Improving the Efficiency of Residential HVAC Systems Using Computer-Based Power-Electronic Controls Jason M. Anderson, Robert W. Cox, and Prayag K. Parikh Department of Electrical and Computer Engineering UNC Charlotte Charlotte, NC 28223 Email: jmander1@uncc.edu, rcox3@uncc.edu, pkparikh@uncc.edu Abstract—Space heating and cooling are responsible for about 43% of energy consumption in the average American home [1]. That number can be reduced significantly through the use of a computer-based power-electronic control system. This paper describes one proposed solution, which uses a PC to control the motors in the system. The central PC uses wireless communications to coordinate fan and compressor speeds. The paper describes some new control concepts designed to implement demand-side management, and it shows how the system can be operated in a diagnostic mode that regularly checks for increased energy consumption resulting from degrading equipment conditions. I. I NTRODUCTION Buildings are responsible for approximately 39% of primary annual energy consumption in the United States [2], and heating, ventilation, and air conditioning (HVAC) systems represent a significant portion of that consumption. Studies released by U.S. Department of Energy (DOE), for instance, indicate that space cooling and heating account for about 43% of the energy delivered to the residential sector [1]. In large commercial buildings this percentage is lower because power-electronic drives are used to better control cooling load by varying equipment speeds. Given the projected growth in energy prices, it will likely be necessary to bring the same efficiency improvements to homes and small businesses. This document describes a system that uses power electronics and high-level, computer-based supervisory controls to generate the necessary improvements at relatively low cost. The system described in this paper makes use of a distributed network of motor drives and sensors, all under the control of a single PC. In this arrangement, the computer coordinates the operation of motors in a residential or packaged HVAC unit. At a high level, this system implements two types of energy-saving features, namely variable-speed control and routine motor diagnostics. Control commands are determined by the central PC using set-point data, sensor information, and other control inputs. These inputs include quantities such as power-system frequency and voltage magnitude, and they can Christopher R. Laughman Laboratory for Electromagnetic and Electronic Systems Massachusetts Institute of Technology Cambridge, MA 02139 Email: crlaugh@mit.edu be used to indicate when the power system is most able to accept additional load. Use of these features would help to support the SmartGrid initiative, which is a program aimed at modernizing the electrical grid in the United States [3]. Each motor drive can also be commanded to operate in a diagnostic mode that allows the system to determine if equipment is degrading. This capability is important because faults such as refrigerant leaks can increase consumption by as much as 20% [4]. This paper describes the proposed system and presents results from initial tests. Section II provides an overall description and explains the motor drives developed for this application. Section III discusses diagnostic capabilities that have been incorporated into the system, and it describes a specific example that was tested in the field. Section IV describes some new demand-side management features, and finally Section V presents several conclusions. II. S YSTEM OVERVIEW AND BASIC C ONTROL F EATURES Figure 1 shows the layout of the system that is currently under test in a single 2500ft2 home in Charlotte, North Carolina. The system consists of three sets of components - a central PC, several motors and drives, and a number of sensors. These devices all communicate wirelessly over a mesh network using the ZigBee protocol. This section describes the overall layout of the system and it describes the custom motor drives used throughout the network. A. Test System Layout Typically, HVAC plants feature three motor-driven devices a condenser fan, a compressor, and an evaporator fan. In most homes, the condenser fan and compressor are located outdoors as in Fig. 1. In commercial buildings, all three devices might be packaged into a single roof-top unit (RTU). The test system has been designed to demonstrate some of the key features enabled