
External
Control
Terminal
Main MCCB
InverterON / STAND BY Switch
EXT.
BATTERY
MAINTENANCE
MCCB
EXT.
BATTERY
MAINTENANCE
MCCB
You can change the orientation of the front LCD display panel.
Cooling Fan
ON
ON
OFF
OUTPUT B
MCCB
OUTPUT C,D
MCCB
OFF
OUTPUT A
MCCB
5 kVA back
Contact Signal Interface
Cooling Fan
Optional Card Interface
OUTPUT C
L
OUTPUT D
External Control Terminal
INPUT
N
OUTPUT A
E
INPUT
INPUT
OUTPUT
OUTPUT
U
OUTPUT
NEMA L6-20R
V
OUTPUT B
Optional Slot
I/O Terminal Block
Unit-to-Unit Interface
PC Interface
I/O Terminal Block
NEMA L6-30R
Network Options
Item
Model
Remarks
LAN interface card
PRLANIF003-US
This interface card allows UPS units to directly connect to LAN. It monitors and reports on power supply status, takes quick
action in case of a power failure and other malfunction, and informs the system administrator via E-mail on any power
problems. Support for SSH (Secure SHell).
Provides continuous monitoring and reporting of power conditions. Power problems can also be reported to the system
manager via e-mail.
PRLANIF005-US (Environmental monitoring function)
This model includes the functions of the PRLANIF003 and adds the capability to monitor UPS ambient temperature and
humidity utilizing temperature and humidity sensors.
Temperature sensor : PRLANSN001, Humidity sensor : PRLANSN002 (sold separately)
PMS40J00E (Windows version without cable)
PMS41J00E (Multi-OS version * without cable)
This software automatically shuts down the system and stops the UPS when a failure occurs in the commercial power supply.
Smooth power management is still ensured even when the UPS is connected to many computers.
See our web site for the most recent list of supported operating systems.
SANUPS SOFTWARE
* For Windows, Unix and Linux.
Optional Battery Composition
■ Battery Box
Output capacity 5 kVA
Output capacity 10 kVA
UPS Unit P/N: A11J502A002TU
Model No.
UL / CE
UPS Unit P/N:A11J103A002TE
15 min.
25 min.
35 min.
45 min.
15 min.
25 min.
BCA11J005A00UA
1unit
―
1unit
―
―
―
35 min.
―
BCA11J005A00UB
―
1unit
1unit
2 unit
―
―
―
2 unit
BCA11J005A00AE
―
―
―
―
―
―
2 unit
BCA11J005A00BE
―
―
―
―
―
1 unit
―
―
BCA11J005A00CE
―
―
―
―
―
―
―
2 unit
Capacity of battery (Ah・cell)
960
1440
1920
2400
1290
2880
3840
■ Battery Cabinet [Not UL-certified and CE-marking]
Model No.
Output capacity 5 kVA
Output capacity 10 kVA
UPS Unit P/N: A11J502A002TU
UPS Unit P/N:A11J103A002TE
30 min.
60 min.
180 min.
30 min.
60 min.
BCA11J028A00X1E
1 unit
―
―
―
―
―
BCA11J028A00X2E
―
―
―
1 unit
―
―
BCA11J044A00X1E
―
1 unit
―
―
―
―
BCA11J044A00X2E
―
―
―
―
1 unit
―
―
―
1 unit
―
―
2 unit
2688
4224
8448
5376
8448
16896
BCA11J044A00P2E
Capacity of battery (Ah・cell)
180 min.
Specifications
Model No.
