8 022 UNIGYR® VISONIK® Process Bus The process bus serves to exchange process-related data between the PRU and RWP80 process units for UNIGYR or PRV units for VISONIK and the PTM I/O modules. The process bus has been designed as a control panel bus and is thus referred to as Panel Bus or, in short, P-bus. Use The P-bus is a Landis & Staefa bus to transfer process-related data. The total length for the standard P-bus is 50 meters and 200 meters for the remote P-bus. Line connections to neighbouring control panels are permitted. P-bus structure The P-bus consists of the following three lines: P-bus L T1 8022Z01E – PD data line to transfer telegrams – PU reference voltage for PD and PC as well as DC voltage for I/O modules – PC clock line for telegram synchronisation G G0 G G0 N N1 U1 P-bus U2 p p N1 T1 U1 U2 Note Refer to the following documentation for information on units connected to the P-bus: – – – – – – – Siemens Building Technologies Landis & Staefa Division PRU, PRV, RWP80 process unit AC 230 V / AC 24 V transformer I/O module group with outputs to the control panel units I/O module group with outputs to external field devices I/O Modules PTM_. ... Data sheets 8100, 8110 to 8199, 8663 to 8666 Accessories for I/O Module System Data sheet 8105 Universal Process Unit PRU10.64 Data sheet 8211 Standard Process Unit RWP80 ... Data sheet 8221 Universal Process Unit PRU1 ... Data sheet 8241 Controller PRV1 ... Data sheet 8341 Process Units PR_2 ... Data sheet 8411 CM2N8022E / 02.1999 1/8 Mode of operation The sections below explain the mode of operation for data transmission on the P-bus. For UNIGYR and VISONIK, the terms ‘Master’ and ‘Slave’ can be replaced with ‘Process unit’ and ‘I/O module’ respectively. Master-Slave principle The master sends the start condition on the PC line (clock line for telegram synchronisation) to all slaves. A slave address and the function byte is then transmitted on the PD line (data line). The function byte determines if data is subsequently read or written. The master retrieves the data in the read telegram from the addressed status, measured value, or counter module. In the case of the write telegram, the commands to be executed are sent to the addressed switching or positioning module. Telegram format For read or write access, a telegram always consists of five bytes (= 40 bits). These bytes are transmitted in the following sequence: 1. 2. 3. 4. 5. byte byte byte byte byte I/O module address function, i.e., read or write access data 1 Data contents and structure are data 2 dependent on the I/O module function telegram check CRC test (= Cyclical Redundancy Check) Direction of data for the function in a polling cycle Read: 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Address Function Data 1 Data 2 CRC Write: 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Function Data 1 Data 2 Telegram with 5 bytes = 40 bits CRC 8022D01E Address Direction of data: Master-slave Direction of data: Slave-master Telegram termination with telegram check After the 40th bit, the telegram is terminated. If the transmission was error-free, an acknowledge is sent and a not acknowledge in the case of a faulty transmission. If the latter applies, the telegram is re-transmitted. Note At the given transmission rate of 62.5 kBaud (62,500 bps) over 1,000 telegrams can be transmitted per second. Digital signals on the PD and PC lines Digital signals are transmitted on the P-bus PD and PC lines. The data on PD are binary raw values in the range of 0 to 256. They do not reflect units: conversion into physical units (e.g., temperature measured value in °C) occurs in the process unit. PU reference voltage The reference voltage of ca. DC +23.5 V on the PU line is generated in the process unit. The system neutral (=G0) represents the zero potential for this voltage. AC 24 V operating voltage The AC 24 V operating voltage is derived directly from the control panel transformer. G then represents the potential line for the operating voltage (=system potential) and G0 the zero line for the operating voltage (=system neutral). CM2N8022E / 02.1999 2/8 Siemens Building Technologies Landis & Staefa Division I/O strip with module supply block The illustration below contains the P-bus lines and the AC 24 V operating voltage line as arranged on the I/O strip. L 230V~ N 24V~ T1 G G0 G G0 P-bus 8022V03E PD PU PC X1 G G0 PC PU PD N1 G G0 PD PU PC G0 G Data line Reference voltage Clock line System neutral System potential From master From transformer PC PU PD U1 N1 T1 U1 X1 Characteristics PRU, PRV, RWP80 process unit (rear) AC 230 V / AC 24 V transformer PTX1.01 module supply block PTX1. ... I/O strip The P-bus has the following characteristics: – synchronous, byte-oriented serial data transmission with telegram