through the use of distributed power- electronic controls. Experimental motor drives have been deployed at the evaporator and condenser fans, and a simple data-collection unit with current and voltage sensors has been installed at the compressor. Data from this unit is used to demonstrate some unique diagnostic possibilities. Temperature sensors integrated onboard PICDEMZ demonstration boards from Microchip have been placed both outdoors and indoors. Other sensors could be used, but have not been considered in this test application. A central PC located inside the home can communicate with the motor drives, temperature-sensing nodes, and the remote data-collection unit. A small voltagemeasuring device has also been installed at the central computer in order to demonstrate the demand-side management features described in Section IV. B. Custom Motor Drives and Basic Control Features Speed coordination, which has long been used to realize energy savings in large commercial buildings, has been shown to offer similar benefits in residential settings [5]. By controlling fan and compressor speeds, one can modulate both compressor capacity and air flow so that overall cooling capacity matches the heat gain in the conditioned space [6]. The goal of the currently proposed system is to achieve this control at relatively low cost. The key components enabling this savings are the low-cost wireless modules and the motor drives. To keep costs down, the drives are designed to be easily retrofit into existing HVAC equipment with split-capacitor AC induction motors. Brushless DC machines were considered as replacements, but it was decided to design a solution that would keep nearly all mechanical connections intact, thus minimizing both installation effort and cost. 1) Drives: Each motor drive is comprised of the subsystems shown in Fig. 2. The power stage consists of a two-phase rectifier and an inverter formed using the IRAMX16UP60A integrated power module from International Rectifier [7]. At present, both the condenser fan and the evaporator fan are controlled by the drive circuits shown in Fig. 3. Both of these motors are two-phase, 1/4 hp machines, and both were previously operated with a capacitor permanently placed in series with the B-phase winding. Note that this capacitor has been removed and that the neutral point on the motor has been connected between the two series capacitors that comprise the DC bus. 240V AC Mains Wireless Tranceiver Power Stage Microcontroller Motor Fig. 2. Block diagram of the motor drives used in the current system. Speed commands are passed to the power stage from the wireless transceiver. L D1 + Thermostat Outdoor Temperature Sensor vAC Wireless Transceiver PC VDC Q1 - C1 Q2 Q4 Q3 Q5 C2 iB Fig. 3. Schematic of the power stage used for the condenser and evaporator fans. The IGBTs are part of the IRAMX16UP60A integrated power module. A boost rectifier was constructed using one of the three phase legs and a separate single-phase rectifier module. Outdoor Unit Condenser Fan Evaporator Fan Compressor Fig. 1. A home with intelligent HVAC controls. Motor drives with wireless transceivers are incorporated with the condenser fan, compressor, and evaporator fan. Sensors can be placed as needed, and the locations shown here do not indicate all relevant possibilities. Currently, the system uses two temperature sensors - one placed at the thermostat and another placed outdoors. The operation of the network is coordinated by the PC. The power stage topology shown in Fig. 3 was selected primarily on the basis of initial cost; specifically, it was desired to integrate both rectification and inversion into a single, offthe-shelf three-phase inverter module. In initial studies, we have also included a single-phase rectifier and an inductor in order to form a boost rectifier. The decision to use the boost topology was motivated by the desire to investigate active power factor correction and harmonic cancellation [8]. Ultimately, the system will likely make use of a simple doubling rectifier as shown in Fig. 4 Overall control of the rectifier and inverter is performed using the dsPIC60F10A from Microchip. This microcontroller monitors the inductor current, DC bus voltage, and rectifier iA + Q2 VDC vAC The drives could be designed to always include the series capacitor, but this leads to decreased efficiency, higher current, and increased pulsating torque [9]. C1 Q4 Q6 Q3 Q5 iB C2 - Q1 iA + Fig. 4. Schematic of the power stage that is currently under consideration. The switches Q1 and Q2 and their parallel diodes are used as part of voltagedoubling rectifier. This approach offers a cost savings over the boost rectifier shown previously. Q2 Q4 - Q1 Q3 iA iB (a) + VDC - iA Q1 Q6 Q4 Q2 iB Q3 Q5 (b) Fig. 6. Two other possible inverter topologies for a two-phase motor. (a) Two-phase inverter with series capacitor. (b) Three-phase inverter with series capacitor. Other topologies can also be considered. 