Z = V/I Does Not Make a Distance Relay J. Roberts, A. Guzman, and E. O. Schweitzer, III Schweitzer Engineering Laboratories, Inc. Presented at the 48th Annual Georgia Tech Protective Relaying Conference Atlanta, Georgia May 4–6, 1994 Previously presented at the 47th Annual Conference for Protective Relay Engineers, March 1994 Originally presented at the 20th Annual Western Protective Relay Conference, October 1993 z = v II DOES NOT MAKE A DIST ANCE RELA y INTRODUCTION Distance relays can provide effective transmission line protection. Their characteristics have usually been created from comparators and various combinations of voltages and currents. The mho characteristic, for example, is a popular design because it can be made from a single comparator, has well-defined reach, is inherently directional, and can be made to tolerate fault resistance quite well without serious overreaching errors due to load . Quadrilateral characteristics traditionally require four comparators; e.g., one for each side of the characteristic. Because of the variety of fault types possible on a three-phase circuit, distance relays must be available to respond to the voltages and currents associated with six different fault loops. The number of relay elements required for complete schemes is usually quite large. For example, a four-zone phase and ground mho distance relay requires 24 comparators. Quadrilateral characteristics require even more. One approach to making a distance relay with a computer is to calculate the apparent impedance Z = V 11, and then check if that impedance is inside some geometric shape, like a circle or box. The hope is that one impedance calculation (per loop) might be useful for all zones. Although relays have been made using this approach, their performance suffers under many practical conditions of load flow and fault resistance. This paper examines the z = V II approach, and shows the degradations due to load flow and fault resistance. It shows us that calculating Z = V II and testing Z against a circle passing through the origin is equivalent to a self-polarized mho element --generally a poor performer for distance protection. This paper shows some much better methods used in numerical relays, and emphasizes that these methods have their roots in better polarization methods. z = v II AS A DIST ANCE MEASUREMENT Consider the making of a distance relay by calculating the apparent impedance and comparing the result against some geometric shape. In this paper, we refer to this approach as the Z = VII method. This method is appealing in that it only requires one impedance calculation per fault loop. Multiple zones (or geometric shapes) only require more geometric tests of the result. These apparent impedance equations are listed in Table I. 1 Table I: Z = VII Apparent Impedance Equations Fault Loop Equations First look at the AG element performance for an AG fault on the radially configured system in Figure I. The A<p voltage at Bus S is: v = m.Z . (1 tL + k O .I A \ R1 + R .1 F Equation F where: v = A<t> voltage m = per-unit ZlL measured distance = positive-sequence IR = residual IF = total current from Bus S line impedance IA = A<t> current measured kO = (ZoL -ZlL)/(3.Z1J RF = fault at Bus S to the fault at Bus S (ZoL = zero-sequence measured line impedance) at Bus S resistance current flowing through RF ELcS 0- 215 Z 05 PTR CTR m kV = Z1L .(0,1) = 3 ' Z 15 = 3500:1 = 320'1 = 0,85 = 400 Z1L =10+j.110!2pri. = 0.91 + j 10.06 Q sec Z OL = 3. Z 1L Figure 1: System Single Line Diagram 2 21R =215 2 OR = 2 os 1 Convert Equation 1 into an impedance measurement by dividing kO.IJ. I = (IA + kO.IJ, This yields: every term by I, where = ~v = m .Z + R .~ = -= m.Z1L I lL F I I Z Z Equation Equation z includes the line impedance to the fault plus RF.(IF/I). RF"(IF/I}" Z For the radial system, If = L IF 2 2 L I fault. Figure 2 shows the resistance and and Z accurately measures the reactance to the fault, reactance impedance measured by the relay for an AG fault at m = 0.85, with ~ = 4.60 secondary (or 500 primary Im(V/I) = m. m" I X1L I, given PTR/CTR 3500/320}. = 3500/320), Rf"(IF/I} is all real, Because RF.