synchronisation by master clock (master-slave principle) – half duplex mode, i.e., data are only received in one direction at a time; sending or receiving – polling cycle 0.5 seconds, i.e., every 0.5 seconds, data transmission occurs cyclically between the master (process unit) and each slave (I/O module), regardless of the number of connected slaves. Engineering notes During engineering, the permissible total line lengths for the bus lines (50 m or 200 m) must be observed. The total line length must include the sum of all line sections. P-bus cable length If the P-bus is a 3-core round cable (unshielded), the maximum total length is 50 meters (standard P-bus). By using two shielded cables (coaxial cables), the P-bus line length can be extended to 200 meters (remote P-bus). Combination of standard and remote P-bus The P-bus can be divided into a standard P-bus section (with round cable, e.g., to connect the process unit to the I/O modules within the same control panel) and a remote P-bus section (with coaxial cable, e.g., for remote "I/O module islands"). In the case of a combination P-bus, the length of the remote bus section depends on the length of the standard bus section as well as the number of connected I/O modules, whereby one PTK1... I/O compact unit corresponds to eight I/O modules. Both P-bus sections can be subdivided into several P-bus sections or I/O module islands. The diagram below contains the permissible P-bus line lengths in the case of a combination P-bus (standard and remote). Siemens Building Technologies Landis & Staefa Division CM2N8022E / 02.1999 3/8 m P-bus cable lengths Remote P-bus (coaxial cable) 200 190 40 I/O m m od o ule dul es s* *) ) I/O I/O 30 50 ≤ 150 *) es ul od m 100 50 m 0 0 10 12 20 30 Example: With a standard P-bus length of 12 m and a total of 25 connected I/O modules, the maximum permissible length of the remote P-bus is 190 m. ∧ *) 1 I/O compact unit PTK1.. = 8 I/O modules 40 50 Standard P-bus (round cable) 8022D02E Note The total line lengths of 50 and 200 meters represent absolute limits. Extending the Pbus line length by adding repeaters is not possible. Process unit with two P-bus connections For the PRV1.128 and PRV2.128 process units with two P-bus connections, the total length per P-bus is relevant, i.e., a remote bus of up to 200 meters may be connected to each P-bus connection. Consequently, connecting the standard P-bus with max. 50 meters to the first connection and the remote P-bus with max. 200 meters to the second connection, or a combination of standard and remote P-bus connections as illustrated above is possible. Bus topology Line, star, or tree-like bus topologies are permitted whereby the length of all sections must amount to a maximum of 50 or 200 meters respectively. A ring-type P-bus structure is not permitted. Installation notes Standard P-bus wiring With the standard P-bus, the PD, PU, and PC lines are laid in a 3-core unshielded round cable. Unshielded round cables are permitted within and outside of the control panel. – Ribbon cables with PU reference line in the centre are permitted; however, they are not as immune to noise as round cables. Single wires are not permitted. Remote P-bus wiring CM2N8022E / 02.1999 4/8 The remote P-bus is wired with two coaxial cables. The clock (PC) and data (PD) lines must be connected to the inner conductor of each coaxial cable. The reference voltage (PU) must be laid in the shielding of both coaxial cables whereby the shielding of the two cables must be interconnected (see bottom right drawing in the wiring diagram below). In this case, the cable shielding is used as a conductor and must not be connected to the ground. Siemens Building Technologies Landis & Staefa Division Remote P-bus Wiring diagram Control panel AC 230 V G AC 24 V AC 24 V I/O modules (AC 24 V) B AC 230 V G0 G G GO G T1 G GO PTX1.01 PC / PU / PD Remote P-bus I/O modules (AC 24 V) PC / PU / PD G GO G0 Standard P-bus G C GO GO GO T2 PTX1.01 PC / PU / PD A PC PU PD (P-bus) PRU... PRV... G GO PC / PU / PD PTX1.01 8022V04E I/O modules D PC / PU / PD G GO PTX1.01 PC / PU / PD G I/O modules (AC 24 V) PC / PU / PD G GO E G0 T3 PC PD PTX1.01 PC / PU / PD PU I/O modules F Supply of the I/O strips or I/O module islands PC / PU / PD G GO RG-62A/U G0 1.5 mm² PTX1.01 The above wiring diagram shows a remote P-bus combined with section A as the standard P-bus. The following must be observed for the I/O strip or I/O module island supply: • For I/O strips containing I/O modules, supplied with AC 24 V operating voltage (normal), a supply transformer must be installed locally at the PTX1.01 module supply block (I/O strips B, C, and E). • For I/O strips containing just I/O modules requiring no AC 24 V operating voltage, a supply transformer is not necessary (I/O