500 0 −500 0 iA (A) vAB (V) output voltage, and it uses these signals to control the average current in the inductor [8]. Motor speed commands are communicated using a wireless transceiver, and PWM switching signals for the inverter switches are generated at 16kHz using a 256-entry sine table. Currently, each motor is operated using an open-loop, constant volts-per-Hertz strategy. When a speed change is needed, the PC sends the frequency and modulation commands needed to set the desired operating point. Figure 5 shows voltage and current waveforms recorded during steady-state operation at the evaporator. Note that the currents, which are separated in phase by 90 degrees, have different magnitudes. This difference is the result of the asymmetry in the two sets of stator windings. VDC 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 Time (sec) 0.5 0 −0.5 0 Time (sec) iB (A) 0.5 0 −0.5 0 Time (sec) Fig. 5. Waveforms recorded during steady-state operation of the evaporator fan . Upper trace: Voltage between phases A and B of the two-phase machine. Middle trace: Current flowing into the phase A of the motor. Bottom trace: Current flowing into phase B of the motor. Other inverter topologies were considered, and Fig. 6 shows several possibilities. It is important to note that these other approaches may be required in some cases. Many compressor motors, for instance, contain an integrated capacitor that is connected in series with the auxiliary winding. This capacitor cannot be easily removed, so an inverter of the type shown in Fig. 6(a) would be more appropriate. Commercial versions of the final drives might include a switch that allows one to indicate whether the capacitor will remain connected. Such an input is needed because use of the series capacitor requires the two output voltages to maintain different phase angles. 2) Basic Control Features: At present, the evaporator and condenser motors can operate in a number of different modes. During steady-state operation, these motors typically operate using an open-loop, constant volts-per-Hertz strategy. Frequency and modulation commands are created at the central PC and transmitted wirelessly to the motor drives. If communications are lost, the system resumes normal fullspeed operation. Each machine can also be operated in a special diagnostic mode in which it is hard-started and brought immediately to full speed. The purpose of this mode of operation is related to the richness of transient signatures as viewed from the perspective of on-line diagnostics. Further details are provided in the next section. Ongoing work aims to devise a control algorithm that minimizes overall HVAC input power for a given cooling load, Q. Total input power can be expressed using the objective function J = f (Q) = Wcomp + Wcond + Wevap (1) where Wcomp is the compressor input power, Wcond is the condenser-fan input power, and Wevap is the evaporator-fan input power. To minimize J for a given cooling load, further information is needed and more complete component models are required. Recent work indicates that the use of such controls in combination with other techniques such as thermalenergy storage offer the potential for significant national energy savings [10]. III. D IAGNOSTIC F EATURES Faulty HVAC systems waste considerable amounts of energy. Researchers in the HVAC community have developed diagnostic systems that use mechanical measurements to detect key faults, including liquid slugging, fan imbalances, and refrigerant leaks [4], [11]. The use of such systems is limited, however, because the necessary sensors are both expensive and potentially unreliable. An alternative approach is to rely on electrical measurements. Using electrical current data, for instance, one can often extract considerable information about the status of the driven load [12], [13], [14]. This approach, which is potentially cheaper than more traditional techniques, motivates the use of power-electronic