Data sheet - 07/016 Single Channel Input Unit MCIM-C Description The MCIM-C is a variant of the single Channel output unit MCIM.This device is identified as a call point module by the COOPER addressable panel.The maximum number of addressable MCIM-C per loop is 200. Dimensions Recommendation 18.5 m m Only connect cable screen to its adjacent earth terminal. The end of line resistor must always be fitted, even if the input is unused. Monitored input can detect open or short circuit faults. Installation 1. Fit the box in position using the mounting details below. 2. Connect the unit according to the diagram below. 3. Recommended Loop Cable Type: FIRETUF, FP200, MICC 63 mm No addressing of the interface is required. See control panel operation for details. 35 mm Notes: 5k6 Connexions Loop In + EARTH Lo op nI Loop In Earth Loop Ou t+ MCIM-C 37.5m m Earth INTPUT IN - LOOP 22k IN + Loop Out Loop Out- 20 mm Mounting Details (Drilling positions, template over leaf) Specifications Loop Load Min Nom Max Units Quiescent Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .310 . . . . . . .µA Operating Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 . . . . . . . . . . . . . . . . . . .30 . . . . . . . .V DC Inputs Trigger Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5,6 . . . . . . . . . . . . . . . . . . kohms End Of Line Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 . . . . . . . . . . . . . . . . . . . kohms Short Circuit Fault Threshold Resistance . . . . . . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . . . . . . kohms Open Circuit Fault Threshold Resistance . . . . . . . . . . . . . . . . . . . . .33 . . . . . . . . . . . . . . . . . . . kohms Environmental Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . -10 . . . . . . . . . . . . . . . . . . +60 Humidity (Non Condensing) Standards EN54 : Pt2 & 4 BS5839 : Pt1 (Installation) Compatibility Suitable for use with Cooper Analogue Addressable Fire Systems Physical Dimensions 63mm x 35mm x 18.5mm Weight >0.1kg Ingress Protection IP40 . . . . . .°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 . . . . . . . . . . . . . . . . . . .%RH