Distance Relay Distance and Impedance relay Brief History • • • • • 1921 Voltage restrained time over current 1929 balance beam impedance 1950 Induction cup phase comparator 1965 Solid state implementations 1984 Microprocessor based implementation Distance Relay Need • Faults level are higher in high voltage transmission line • Faults need to be cleared rapidly to avoid instability and extensive damage Advantages • The impedance zone has a fix impedance rich • Great instantaneous trip coverage with security • Easier setting calculations and coordination • Fixed zone of protection that are relatively impedance of the system change • Higher independence of load Basic Principle • A distance relay has the ability to detect a fault within a pre-set distance along a transmission line or power cable from its location. Every power line has a resistance and reactance per kilometer related to its design and construction so its total impedance will be a function of its length. A distance relay therefore looks at current and voltage and compares these two quantities on the basis of Ohm’s law. Basic Principle Ctd.. Since the impedance of a transmission line is proportional to its length, for distance measurement it is appropriate to use a relay capable of measuring the impedance of a line up to a predetermined point (the reach point). Distance relay is designed to operate only for faults occurring between the relay location and the predetermined (reach) point, thus giving discrimination for faults that may occur in different line sections. The basic principle of distance protection involves the division of voltage at the relaying point by the measured current. The calculated apparent impedance is compared with the reach point impedance. If the measured impedance is less than the reach point impedance, it is assumed that a fault exists on the line between the relay and the reach point. Advantage of Distance Relay • the key advantage of distance protection is that its fault coverage of the protected circuit is virtually independent of source impedance variations. Transmission Line Impedance • Z ohms/mile = Ra+ j (Xa+ Xd) • Ra, Xa function of conductor type, length Xd function of conductor spacing, length Xa+ Xd >> Ra at higher voltages Line Impedance Zones of Protection • Zone 1: this is set to protect between 80% of the line length AB and operates without any time delay. This “under-reach” setting has been purposely chosen to avoid “over-reaching” into the next line section to ensure selectivity since errors and transients can be present in the voltage and current transformers. Also manufacturing tolerances limit the measurement accuracy of the relays. • Zone 2: this is set to protect 100% of the line length AB, plus at least 20% of the shortest adjacent line BC and operates with time delay t2. (≈0.5s) It not only covers the remaining %20 of the line, but also provides backup for the next line section. • Zone 3: this is set to protect 100% of the two lines AB, BC, plus about 25% of the third line CD and operates with time delay t3. (≈1.5s) P-Q and R-X relationships If the direction of real and reactive power is from bus 1 to bus 2, the R-X coordinates are located in quadrant I. If the direction of real power is from bus 1 to bus 2 and the reactive power is from bus 2 to bus 1, then the R-X coordinates are located in quadrant IV Tripping Characteristics The shape of the operation zones has developed throughout the years. An overview of relay characteristics can be seen below: Impedance Characteristic: If the relay’s operating boundary is plotted on an R-X diagram, its impedance characteristic is a circle with its center at the origin of the coordinates and its radius will be the setting (the reach point) in ohms. The relay will operate for all values less than its setting i.e. for all points within the circle. This type of relay, however, is non-directional. It can operate for faults behind the relaying point. It takes no account of the phase angle between voltage and current. It is also sensitive to power swings and load encroachment due to the large impedance circle. Mho Characteristic The limitation of the impedance characteristic can be improved by a technique known as self polarization. Additional voltages are fed into the comparator in order to compare the relative phase angles of voltage and current, so providing a directional feature. This has the effect of moving the circle such that the circumference of the circle passes through the origin. Angle π is known as the relay’s characteristic angle. It appears as a straight line on an admittance diagram. Mho Characteristic Ctd… By use of a further technique of feeding in voltages from the healthy