Wylex All Metal Consumer Unit Catalogue File size 5.48MB

advertisement
NM Consumer Units
for use in Domestic
Household Premises
Amendment No. 3 BS 7671
CONSUMER UNITS FOR USE IN DO
REGULATION 421.1.201
17th Edition Wiring Regulations Incor
From January 2015 Amendment No. 3 to BS 7671
IET Wiring Regulations prescribe that within
domestic (household) premises, consumer units and
similar switchgear assemblies shall have their
enclosures manufactured from non combustible
material, or be enclosed in a cabinet or enclosure
constructed of non combustible material and comply
with product standard BS EN 61439-3.
What are Domestic Household Premises ?
Typical Domestic household premises would include single and
multiple occupancy homes such as Houses, Bungalows, High Rise &
Low Rise Flats, Apartments, Student lets, Sheltered
Accommodation, Farmhouses, Houseboats, Static Homes, Home
Office, attached Garages, Workshops and Detached
Summerhouses etc.
What is Non Combustible Material ?
There are many types of non combustible material however,
amendment 3 of the 17th Edition regulations provides an
acceptable example as ferrous metal i.e. Steel Consumer Units.
What is an Enclosure ?
The consumer unit enclosure must be manufactured from a non
combustible material so as to limit the spread of fire. An
enclosure means the box, cover, door, hinges, handle and any
components required to maintain the integrity of the unit.
What is Similar Switchgear ?
Similar switchgear is switchgear that is used for the same
fundamental application ie. a circuit protection assembly with two
pole isolator and one or more circuit protection devices, e.g. MCB
distribution board, fuse switch, garage unit or PV switchgear etc.
What are Cabinets ?
Typical cabinets are meter cabinets that are normally built into the
fabric of the building and that may or may not include consumer
units within. If the cabinet is of an all metal construction (noncombustible), then a standard skeleton consumer unit (FAL) can
be installed within. If the cabinet is of a combustible material, a
metal consumer unit is required.
What about Cable Entry ?
As usual good workmanship and proper materials should be
applied to all installation work, consumer units must be installed
to achieve IP4X on the top elevation (regulation 416.2.2) and
IP2XC on all other elevations. This can be achieved by use of cable
entry accessories such as consumer unit pattrass or other means
such as glanding.
This guide to Wylex consumer units is not a suitable substitute for the standards and regulations that should always be used for all types of electrical installation design & installation work.
OMESTIC HOUSEHOLD PREMISES
rporating Amendment No. 3 : 2015
l All metal enclosure, no
external plastic parts
l Low Smoke & Fume paint
l Non combustible cover blanks
l Compact enclosure
l Available in ‘no miss terminal’ fixed
busbar versions and flexible
versions
l Raised & removable DIN rail /
busbar assembly
l Cable entry knockouts on 5 sides,
top, bottom, left, right and rear
l Mains tails cable entry grommet /
gland for supplementary insulation
similar to Class II level of
protection to mains tails
l Time delay RCD available for
TT systems
l Up to 38 way units, all designs Main
Switch, High Integrity, Split Load,
Dual RCD
l RoHS compliant in excess of
UK standards
l UKAS certified to BS EN 61439-3
What about Cable Entry ?
The IET on site guide also recommends that where metal consumer units are installed into TT systems the mains tails are protected
against the possibility of becoming loose and making contact with the metal enclosure by incorporating into the installation 100mA
time delayed (S type) RCCB protection.
Furthermore in all cases (including TT) the mains tails should be protected at the point of entry into the metal enclosure e.g. by use
of a mains tails gland to protect against the possibility of mechanical damage and or disturbance that could lead to tails becoming
loose and making contact with the metal enclosure.
CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES
17th Edition Wiring Regulations Including Amendment No. 3
17th Edition Wiring Regulations Including Amendment No. 3
Amendment No3 has brought about the requirement for ‘all metal’ non combustible enclosures for consumer units and similar switchgear.
