Low-voltage Wall Switch w/Pilot Light to Electronics Chassis Drawing Number ~ WD6LVPLSJ Revision Date ~ May 1997 Description Specifications This drawing shows typical wall switch connections for MicroLite's MLC-600 Series Lighting Controllers. Switch Inputs are located at the bottom of the main circuit board (IBL). The Pilot Light Module is located directly above the switch input terminals. Type: Momentary or Maintained Wiring notes: 1. All switch wiring is class 2, as defined by article 725 of the National Electrical Code. 2. Recommended wire size: #18–#22 AWG stranded wires. 3. Maximum circuit length: 2000 ft. For longer distances, consult MicroLite. 4. Maximum current flow: 6 mA per switch input and 20 mA per pilot light at 28 VAC. All information, including illustrations, is believed to be reliable. MicroLite makes no warranties as to the accuracy or completeness of this information and disclaims any liability regarding its use. Specifications are subject to change without notice. ML5753 © 1997 MicroLite Corporation Style: Toggle, Rocker, Pushbutton, Rotary and Key Total Pilot Light current draw per panel is 960 mA maximum. The switch and Pilot Light common wires can be jumpered together and connected to either switch commons on the IBL/IBE or the PLM. Metasys Compatibility Note: ILC-Type: Network is capable of programming inputs 1-32 only. Inputs 33-48 can only be programmed via the LCU keypad and are not addressable from Metasys. VND-Type: Network is capable of programming and addressing all 48 inputs. MicroLite Corporation 1150 Powis Road West Chicago, IL 60185 Phone (630) 876-0500 FAX (630) 876-9654