Installation Sheets Manual Temperature Controls Section Technical Bulletin Issue Date 121 A A19 0588 A19 Series Immersion Hot Water Controls -- SPST and SPDT Application These controls are used on hot water boiler systems. Typical applications include: • high temperature cutout control • operating control to maintain hot water supply • circulator or unit heater control • ! CAUTION: Do not dent or deform the sensitive bulb of this control. A dent or deformation will change the calibration and cause the control to cycle at a temperature lower than the dial setting. 1. combined operating and circulator control Drain the system to a level below tapping. 2. The controls have an adjustable range and adjustable or fixed differential. They are also available with lockout that requires manual reset. Remove bulb well from the control by loosening set screws in the hex nut. 3. Place a small amount of pipe dope on the bulb well threads to prevent leakage. 4. Turn bulb well securely into the boiler tapping. All Series A19 temperature controls are designed for use only as operating controls. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) or systems (alarm, supervisory systems) that protect against, or warn of, control failure. Installation Follow equipment manufacturers’ instructions, if provided. Mount the control in top or side boiler tappings. Specifications Fig. 1 -- An A19 Hot Water Control less cover with adjustable differential. To install: 5. Insert the bulb into well applying a firm pressure to be sure the bulb is at bottom of well. Tighten set screws. a. ! CAUTION: Be sure that unobstructed depth is sufficient so bulb well will not make metal-to-metal contact. The bulb well must be completely submerged-avoid mounting where it might be partly above the operating liquid level or surrounded by an air pocket. On remote bulb models, remove bushing from the bulb well. Insert bulb into well. Slide bushing over capillary and push into bulb well. Tighten set screws. ! CAUTION: For Remote Mounting Models Only. On rough mounting surfaces use the top two mounting holes only. When these controls are mounted on an uneven surface using screws in all four holes, the case can be twisted enough to affect the control’s calibration and operation. Wiring ! CAUTION: Disconnect power supply before wiring connections are made to avoid possible electrical shock or damage to equipment. © 1988 Johnson Controls, Inc. Form 997-529-7 Code No. LIT-121020 1 3. All wiring should conform to the National Electrical Code and local codes. Single-pole, double-throw models should be wired as shown in Fig. 3. Red is the common terminal. Use copper conductors only. ! CAUTION: Use terminal screws furnished (8-32 × 1/4 in. binder head). Substitution of other screws may cause problems in making proper connections. Adjustments Dial settings normally indicate the cutout setting unless otherwise specified by the equipment manufacturer. Models with SPDT contacts are normally set so the red (common) to blue contacts open at the dial setting on a rise in temperature. Rotate adjusting knob to raise or lower both the cutout and cut-in settings. Convertible adjustment models can be field converted from concealed screwdriver slot adjustment to knob adjustment or external screwdriver slot adjustment. They are supplied with a snap-in plug in the cover to provide concealed screwdriver slot adjustment. For knob adjustment remove the snap-in plug and press the knob onto the slotted shaft. For external screwdriver slot adjustment remove the snap-in plug. Models with adjustable differential have a differential scale plate (see Fig. 1) with a multiplier shown. For example, when “MIN.” differential is 6F° (3.3C°), then x2 is 12F° (6.6C°), x3 is 18F° (9.9C°), etc. The controls are supplied with adjusting lever at minimum differential stamped on the control. To adjust, move the lever to the differential required. Loosen the cutout stop screw, slide the screw to the front of the temperature control against the plastic step behind the dial and tighten the screw. (See Fig. 4.) Note: Sometimes an exact stop setting is not possible and the stop must be set to the closest step corresponding to the dial setting. Checkout Procedure Before applying power, make sure installation and wiring connections are according to job specifications. Before leaving the installation, observe at least three complete operating cycles to be sure that all components are functioning correctly. Repairs and Replacement Field repairs must not be made. For a replacement control contact the nearest Johnson Controls wholesaler. High Temperature Cutout Stop Fig. 2 -- An A19 with convertible adjustment has a snap-in plug in the cover and a knob for field installation. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 2 A19 Technical Bulletin The high temperature cutout stop is an integral part of these hot water controls and can be field adjusted. To set high temperature cutout stop, proceed as follows: 1. Set dial to temperature at which stop is desired. 2. Remove control cover. Printed in U.S.A.