(IF/I) regardless the magnitude of RF, RF. Jm(+) RF'(-1fj E Re (+ Figure Figure 2: 2: AG Apparent AG Apparent ) Impedance Method Impedance Method Correctly Correctly Measures Measures Reactance Reactance to Fault Fault for a Radial for Radial Line Line This suggests that we can define a zone of ground distance protection resistance thresholds; with two reactance and i.e., the geometric test is a rectangle. i,e., Figure 3 shows how these threshold checks enclose AG faults up to m = 0.85 with ~ less than 9.20 secondary .Reactance Threshold 2 and Resistance Threshold 2 define the desired reactance and resistance reach thresholds respectively. Reactance Threshold 1 and Resistance Threshold 1 restrict the zone definition to mostly the first quadrant in the impedance plane. Their small negative settings accommodate slight measurement errors near either axis (Im[V /1] or Re[V/I]). These later thresholds must be replaced with a separate directional element to insure directional security , II approach is not inherently Thus, the first major problem to note is the Z = V /1 ground faults. 3 directional for ~ Im(~) (+) Im RESIST ANCE THRESHOLD 1 ~ II ,\-RESISTANCE : \ RESISTANCE THRESHOLD 2 : r :I : , r THRESHOLO2 ;1 m=1 m=1 ~ 10 , I ;I II ! ~ I 9 ---[':':':':':':':'. ~:':':':':' :,:,~:,:,:,:,:,:,:,:,:,:':':':':':':':':':':':':':,:,:,:,:,:,:,:,~:,:,r---.~~~~~~r-",~~,~~~~,~~~~,~,,~,. ! " " '1 ::~~::~ N. " :::;::] :-:7 u '1 --:' '1 :~::::.~..7:..0:J~::::::~:::::::::~:::: .. Q) If) ~ '"-' J , J 00 , ~~~~J '-- REACTANCE THRESHOLD 2 (8596 .Z1U ... w :::~::~: """"""""" """"".""" " m " -" 05 "" ." u z i<3:: 1U <3:: w ~ (1: L~" 4..~ ~ ~ ~ :[ : : : : : [ : [ : ~ ~ ~ : : : : : : : : : :: [ : [~ : : [ ~ ~ :[ : : : : : [ : ~ ~ ~: : : : : : : ~ :[ : : ~ ~ : ~ : : : : :j J i';-; ,',', l' l~"" ! , : : : : : :j 'J ~~~ : .1::~ t""C1C t;:;:;:;:;:;.;.;. t~~~~~~:~i Re ";r t "J...:.:. :.. J 2 j :4 S [) , B gJ ;~~.~~~:~~~~~:~. ~~~~:~~~~~~ ~~~~~~~~~~~~~~:~:~ t 1D \ RESISTANCE [.0. sec.] '-- RESISTANCE[.0.sec Figure 3: Figure 3: " '-- ( J (v-Yt REACTANCE REACTANCE THRESHOLD THRESHOLO1 1 AG Apparent Impedance Compared to Reactance and Resistance Thresholds (Radial Case) Load Resistance Effects Effects on on Z Load Flow Flow and and Fault Fault Resistance Z What effect effect does does load load flow and RF the Z = V II measurement? measurement? Consider Consider the What flow and RF have have on on the the faulted faulted system in Figure Figure 1 again, again, except except now now close close the the switch Bus R and and assume load flows flows system switch near near Bus assume load from Bus to Bus Bus R with with O 0 = 30°, from Bus S to 30°, Figure 4a 4a shows shows the at Bus Bus S overreaches overreaches in that that Im(V Im(V II) II) measures measures a reactance reactance less less than Figure the relay relay at than the line reactance to to the the fault. fault. This This is because IF and and I are not in phase phase {Figure (Figure 4b) 4b) and and RF the line reactance because IF are not RF appears as as a complex impedance. appears complex impedance. This overreach becomes more pronounced with increasing RF and 0, 0. 4 ~ (V~ (l" II mlT) fu IF-R F 'F.RF , '.R L '.R L-. Re(+) a Impedance ImpedancePlane Plane b. Voltage Voltageand and Current Current Phasors Phasors b. a Figure 4: AG Apparent Impedance Overreach with R.. and Load Flow Out (0 = 300) Figure Figure 5 illustrates illustrates underunder- and and overreaching overreaching of of the the Z = V V II approach approach for for different different ~ and and load 0.85. The load flow flow conditions. conditions. The The relay relay reach reach is is set set to to r.ZlL' r.ZlL' where where r = 0.85. The Z Z = VII VII approach approach underreaches underreaches for for incoming incoming load load (IF (IF leads leads I), I), and and overreaches overreaches for for load load out out (IF (IF lags lags I). I). Im(V/I) Im(V/I) 20 20 0=.60 . / m=O.85 m::0,85 / / vv (1) (1) In tn I 0: 0: LJ.J LJ.J u u z z <1: <1: ffu u <I: « ~ LJ.J cx: / k 10 / 0. = 6=0. : ;:! N-' 15=+30. 