EMERGENCY BACKUP 700 LUMENS
INSTALL INSTRUCTIONS
ASSEMBLY AND INSTALLATION INSTRUCTIONS
WARNING: When using this lighting device, safety precautions should be followed at all times
READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY!
1. This device is designed for indoor use. Do not use outdoors.
2. Prior to installation, battery connector must be open to prevent high voltage from being present on
out put leads (red & yellow).
3. This device is designed for use with 17W–110W single pin or bipin fluorescent lamps, from
2’ through 8’. Please use energy-saving circline, U-shaped, or 4-pin rapid start long compact
fluorescent lamps.
4. Please ensure the electricity connections conforms to the National Electrical Code and local
regulations if applicable.
5. To avoid electric shock, please disconnect normal and emergency power supplies, and battery
connector of the emergency ballast before servicing.
6. This device is designed for factory or field installation in either the ballast channel, or on top of the
indoor fixture, except air handling heated air outlets, wet or hazardous location fixtures. Do not install
this device near gas or electric heaters.
7. AC power source of 120 VAC or 277 VAC is required.
8. The battery is sealed, non-maintenance, and is not replaceable in the field. Please contact
manufacturer for information on service. Do not attempt to service the battery please.
9. Do not use accessory equipment that is not recommended by manufacturer. Failure to do so may
cause unsafe conditions. Servicing should only be performed by qualified service personnel.
10. Do not use the product for other purpose that the product is NOT designed for.
PLEASE SAVE THESE INSTRUCTIONS
P.Q.L., Inc. • 2285 WARD AVENUE • SIMI VALLEY, CA 93065 • 800.323.8107 • FAX: 877.619.7053
www.PQLighting.com
82195
EMERGENCY BACKUP 700 LUMENS
INSTALL INSTRUCTIONS
INSTALLATION INSTRUCTIONS
NOTE: All the branch circuit wiring has to be ready as well as an unswitched source of
power before the fixture is installed. Confirm the same branch circuit would be used for both
the emergency ballast and the AC ballast.
DIAGRAM 1
CAUTION: Battery connector has to be opened for preventing high voltage on output leads
(red and yellow). Wait until the installation process has been completed and AC is supplying
power to the emergency ballast, and then join the battery connector.
1. AC power has to be off before installation.
2. Choose the right wiring diagram to connect the ballast to the AC ballast and lamp.
3. Please ensure the electricity connections conform to the National Electrical Code and
local regulations.
4. Follow diagrams 1 and 2 to install the battery pack on the top of the fixture or in the ballast
channel.
DIAGRAM 2
5. To install the test switch, it would go through the side of a strip fixture or the ballast
channel cover of a troffer. Follow diagrams 1 and 2 to drill a 1/2” hole and install the test
switch. In order to remove AC power from both the emergency ballast and the AC ballast, the
test switch has to be connected properly (see diagram 4).
6. Match violet and brown leads to connect the charging indicator light to the battery pack
(see diagram 5). The charging indicator will be on after the fixture is installed properly.
7. Please search for a readily visible location to apply the CAUTION label which reads, “This
unit has more than one power supply connection point. To reduce the risk of electric shock,
disonnect both the branch circuit-breakers or fuses, and emergency power supply before
servicing.”
8. Do not join the inverter connector until the fixture is completely installed and supply.
AC power to the emergency ballast.
DIAGRAM 3
9. The battery needs to be charged for one hour in order to have short-term testing on the
emergency function. Before having a long-term emergency function testing, the battery in the
emergency ballast has to be charged for 24 hours.
DIAGRAM 4
SINGLE POLE
UNSWITCHED FIXTURE
SWITCHED FIXTURE
P.Q.L., Inc. • 2285 WARD AVENUE • SIMI VALLEY, CA 93065 • 800.323.8107 • FAX: 877.619.7053
www.PQLighting.com
82195
EMERGENCY BACKUP 700 LUMENS
INSTALL INSTRUCTIONS
DIAGRAM 5
TROFFER-STYLE FIXTURE
OPTIONAL STRIP-STYLE FIXTURE
Fixture
Fixture
Emergency Ballast
Indicator
Light
Ballast Channel Cover
Violet (+)
Leads to Charging Indicator Light
Brown (-)
Indicator
Ligh t
Fixture
Violet (+)
Brown (-)
7/8” Punc h
7/8” Bushing Inserted int
Ballast Channel Cover
AC O N
TEST
o
Plastic Tubing
(please cut to necessary length)
Step 1S
tep 2
1/2” White Bushing to Hold
Charging Indicator Light
Fixture Len s
Charging Indicator Light
OPERATION
• The charging indicator light would be on to indicate the battery is being charged when AC power is applied.
• This emergency ballast would function and operate one or two lamps at least 90 minutes when the AC power is failed.
TESTING & MAINTENANCE
Note: Services should only performed by qualified personnel. The emergency ballast should be checked periodically to
confirm proper functioning and the following schedule is recommended:
1. To inspect the charging indicator every month and confirm that is illuminated.
2. Push the test switch for 30 seconds to ensure the emergency ballast is functioning. Recommended to perform this
testing every 30 days.
3. Perform a long-term test (90-minute battery discharge) at least once every year. One or two lamps should operate for
no less than 90 minutes.
