CONNECTIONS 4K7 22K INPUT Monitored for Open and Short-Circuit - Can be driven by Conventional Panel’s Zone Repeater Outputs. Each I/P should be fitted with 22 K Ohm end-of-line resistor. Fire Condition set with 4.7 K Ohms resistor in parallel with e.o.l. resistor. 3IO-PLUS Addressable Triple I/O Module OUTPUT The relay output provided is a latching relay. In order to reset it apply reset to the panel or alternatively remove power to the panel and re-apply. After a few seconds the relay will revert to its default position. REPORTING DETAILS In order to indicate the status of the module’s working condition, the following LEDs are provided: Status: This LED will flash GREEN, every time the address associated with the module is polled by the addressable panel. Input Status: An I/P status RED LED is provided for the input. This RED LED will be illuminated continuously whenever there is a FIRE condition present at the input terminals. The analogue value reported by the module in this state is 64. Output Status: An O/P status RED LED is provided for the output. This RED LED will be illuminated continuously whenever the output relay is activated. Fault: This YELLOW LED will be activated whenever there is either an open or short circuit fault on that particular input. If there is an open or short circuit condition, the analogue value reported to the addressable panel is 4. SC Fault: This YELLOW LED will be ON when there is a short circuit in the loop. TECHNICAL SPECIFICATIONS SUPPLY VOLTAGE LOOP CURRENT - QUIESCENT (IQ) LOOP CURRENT - ALARM LOOP CURRENT - SHORT-CIRCUIT LOOP CURRENT - OPEN CIRCUIT LOOP CURRENT - OUTPUT ACTIVE OUTPUT RELAY CONTACT RATING MAX. CABLE SIZE CASE MATERIAL MAX. HUMIDITY OPERATING TEMPERATURE DIMENSIONS WEIGHT Loop Powered - 17V to 30V DC 1.4 mA (1 ch.) - 1.5 mA (2 ch.) - 1.6 ma (3 ch.) IQ +1.2 mA for each I/P in alarm IQ +1.4 mA max. IQ +1.0 mA max. IQ +1.1 mA for each O/P activated 2 A 30V DC / 0.5 A 125V AC 2.5 mm2 ABS 95% RH Non-Condensing -10ºC to 50ºC 150 (W) x 90 (L) x 32 (H) mm 216 g inc. packaging ORDER CODE DESCRIPTION 3IO-PLUS-1CH 3IO-PLUS-2CH 3IO-PLUS-3CH 1 Channel, boxed w/ Loop Isolator 2 Channel, boxed w/ Loop Isolator 3 Channel, boxed w/ Loop Isolator The 3IO-PLUS Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel using normally open dry contact connections. Each module can be fitted with a maximum of 3 inputs and 3 outputs. The connection to each input is monitored for fault (open or short-circuit) and Alarm conditions. The interface is used to monitor the contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in Gas Extinguishing Systems, etc. Module is provided with a loop short-circuit isolator and with up to 3 voltage free single pole change over relay outputs. The output relays are always powered directly from the detection loop. It is not required to use an external 24V DC power supply. Relay operation is confirmed by an onboard red LED. A 8 way D.I.L. switch is provided to configure the module’s address. This value can be set in the range 1 to 125. FEATURES Fast Activation Response Loop Powered Status LEDs provided for each i/p and o/p Low Power Consumption The following programmable functions are available: Input Activation Mode, Delayed Input Alarm Activation, Output Delayed Activation. For further details please refer to IO Programming Guide which is available for download from our web site www.globalfire.pt Module features an integral short-circuit loop isolator GLOBAL FIRE EQUIPMENT S.A. Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt Instruction Manual V1 - 02/2014 Made in Portugal-EU CONNECTIONS ADDRESS SETTINGS Device is polarized 1 2 3 4 5 6 7 8 1 2 3 01 1 2 3 4 5 6 7 8 1 2 3 09 1 2 3 4 5 1 2 3 6 7 8 1 2 3 2CH LOOP IN 3CH OUT + 5 C NC NO C OUT 1 NC NO C OUT 2 2 3 6 7 8 1 2 3 EN 54-17 & EN 54-18 Input Status 4 5 6 7 8 1 2 3 1 2 3 Status SC Flt 4 5 6 7 8 1 2 3 1 1 2 3 4 5 6 7 8 1 2 3 1 Loop OUT 2 3 4 5 6 7 8 1 2 3 Input Resistance values Fault Short circuit Open Circuit Normal Fire END OF LINE MONITORING RESISTOR 22K ALARM RESISTOR (4K7) IN SERIES WITH NORMALLY OPEN CONTACT 2 3 4 5 6 7 8 1 2 2 3 - < 2K2 > 47K 8K2 to 47K 2K2 to 8K2 1 2 3 1 4 5 6 7 8 1 2 8 OFF Switches 1-7 used to configure the module’s address ON OFF 4 5 6 7 8 1 2 3 8 1 2 3 4 5 4 5 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 6 7 8 1 2 3 4 5 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 6 7 8 1 2 3 4 5 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 6 7 8 1 2 3 4 5 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 6 7 8 1 2 3 4 5 5 6 7 8 4 5 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 7 8 7 8 16 6 7 8 1 2 3 23 30 4 08 15 22 29 4 07 14 21 28 4 06 13 20 27 4 05 12 19 6 4 04 11 2 3 4 5 2 3 4 5 2 3 4 5 Address Switches binary weights 1 on =1 4 on =8 7 on = 64 2 on =2 5 on =16 3 on =4 6 on =32 1 2 3 4 5 6 7 8 1 2 3 4 5 5 6 7 8 1 2 3 4 5 4 5 4 5 4 5 4 5 4 5 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 6 6 121 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 7 8 1 2 3 4 5 3 4 5 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 7 8 1 2 6 6 122 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 3 4 5 4 5 4 5 4 5 3 4 5 3 4 5 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 7 8 1 2 6 6 123 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 7 8 1 2 3 4 5 24 6 7 8 1 2 3 31 3 4 5 3 4 5 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 6 6 6 124 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 8 1 2 3 4 5 3 4 5 32 4 5 4 5 4 5 4 5 3 4 5 3 4 5 1 2 3 4 5 6 7 8 1 2 6 6 6 125 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 8 7 8 1 2 3 3 4 5 3 4 5 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 7 8 1 2 3 4 5 3 6 7 8 1 2 7 8 1 2 3 4 5 3 6 7 8 1 2 3 7 8 1 2 3 4 5 6 7 8 1 2 3 7 8 1 2 6 6 3 4 5 6 7 8 1 2 8 1 2 3 4 5 6 7 8 1 2 8 1 2 3 4 5 4 5 4 5 3 4 5 3 4 5 88 6 7 8 1 2 3 4 5 96 6 7 8 1 2 6 6 119 3 4 5 104 7 8 1 2 111 7 5 80 103 7 4 72 95 6 5 64 87 6 4 56 79 6 5 48 71 6 4 40 63 118 7 6 55 110 7 5 47 102 7 4 39 94 117 7 2 86 109 7 1 78 101 7 8 70 93 6 7 62 85 6 6 54 77 6 5 46 69 6 4 38 61 116 7 6 53 108 7 5 45 100 6 4 37 92 115 7 2 84 107 7 1 76 99 6 8 68 91 6 7 60 83 6 6 52 75 6 5 44 67 6 4 36 59 114 7 6 51 106 7 5 43 98 6 4 35 90 113 2 4 82 97 1 Switch 8 Programming Mode 7 74 105 7 3 89 1 6 6 66 81 D.I.L. SWITCHES CONFIGURATION 5 3 73 1 4 5 58 65 1 3 4 4 03 50 57 2 3 42 49 1 2 34 41 ON 1 26 33 Conforms with 3 I/P Fault Loop IN 8 NC NO 1 2 7 OUT 3 INPUTS 1 6 18 25 Fault Address 3IO-PLUS 1CH 4 5 10 17 Output Status 4 02 3 4 5 6 112 7 8 1 2 3 4 5 6 120