1. PRE-ACTION SYSTEM DESIGNED AS A DOUBLE INTERLOCK ELECTRIC/ELEC-PNUEMATIC: (2) OPERATIONS NEED TO HAPPEN BEFORE THE SOLENOID VALVE ACTIVATES THE DELUGE VALVE AND ACTIVATES THE FIRE SPRINKLER SYSTEM: a - SMOKE DETECTOR IS ACTIVATED. b - LOW PRESSURE SWITCH IS ACTIVATED DUE TO THE LOSS OF AIR IN THE SPRINKLER SYSTEM BECAUSE OF SPRINKLER ACTIVATION. SD 2. IF SMOKE DETECTOR IS ACTIVATED A SUPERVISORY ALARM IS SENT TO THE FACP AND THE LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED. STORAGE AREA 3. IF LOW PRESSURE SWITCH IS ACTIVATED A SUPERVISORY ALARM IS SENT TO THE FACP AND LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED. 4. IF A CONTROL VALVE IS MOVED FROM ITS OPEN POSITION A SUPERVISORY ALARM IS IS SENT TO THE FACP AND LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED. 5. IN THE CONDITION THAT A SMOKE DETECTOR AND THE LOSS OF AIR PRESSURE BELOW 20 PSI IS MET THE SOLENOID VALVE IS TRIPPED AND THE DELUGE VALVE IS OPEN, ALARM PRESSURE SWITCH SENDS A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A FLOWING CONDITION INITIATING BUILDING FIRE ALARM SYSTEM. EOLR 5.1K BASEMENT - DETECTION PLAN 1/4"=1'-0" SD SD AC POWER SUPPLY 120 VAC 60 Hz 165 VAC MAX 220 VAC 50Hz 185 VAC MAX CIRCUIT IS NON-POWER LIMITED AND SUPERVISED EOLR 5.1K SD TS SD TS SD HOT - BLACK EOLR 5.1K NEUTRAL - WHITE A EARTH GROUND - GREEN (BY OTHERS) N L + + 24 VNR DC RS-485 A EOLR 5.1K 120 OHM + AUX. POWER 24 VR DC S EOLR 5.1K TS A SD A LAS TS APS SD EOLR 5.1K EOLR 5.1K + SUP1 + SUP2 + ZONE 1 + ZONE 2 + ZONE 3 + ZONE 4 SYMBOL LEGEND SMOKE DETECTOR SD 7 APS TS LAS ZONE 2 OUTPUT 2 ZONE 3 OUTPUT 3 ZONE 4 OUTPUT4 TAMPER SWITCH INTERNAL ON BUTTERFLY VALVES 4 PROGRAM MODE LOW AIR PRESSURE SWITCH POTTER ELECTRIC PS40-2A 1 PRE-ACTION SYSTEM RELEASING SOLENOID VALVE ELECTRIC BELL 24VDC WITH BACK BOX 1 1 RUN MODE SCROLL-UP BUZZER SILENCE 1 PARP OUTPUT 1 ALARM PRESSURE SWITCH POTTER ELECTRIC PS10-2A 1 SOL BELL ZONE 1 PRE-ACTION SYSTEM RELEASING PANEL VIKING VFR-400 NOTE: TAMPER SWITCHES ARE INTERNALLY WIRED INTO EACH BUTTERFLY VALVE. AC POWER SUPERVISORY 1 POWER TBL SUPERVISORY 2 SYSTEM TBL COMMON ALARM SUP TBL ALARM SILENCE GROUND FAULT STEADY DISCHARGED FLASHING PREDISCHARGED CABLE TYPES LAMP TEST SET SCROLL-DOWN BUZZER SILENCE SELECT SIGNAL SILENCE FUNCTION SYSTEM RESET VIEWING ANGLE PAIGE ELECTRIC 4547OARE 16/2 FPLP SLC CABLE (NON SHIELDED) B PAIGE ELECTRIC 454719ARE 14/2 FPLP NAC CABLE BATTERY CABLE OBSERVE POLARITY RED + BLACK NON-POWERED LIMITED AND SUPERVISED RED BAT+ BAT- BLACK A OUTPUT 1 + OUTPUT 2 + OUTPUT 3 + OUTPUT 4 + BELL SOL 5.1K EOLR 5.1K EOLR B B 5.1K EOLR + POS NEG 12V BATTERY + POS com no nc com no nc com no com no WIRED TO BUILDING FIRE ALARM CONTROL PANEL (BY OTHERS) 5.1K EOLR NEG 12V BATTERY PRE-ACTION SYSTEM RELEASING CONTROL PANEL NOT TO SCALE (1) - (7) - SD BELL 6. IF EMERGENCY RELEASE LOCATED ON TRIM OF DELUGE VALVE IS PULLED SOLENOID IS ENERGIZED TRIPPING THE DELUGE VALVE AND A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A FLOWING CONDITION. (NO WATER IS SENT INTO THE PIPING OR DISCHARGED UNTIL A SPRINKLER IS ACTIVATED.) VIKING RELEASING CONTROL PANEL, MULTI HAZARD VFR-400 WITH (2) 12V BATTERIES SEQUENCE OF OPERATION PARP ELECTRIC BELL TO BE LOCATED ABOVE RELEASING PANEL AS SHOWN ON THE MOUNTING DETAIL SHOWN ON THIS SHEET. SHOWN BESIDE PARP FOR CLARITY. Bldg. Inspectors ALL WIRING FROM RELEASING PANEL TO FACP AND POWER WIRING TO BE DONE BY OTHERS. 02-05-2013 3. (1) - SD ALL WIRING FROM THE DEVICES TO THE RELEASING PANEL TO BE DONE IN ACCORDANCE WITH ALL APPLICABLE CODES, THE LOCAL AUTHORITY AND THE SPECIFICATIONS. SYSTEM SENSOR 6" ELECTRIC BELL 24 VDC, RED 22M24-6 SECURE STORAGE ROOM 2. SYSTEM SENSOR PHOTOELECTRIC SMOKE DETECTOR, 2 WIRE 2W-B MECH/ELECTRICAL ROOM SD SD ALL ELECTRICAL DEVICES FOR THE PRE-ACTION SYSTEM TO BE MOUNTED AND INSTALLED PER PER NFPA 72 AND THE DEVICE MOUNTING DETAILS SHOWN ON THIS SHEET. BELL PARP SD 1. AS-NOTED SD DRC SD 12-153 GENERAL NOTES: (ELECTRICAL)