Rated output capacity
(Apparent power/Active power)
System
A11J502A002TU
A11J103A002TE
N unit setting
5 kVA / 4.5 kW
10 kVA / 9 kW
N+1 unit setting
Power supply system
—
True online power supply synchronized with commercial power source
5 kVA / 4.5 kW
Cooling system
Forced air cooling
Inverter system
High-frequency PWM
IEC Standard (UPS classification)
AC
Number of phase
input
Rated voltage
VFI-SS-111
Single-phase 2 wires
200 V, 208 V, 220 V, 230 V, 240 V (User settable. Factory setting: 200 V)
-40% to +15%
50Hz / 60Hz (Selectable Auto-detect or Constant frequency*2 Factory setting: Auto-detect)
Acceptable voltage range *1
Rated frequency
Max. capacity
N unit setting
N+1 unit setting
AC
output
5.5 kVA
—
Power factor
0.95 min (At rated input voltage and input voltage distorsion rate under 1%)
Number of phase
Single-phase 2 wires
Rated voltage (same as input)
Voltage accuracy
200 V, 208 V, 220 V, 230 V, 240 V (Factory setting: 200 V)
Within ± 2% of rated voltage
Rated frequency (same as input)
Frequency range *2 On normal operation
50Hz / 60Hz
Rated frequency Within ± 1, 3, 5% (Factory setting: 3%)
On battery operation
Voltage waveform
Within 3% / 8% (Linear load / Rectifier load at rated output)
Transient
voltage
variation
Rapid load factor change
Within ± 5% (0 ⇔ 100% rapid change)
Power outage / recovery
Rapid input voltage change
Within ± 5%
Within ± 5% (± 10% rapid change)
N unit
0.9 lag (acceptable range 0.7 (lag) to 1.0)
N+1 unit
0.9 lag (acceptable range 0.7 (lag) to 1.0)
Inverter
N unit
N+1 unit
N unit
110% and over (Automatic swith to bypass *4)
—
110% (1 min) / 118% (inst.)
220% and over (Automatic swith to bypass *4)
110% (1 min) / 118% (inst.)
Bypass
N+1 unit
N unit
—
200% (30 s) / 800% (2 cycles)
220% (1 min) / 236% (inst.)
200% (30 s) / 800% (2 cycles)
N+1 unit
—
Small-sized sealed lead-acid battery
16 unit (12 V / 1 unit)
400% (30 s) / 160% (2 cycles)
Type
Composition
Rated capacity
Battery runtime
5 Ah / unit
5 min (Ambient Temp. of 25゜
C, Load power factor 0.8 , Default)
Overcurrent protection
Overload
capacity
Battery*3
Within ± 0.5%
Sine wave
Distortion factor of voltage
Load power factor
11 kVA
6.2 kVA
110% and over (Automatic swith to bypass *4)
32 unit (12 V / 1 unit)
Input leak current
Acoustic noise (At 1m from the front of unit)
4 mA max.
45 dB max.
8 mA max.
50 dB max.
Nominal heat dissipation (at rated output after full recharged)
Environment
Operating temperature
Relative humidity
Input Connector
I/O Connector /
Wiring Wire, etc. *5 Input wire
339 W
0゜
C to 40゜
C
20% to 90% (Non-condensing)
Field wireless terminal / block: Applicable wire 20 to 4 AWG
8 mm2 (8 AWG)
730 W
M6
22 mm2
Output Connector
Output wire
Field wireless terminal / block: Applicable wire 20 to 4 AWG
8 mm2 (8 AWG)
M6 / NEMA L6-30R ×2 / NEMA L6-20R ×2
22 mm2
Grounding wire
Input breaker capacity
5.5 mm2 (10 AWG)
35 A (UL489 certified unit)
UL1778-4th/C22.2 No.107.3-05-2nd, CE: IEC62040-1:2008
14 mm2
80 A min.
—
EN62040-2 C3 : 2006, EN55022:2006 Class-A, FCC Part15 Sub partB
Class-A
EN62040-2:2006, EN55024:1998/A1:2001/A2:2003
—
Safety standard
Emission standard
Immunity
—
The output supplied from the inverter startup (Inverter start-up type)
*1 AC input voltage range changes by load factor.
Load factor 70% or less: -40% to +15% / Load factor more than 70%: -20% to +15%
Note that when recovering from power outages at a load factor of 70% or less, the abnormal voltage detection value (-40%) will be -20%.
*2 At auto-detect frequency setting, synchronized frequency range is selectable as ± 1%, ± 3% or ± 5% (factory setting: ± 3%). Acceptable frequency range is ±8% at this setting.
At constant frequency setting, output frequency is fixed to 50Hz or 60Hz without regard to input frequency. Acceptable range is from 40Hz to 120Hz at this setting.
Note that when recovering from outside the acceptable range, acceptable frequency range will be±8% in either setting.
The inverter will not run if input frequency is not within the set value (±1%, ±3%, ±5%) of the synchronized frequency range.
*3 Battery runtime can be extended through the addition of optional battery boxes. Contact us for details.
*4 A conditions to switch to bypass synchronously are as follows.
Frequency auto-detect setting is selected.・Input frequency is in the synchronized range and input voltage is in the rated voltage range.
