MCV2500 Series Control Valves

advertisement
MCV2500 SERIES
2-WAY AND 3-WAY HYDRONIC VALVES
PRODUCT SPECIFICATION SHEET
FEATURES
2-way or 3-way body
Control by a low or line voltage SPST or SPDT
controller
100~130 VAC or 200~240VAC actuators available
1000mm lead wires
Minimal actuator power consumption
Pressure differential up to 3.0bar
1~90 °C fluid temperature
0~65 °C ambient temperature
APPLICATION
The MCV2500 series hydronic valves are designed for
residential heating and cooling applications.
The MCV2500 series 2-position hydronic valves are
used in residential and small commercial applications
to control the flow of hot and/or cold water. They
consist of actuator and valve.
2-way valves are designed for ON-OFF "zone" control
of domestic systems.
3-way valves can be piped for mixing valve
applications to control individual fan coil, baseboard
radiator in domestic central heating and/or cooling
systems.
2-way valves are suitable from A to B, and 3-way
valves are for mixing water from A or B to AB.
Depending on the model selected they can be
controlled by a low or line voltage SPST or SPDT
controller, such as a room thermostat, aquastat or flow
switch.
ENS5002R0 KO06 2005
Contents
Application ………………………………………………… 1
Features …………………………………………………… 1
Specification ………………………………………………… 2~3
Dimensions ………………………………………………… 3
Installation …………………………………………………. 4
Wiring Diagram ……………………………………………… 4
1
MCV2500 SERIES HYDRONIC VALVE
SPECIFICATION
Voltage
: AC110/220V±10%, 50/60Hz
Pipe connection
: PT
Colour-coded
label
: Green, Black, White
Maximum pressure
: 16bar max.
Control
Performance
: SPST/SPDT control
Electrical termination
: with integral 1000mm lead-wire cable
Power
consumption
Operational life
Timing
Ambient Temperature : 0 ~ 65 °C
: 6W at nominal voltages
(during valve position change only)
: Greater than 60,000 cycles (all loads) for
motor and valve contacts at 110/220 V
Ambient Humidity
: 10 ~ 95%RH (no condensing)
Storage temperature
: -25 ~ 65 °C
Storage Humidity
: 10 ~ 95%RH (no condensing)
: 20sec
Table 1. Kv & Differential Pressure
Valve
Size
Port
Kv
Max. operating differential pressure
2-way valve
3/4"
A to B
3.0
3.0 bar
3-way valve
3/4"
A to AB
3.0
3.0 bar
B to AB
3.0
1.0 bar
Table 2. Model selection guide (1)
MCV2510AJ
MC25 10 HE + MV2000 A J
* MC25 : Actuator family identifier
* J : 3/4”, Both internal thread
* xx00 : AC220V, SPST
* xx01 : AC220V, SPDT
* xx10 : AC110V, SPST
* xx11 : AC110V, SPDT
* A : 2-way valve
* M : 3-way valve
* HE : 1.5Nm motor
* MV2000 : valve family identifier
* MCV2510AJ = MC2510HE + MV2000AJ : AC110V, SPST, 1.5Nm, 3/4”, 2-way valve (with both internal thread & PT fitting)
ENS5002R0 KO06 2005
2
MCV2500 SERIES HYDRONIC VALVE
Table 3. Model selection guide (2)
Assembled
Actuator
Valve
Model OS#
OS#
OS#
MCV2500AJ
MC2500HE
MV2000AJ
AC220V, SPST, 1.5Nm, 3/4" 2-way valve, Both internal thread, PT fitting
MCV2501AJ
MC2501HE
MV2000AJ
AC220V, SPDT, 1.5Nm, 3/4" 2-way valve, Both internal thread, PT fitting
MCV2510AJ
MC2510HE
MV2000AJ
AC110V, SPST, 1.5Nm, 3/4" 2-way valve, Both internal thread, PT fitting
MCV2511AJ
MC2511HE
MV2000AJ
AC110V, SPDT, 1.5Nm, 3/4" 2-way valve, Both internal thread, PT fitting
MCV2500MJ
MC2500HE
MV2000MJ
AC220V, SPST, 1.5Nm, 3/4" 3-way valve, Both internal thread, PT fitting
MCV2501MJ
MC2501HE
MV2000MJ
AC220V, SPDT, 1.5Nm, 3/4" 3-way valve, Both internal thread, PT fitting
MCV2510MJ
MC2510HE
MV2000MJ
AC110V, SPST, 1.5Nm, 3/4" 3-way valve, Both internal thread, PT fitting
MCV2511MJ
MC2511HE
MV2000MJ
AC110V, SPDT, 1.5Nm, 3/4" 3-way valve, Both internal thread, PT fitting
Specification
* Product Examples
-
MCV25xxAJ/MJ : Assembled model, Egg crate with 10 actuators and 10 valves
-
MC25xxHE : Actuator only, Egg crate with 15 actuators
-
MV2000AJ/MJ : Valves only, Egg crate with 30 pieces of 2-way/3-way valves
DIMENSIONS
Fig. 1 2-way MCV Dimensions (in mm)
ENS5002R0 KO06 2005
Fig. 2 3-way MCV Dimensions (in mm)
3
MCV2500 SERIES HYDRONIC VALVE
WARNING
CAUTION
Take care that installer is a trained experienced service
person.
Disconnect Power Supply before making electrical
connections to prevent electrical shock and
equipment damage.
When installing this product:
Read these instructions carefully.
Failure to follow them could damage the product or
cause a hazardous condition.
Check the ratings given in the instructions and on the
product to make sure it is suitable for your application.
Always conduct a through checkout after installation.
INSTALLATION
WIRING DIAGRAM
1. The valve may be plumbed in any angle but
preferably not with the actuator head below the
horizontal level of the valve body. Make sure there is
enough room around the actuator head for servicing
or replacement.
2. The valve body can be mounted directly onto the inlet
pipe. Mount the metal flange inserted in socket to
outlet pipe. And then tighten the socket enough to
make a seal. See Figure 1~2 for the detail dimension.
3. Mount the valve directly in the tube or pipe. Do not
grip actuator head while making and tightening
plumbing connections. Either hold valve body in your
hand or attach adjustable spanner across the
hexagonal or flat faces on the valve body.
MCV2500 Series
WHITE
(OPEN)
SPST Controller
BLACK
(CLOSE)
L
NO
N
NC
RLY
GREEN
Fig. 3 Diagram with 3-wire Actuator for SPST Controller
SPDT Controller
WHITE
MCV2500 Series
(OPEN)
NC
NO
BLACK
L
(CLOSE)
N
GREEN
Fig. 4 Diagram with 3-wire Actuator for SPDT Controller
Honeywell Co., Ltd.
Environmental Controls
18F, Kukje Center Building 191, Hangangro-2ga,
Yongsan-gu, Seoul, 140-702, Korea
Tel. 82-2-799-6170/6194
Fax. 82-2-799-6188
ENS5002R0 KO06 2005
4
Download