phases into the comparator (known as cross polarization) a reverse movement or offset of the characteristic can be obtained. This is called the offset mho characteristic. Mho Circle Component The mho circle is composed of its impedance maximum reach, maximum torque angle and relay characteristic angle • Impedance Maximum Reach: The mho circle maximum reach is set by the impedance reach Zr of the protective zone. These impedance reaches vary depending on the zone of protection such as zone 1, 2, 3 and 4. Each impedance value determines the diameter of the mho circle. • Maximum Torque Angle (MTA): The angle of maximum torque of a distance relay using the mho characteristic is the angle at which it has the maximum reach. For microprocessor relays, the MTA is the same as the positive sequence line impedance angle. • Relay Characteristic Angle: The relay characteristic angle (RCA) of a mho circle is 90°. For purposes of calculating the maximum relay loadability, the RCA is the angle whose vertices are made between the load impedance vector and the difference between the line impedance and load impedance vectors Mho Circle Component Relay Impedances - Zr High Load •The relay impedances are the values that a distance relay uses for zones of protection •Diameter of each mho circle is based on the value of each zone of protection •During steady-state or normal system conditions, the load impedance remains constant and is high enough to keep it away from the relay zones of protection Hint: As load increases, the load apparent impedance decreases, moving it closer to the origin Quadrilateral Characteristic Modern distance relays offer quadrilateral characteristic, whose resistive and reactive reach can be set independently. It therefore provides better resistive coverage than any mhotype characteristic for short lines. This is especially true for earth fault impedance measurement, where the arc resistances and fault resistance to earth contribute to the highest values of fault resistance. Polygonal impedance characteristics are highly flexible in terms of fault impedance coverage for both phase and earth faults. For this reason, most digital relays offer this form of characteristic. Quadrilateral Characteristic Zone Protection Calculation Example π1 = 138∠0° πΎπ = ππΏπ = 79.6∠0° πΎπ π2 = 138∠30° πΎπ = ππΏπ = 79.6∠30° πΎπ −79.6∠0° πΎπ + πΌ66∠75° + 79.6∠30° πΎπ = 0 79.6∠0° πΎπ-79.6∠30° πΎπ 10.97 − π39.8 41.28 πΎπ∠ −74.75° ° πΌ= = = = 625.45∠ −150 66∠75° 66∠75° 66∠75° Example Ctd… S@π΅π’π 1 = 79.6πΎπ ∗ (−537.88 − π312.5 π΄πππ )∗ S@π΅π’π 1 = 79.6πΎπ ∗ (−537.88 + π312.5 π΄πππ ) S@π΅π’π 1 = −42.48πππ΄ + π24.87πππ΄ S@π΅π’π 1 = 49.22∠150° S@π΅π’π 1 = −42.48ππ€ππ‘π + π24.87ππ£πππ Example Ctd… πππππ 79.6∠0° ∗ 79.6πΎπ 2 ∠150° ° πβππ = = = 128.73∠150 ∗ 49.22πππ΄ 49.22∠150° πππππ = −110.70 + j64.35 Ohms Example Ctd… πππππ = −110.70 + j64.35 Ohms The load impedance has a negative R value and a positive jX value, and those coordinates are located in quadrant II, as indicated in Figure below. This example has demonstrated that the location of the load impedance depends on the direction of power. This concept will be emphasized even further when we calculate the maximum loadability of the relay for different power factor conditions. Calculating the Maximum Loadability of a Distance Relay with mho Characteristics • The relay impedances zones of protection must be selected carefully in order to avoid load encroachment problems. The zone of protection with greater risk is zone 3, since it is the mho circle with the greatest area and closest proximity to the load impedance. Zone 3 settings are certainly vulnerable to load encroachment conditions during high load and power swings conditions, which can cause the load impedance to travel towards the boundaries of the zone 3 mho circle and cause an undesired trip. Example Maximum relay loadability that zone 3 will calculated by following steps: 1. Draw the zone 3 impedance vector in the R-X diagram. 2. Draw the load impedance vector at a specified power factor. For this example, . 3. Draw a right triangle forming the 90 ° relay characteristic between the load impedance vector and the difference vector that is made up of Z3 – Zload. Calculating the Maximum Load ability of a Distance Relay with mho Characteristics Example Ctd… 4. Calculate the interior angle that is made between the load and line impedance vectors. This is done by subtracting the line impedance angle minus the power factor angle 5. Calculate the load impedance that the relay will experience at the specified power factor using right triangle properties: Example Ctd… 6. Calculate the maximum loadability of the relay in MVA by: Relay will Trip at 269 MVA