5=+60 8::+60 . Re(V/I) a G 6+ 8+ -+ LOAD OUT 68- -+ LOAD IN -5 0 -5 -so 20 10 10 RESIST RESIST ANCE ANCE [Q [..\2sec.] sec.] FAUL T RESIST ANCE LEGEND' x RF=O..\2 Figure 5: AG Apparent .RF::10..\2 Impedance .RF::25..Q Method 5 Performance ~ RF::50..Q PRI. Depends on RF and 0 To better illustrate the under- and overreaching of this reactance measurement. compare X = Im(Z)lIm(r.Z1J to unity for the same system conditions shown in Figure 5. The results are shown in Figure 6 where the ideal X is unity . 5.0 m=O.85 w Rf=50.QPRIMARY u z ' ., ./ ! .1 1 <! I-z u O <!w 1-' a:<! 1- 5' zw-Ju a: 11:6 O.J: <! . ", ~ -Rf=25.Q --.< u , \" . \, C --'. , ~ , a: w \ \ :\ 1-<! ~ '. F3!:=.1P-~ " ,- w CI: ' 0= ~---~'.,. ~ , 1.0 ;,;: -.""'- Rf-O.Q 0. t SET REACH :1: ---:0.:::-.=::-.=-.:-.:-.:-.:-.=::::=. ~ ~ ~ 0= 0 -60 .LOAD IN O I 60 LOADOUT ~ O - Per-unit AG Apparent Apparent Impedance Illustrates the Amount of Per-unit AG Impedance Calculation Calculation ~ Illustrates the Amount UnderUnder- and and Overreach Overreach with with Fault Fault Resistance Resistance and and Load Load Flow Flow Figure 6: Figure 6: The overreaching problem can be minimized by restricting the reactive reach. For a zone 1 element, this means reducing the amount of instantaneous protective coverground distance element. age. We could also restrict the resistive coverage to avoid the overreach which occurs for line-end faults. However, However. this penalizes the fault resistance coverage for all fault locations. IMPROVED IMPROVED QUADRILA QUADRILA TERAL TERAL CHARACTERISTIC CHARACTERISTIC There are much the reactance reactance to the the fault, the fault fault resistance, There are much better better ways ways to to estimate estimate the fault, and and the resistance, than than to use use R + j.X j.X = VII. VII. These better methods depend on proper selection of polarizing quantities quantities. Reactance Reactance Element Element Reference 1 describes one means of obtaining an improved reactance characteristic using the sine-phase comparator. This comparator measures the angle, e, between the operating (Sop) and polarizing (SPOJ (SpQJ signals. The torque of this comparator is defined by Im(Sop.SPOL *); where * indicates the complex conjugate. For 00 ~ e ~ 180°, the characteristic is a 6 straight line, and the torque is positive. The angles e = 00 and e = 180° define the boundary line in the impedance plane. The reactance element comparator has the following input signals: SOP== oV oV Sop SPOL SPOL== Ip Ip where: where: oV oV r ZlL ZlL I V Ip Ip = = = = = = = (r.ZlL.I (r.ZlL .1 -V), -V), line-drop line-drop compensated compensated voltage voltage per-unit per-unit reach reach positive-sequence line positive-sequence line impedance impedance IA IA + kO. kO.IR IR A<1> A<1> measured measured voltage voltage polarizing polarizing current current Figure 4 shows that the faulted phase current is not always in-phase with the total fault current, IF. Thus, phase current makes a poor choice for the polarizing reference signal, signal. Negative-sequence or residual currents are much better choices. Equation 3 illustrates why IR is an appropriate polarizing choice. In this equation, the residual current measured at Bus S is expressed in terms of the total fault current, 4. For systems where the L Zos Z05 = L ZOL= L ZOR(homogeneous systems), the L IR equals the L IF regardless of the load condition or fault resistance magnitude. I = I = R R [ (l-m).Z OL +Z OR.] Z +Z + Z 05 OL OR I Equation Equation F 33 By By selecting selecting Ip Ip = IR, IR, the the reactance reactance element element measurement measurement is is insensitive insensitive to to load load flow flow condiconditions. tions. Equation Equation 4 defines defines the the reach reach of of a residual residual