Operating and installation instructions Translation of the original operating instructions NOTE: Print document on both sides Electronic controller Type: 2200 Siemensstraße 10 - 14 50170 Kerpen Germany www.bollfilter.de Date Version Language Order no. Item no. 05.2015 007 en - - 1/34 2 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 Table of Contents 1 Basic safety instructions for the electronic controller . . . . . . . . 5 2 Technical data of controller and control cabinet components . . 7 2.1 2.1.1 2.1.2 2.1.3 2.1.4 Power components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Fuse protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.2 2.2.1 2.2.2 2.2.3 Control circuit board inputs / outputs . . . . . . . . . . . . . . . . . . . . . . . . . 8 Optocoupler inputs (E1 - E5), terminals 31 - 40 . . . . . . . . . . . . . . . . 8 Live relay outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Potential-free relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.1 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.1.7 3.1.8 Device functions and control sequence . . . . . . . . . . . . . . . . . . . . . . . 9 Master switch operation feedback contact. . . . . . . . . . . . . . . . . . . . 10 Control voltage monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Motor fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Differential pressure too high, flushing oil treatment cartridge alarm10 DP - too high, backflushing filter (100 %) . . . . . . . . . . . . . . . . . . . . 10 Key C (number of flushes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Multiple flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 DP alarm (flushing frequency monitoring) . . . . . . . . . . . . . . . . . . . . 11 3.2 Display for "Operation" mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.3 3.3.1 3.3.2 3.3.3 Text messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Text display after switching on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Text display in "Operation" mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.4 3.4.1 3.4.2 3.4.3 Setting and operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Setting level - Viewing and selecting parameters . . . . . . . . . . . . . . 13 Setting level - Changing and saving parameters . . . . . . . . . . . . . . . 13 Return to operation level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.5 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 3.5.6 3.5.7 3.5.8 3.5.9 3.5.10 3.5.11 3.5.12 3.5.13 3.5.14 List and description of parameters. . . . . . . . . . . . . . . . . . . . . . . . . . 14 P0 Filter type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 P1 Multiple flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 P2 Time-controlled backflushing . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 P3 Time-controlled backflushing . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 P4 Back-flushing time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 P5 Filling time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 P6 After-blowing time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 P7 Cartridge alarm delay time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 P8 DP alarm (flushing frequency monitoring) . . . . . . . . . . . . . . . . . 16 P9 Motor fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 P10 Back flushing time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 P11 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 P12 Testcode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 P14 Pressure compensation time . . . . . . . . . . . . . . . . . . . . . . . . . . 18 4 Description and function of controller . . . . . . . . . . . . . . . . . . . . 19 4.1 Controller type 6.18 / 6.19 / 6.44 . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3 / 34 4 / 34 4.2 Controllers of types 6.21/6.22/6.23 / 6.24 . . . . . . . . . . . . . . . . . . . . 20 4.3 Controllers of type 6.60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 4.4 Controllers of type 6.61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 4.5 Controllers of type 6.62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 4.6 Controllers of type 6.64 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 4.7 Controllers of type 6.72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 5 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 5.1 Setting values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 5.2 Worldwide sales and service network, subsidiaries and representatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 1 Basic safety instructions for the electronic controller DANGER! Risk of accidents from improper installation Installing the controller or the connected equipment improperly may cause the device to fail and lead to serious or even fatal personal injuries. You must therefore follow the general safety regulations for equipment in industrial electrical systems and pay particular attention to the following points: • The controller must be installed by qualified specialist staff only (as defined by the guidelines IEC 364, DIN VDE 0105 for electrical equipment). • The laws, guidelines, directives and regulations for the installation of electrical equipment which are valid at the location for installation must be adhered to. • Settings on devices with protection class IP00 without covers must only be made by authorised specialist staff when the devices are switched off. The local regulations for safety and the prevention of accidents must be observed. • The controller must only be operated within the permitted area of application. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 5 / 34 6 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 2 Technical data of controller and control cabinet components 2.1 Power components 2.1.1 Supply Supply L1-L2-L3 direct to 4-pole master switch – Q1 (T1-T2-T3) 2.1.2 Motor control Motor connection U-V-W direct to motor contactor – K1 (2-4-6) 2.1.3 Power supply Primary voltages 0 - 220 V, 380 V, 400 V, 440 V, 500 V, 550 V Secondary voltages 2.1.4 0 V AC - 230 V AC Valve voltage 230 V AC 0 V AC - 115 V AC Valve voltage 115 V AC 0 V DC - 24 V DC Valve voltage 24 V DC 0 V AC - 20 V AC Control circuit board supply voltage Fuse protection Fuses in the control cabinet F1 to F3 each 1 A Fuses on the control circuit board Fuse F1 0.8 A T (slow-blow) Fuse F2 2.0 A T (slow-blow) Operating instructions Typ 2200 Betriebsanleitung Typ 2200 7 / 34 2.2 Control circuit board inputs / outputs 2.2.1 Optocoupler inputs (E1 - E5), terminals 31 - 40 2.2.2 Live relay outputs Outputs VE1 - VN1 to VE3 - VN3 Terminals 8 - 13 NOTE The connections and designations depend on the type of filter and can be found in the respective circuit diagrams. 