This is in addition to the requirements for Additional Protection (30mA RCD) as summarised below. Within domestic household premises.
l Installations should be divided up into circuits so as to take account
l All socket outlets should be protected by 30mA RCD
of danger and inconvenience caused by a single fault - e.g. such as a
l All circuits serving or passing through a room with a fixed bath or
lighting circuit***
shower should be protected by one or more 30mA RCDs**
l All cables buried beneath the plaster surface of the wall or partition l Installations should be designed and arranged so as to prevent
unwanted tripping of RCDs***
(at less than 50mm) should be protected by 30mA RCDs***
l
Safety services such as smoke alarms should be on independent
l All cables concealed in metal stud partitions (common in new
circuits****
builds) should be protected by 30mA RCDs***
l Installed units must be to IP4X on top elevation & IP2XC elsewhere
REGULATIONS
411.3.3 *
701.411.3.3 **
522.6.200 series
and
560.7.1*****
RELATING TO :
Sockets up to
20A rating
All Circuits serving or
passing through a room
with a fixed bath or
shower
All circuits buried in
a wall or partition at
less than 50mm and
without mechanical
protection
ADDITIONAL PROTECTION
EXAMPLES
Upstairs Sockets
30mA RCD
Downstairs Sockets
Kitchen Sockets
Taking into account
Cooker outlet with integral 13A socket
3.14.1 ****
Garage Sockets
3.14.2 ****
Plus any other sockets up to 20A rated
Shower circuit
Lighting circuit
Heating circuit
Ventilation circuit
Shaver Socket
Plus Other circuits
Downstairs Lighting
Upstairs Lighting
Immersion heater
Smoke Alarms
Burglar Alarm (Safety service)
Plus any other circuits
30mA RCDs
Taking into account
3.14.1 ****
3.14.2 ****
30mA RCD
Taking into account
3.14.1 ****
3.14.2 ****
A The IET on site guide also recommends that where metal consumer units are installed into TT systems the mains tails are protected against the
possibility of becoming loose and making contact with the metal enclosure by incorporating into the installation a 100mA time delayed (S type)
RCCB protection.
B Furthermore in all cases the mains tails should be protected at the point of entry into the metal enclosure by use of a mains tails gland to protect
against the possibility of mechanical damage and or disturbance that could lead to tails becoming loose and making contact with the metal
enclosure.
*
**
***
Regulation 411.3.3 socket outlets with a rated current not exceeding 20A.
Regulation 701.411.3.3 Additional protection shall be provided for all circuits of the location by use of one or more 30mA RCD.
Regulations in the 522.6.200 series cables concealed in a wall or partition at less than 50mm depth and without earthed mechanical protection
e.g. conduit.
**** Regulation 314.1 Every installation shall be divided into circuits as necessary to avoid danger and inconvenience in the event of a fault, take
account of danger that may arise from the failure of a single circuit such as a lighting circuit, reduce the possibility of unwanted tripping of RCDs
etc.
**** Regulation 314.2 Separate circuits to be provided for parts of the installation that need to be separately controlled in such a way that those
circuits are not affected by the failure of other circuits.
***** Regulation 560.7.1 Chapter 56 circuits for safety services shall be independent of other circuits.
In addition Chapter 51 requires designers/installers to take account of all relevant British Standards and manufacturers instructions. For example
BS5839 Part 6 is the British Standard for fire detection and alarm systems in dwellings. It states that power supplies to Grade D smoke alarms