current current (IR) (IR) polarized polarized reactance reactance element element of of reach reach r for for a boundary boundary fault fault condition. condition. ! = Im(V.IR .) .Equation Im(I.ZlL.IR ) Equation In In Equation Equation 4, 4, r is is equal equal to to the the reach reach setting setting r for for a fault fault on on the the boundary boundary of of a zone. zone. For For faults faults internal internal to to a zone, zone, r < r . To To show show the the improved improved performance performance of of the the IR IR polarized polarized reactance reactance element element for for different different RF RF and and load load flow flow conditions, conditions, compare compare the the per per unit unit reach reach result result of of Equation Equation 4 to to unity; unity; where where per-unit per-unit reach, reach, r' = r/r. rlr. These These results results are are shown shown in in Figure Figure 7. 7. From the figure, notice this reactance element does not have the under-and overreaching problems we saw earlier with the Z = V II method. 7 7 4 4 5.DI U.J u z < 1U < U.J 0: O U.J N 5: < -J ~ -0: 1z => d: U.J 0. I I I I I I I m=O85 ~ z Q 1<1: -' => u ..J <1: u ~ \ ::I: u « w c: c: w O z => SAME LINE FOR Rf:O, 10, 25, AND 50.Q PRIMARY J: \ u <1: LU 0: 1,lI -\1 SET REACH ::I: u « w I I I , I I I c: ~ -c: -60 O -LOAD Figure Resistive 7: IN I 60 LOAD OUT w > --0 Per-unit Improved Reactance Reach Calculation (r') Shows IR Polarization Not Affected by O and Fault Resistance in Homogeneous Systems Elements The job of a resistive element is to limit the resistive coverage for a quadrilateral zone of protection. Some resistive elements measure the line resistance plus RF. Reference 1 describes a resistance element which limits its measurement to RF alone. Reference 1 also shows the derivation of the following equation for RF: The greatest advantage of this fault resistance element is that its measurement is not appreciably affected by load flow conditions. This allows setting the resistive boundary (or threshold) greater than the minimum load impedance. The resulting quadrilateral characteristic and its response to different load flow and RF conditions for an AG fault at m = 0.85 is shown in Figure 8. 8 LU U Z ~ fu ~ LU cr O LU N u Q) (/1 9 f-I => (/) LU a: Z Q cr: f~ <! -' -I => ~ U -I CX~ U RF CALC Figure 8: Improved Quadrilateral MHO Characteristic Performance Does Not Depend on O CHARACTERISTIC The typical means of obtaining a mho characteristic is to use the cosine-phase comparator . This comparator measures the phase angle, e, between the operating and polarizing signals. For -90 o ~ e ~ 90 0, the characteristic is circular .The angle e = -90 ° and e = + 90 ° defines the boundary of the characteristic The mho characteristic Sop = oV comparator in the impedance plane. has two inputs: operating (Sop) and polarizing SPOL = Vp where: oV r ZlL I V Vp = = = = = = (r.ZlL .1 -V), line-drop compensated voltage per-unit reach positive-sequence line impedance IA + kO.IR A<t>measured voltage polarizing voltage 9 (SPOL): Reference 1 describes the torque expression for this cosine-phase comparator, p = Re(SOp.SPOL *) = Re[(r.ZlL.I -V).Vp*] Equation All points where p = O define the boundary of a mho characteristic Self-Polarized Mho labeled P, as: 5 of reach r.Z1Lo Characteristic Earlier we checked the Z = V II result against a rectangular against a self-polarized For a self-polarized mho characteristic mho characteristic, characteristic. Let's now test Z to see how it performs. Vp = V. To determine the boundary characteristic of this element, set p = 0, substitute V for Vp in Equation 5, and solve for z: Re[(r.ZtL.I Re(r.ZtL.I.V*) Let r.Z1L = I r.Z1L -V).V*] = O -I V I 2 = 0 where eL = positive-sequence ev = angle of V el = angle of I I L eL = and <I>= (ev -el I Z I L <1>= VII When I/> = eL, I Z I = Z line angle Re {1.1 L eL.v*) I r.Z1L I 6 I v 12 = r.ZlL Next, let Z = Equation I = I r.Z1L I. I r.ZlL I .COS(eL- <1» ) Equation Equation 7 describes a mho circle passing through the origin and r.Z1L on the impedance plane (Figure 9). Equation 7 also shows the self-polarized mho distance element is equivalent to testing Z = V II against a circular characteristic in the impedance plane. 