strips D and F). The following I/O modules do not require AC 24 V (G/G0) operating voltage: – PTM1.2D20 – PTM1.2R1K, PTM1.4R1K – PTM1.2QD, PTM1.4QD System neutral, G0 line Siemens Building Technologies Landis & Staefa Division PTM1.2D42 PTM1.2P100 PTM1.2Q250 PTM1.2D250 PTM1.2P1K Use a single-core copper cable, 1.5 mm2 diameter, for the system neutral (G0 line). For reasons of electromagnetic compatibility, the P-bus lines and the G0 line must be laid parallel and a cable tie must be used every 3 to 4 meters (see bottom right drawing in the above illustration). CM2N8022E / 02.1999 5/8 General installation notes Refer to the Mounting and Installation Handbook M8012 for PRU or M8017 for PRV for information on installing the units to be connected to the P-bus as well as for general wiring and earthing information. P-bus cable connection and operating voltage The P-bus cable is connected to the rear side of the unit and to the PTX1.01 supply module block. The AC 24 V operating voltage is also wired from the transformer to the rear side of the unit and the PTX1.01 supply module block. (The AC 24 V operating voltage and the P-bus are not directly led to the I/O modules). System neutral, G0 line The G0 line is wired together with the G line (AC 24 V operating voltage) in a star-like manner from the transformer. G0 from the process unit and supply module block of the associated I/O strip(s) must always be galvanically separated. Network lines For the standard as well as the remote P-bus, the P-bus cable may be laid together with the AC 24 V operating voltage lines and the AC 3 x 400 V 3-phase network lines. Commissioning notes The P-bus works properly only if PD, PU, PC, and G0 are wired. We recommend to also wire line G of the AC 24 V operating voltage to the I/O module groups. – If several process units are installed, ensure that the P-bus of a process unit is wired only to the respective I/O strip(s). – Two or several process units cannot be connected via the same P-bus. Technical data Standard P-bus: Round cable for PD, PU, PC Bus length incl. all sections Wire diameter (for 50 m bus length) 3-core, unshielded max. 50 m 1.5 mm2 Remote P-bus: Two coaxial cables Bus length incl. all sections Characteristic impedance Capacity single-core (e.g., type RG-62 A/U) max. 200 m 50 .. 120 Ohm < 43 pF/m Rate of transmission Polling cycle Bus topologies 62.5 kBaud (62,500 bps, fixed) 0.5 seconds line, star, tree-like We reserve the right to make changes to technical data. Connection diagram P-bus 24V~ PTM... PRU... / PRV... / RWP80... G G0 PC PU PD G G0 PC PU PD PD PU PC PTX1.01 8022V02E P-bus 24V~ AC 24 V operating voltage G System potential G0 System neutral CM2N8022E / 02.1999 6/8 Process bus (P-bus) PD Data line PU Reference voltage PC Synchronisation line (clock) Siemens Building Technologies Landis & Staefa Division P-bus characteristics Line signals P-bus Ulref * PU Master Rline Udatam Udatas PD Process unit / Controller Umckm Slave R-Line DATA PC I/O-modules Ubez MCK G0 * Protection diode in module supply block Electrical characteristics of P-bus Characteristic Symbol Reference voltage Line voltage drop Min. Typical Max. Unit Uref 22 23.5 26 V Ulref 0 0.5 V Data transmission from master Signal level LOW UdatamL UmckmL 6.6 8.0 V Signal level HIGH UdatamH UmckmH 0 0.4 V Data transmission from slave Signal level LOW UdatasL 5.2 8.0 V Signal level HIGH UdatasH 0 0.1 V 50 m Line length Capacitance between lines data mck m s U L H Note 100 pF/m 8022T01E Line characteristics Data line Clock line (synchronization) Master Slave Signal Low level = log 1 High level = log 0 The signal level Udata on the PD and Umck line on the PC clock line correspond to negative logic, i.e., signal level at logical "0" is higher than at logical "1". The following typical signal levels apply: – at logical "0", Udata = Uref - Signal level HIGH – at logical "1", Udata = Uref - Signal level LOW = ca. DC +23.5 V = ca. DC +16.5 V Uref = Reference voltage on PU line Siemens Building Technologies Landis & Staefa Division CM2N8022E / 02.1999 7/8 Transition from the end of one P-bus telegram to the start of the next MCK End of telegram Start of telegram t t t 1 2 3 t 4 UH UL 40* 1* 2* t * = Number of positive clock edge within a telegram Dynamic characteristics of P-bus Min. Last positive pulse of a telegram (time out) t Min.pause between two telegrams (idle time) t Clock pulse HIGH within a telegram t Clock pulse LOW within a telegram t Rate of transmission 1 2 3 4 Type *) *) 25 Max. Unit 110 µs µs 8 µs 8 µs 62.5 62,500 kbaud bps 8022T02E Characteristic *) Times t1 and t2 characterize the quality of the telegram (acknowledge = TRUE or FALSE) 1999 Siemens Building Technologies Ltd. CM2N8022E / 02.1999 8/8 Siemens Building Technologies Landis & Staefa Division