should be an independent circuit at the consumer unit, or a separately electrically protected local lighting circuit.
****** Regulation 416.2.2 requires that the installed consumer unit achieves IP4X (1mm probe) on the top elevation. All other elevations should be
to IP2XC (2.5mm probe).
A typical domestic household application with meter cabinets
B
NM All Metal Consumer Units
4
NM All Metal Duplex Consumer Units
6
FAL Skeleton Units
6
PV All Metal Micro Generation Units
7
MCBs and RCBOs
8
Accessories
9
Custom Built
10
Dimensions
11
ALL INDEPENDENT CIRCUITS
Full metal Main Switch unit with RCBOs
B
SOME INDEPENDENT CIRCUITS
Full metal High Integrity unit with RCBOs and MCBs
B
HALF INDEPENDENT CIRCUITS
Full metal Split Load unit with RCBOs and MCBs
B
NO INDEPENDENT CIRCUITS
Full metal Dual RCD unit with MCBs
Other Amendment 3 Product Publications
Switch Fuse Units
for use in Domestic
Household Premises
(and other buildings)
B
Domestic
Switch Fuse
A
TT SYSTEM
All independant
circuits & 100mA
Time Delay RCD
30mA Earth leakage protection
I
S
0
Amendment 3
Meter Cabinet
Metal Cased
Consumer Units
fo r u s e i n D o m e s t i c
H o u s e h o l d P re m i s e s
Meter Cabinet
Metal Consumer
Units
NMFS Intumescents & Accessories
for use in Consumer Units for
Domestic Household Premises
Amendment No. 3 BS 7671
NMFS
Intumescents
NM all metal consumer units available from January 2015
MAIN SWITCH
CAT REF
NM206/40
NM206/63
NM506
NM806
NM1106
NM1406
NM1906
4
MS RATING
*WAYS
40A
63A
100A
100A
100A
100A
100A
2
2
5
8
11
14
19
NM All Metal Consumer Units
FLEXIBLE MAIN SWITCH
CAT REF
NM1406
NM506FLEX
NM806FLEX
NM1106FLEX
NM1406FLEX
NM1906FLEX
MS RATING
*WAYS
100A
100A
100A
100A
100A
5
8
11
14
19
HIGH INTEGRITY
CAT REF
NMRS23206
NMRS44206
NMRS43306
NMRS33406
NMRS76206
NMRS66306
NMRS46506
NMRS55506
NMRS45606
30mA
30mA
RCD WAYS RCD WAYS
MCB
MCB
2
4
4
3
7
6
4
5
4
MS
RATING
MS
WAYS *
TOTAL
3
4
3
3
6
6
6
5
5
100A
100A
100A
100A
100A
100A
100A
100A
100A
2
2
3
4
2
3
5
5
6
7
10
10
10
15
15
15
15
15
1 to 4
2 to 5
2 to 9
100A
100A
100A
1 to 4
2 to 5
2 to 9
7
10
15
FLEXIBLE HIGH INTEGRITY
NMRS10SSLMHI
NMRS7SSLMHI 1 to 4
NMRS10SSLMHI 2 to 5
NMRS15SSLMHI 2 to 9
SPLIT LOAD
CAT REF
NMRS12SLM
NMRS2406
NMRS3306
NMRS4206
NMRS5406
NMRS4506
NMRS3606
NMRS6306
NMRS3906
NMRS4806
NMRS6606
NMRS5706
NMRS7506
NMRS8406
NMRS9306
NMRS12506
NMRS11606
NMRS10706
NMRS61106
NMRS71006
NMRS9806
NMRS8906
NMRS51206
RCD RATING
MCB WAYS
MS RATING
*WAYS
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
2
3
4
5
4
3
6
3
4
6
5
7
8
9
12
11
10
6
7
9
8
5
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
4
3
2
4
5
6
3
9
8
6
7
5
4
3
5
6
7
11
10
8
9
12
FLEXIBLE SPLIT LOAD
NMRS4506
CAT REF
RCD RATING
NMRS6SLM
NMRS9SLM
NMRS12SLM
NMRS17SLM
80A 30mA
80A 30mA
80A 30mA
80A 30mA
MCB WAYS
MIN MAX
2
3
3
5
4
6
9
12
MS RATING
100A
100A
100A
100A
* WAYS
MIN MAX
2
3
3
5
4
6
9
12
* WAYS
TOTAL
6
9
12
17
* RCBOs or MCBs may be fitted to non RCD protected ways depending upon the
installation requirements, see page 8.
Complete flush mounting consumer units available to order.
DIN rail modular devices suitable for flexible consumer units only.
DUAL RCD 2 x 80A 30mA RCD
CAT REF
NMISS3406
NMISS4606
NMISS5506
NMISS8706
MS
WAYS
RCD 1
MCB WAYS
RCD 2
MCB WAYS
TOTAL No of
MCB WAYS
-
3
4
5
7
4
6
5
8
7
10
10
15
5
FLEXIBLE DUAL RCD 2 x 80A 30mA RCD
CAT REF
RCD 1
MCB WAYS
RCD 2
MCB WAYS
TOTAL No of
MCB WAYS
-
6 Max
9 Max
6 Max
9 Max
10
15
RCD INCOMER
CAT REF
NMISS5506
NMRS206/40
NMRS206/63
NMRS506
NMRS806
NMRS1106
NMRM206/40
NMRM206/63
NMRM506
NMRM806
NMRM1106
NMTM506
NMTM806
NMTM1106
NMTM1406
MNTM1906
RCD RATING
MCB WAYS
40A 30mA
63A 30mA
100A 30mA
100A 30mA
100A 30mA
40A 100mA
63A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA time delay
100A 100mA time delay
100A 100mA time delay
100A 100mA time delay