*5 Transfer signal:
(1) Contact signal: DSUB15 (female) fixing screw M3
(2) PC interface: DSUB9 (male) fixing screw #4-40UNC
Remote control: Spring clamp terminal block Applicable wires: 26 AWG to 20 AWG
■ UL-certified and CE-marking
Line up
UL / CE
5 kVA : A11J502A002TU
―
10 kVA : A11J103A002TE
only 5kVA type
Battery Box
―
Battery Cabinet
Installation of battery box and cabinet must be done by UL-certified stuff when it is treated as an UL-certified and CE-marking product.
130
480
115
443
435
700
435
I
190
Dimensions : mm
Mass 61 kg
Horizontal / Rack mounting
Vertical
130
I
Vertical
90
262
700
90
443
435
435
190
322
262
130
480
115
115
443
435
700
435
700
700
I
II
I
Horizontal / Rack mounting
480
Mass 61 kg
Mass 124 kg (Without a battery pack 54 kg)
Paint color: Black (Munsell N1.5)
Horizontal / Rack mounting
Vertical
700
90
Option Dimensions : mm
700
90
I
II
I
262
443
435
■ Battery Box [Only 5 kVA type is UL certified and CE marking]
435
Dimensions : mm
480
Width
Mass
Depth*1 Height
435
700+80
130pack 54 49
Mass 124435
kg (Without
a battery
kg)kg
BCA11J005A00UA,
BCA11J005A00AE
BCA11J005A00UB,
BCA11J005A00BE,
Black130
(Munsell 84
N1.5)
435Paint color:
700+80
kg
BCA11J005A00CE
700
130
262
322
Model No.
*1: Battery Box + cable cover
■ Battery Cabinet [Not UL-certified and CE-marking]
Depth*1
Height
BCA11J028A00X1E
1
440
700+12
544
215 kg
BCA11J028A00X2E
2
440
700+12
988
415 kg
BCA11J044A00X1E
3
440
870+12
544
320 kg
BCA11J044A00X2E, BCA11J044A00P2E
4
440
870+12
988
620 kg
Fig.1
Fig.2
440
440
700
700
440
*1: Battery Cabinet + cable cover
Fig.2
440
700
Fig.3
Used for mounting the UPS onto a 19 inch rack.
544
988
133
700
48
440
544
440
Model No.: RM027
Fig.4
440
870
870
988
Fig.1
■
Rack Support Rail
654 to 798
Rack mounting dimension
A set of left and right rails. The figure shows the left rail.
Eco Products
Sanyo Denki’s ECO PRODUCTS are designed with the concept of lessening impact on the environment in the process from product development to waste. The
product units and packaging materials are designed for reduced environmental impact. We have established our own assessment criteria on the environmental
impacts applicable to all processes, ranging from design to manufacture. Those products that satisfy the criteria are accredited as ECO PRODUCTS.
Notes when investigating use of this product in your applications
Before starting installation, assembling and use, read the “Operation
Manual” carefully and use the product correctly in your applications.
For the applications that undergo vibration such as vehicles, ships and
transportation facilities, please consult with our company.
When you are going to use this product in the following application, the
special considerations are required for operation, running, maintenance
and control. Be sure to consult with our company as a part of your
investigations.
Never modify this product or give additional processing to this product.
(a) Medical equipment and other equipment that are related directly to
human life.
(b) Train or elevator that can give injury to human body.
(c) Socially and publicly important computer systems.
(d) And other equipment that are related to safety of human life and that
can affect severe effects on maintenance of public functions.
Fig.3
544
Width
988
Mass
Fig.
544
Dimensions : mm (inch)
Model No.
For the installation andmaintenance work, please consult with our
company or with specialized company.
This product may be regulated under export and trade control
regulations of each country. During export of each product, compliance
to the export regulations of each country is highly recommended.
Our company shall not be responsible for damages (including but not
limited to equipment downtime, power sales revenue, business
interruptions, increased power purchases) resulting from use or non-use
of this product and services.
※For any inquiry or consultation, please contact our sales representative.
3-33-1, Minami-Otsuka, Toshima-ku, Tokyo, 170-8451, Japan TEL: +81 3 5927 1020
http://www.sanyodenki.com
The names of companies and/or their products specified in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies.
Specifications are subject to change without notice.
CATALOG No.P1012B002 ‘15.5
Download