P.Q.L., Inc. • 2285 WARD AVENUE • SIMI VALLEY, CA 93065 • 800.323.8107 • FAX: 877.619.7053
www.PQLighting.com
82195
EMERGENCY BACKUP 700 LUMENS
INSTALL INSTRUCTIONS
WIRE DIAGRAMS FOR 1 and 2 LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
FOR 1 LAMP EMERGENCY OPERATION
A. INSTANT START AC BALLAST
AC
BALLAST
E. THREE-LAMP INSTANT START BALLAST
LINE
EMERGENCY
BALLAST
BLUE
BLAC K
WHITE
AC
BALLAST
BLUE
BLUE
RED
BLUE
BL UE/WHITE
YELLOW/GRE EN
YELLO W
VIOLET (+)
BROWN( -)
ORANGE
BLA CK
WHIT E
EMERGENCY
BALLAST
RED
277 V
120 V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
WHIT E
RED
INVERTER
CONNECTOR
LAMP 1
LAMP 2
LAMP 3 (EMERGENCY)
F. THREE-LAMP RAPID START BALLAST
B. RAPID START AC BALLAST
LINE
AC
BALLAST
BLUE
BLAC K
WHITE
BLUE
AC
BALLAST
BLUE/WHITE
EMERGENCY
BALLAST
BLUE/WHITE
RED
RED
YELLOW
YELLOW
BLUE
ORANGE
BLA CK
WHIT E
BL UE/WHITE
YE LL OW/GREEN
YELLOW
EMERGENCY
BALLAST
277 V
120 V
COM
RED
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
WHIT E
VI OL ET (+ )
BR OW N(-)
RED
INVERTER
CONNECTOR
LAMP 1
LAMP 2
LAMP 3 (EMERGENCY)
C. TWO-LAMP INSTANT START BALLAST
LINE
BLUE
BLAC K
WHIT E
AC
BALLAST
BLUE
RED
BLUE
BL UE/WHITE
YELLOW /GRE EN
YELLOW
VI OL ET (+ )
BR OW N( -)
EMERGENCY
BALLAST
ORANGE
BLA CK
WHIT E
RED
277 V
120 V
COM
G. FOUR-LAMP INSTANT START BALLAST
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
LINE
BLUE
BLAC K
WHIT E
AC
BALLAST
YE LLOW
YE LLOW
WHIT E
INVERTER
CONNECTOR
YE LLOW
YE LLOW
BLUE
AC
BALLAST
RED
RED
LAMP 1
WH ITE
EMERGENCY
BALLAST
RED
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
277V
120V
COM
WHIT E
RED
INVERTER
CONNECTOR
LAMP 2
LAMP 3
LAMP 4 (EMERGENCY)
D. TWO-LAMP RAPID START BALLAST
BLUE
VI OL ET (+ )
BROWN( -)
ORAN GE
BLAC K
LAMP 1
LAMP 2 (EMERGENCY)
BLAC K
WHIT E
BLU E
BL UE/WHI TE
YE LL OW/GREEN
YE LL OW
RED
LAMP 1
LINE
BLUE
RED
RED
BLUE
BL UE/W HITE
YELLOW/GRE EN
YELLOW
VIOLET (+ )
BR OWN( -)
ORANGE
BLA CK
EMERGENCY
BALLAST
WHIT E
RED
277 V
120 V
COM
WHIT E
RED
H. FOUR-LAMP RAPID START BALLAST
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
LINE
BLACK
WHIT E
YE LL OW
YE LLOW
BROWN
BROWN
RED
RED
AC
BALLAST
INVERTER
CONNECTOR
BLUE/W HITE
BLUE/W HITE
BLUE
BLUE
BLUE
OR AN GE
BLUE/WHITE
YELLOW/ GREE N
BLAC K
YE LLO W
RE D
VI OLET (+ )
BR OW N(-)
EMERGENCY
BALLAST
WHITE
277V
120V
CO M
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
WHITE
RE D
LAMP 1
INVERTER
CONNECTOR
LAMP 2
LAMP 3
LAMP 2 (EMERGENCY)
LAMP 4 (EMERGENCY)
NOTE: Use the proper tap cap to unswitched AC lead
P.Q.L., Inc. • 2285 WARD AVENUE • SIMI VALLEY, CA 93065 • 800.323.8107 • FAX: 877.619.7053
www.PQLighting.com
82195
EMERGENCY BACKUP 700 LUMENS
INSTALL INSTRUCTIONS
WIRE DIAGRAMS FOR 1 and 2 LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
FOR 2 LAMP EMERGENCY OPERATION
A. TWO-LAMP INSTANT START AC BALLAST
AC
BALLAST
D. TWO-LAMP RAPID START AC BALLAST
AC
BALLAST
EMERGENCY
BALLAST
B. THREE-LAMP INSTANT START AC BALLAST
AC
BALLAST
E. THREE-LAMP RAPID START AC BALLAST
AC
BALLAST
EMERGENCY
BALLAST
C. FOUR-LAMP INSTANT START AC BALLAST
AC
BALLAST
EMERGENCY
BALLAST
EMERGENCY
BALLAST
F. FOUR-LAMP RAPID START AC BALLAST
AC
BALLAST
EMERGENCY
BALLAST
EMERGENCY
BALLAST
EMERGENCY ONLY OPERATION
A. ONE-LAMP WITHOUT AC BALLAST
B. TWO-LAMP WITHOUT AC BALLAST
EMERGENCY
BALLAST
EMERGENCY
BALLAST
NOTE: Use the proper tap cap to unswitched AC lead
P.Q.L., Inc. • 2285 WARD AVENUE • SIMI VALLEY, CA 93065 • 800.323.8107 • FAX: 877.619.7053