100A 100mA time delay
2
2
5
8
11
2
2
5
8
11
5
8
11
14
19
SPLIT LOAD WITH TIME DELAY RCD INCOMER
CAT REF
NMRS1106
RCD RATING
NMSTM2406
NMSTM3306
NMSTM3606
NMSTM4206
NMSTM4506
NMSTM5406
NMSTM6306
NMSTM3906
NMSTM4806
NMSTM6606
NMSTM7506
NMSTM9306
NMSTM8906
NMSTM9806
NMSTM71006
NMSTM61106
NMSTM51206
MCB WAYS TD RCD RATING
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
80A 30mA
4
3
3
2
4
5
6
3
4
6
7
9
8
9
7
6
5
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
100A 100mA
*WAYS
2
3
6
4
5
4
3
9
8
6
5
3
9
8
10
11
12
FLEXIBLE SPLIT LOAD ( TIME DELAY )
CAT REF
RCD RATING
NMSTM9SLM
NMSTM12SLM
NMSTM17SLM
NMSTM9SLM
MCB WAYS
MIN MAX
80A 30mA
80A 30mA
80A 30mA
3
3
5
6
9
12
* WAYS
MIN MAX
TD RCD
100A 100mA
100A 100mA
100A 100mA
3
3
5
6
9
12
* WAYS
TOTAL
9
12
17
DUAL TARIFF 100A MAIN SWITCH & 100A MAIN SWITCH
CAT REF
NMIIX2406
NMIIX3306
NMIIX5406
NMIIX4506
NHIIX3906
NHIIX4806
NMIIX7506
NMIIX6606
NMIIX5706
NMIIX9806
NMIIX8906
NMIIX51206
NMIIX11606
MS RATING
*WAYS
MS RATING
* WAYS
63A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
2
3
5
4
3
4
7
6
5
9
8
5
11
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
4
3
4
5
9
8
5
6
7
8
9
12
6
DUAL TARIFF 100A MAIN SWITCH & 100A 30mA RCD SWITCH
CAT REF
NMIIX4506
NMRSX5706
NMRSX6606
NMRSX7506
NMRSX8906
NMRSX9806
RCD RATING
MCB WAYS
MS RATING
*WAYS
100A 30mA
100A 30mA
100A 30mA
100A 30mA
100A 30mA
5
5
7
8
9
100A
100A
100A
100A
100A
7
6
5
9
8
SPLIT LOAD DUAL TARIFF 100A MAIN SWITCH & 100A 30mA RCD SWITCH
CAT REF
NMRS10SLMDT
NMRS15SLMDT
RCD RATING
MCB WAYS
MS RATING
*WAYS
100A 30mA
100A 30mA
2-5
2-5
100A
100A
2-5
2-5
NM All Metal Consumer Units
NMISS10SLM
NMISS15SLM
MS
WAYS
SPLIT LOAD DUPLEX
TOP BANK
MS RATING
*WAYS
CAT REF
NMDIS88
NMDIS1111
NMDIS1414
NMDIS1919
6
100A
100A
100A
100A
80A 30mA
80A 30mA
80A 30mA
80A 30mA
8
11
14
19
HIGH INTEGRITY DUPLEX 2 xRCDS, 1x 100A MAIN SWITCH
CAT REF
Duplex All Metal Consumer Units & FAL Skeleton Units
8
11
14
19
BOTTOM BANK
RCD RATING
MCB WAYS
80A 30mA
RCD WAYS
BOTTOM BANK
NMDRS14SSLHI
NMDRS20SSLHI
NMDRS26SSLHI
NMDRS36SSLHI
80A 30mA
RCD WAYS
BOTTOM BANK
-
8
11
14
19
80A 30mA
RCD WAYS
TOP BANK
* WAYS
MS
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
TOTAL
14
20
26
36
HIGH INTEGRITY DUPLEX 3xRCDS, 1x 100A MAIN SWITCH
CAT REF
80A 30mA
RCD WAYS
BOTTOM BANK
NMDRS12HI
NMDRS18HI
NMDRS24HI
NMDRS34HI
80A 30mA
RCD WAYS
BOTTOM BANK
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
80A 30mA
RCD WAYS
TOP BANK
* WAYS
MS
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
Flexi
TOTAL
12
18
24
34
DUAL RCD DUPLEX 2 x RCDS, 100A MAIN SWITCH
CAT REF
BOTTOM BANK
80A 30mA
80A 30mA
RCD WAYS RCD WAYS
NMDISS119
NMDISS1214
NMDIS1111
-
11
14
TOP BANK
80A 30mA
MS
RCD WAYS
WAYS
9
12
-
TOTAL
20
26
DUAL TARIFF DUPLEX
CAT REF
TOP BANK
MS RATING
*WAYS
NMDIIX88
NMDIIX1111
NMDIIX1414
NMDIIX1919
CAT REF
BOTTOM BANK
MS RATING
* WAYS
100A
100A
100A
100A
8
11
14
19
100A
100A
100A
100A
8
11
14
19
MS RATING
*WAYS
RCD RATING
MCB WAYS
100A
100A
100A
100A
8
11
14
19
80A 30mA
80A 30mA
80A 30mA
80A 30mA
8
11
14
19
NMDISX88
NMDISX1111
NMDISX1414
NMDISX1919
MAIN SWITCH
CAT REF
80A 30mA
RCD WAYS
80A 30mA
RCD WAYS
MS
RATING
* WAYS
TOTAL
-
-
100A
100A
100A
8
12
17
8
12
17
-
Flexi
Flexi
100A
100A
Flexi
Flexi
10
15
Flexi
Flexi
7
Flexi
Flexi
6
100A
100A
100A
Flexi
Flexi
2
10
13
15
Flexi
Flexi
6
5
7
100A
100A
100A
100A
100A
-
10
15
10
10
15
FALNH806
FALNH1206
FALNH1706
SPLIT LOAD
FALNHRS10SL
FALNHRS15SL
HIGH INTEGRITY
FALNHRS10SSL
FALNHRS13SSL
FALNHRS76206
DUAL SPLIT LOAD RCD
FALNHISS10SL
FALNHISS15SL
FALNHISS4606
FALNHISS5506
FALNHISS8706
FALNHR10SL
Flexi
Flexi
4
5
8
RCD INCOMER
CAT REF
FALNHRS706
FALNHRS1106
100A 30mA
RCD WAYS
TOTAL
7
11
7
11
* RCBOs or MCBs may be fitted depending upon the installation requirements.
