Specifications
This drawing shows typical wall switch
connections for MicroLite's MLC-600 Series
Lighting Controllers. Switch Inputs are located at
the bottom of the main circuit board (IBL). The
Pilot Light Module is located directly above the
switch input terminals.
Type: Momentary or Maintained
Wiring notes:
1. All switch wiring is class 2, as defined by article
725 of the National Electrical Code.
2. Recommended wire size: #18–#22 AWG
stranded wires.
3. Maximum circuit length: 2000 ft. For longer
distances, consult MicroLite.
4. Maximum current flow: 6 mA per switch input
and 20 mA per pilot light at 28 VAC.
All information, including illustrations, is believed to be reliable.
MicroLite makes no warranties as to the accuracy or completeness
of this information and disclaims any liability regarding its use.
Specifications are subject to change without notice.
ML5753
© 1997 MicroLite Corporation
Style: Toggle, Rocker, Pushbutton, Rotary and Key
Total Pilot Light current draw per panel is 960 mA maximum.
The switch and Pilot Light common wires can be jumpered
together and connected to either switch commons on the
IBL/IBE or the PLM.
Metasys Compatibility Note:
ILC-Type: Network is capable of programming inputs 1-32
only. Inputs 33-48 can only be programmed via the LCU
keypad and are not addressable from Metasys.
VND-Type: Network is capable of programming and
addressing all 48 inputs.