10 7 ~ n(V/IJ 20 ~ "' 9. 10 w u z < 1U < w a: Re(V/I) 0 .5 Figure 9: Self-polarized Mho Characteristic with Reach r.Z1L Figure 10 shows the Z = VII AG apparent impedance values tested against the self-polarized mho characteristic for different load flow and fault resistance conditions. With load flow and fault resistance, this relay has severe underreaching problems and slight overreaching problems. As compared with the rectangular characteristic, the overreaching problem is reduced because there is less resistive coverage. -so 10 20 RESISTANCE [.Q sec.] FAUL T RESISTANCE LEGEND: X RF=O.Q .RF=10.Q .RF=25.Q ~ RF=50.Q PRI. Figure 10: Self-Polarized Mlo Performance Depends on ~ and O 11 Solving Equation 6 for the minimum reach required to just detect a fault, instead of Z, results in the following expression: Re Re (v.v.) (V.V.) r = -Re Re (IoZlLoV.) (I.Z1L.V.) To determine if the fault is inside or outside the characteristic, compare the r calculation against r (same process as for the reactance element). The per-unit self-polarized mho element reach result, r', in Figure 11 shows the amount of under- and overreach for various RF and load flow conditions for the system shown in Figure 1. The source impedance ratio (SIR) for this example equals 0.1 (SIR = Z1S/(r.Z1J). ZIS/(r.Z1J). SO, 5.0 ~.:~!2-P-~~ARY' O I ~ ~ O I ~ O O w 1UJ N N -I 1..J 0= ...1 cr 4: ~ ::. <1: -.J1n -.J (I) ~ w UJ , cr a: ~ u.I :r: u. -' -' uu w UJ In «4: U) ~ UJ a: f- cr ,I. , , m=~8S r ' I m=O.BS , -, ., ,, ,, Rf=25.Q Rf=25.Q , '" :I: u < :I: u < w , ---w w -' ~ c:i: w ci UJ a.. 0.. , Rf=5O.Q PRIMARY .,/ ~ ,/ '" I '. ., .,I' ~!-=-:~~--- ---, ', 0: ---~ 0: t ---, Rf=10.Q ---'--- :--~--~---: 10 1.-Rf=O.Q I::> t ~~ :-:--- - Rf=O.Q I u :I: SET REACH REACH SET ~ < 0 O ~ ~ a: , I -60 -60 ~ ~ Figure 11: II: Figure : I I -". LOADININ LOAO 8 I I I I I LOADOUr - I LOADOUT - 8 60 60 ffi w > > 0 o Per-unit Self-polarized Mho Reach Result Illustrates the Amount of Underand Overreach (for SIR = 0.1) Positive-seouence Positive-seouence Memorv MemorY Polarized Polarized Mho Mho Characteristic Characteristic The biggest disadvantage of using V for the polarizing signal is the lack of security for zero voltage faults. For these faults the polarizing signal has no definite phase angle. The ideal polarizing signal should be available at all times, and not disappear with the fault. One thing we know is that if the system is energized prior to the fault, the prefault voltage is available. We must memorize this prefault voltage and use it for the polarizing signal. Table 2 compares the self-polarized and phase-voltage memory-polarized cosine-phasecomparator results for an AG fault at m = 0. Notice the eov -evPRE is available (not indeterminate) and less than 90° for all cases. This shows memorized prefault voltage is excellent polarization. 12 12 Table 2: Memory Polarization is Better than Self-Polarization for Close-in Faults If we use memorized positive-sequence voltage (Vlmem) for Vp, the polarizing signal is present even if the memory has expired for all fault types except three-phase faults .Another benefit of V p = V 1mem is the improved security during open-pole conditions in single-pole tripping schemes . To obtain the boundary equation for the positive-sequence memory-polarized mho characteristic, set Vp = Vlmem in Equation 5, and solve for the boundary condition. This yields: Equation Figure 12 shows the per-unit reach calculation (r') for different RF and load flow conditions for a SIR = 0.1. Notice there is not much difference between the performance of the V1mem and V polarized mho elements for AG faults at m = 0.85. This is due to the relatively strong source behind the relay. What happens if we increase the SIR? 13 8 ~ 5.0 5.0 I o O I~ ~ 0 O UJ UJ N t:::! -1a: a: ~, ~ ~ --1 O O 0. 