For use in full metal meter cabinets (non combustible).
MAIN SWITCH DUAL SUPPLY PV CONSUMER UNIT WITH MID
CERTIFIED GENERATION METER
CAT REF.
DESCRIPTION
NM15DSMPVF
NM10DSMPVF
NM14DSRCBMPVF
NM9DSRCBMPVF
15 Way unit with dual supply isolators & 16A SP MCB
10 Way unit with dual supply isolators & 16A SP MCB
14 Way unit with dual supply isolators & 16A DP RCBO
9 Way unit with dual supply isolators & 16A DP RCBO
7
HIGH INTEGRITY DUAL SUPPLY PV CONSUMER UNIT WITH MID
CERTIFIED GENERATION METER
CAT REF.
DESCRIPTION
NM11DSMPVHI
NM10DSRCBMPVHI
11 Way unit with dual supply isolators & 16A SP MCB
10 Way unit with dual supply isolators & 16A DP RCBO
HIGH INTEGRITY DUAL SUPPLY P V CONSUMER UNIT
NM12DSPVHI
NM11DSRCBPVHI
12 Way unit with dual supply isolators & 16A SP MCB
11 Way unit with dual supply isolators & 16A DP RCBO
Double Pole MCB options available on request
NM11DSMPVHI
SPLIT LOAD DUAL SUPPLY PV CONSUMER UNIT WITH MID
CERTIFIED GENERATION METER
CAT REF.
DESCRIPTION
NM13DSMPVSL
NM8DSMPVSL
NM12DSRCBMPVSL
NM7DSRCBMPVSL
13 Way unit with dual supply isolators & 16A SP MCB
8 Way unit with dual supply isolators & 16A SP MCB
12 Way unit with dual supply isolators & 16A DP RCBO
7 Way unit with dual supply isolators & 16A DP RCBO
DUAL RCD DUAL SUPPLY PV CONSUMER UNIT WITH MID
CERTIFIED GENERATION METER
NM13DSMPVSL
CAT REF.
DESCRIPTION
NM11DSMPVDR
NM6DSMPVDR
NM10DSRCBMPVDR
NM5DSRCBMPVDR
11 Way unit with dual supply isolators & 16A SP MCB
6 Way unit with dual supply isolators & 16A SP MCB
10 Way unit with dual supply isolators & 16A DP RCBO
5 Way unit with dual supply isolators & 16A DP RCBO
Double Pole MCB options available on request
P V CONSUMER UNIT
Insulated metered consumer unit supplied with either Main Switch
and 16A SP MCB or 16A RCBO with optional MID meter.
l 63A 320V AC DP Isolator
l 16A B Curve SP MCB
l 40A direct read MID Meter.
l Ready assembled consumer unit complete with MID Certified meter
l Combined unit simplifies and speeds up installation
l Complete with Isolator & MCB
l Easy read permanently displayed kWh reading
l Option available with RCBO or MCB
NMB16MPV
CAT REF.