drives with integrated diagnostic features. To demonstrate the potential, current transducers (CTs) have been embedded into each motor drive and an additional data-collection unit with a CT has been installed on the compressor. Two primary analytical approaches have been considered. First, faults such as load imbalances have been detected using spectral techniques; other failure mechanisms have been analyzed using transient current signatures. Research has demonstrated that current transients are particularly rich in information indicating the status of the driven mechanical load [15], [12], [13], [16], [17]. For instance, changes in current transients have been used to detect the build-up of liquid refrigerant in compressors [17] and to detect clogs in fluid systems [16]. The rich quality of transient signatures motivates the use of a special diagnostic mode in which motors are hard-started and data is recorded for later analysis on the central PC. This approach minimizes data-storage and processing concerns, as current data is only collected for a short period before and after each start. Once the machine has been started, variable-speed operation can begin. A. Example: Refrigerant Leak Detection Field tests were conducted in order to demonstrate the critical diagnostic information that can be extracted from electrical transients using the proposed system. A key fault condition was introduced into the HVAC plant by removing a small amount of liquid refrigerant from the compressor. Depending on both the severity of the leak and ambient conditions, refrigerant loss can cause an HVAC system to significantly increase its frequency of operation. This fault was simulated by removing approximately 20% of the required refrigerant, an amount considered to be relatively modest [18]. Compressor start-up data was collected for several weeks before and after the removal of the liquid, and analysis was conducted off-line on the central PC. Transient analysis of the type considered here can be performed by computing time-varying estimates of the frequency content of the measured line current. Formally, these timevarying estimates, or spectral envelopes, are defined as the quantities [19] 2 am (t) = T Z 2 bm (t) = T Z t i (τ ) sin (mωτ ) dτ (2) i (τ ) cos (mωτ ) dτ (3) t−T and t t−T These relationships are Fourier-series analysis equations evaluated over a moving window T [20]. The coefficients am (t) and bm (t) contain time-local information about the frequency content of i(t). Provided that the basis terms sin (mωt) and cos (mωt) are synchronized to the line voltage, the spectralenvelope coefficients have a useful physical interpretation as real, reactive, and harmonic power [19]. In this specific case, analysis is performed using the coefficient a1 (t). When properly scaled, this coefficient accurately represents real power. Figure 7 shows experimental results obtained as the refrigerant level was varied. Figure 7(a) shows the power recorded both during and after the motor in-rush. Note that both the transient and steady-state power levels are lower when the compressor is slightly undercharged, i.e. refrigerant has been lost. The average power level during the transient was recorded and trended throughout the course of the experiment. Figure 7(b) presents a scatter plot that shows how the transient power level varied as a function of the difference between outdoor and indoor temperature. Note that for any given temperature difference, more power was absorbed when the compressor was fully charged. This result is consistent with physical arguments [18], and it has been observed reliably in the field. A fault-detection algorithm based on clustering analysis is currently under development. The resulting algorithm could ultimately be executed automatically by control software on the central PC. IV. C ONTROLS FOR D EMAND -S IDE M ANAGEMENT The use of a central PC makes it possible to introduce a number of new control features. For instance, the PC can coordinate the operation of the HVAC system so that it responds to changes in power-system condition. This concept was first introduced in [21], where the authors used frequency deviations to detect imbalances between the supply and demand for real power on the grid. The central PC allows this concept to be expanded, as its computational power can be used to track power-system quantities, including frequency and voltage magnitude. Additionally, a connection to the