0. 1--I' -J ~ ~ tn tn w w a: 0: ~ :I: :I: u u ~ .-UJ ~ .> UJ a: > 0: I , a: a: w UJ 0. 0. , I I I m=O.BS m=0.85 -, , , , -, r I -,- Rf=2S.Q '" Rf=25.Q. ' , -- ---'-- Rf=10.Q --0,0 Rf=10.Q. ffi 0-0'0 , , 1.0 1.0 :1: :x: uu ..< w w 0: c: c: w o O zz " : ::> :) :~;:;~::::::-~~: Rf=O.Q Rf=O.Q. 0 I 0 t :I: ~ :::::::::-: SET REACH SET REACH L> < w 0: I I -6U -60 -LOAD -LOAD Figure 12: 12: Figure I ,- , 1- != z:5 => I Rf=SO.Q PRIMARY PRIMARY Rf=50..Q I IN IN I 15 8 I I I Il 60 60 ffi > o LOADOUT OUT-LOAD Mlo Reach Result Illustrates the Same Amount Per-unit V1mem Polarized !\fi1o Mlo (for SIR = 0.1) of Under- and Overreach as the Self-polarized !\fi1o Figures 14 and 15 show the amount of underreach for the self- and positive-sequence memory polarized relays for a AG fault at m = 0.85 on the system in Figure 13 (SIR = 1.2). From these figures, you can see the V1mem relay performance is better than the self-polarized relay because its underreach is much less. This improvement increases with increasing SIR. EL15 BUSS BUSR ELO 7777 zZ1S 15 = Z 1L =Z1L Z OS ZOS PTR CTR m kV = 3 .Z 15 =3.Z1s = 3500:1 =3500:1 = 320:1 = 0.85 = 400 zZ1L 1L = 2 + j ,22 .Q.pri. =2+j-22.Qpri. = 0.18 + j'2.01.Q. sec. =0.18+j-2.01.Qsec. ZOL=3Z1L Z OL= 3 Z 1L Figure 13: System Single Line Diagram (SIR = 1.2) 14 14 zZ1R 1R = z 15 =Z1S Z OR= Z OS Zo~=Zos ~ 15.D 15.0 III j Rf=5D.Q Rf=5D.QPRIMARY PRIMARY I / / / ./. / I m=085 m=085 /;/ 0 :I: , ~ .., 10.0 10,0 ..:. ~ 0 w Q w N 1N -",! 1-' a: :J rr' ii: ::> -t (/) -t tn -' w'/ -' UJ Oa:c::I: -/ I:i ~ u:. :t u:. -' u u -' w -t <I: w (/) UJ ~ 5.0 VJ 5.0 c: 1f-'zz, => => a: ci: w a. w I ~ -.'. / , :, , ,, , / .,/ , , , ,, , n Rf=25n --- 1"1= f 25 J: ~n -----u --w 0. --a: t Rf=10.Q. ~f-=-1-0-~ 1.0 D 0 -60 -60 -~ SET REACH Rf=O.Q.-1--- III I IN LOADIN Selr-Polarized Self-Polarized M1o Mlo 5 I i , I O 5 ~-LOAD Figure Figure 14: 14: I 60 60 II LOAD OUT LOADOUT Underreach Underreach -~ Increases Increases Dramatically Dramatically with with Increasing Increasing SIR SIR (SIR (SIR shown shown == 1.2) 1.2) 1S.0 15.0 r I I I I I I m=0.85 I m=0.85 ~ 10.0 ~ 10.0 L: Rf=50.Q L: Rf=50.Q PRIMARY PRIMARY o 0 w N ~ 1a: -' r I.-. .~ 1a: ..1 r <fEu -' O a. (j) ~ If) w => <f <I: ::> In w 0: I E u 1 -a: z> E <11 w < E w 0: ." -' O Q. " ," S."0 '. Rf=25.Q -' c :I: 5.0 '. > 1- Rf=25.Q. :)" Z :) a: ci: w w a. Q. -'-.- u w 1 ~ w Rf=10.Q Rf=10.Q. Rf=O.Q § SET SET REACH REACH 1.0 1.0 Rf= 0 0 1--- I -60 -60 04 ..LOAD Figure Figure 15: 15: I I I I 6 O LOAD IN IN II :I: I 60 60 LOAD our ----~ LOADOUT u i ~ i I > 0 V1mem Polarized M1o Underreach is Less than Selr-polarized M1o with Increasing SIR (SIR shown = 1.2) 15 15 THE V1mem POLARIZED DIRECTIONAL ELEMENT MHO DENOMINATOR TERM IS A In Equation 8, V in the numerator could be zero for close-in faults. Therefore, we cannot rely on the sign of r to dependably indicate direction. Fortunately, the denominator of Equation 8 defines a directional element. This directional element measures the angle e between the operating signal {I.Z1J and the polarizing signal (Vlmem). (V1mem). The angle e = -90° and e = 90 ° defines the zero torque threshold. Label the denominator term for the AG mho distance element as MAGD. MAGD is defined as: From Equation 8, MAGD .(V1mem)*] MAGD = Re[l.Z1L Re[I°ZlL"(Vlmem)*] Equation 9 9 Equation Figure 16 shows the inputs to this denominator for forward (16a) and reverse (16b) AG faults. For simplicity of illustration, this example assumes O = 00, 0°, RF = 0, and a 90° system angle. 90. 90. 90. V1mem V1 V1 mem Z1L.1 Z1L.1 270.270 . 