DESCRIPTION
NMRCBO16BMPV
NMB16MPV
NMRCBO16BPV
NMB16PV
With DP 16A RCBO (with meter)
With SP 16A MCB (with meter)
With DP 16A RCBO (no meter)
With SP 16A MCB (no meter)
P V supplies should be connected to a dedicated circuit at the
consumer unit (not share a final sub circuit)
P V supplies should be connected to the supply side of the MCB at
the consumer unit (not reverse fed)
P V Meters must comply with MID2004/22/EC B&D or B&F
Note : Surge Protection devices and Type B RCDs are
available on request
Photo Voltaic All Metal Consumer Units
NM15DSMPVF
MINIATURE CIRCUIT BREAKERS (6KA)
Consumer Unit Outgoing Devices & Control Modules
8
NHXB06
NHXB16
NHXB32
NHXB50
NHXB10
NHXB20
NHXB40
B CURVE
C CURVE
RATING
POLES
MODULES
NHXB06
NHXB10
NHXB16
NHXB20
NHXB25
NHXB32
NHXB40
NHXB50
NHXC03
NHXC06
NHXC10
NHXC16
NHXC20
NHXC32
NHXC40
NHXC50
3A
6A
10A
16A
20A
25A
32A
40A
50A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ACCESSORIES
MCBLDX
WPL
MCB Locking device
Padlock for MCBLDX
NSBS RCBO ( combined MCB / RCD device )
NHXSBS1B06 NHXSBS1B16 NHXSBS1B32 NHXSBS1B50
NHXSBS1B10 NHXSBS1B20 NHXSBS1B40
B CURVE
C CURVE
RCD RATING
POLES
MODULES
NHXSBS1B06
NHXSBS1B10
NHXSBS1B16
NHXSBS1B20
NHXSBS1B32
NHXSBS1B40
NHXSBS1B50
NHXSBS1C06
NHXSBS1C10
NHXSBS1C16
NHXSBS1C20
NHXSBS1C32
NHXSBS1C40
NHXSBS1C50
6A
10A
16A
20A
32A
40A
50A
30mA
30mA
30mA
30mA
30mA
30mA
30mA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
WRCBL6C2+
WRCBL10C2+
WRCBL16C2+
WRCBL20C2+
WRCBL32C2+
6A
10A
16A
20A
32A
30mA
30mA
30mA
30mA
30mA
2
2
2
2
2
2
2
2
2
2
WRCBL40C2+
40A
30mA
2
2
-
CURRENT RATING
+ Suitable for flexible comb busbar consumer units only
DIN RAIL MODULAR DEVICES FOR USE IN + UNITS & FLEXIBLE UNITS
MESB-40NO
CAT REF
PRODUCT
ME242/230
SMSCD11
TMSCD21
TMTCD22
MESB-20NO
MESB-24NO
MESB-40NO
MESB-63NO
MTS8
TRMSCT31
TRMSCT11
SMSCT11
Staircase timer
Digital time clock 1 channel 1xNO/NC contact 16A
Digital time clock 1 channel 1xNO contact 16A
Digital time clock 2 channel 24 hour 7Day prog
20A 2 pole contactor
24A 4 pole contactor
40A 4 pole contactor
63A 4 pole contactor
Bell transformer 12V 8VA
Disc type time clock 1 channel 1xNC contact 16A
Disc type time clock 1 channel 1xNC contact 16A
Disc type time clock 1 channel 1xNO contact 16A
MODULE
1
1
2
2
1
2
3
3
2
3
3
1
When fitting in NH Consumer Units contact Wylex technical services department
NH ACCESSORIES
NMMB
NHB1PP
CAT REF
PRODUCT
NMMB
NHB1PP
NHET25
WPL
NH13CBKIT
Metal blanking plate - Twist fit
1
Blanking plate - Busbar & cover (insulated 960ºC)
1
25mm Earth Terminal
Padlock for NHLDK & MCBLDX
13 pin comb busbar c/w labels and 5 protection covers
MODULE
FLUSH MOUNTING KITS FOR NM
CAT REF
PRODUCT
NM07FLA
NM10FLA
NM13FLA
NM16FLA
NM21FLA
7 module flush kit assembly
10 module flush kit assembly
13 module flush kit assembly
16 module flush kit assembly
21 module flush kit assembly
9
For use on upgrading NM metal units only
Accessories
NM CONSUMER UNIT PATTRESSES
CAT REF
TOP/BOTTOM
LEFT/RIGHT
CABLE ENTRY
ENCLOSURE
WIDTH
DEPTH
MNSPE-6462/BNR
MNSPE-6462/CNR
MNSPE-6462/DNR
MNSPE-6462/ENR
MNSPE-6462/FNR
MNSPE6668/7NR
MNSPE6668/10NR
MNSPE6668/13NR
MNSPE6668/16NR
MNSPE6668/21NR
7 Module
10 Module
13 Module
16 Module
21 Module
16mm
16mm
16mm
16mm
16mm
For use with NM consumer units. Allows surface cable entry through rear
knockouts and automatically maintains enclosure IP rating to comply with BS7671
and BSEN61439-3
• Cable entry slot may be positioned top or bottom, or left/right
ACCESSORIES
CAT REF
PRODUCT
EIU
Moulded cable gland kit for metal consumer unit to
provide additional support and supplementary insulation
similar to Class II construction for the incoming cables.
