890-00502 - Automated Production Systems

advertisement
NOTE: For more complete information on the product, please refer to the manual on the USB key provided with your Agri Alert 128 Touch or go to the following web sites :
AP website: http://www.automatedproduction.com/en/apmanuals.php
Cumberland website: http://www.cumberlandpoultry.com/sales-and-service/manuals.html
Power
ZONE INPUTS
B
C
E
D
F
H
G
EXT. MIC.
VBAT
2ND
SERIAL
PORT
2
3
4
5
6
7
8
Z1 GND1 Z3 GND3 Z5 GND5 Z7 GND7
Z2 GND2 Z4 GND4 Z6 GND6 Z8 GND8
Normally open
circuit with EOLR
1.5 ohms
1/2 Watts
9
10
11
12
A
B GND
13
14
See KP-8IN-1REL,
TP-8IN-1REL, TR2IN-1RELwiring
diagram
2
15
Com A
1
12VDC
SBI
1
3
16
4
17
19
20
21
SIREN BAT TEMP
22
23
24
25
27
29
NO COM NC
VDC
30
31
32
NO COM NC
Examples:
-Light switch
-Propane shutoff
-Fan shutoff
Siren
12VDC @ 1.5A max.
Normally closed circuit without EOLR
1.5K ohms
1/2 Watts
28
VDC
RELAY 2
RELAY 1
26
VBAT
See TP-800,
KP(B)-400
wiring diagram
Normally open circuit without EOLR
Normally closed
circuit with EOLR
18
28VDC
Com B
A
External microphone
28VDC device
350mA max.
To battery box
Earth ground
Metal rod 10 feet (3m)
12VDC device
750mA max.
891-00502 rev.01
Wiring in the battery box
Wiring diagram with a DPST disconnect switch
Wiring diagram with a SPST disconnect switch
Technical Specifications
TYPE: Agri Alert system
Operating Temperature: 32 to 104°F (0 to 40°C)
Indoor use only
Pollution Degree: 2
Installation Category: 2
Altitude: 7900 Ft. Max (2000 Meters Max)
Humidity (maximum relative) operating:
• 0 to 10 °C (32 to 50 °F) Non condensing
• 10 to 30 °C (50 to 86 °F) 95 % (± 3 %) Non condensing
• 30 to 40 °C (86 to 104 °F) 95 % (± 3 %) Non condensing
SUPPLY INPUT :
100VAC-240VAC, 1 phase, 240W, 50-60Hz
BATTERY: Rechargeable, sealed, lead-acid, 12V-7.0AH
OUTPUTS :
RELAY 1-2: 28Vdc, 4A max.
SERIAL BUS: 28Vdc, 2A max.
SIREN: 12Vdc, 1.5A max.
12VDC: 12Vdc, 750mA max.
28VDC : 28Vdc, 350mA max.
Main supply voltage fluctuations shall not exceed +/- 10% of the nominal supply voltage.
Table 1 Main enclosure specifications
Item
Description
Enclosure material
Flame retardant ABS
Dimensions
Width
16-11/16 inches (42.4 cm)
Height
13- 13/16 inches (35.1 cm)
Depth
7 inches (17.8 cm)
Weight
5.15 kilograms (11.35 lbs)
Table 1 Main enclosure specifications (cont'd.)
Item
Description
Sensor inputs
8 inputs, self-configuring for various sensor types
Touch screen
Size
7 inches (17.8 cm)
Type
TFT color LCD
Resolution
WVGA (800 × 480 pixels)
Table 2 Battery enclosure specifications
Item
Description
Enclosure material
Flame retardant ABS
Dimensions
Width
11 inches (28 cm)
Height
9- 7/8 inches (25 cm)
Depth
5 inches (12.7 cm)
Weight
2.97 kilograms (6.55 lbs) including the weight of the battery
Nominal voltage
12 Volts
Nominal capacity
7.00 Ah
Terminal
T2 (Faston Tab 250)
Storage temperature
-20 °C to 40 °C (-4 °F to 104 °C)
Battery
Type
Sealed lead-acid battery
(the values shown
are based on ambient
temperatures of 20 25 °C (68 - 77 °F))
Power output
12 VDC, 7.5 Ah
Shelf discharge
3% per month
Average battery
capacity with low load
When the siren, the 12 VDC outputs and the SBI are not used.
32 hours
Average battery
capacity with high load
When the siren, the 12 VDC outputs and the SBI are used.
20 minutes
Average lifespan
3 years
Battery weight
2.2 kilograms (4.85 lbs)
Table 3 Sensor specifications for zone types
Zone type
Sensor specifications
Internal and external temperature zones
Compliant to GSIE temperature probes (orange cap)
Analog 0-5 Volts
Sensor must be able to drive a 2k Ohms load, which
means the sensor must drive at least 2.5mA to ensure
correct readings
Analog 4-20mA
Sensor must be able to drive a 120 Ohms load
Maximum 20.8mA, 2.5V
The load =120 Ohms
Dry contact, Intrusion
Close contact resistance must be lower than 200 Ohms
Table 3 Sensor specifications for zone types (cont'd.)
Open contact resistance must be higher than 100k
Ohms
The resistance value includes the value of wire
resistance
End of line rsistor is 1.5k Ohms
Water meter, Pulse speed
Dry contact without end of line resistor
Max 100Hz, pulse width minimum of 3.2ms
Max 100 Ohms (close contact) and min. 100k Ohms
(open contact) including the value of the wire
resistance
AA-CS
Model AT1-005-000-FT only
Download