270. a. ForwardAG AGFault a. Forward Fault b. Reverse Reverse AG AG Fault Fault b. Figure 16: AG Mho l\D1o Denominator Term Inputs for Forward and Reverse AG Faults The sign of MAGD is positive for forward faults and negative for reverse faults. Because the sign changes with fault direction, we can use the denominator as a directional element. CAN CAN SUPERPOSITION SUPERPOSITION IMPROVE IMPROVE THE THE Z = = V V IIII PERFORMANCE? PERFORMANCE? v II method under- and overreaches for resistive ground faults with load because I The zZ = V (IAPRE)from the faulted phase and IF are not in phase. Subtracting balanced prefault current {lAPRE) (IJ results in a current (1') current {lJ {1') which is in phase with the total fault current, IF, assuming balanced prefault load. This I' current is referred to as the superposition current. Let's analyze the approach of substituting I' for the faulted phase current in the AG equation shown in Table 1 and check its performance. 16 16 Figure 17 shows the superposition current apparent impedance calculation (Z') results for AG faults at m = 0.85 and various RF and load flow conditions. This modification of the apparent impedance relay has severe under- and overreaching tendencies. One difference between the distance measurement results shown in Figure 17 and those shown in Figure 10, is the load flow conditions which cause under- and overreach are exactly opposite. The superposition apparent impedance relay underreaches for load out, and overreaches for incoming load flow, where the simple apparent impedance relay underreached for incoming load and overreached for load out. Im(Z') ~ " 8=+30" 8=0 " x 8=-30 " Re(Z') 8=-60 " FAULT RESISTANCELEGEND' X RF=O.Q .RF=10.Q .RF=25.Q ~ RF=50.QPR(, Figure 17: Superposition Apparent Impedance Performance Depends on RF and O Also notice the right-hand resistance threshold must be set almost ten times greater than the line resistance value to just detect an AG fault with zero fault resistance during heavy incoming load flow conditions (0 = -600). -60°). While it is desirable to detect these faults, this large resistance reach makes the relay susceptible to overreach for lower incoming load conditions (eg. 0 = -30°) with fault resistance. These These last last points, points, coupled coupled with with those those noted noted earlier earlier for for the the Z = V II calculation calculation results, results, emphasizes not an emphasizes that that an an apparent apparent impedance impedance relay relay is is not an acceptable acceptable alternative alternative to to properly properly polarized polarized distance distance elements. elements. 17 17 WHEN CAN WE USE V II CHARACTERISTICS? One One example example where where Z == VII VII can can be be useful useful is is the the detection detection of of balanced balanced conditions, conditions, such such as as load. load. For For example, example, we we can can define define incoming incoming (ZLOADIN) (ZLOADIN) and and outgoing outgoing (ZLOADoUT) (ZLOADoUT) load load regions regions with with thresholds thresholds and and check check the the V II calculation calculation result result against against these these thresholds. thresholds. These These regions regions define define the the Load-Encroachment Load-Encroachment Characteristics. Characteristics. If the the calculated calculated V VIIII is is inside inside either either of of these these regions, regions, the the load-encroachment load-encroachment logic logic blocks blocks the the phase phase distance distance elements elements from from tripping. tripping. A load load condition, condition, a three-phase three-phase mho mho (3P21) (3P21) and and relay relay load-encroachment load-encroachment characteristics characteristics are are shown shown in in Figure Figure 18. 18. For For this this heavy heavy load-out load-out condition, condition, the the 3P21 3P21 element element is is blocked blocked from from operating operating because because load load also also resides resides inside inside the the LOADoUT LOADoUT load-encroachment load-encroachment characteristic. characteristic. Im(V/I) 35 35 I T u (1) ~ 9. ~ v IJ) U1 3P21 TIME TIME DELAYED DELAYED 3P21 ZLOAD ZLOAD OUT OUT LOAD Re(V/I) W .uU~ Z « 1U « W a: ZLOAD ZLOAD IN IN 1U ~ L ZLOAD OUT 52A ! : -35 -35 II52A -35 35 35 35 RESIST ANCE [.Qsec RESISTANCE [.Qsec.] Z1S=(0.1).Z1L Z1s=(0.1).Z1L Figure 18: 18: Figure 6=60. 