internet makes it possible to receive commands from the local utility provider. All of these possibilities make this system attractive as part of the SmartGrid initative in the United States [3]. A new demand-side management (DSM) feature has been tested using the proposed system. This technique uses voltage measurements to obtain information about the power drawn inside the home as well as information about overall utility load. Whenever a device enters operation inside of a home, for instance, the line voltage will decrease with respect to the neutral and the neutral voltage will increase with respect to 14 Fully Charged 20% Undercharged am (t) = 12 Real Power (kW) bm (t) = 8 6 4 2 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 Time (sec) (a) 13.5 Fully Charged 20% Undercharged 13 Real Power (kW) Z 2 T Z t vN G (τ ) sin (mωτ ) dτ (4) vN G (τ ) cos (mωτ ) dτ, (5) t−T and 10 0 0 2 T 12.5 12 t t−T where vN G (t) is the neutral voltage with respect to ground and the basis terms sin (mωt) and cos (mωt) are synchronized to the measured line voltage. Complete details of the computational process are presented [22] and [23] and will not be discussed here. Reference [23] describes how these measurements can be used to identify the operation of individual household loads, i.e. vacuum cleaners, lamps, etc. Figure 8 demonstrates the operation of the proposed DSM input. Figure 8(a) shows how both the line-voltage magnitude and the neutral-voltage magnitude were affected when a vacuum cleaner was started at a nearby outlet. Figure 8(b) shows how the same quantities were affected by a drop in utility voltage. The latter of these two events, which has been simulated extensively in the lab, was observed almost daily during field tests conducted in July and August 2007. The high frequency of these events hints at the strong potential of this measurement approach. V. C ONCLUSION 11.5 11 10.5 −10 −8 −6 −4 −2 0 2 4 6 Tout −Tin (◦ C) (b) Fig. 7. Results from the refrigerant-loss experiments (a) Real power absorbed by the compressor during and after the motor in-rush. (b) Scatter plot showing how average transient power varies as a function of teperature difference and refrigerant charge. Transient power is measured during the period when then the power is approximately constant. In (a), for instance, the transient power level was measured between approximately 0.2s and 0.3s. ground. By comparison, if the utility decreases its voltage or if nearby customers operate large loads, both the measured line voltage and the measured neutral voltage will decrease. Voltage measurements at a single outlet, therefore, can be used to determine both changes in utility load and changes in load inside the home. This information can be used to sense periods of high demand and can thus be used to curtail HVAC load accordingly. Since changes in voltage magnitude are often extremely small, measurements are conducted using specialized hardware. Analysis is currently performed using analog computers that estimate the time-varying frequency content of both the measured line voltage and the measured neutral voltage. In the case of the neutral voltage, for instance, these circuits esimate the quantities This paper demonstrates the basic control and diagnostic features implemented by the proposed system. Eventually, brushless DC machines may become common in HVAC systems in new residential construction. In the meantime, however, this system offers a simple approach that can be easily retrofit into existing homes. Additionally, the diagnostic features described here offer the potential for increased energy savings, and many of the diagnostic procedures can also be used for brushless machines. ACKNOWLEDGMENT The authors would like to thank Prof. Steven B. Leeb and Prof. Les Norford for their valuable advice and support. This work was supported in part by the Grainger Foundation and the University of North Carolina at Charlotte through a faculty start-up grant. R EFERENCES [1] 2005 Buildings Energy Data Book, U. S. Department of Energy, Office of Energy Efficiency and Renewable Energy, 2005. [2] Annual Energy Outlook 2006, Energy Information Administration, 2006. [3] Grid 2030: A National Vision for Electricity’s Second 100 Years, United States Department of Energy, Office of Electric Transmission and Distribution, Jul. 2003. [4] S. Katipamula and M. Brambley, “Methods for fault detection, diagnostics, and prognostics for building systems - a review, part ii,” International Journal of HVAC&R Research, vol. 11, no. 2, pp. 169–187, Apr 2005. [5] L. Sulfstede, “Applying power electronics to residential HVAC - the issues,” IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. 