Suitable for 16mm2 or 25mm2 cable
32mm knockout
NH UPGRADE / REPLACEMENT COVER
CAT REF
PRODUCT
NH7/MCLA255G
NH10/MCLA255G
NH13/MCLA255G
NH16/MCLA255G
NH21/MCLA255G
7 module cover assembly
10 module cover assembly
13 module cover assembly
16 module cover assembly
21 module cover assembly
For use on upgrading existing NH metal units only (replacing cover, plastic visor
and hinges). Colour Grey RAL 7035
RCCB
CAT REF
PRODUCT
P.O.A
100A 100mA time delay RCCB
Products made to order. Contact Wylex technical
Also see data on page 3, items A & B
CUSTOM BUILT
To meet the ever changing requirements and
designs of the modern electrical installation,
Wylex offers a service to the electrical
installer for all the catalogued NM range of
products - Consumer Units, and Distribution
Boards to be modified and assembled to their
own particular specification and meeting
specific customer needs.
The levels of adaptation may vary from the
basic pre-population and assembly of outgoing
protective devices MCBs, RCBOs into the
units with personalised labelling, to the
complete customisation and wiring of
additional accessory devices within a unit:for example meters, energy monitors,
control switching equipment:- contactors,
relays and timers, and over voltage surge
protection devices plus almost any other
DIN rail mounted piece of electrical
accessory equipment that is available.
This Custom Built service can save time on
site, reduce labour costs, and help achieve
early completion & ultimately save money
for the installer of these units.
Custom built metal consumer unit with
circuit protection and control devices fitted
METAL CONSUMER UNITS
D
DIMENSIONS 185(H) 130(W) 104(D)
4 MODULE
121
98
261
200
255
NM206/40
NM206/63
NMRS206/40
NMRS206/63
11
DIMENSIONS D=188mm(7.4"), E=138mm(4.2")
7 MODULE
NMRS506
NMRM506
DIMENSIONS D=241mm(9.5"), E=160mm(6.3")
10 MODULE
NMRM806
NM10ED6
NMRS2406
NMRS3306
E
NMRS4206
NMRS6SLM
NM806
NMRS806
NMSTM2406
NMSTM3306
NMTM806
DIMENSIONS D=292mm(11.5"), E=210mm(8.3")
13 MODULE
NMRM1106
NMSTM3606
NM1106
NMRS4506
NMSTM5406
NM806+3
NMRSS5406
NMRS9SLM
NMIIX2406
NMRS806+3
NMRS1106
NMRS806+3
NMRS5406
NM13ED6
NMSTM4506
NMRS6306
NMTM1106
NMIIX3306
NMRS23206
NMRS7SSLMHI
DIMENSIONS D=343mm(13.5"), E=260.4mm(10.2")
16 MODULE
NM1406
NMRS1106+3
NMRS4806
NMRS1406
NMRM1106+3
NMRS6606
NM16ED6
NMRM1406
NM806+6
NMRS3906
NMSTM7506
NMRM806+6
NMTM1406
NMRS12SLM
NM1106+3
NMSTM8406
NMISS5506
NMISS10SLM
NMRS44206
NMRS43306
NMRS33406
NMRS10SSLMHI
DIMENSIONS D=438mm(17.2"), E=356mm(10.1")
21 MODULE
NM1906
NMRS61106
NMRS9806
NMRS17SLM
NMSTM9806
NM21ED6
NMSTM8906
TOP/BOTTOM CABLE ENTRY PATTRESS
NMRS1906
NMRS8906
NMSTM71006
NMSTM9806
NMRS5606+6
NMTM1906
NMIIX51206
NMIIX11606
MNSPE6463/BNR
MNSPE6463/CNR
MNSPE6463/DNR
MNSPE6463/ENR
MNSPE6463/FNR
7 Module
10 Module
13 Module
16 Module
21 Module
255
D
NMISS8706
NMISS15SLM
NMRS76206
NMRS66306
NMRS46506
NMRS55506
NMRS45606
NMRS15SSLMHI
MNSPE6668/7NR
MNSPE6668/10NR
MNSPE6668/13NR
MNSPE6668/16NR
MNSPE6668/21NR
CABLE ENTRY PATTRESS
CONSUMER UNIT
TOP/BOTTOM
ENCLOSURE SIZE (D) CABLE ENTRY
LEFT/RIGHT
CABLE ENTRY
7 Module
10 Module
13 Module
16 Module
21 Module
MNSPE6668/7NR
MNSPE6668/10NR
MNSPE6668/13NR
MNSPE6668/16NR
MNSPE6668/21NR
16
LEFT/RIGHT CABLE ENTRY PATTRESS
255
D
16
188mm
241mm