6=60" zZ = VII VII Load-Encroachment Load-Encroachment ZR = 3. Z1L ZR=3.Z1L Characteristic Characteristic Prevents Prevents Phase Phase Distance Distance Element Element from from Operating Operating Under Under Heavy Heavy Load Load Conditions Conditions SUMMARY SUMMARY 1. 1. The apparent impedance calculation result (Z = V /1) II) compared with geometric characteristics (box or circle) presents serious under- and overreaching problems when load flow and fault resistance are combined. 2. 2. The The zZ = VII VII method method has has the the same same performance performance deficiencies deficiencies as as self-polarized self-polarized relays. relays. 18 18 3 The z = v 1I approach is not improved 4. Writing the torque equation for a properly polarized relay characteristic, setting it equal to zero, and solving for the minimum reach required to just detect the fault yields a result which we can test against scalar thresholds (Reference I). This method achieves the very desirable result of offering one calculation (per fault loop) for all zones with the performance of properly polarized relay elements. 5 We present ground-fault-resistance elements which estimate the fault resistance. This estimate rejects the load-influenced positive-sequence current, can be used for multiple zones, and can be set greater than the minimum load impedance. 6. The z = v II calculation encroachment by using superposition can be used to detect load conditions, characteristic current. as in the new load- (Reference I). In conclusion, the Z = V 1I calculations have some use in elements intended to measure load, but perform poorly compared to properly polarized relay element calculations, as represented by the equations given for r and RF" REFERENCES 1. Edmund 0. Schweitzer III and Jeff Roberts, Distance Element Design, 19th Annual Western Protective Relay Conference, October 1992, Spokane, W A, USA. 2. A. R. Van C. Warrington, Protective Relays: Their Theory and Practice, Chapman and Hall, 1969, Volumes I and II. . 3. v. 4. Paul M. Anderson, Analysis of Faulted Power Systems, The Iowa State University Press, 1983. Cook, Analysis of Distance Protection, 19 John Wiley and Sons Inc., 1985 BIOGRAPHIES Edmund 0. Schweitzer. III is President of Schweitzer Engineering Laboratories, Inc., Pullman, Washington, U.S.A., a company that designs and manufactures microprocessorbased protective relays for electric power systems. He is also an Adjunct Professor at Washington State University. He received his BSEE at Purdue University in 1968 and MSEE at Purdue University in 1971. He earned his PhD at Washington State University in 1977. He has authored or co-authored over 30 technical papers. He is a member of Eta Kappa Nu and Tau Beta Pi. Jeff B. Roberts received his BSEE from Washington State University in 1985. He worked for Pacific Gas and Electric Company as a Relay Protection Engineer for over three years. In November, 1988 he joined Schweitzer Engineering Laboratories, Inc. as an Application Engineer. He now serves as Application Engineering Manager. He has delivered papers at the Western Protective Relay Conference, Texas A&M University, Georgia Tech and the Southern African Conference on Power System Protection. He holds multiple patents and has other patents pending. Armando Guzman received a BSEE degree from University Autonomous of Guadalajara (UAG), Mexico, in 1979. He received a Fiber Optics Engineering Diploma from Monterrey Advanced Studies Technological Institute (ITESM), Mexico, in 1990. He served as Regional Supervisor of the Protection Department in the Western Transmission Region of Federal Electricity Commission (the electrical utility company of Mexico) for 13 years. He lectured at the University Autonomous of Guadalajara in power system protection. Since 1993, he has been with Schweitzer Engineering Laboratories, Inc., where he is currently an Application Engineer. He has authored or co-authored several technical papers. Copyright © SEL 1993, 1994 All rights reserved. 20