300–305, Mar/Apr 1993. [6] ASHRAE Handbook HVAC Systems and Equipment, ASHRAE, Atlanta, GA, 2004. Line Voltage Envelope (V) Neutral Voltage Envelope (V) 170 165 160 3 4 5 4 5 6 7 8 9 10 6 7 8 9 10 Time (sec) 0.2 0.1 0 −0.1 3 Time (sec) Neutral Voltage Envelope (V) Line Voltage Envelope (V) (a) 167 166 165 30 32 34 36 38 32 34 36 38 40 42 44 46 48 50 40 42 44 46 48 50 Time (sec) 0.07 0.06 0.05 30 Time (sec) (b) Fig. 8. Demonstration of the proposed DSM approach. (a) The measured linevoltage envelope and the measured neutral-voltage envelope before, during, and after the start of a vacuum cleaner at a nearby electrical outlet. (b) The same quantities measured before, during, and after a step change in utility voltage. Such changes can be initiated directly by the utility, or they can be caused by the operation of other large loads in the vicinity of the home. [7] IRAMX16UP60A Plug N Drive Integrated Power Module, International Rectifier, 2003. [8] R. W. Erickson and D. Maksimovic, Fundamentals of Power Electronics. Norwell, MA:: Kluwer Academic Publishers, 2001. [9] F. Blaabjerg, F. Lungeanu, K. Skaug, and M. Tonnes, “Two-phase induction motor drives,” IEEE Ind. Appl. Mag., vol. 10, no. 4, pp. 24–32, Jul./Aug. 2004. [10] W. Jiang, D.W. Winiarski, S. Katipamula, and P.R. Armstrong, “Costeffective integration of efficient low-lift base-load cooling equipment final,” Pacific Northwest National Laboratory, Tech. Rep. PNNL-17157, Jan. 2008. [11] M. S. Breuker and J. E. Braun, “Common faults and their impacts for rooftop air conditioners,” International Journal of HVAC&R Research, vol. 4, no. 3, pp. 303–318, Jul. 1998. [12] P. R. Armstrong, C. R. Laughman, S. B. Leeb, and L. K. Norford, “Detection of rooftop cooling unit faults based on electrical measurements,” International Journal of HVAC&R Research, vol. 12, no. 1, p. 151175, Jan. 2006. [13] T. DeNucci, R. W. Cox, S. B. Leeb, J. Paris, T. J. McCoy, C.R. Laughman, and W. C. Greene, “Diagnostic indicators for shipboard systems using non-intrusive load monitoring,” in Proc. 1st IEEE Electric Ship Technologies Symposium (ESTS), Philadelphia, PA, Jul. 2005. [14] R R Schoen, B K Lin, T G Habetler, H J Shlog, and S Farag, “An unsupervised on-line system for induction motor fault detection using stator current monitoring, ieee-ias transactions,,” IEEE Trans. Ind. Appl., vol. 31, no. 6, pp. 1280–1286, Nov./Dec. [15] S. R. Shaw and S. B. Leeb, “Identification of induction motor parameters from transient stator current measurements,” IEEE Trans. Ind. Electron., vol. 46, no. 1, pp. 139–149, Feb. 1999. [16] R. W. Cox, G. Mitchell, J. Paris, and S. B. Leeb, “Shipboard fluid system diagnostic indicators using non-intrusive load monitoring,” Naval Engineers Journal, vol. 119, no. 2, pp. 109–119, Oct. 2007. [17] C. R. Laughman, P. R. Armstrong, L. K. Norford, and S. B. Leeb, “The detection of liquid slugging phenomena in reciprocating compressors via power measurements,” in Proc. International Compressor Engineering Conference at Purdue, West Lafayette, IN, Jul. 2006. [18] M. B. Bailey, “System performance characteristics of a helical rotary screw air-cooled chiller operating over a range of refrigerant charge conditions,” ASHRAE Transactions, vol. 104, no. 2, p. 274285, 1998. [19] S. B. Leeb, S. R. Shaw, and J. L. Kirtley, “Transient event detection in spectral envelope estimates for nonintrusive load monitoring,” IEEE Trans. Power Del., vol. 10, no. 3, pp. 1200–1210, Jul. 1995. [20] A. Oppenheim, A. Willsky, and I. Young, Signals and Systems. Englewood Cliffs, NJ: Addison-Wellesley, 1988. [21] F. C. Schweppe, R. D. Tabors, J. L. Kirtley, H. R. Outhred, F. H. Pickel, and A. J. Cox, “Homeostatic utility control,” IEEE Trans. Power App. Syst., vol. PAS-99, no. 3, pp. 1151–1163, May/Jun. 1980. [22] R. W. Cox, S. B. Leeb, S. R. Shaw, and L. K. Norford, “Transient event detection for nonintrusive load monitoring and demand side management using voltage distortion,” in Proc. 21st IEEE Applied Power Electronics Conference and Exposition (APEC), Dallas, TX, 19-23 Mar. 2006. [23] R. W. Cox, “Minimally intrusive strategies for fault detection and energy monitoring,” Ph.D. dissertation, Massachusetts Institute of Technology, Cambridge, MA, Aug. 2006.