282mm
343mm
438mm
MNSPE6463/BNR
MNSPE6463/CNR
MNSPE6463/DNR
MNSPE6463/ENR
MNSPE6463/FNR
Dimensions
NM506
NMTM506
NM7ED6
DUPLEX METAL
F
127
94
DIMENSIONS
F=241mm(9.5"), G=160mm(6.3")
10 MODULE
NMDIS88
NMDIIX88
NMDISX88
500
302
Dimensions
12
NMDRS12HI
NMDRS14SSLHI
DIMENSIONS
F=292mm(11.5"), G=210mm(8.3")
13 MODULE
NMDIS1111
NMDIIX1111
NMDISX1111
NMDRS18HI
NMDRS20SSLHI
NMDISS119
DIMENSIONS
F=343mm(13.5"), G=260mm(10.2")
16 MODULE
NMDIS1414
NMDIIX1414
NMDISX1414
NMDRS24HI
NMDRS26SSLHI
NMDISS1214
G
DIMENSIONS
F=430mm(17.2"), G=235mm(10.1")
21 MODULE
NMDIS1919
NMDIIX1919
NMDISX1919
NMDRS34HI
NMDRS36SSLHI
SKELETON
A
DIMENSIONS
A=333mm(13.2"), B=165mm(6.5"), C=90mm(3.5”) D=230mm(9”)
FALNHRS8SSL
FALNHISS4606
FALNHRS10SL
D
FALNHISS5506
FALNHISS10SL
FALNH806
B
DIMENSIONS
A=444mm(17.5"), B=165mm(6.5"), C=90mm(3.5”)
D=230mm(9”)
C
FALNHRS13SSL
FALNHISS15SL
FALNHRS55506
FALNHRS76206
FALNH1706
FALNHISS8706
FALNHRS46506
FALNHRS66306
FALNHRS15SL
FALN1206
13
Acknowledged as the market leader in the UK domestic circuit protection
market Wylex offers designers & specifiers a wide range of quality products that
caters for a vast array of applications including domestic (household) premises.
Wylex factories operate a
series of internationally
recognized standards
including ISO9001 for quality,
OHSAS 18001 for Health &
Safety and ISO14001 for
Environmental Management.
UK locations are home to the
product management,
engineering, design, quality
& logistics teams.
In the UK Wylex has its UKAS
accredited Laboratory that carries out R&D and
compliance testing on all Wylex products, these
highly accredited facilities ensure that safety, quality
& reliability remain consistent with UK & EU legislation regulations &
Siemens internal standards, policies and practices.
Wylex products are all designed manufactured and tested in
accordance with the recognised BS, EN & ICC product standards, and backed
by standard & extended guarantees.
Wylex also operates to recognised standards for product safety & sustainability,
Wylex products are RoHS and REACH compliant often in excess of the UK
market standards
Recycled materials are used in product packaging,
and declared into a recycling scheme locally to
control environmental impacts and assure that the
maximum level of recycling of materials and use of
recycled materials is achieved.
As a Siemens company Wylex also operates a zero
harm scheme within all of its manufacturing
logistics & sales facilities, and is proud to have
achieved a 5 star Health & Safety rating.
ELECTRIUM SALES LIMITED A SIEMENS COMPANY
Commercial Centre, Lakeside Plaza, Walkmill Lane, Bridgtown, Cannock WS11 0XE.
eMail: info@electrium.co.uk Web: www.electrium.co.uk
UK SALES
Telephone: 01543 455020 Facsimile: 01543 455021 eMail: wylex.sales@electrium.co.uk
TECHNICAL
Telephone: 01543 438320 Facsimile: 01543 438321 eMail: wylex.technical@electrium.co.uk
EXPORT SALES
Telephone: +44 1543 455049 Facsimile: +44 1543 455048 eMail: export@electrium.co.uk
Although every effort has been made to ensure accuracy in the compilation of the technical detail within this publication, specifications and performance data are constantly changing. Latest details can be obtained from Wylex.
Publication No. WY2202b 11/15
Printed in England.