2.2.3 Potential-free relay outputs Outputs A1 - A15 Messages 1 - 5 (change-over contact) Terminals 16 - 30 NOTE The connections and designations depend on the type of filter and can be found in the respective circuit diagrams. 2.3 Circuit diagrams The circuit diagrams for the controller are contained in the appendix of these operating and installation instructions. 8 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3 Operation 3.1 Device functions and control sequence 1 2 3 4 5 Fig. 3-1 Electronic controller type 2200 1 Fastening 2 Display and operating elements 3 Housing 4 Master switch 5 Connection 1 2 3 4 5 Fig. 3-2 Display and operating elements 1 Display screen for text display, 2 lines of 16 characters 2 "Alarm" LED (red) 3 "Service" LED (yellow) 4 "Operation" LED (green) 5 Keypad Operating instructions Typ 2200 Betriebsanleitung Typ 2200 9 / 34 NOTE The three keys on the keypad are assigned to the key references displayed above them in the second line of the display as follows: Key C: When pressed, shows the number of flushes Key F: When pressed, triggers manual flushing Key Q: When pressed, acknowledges the alarm messages 3.1.1 Master switch operation feedback contact When the master switch is in the "On" position, a contact is made. 3.1.2 Control voltage monitoring As soon as the master switch is actuated, the power supply is activated and the controller is working properly, the green "Operation" LED lights up and the "Control voltage monitoring" relay is activated. In the event of operating voltage failure or a fuse fault on the control circuit board, no LED lights up and the "Control voltage monitoring" relay is no longer activated. 3.1.3 Motor fault If the measured motor current exceeds the set setpoint value for parameter P9, a message appears in the display and a potential-free signal is sent to the relay outputs. The motor and the backflushing function switch off immediately. Once the fault has been remedied, the user has to acknowledge the alarm message by pressing the Q key. 3.1.4 Differential pressure too high, flushing oil treatment cartridge alarm The signal transmitter is a pressure switch contact which is connected to the "Differential pressure indicator DP too high flushing oil treatment" optocoupler input. If the message is active for a longer period than the time set in parameter P7, an alarm message appears in the display. Once the fault has been remedied, the user has to acknowledge the alarm message by pressing the Q key. 3.1.5 DP - too high, backflushing filter (100 %) The signal transmitter is a pressure switch contact which is connected to the "Differential pressure indicator DP too high, backflushing filter" optocoupler input. If the message is active for longer than 2 seconds, an alarm message appears in the display screen and the red "Alarm" LED lights up. Once the fault has been remedied, the user has to acknowledge the alarm message by pressing the Q key. 3.1.6 Key C (number of flushes) When key C (number of flushes) is pressed, the number of flushing cycles which have been performed is shown on the display screen for 3 seconds. 3.1.7 Multiple flushing The number of parameterised chambers is worked off with each flushing command. 10 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3.1.8 DP alarm (flushing frequency monitoring) If "DP flushing" has been activated before the "Time-controlled backflushing" time elapses, the "DP alarm" message appears on the display screen and the yellow "Service" LED lights up. 3.2 Display for "Operation" mode The green "Operation" LED lights up once the power supply has been switched on and the controller is at operation level ("Operation" mode). 3.3 Text messages 3.3.1 Text display after switching on Boll & Kirch Company name xxxxxxxxxx Programme number After a short delay, the parameterised controller type is displayed in the second line of the display. 6.18/6.19/6.44 Controller type 0 6.21/6.22/6.23/6.24 Controller type 1 6.60 Controller type 2 6.60 Alarm DP Controller type 3 6.60.07/6.72.07 Controller type 4 6.60.07/6.72.07 AL. DP Controller type 5 6.61 Controller type 6 6.61 Alarm DP Controller type 7 6.61.07 Controller type 8 6.61.07 AL. DP Controller type 9 6.62 Controller type 10 6.62 Alarm DP Controller type 11 6.64 Controller type 12 6.64 Alarm DP Controller type 13 6.64.07 Controller type 14 6.64.07 AL. DP Controller type 15 6.72 Controller type 16 6.72 Alarm DP Controller type 17 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 11 / 34 3.3.2 Text display in "Operation" mode forced fl. 00:01 Remaining time till forced flushing is triggered 00 h 01 min C-F-Q Reference to keys When flushing has been triggered, the following messages appear in the first line (depending on the source): Mains flushing When flushing is triggered by "Power supply on" Manual flushing When flushing is triggered by the F key forced flushing When flushing is triggered by time-controlled backflushing DP flushing When flushing is triggered by backflushing filter differential pressure When flushing has been triggered, the following messages may in the second line (depending on the source): Flush. time 3S Remaining flushing time After bl. t. 3S Remaining after-blowing time NOTE 3S indicates that the remaining flushing/after-blowing time is 3 seconds. If the C key is pressed, the following message appears on the display screen: No.of flushes xxxxxx cycles Number of flushing cycles The number of flushing cycles is saved and backed up in the event of a mains failure. 12 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3.3.3 Alarm messages NOTE • The red "Alarm" LED lights up every time an alarm message is issued. • All alarm messages are saved and backed up in the event of a mains failure. • The alarm message and the operation messages are shown alternately in the second line of the display, switching every 2 seconds. • When the Q key is pressed, all alarm messages are deleted, but only if the respective cause of the alarm has been remedied. If the cause of the alarm is not remedied, the alarm message appears again. Alarm messages in the display: Motor fault In the event of a "Motor fault" alarm DP too high In the event of "Differential pressure too high Filter 100 %" Cartridge alarm In the event of "Differential pressure too high flushing oil conditioning 100 %" If the flushing frequency monitoring is switched on: DP alarm DP alarm backflushing triggered by differential pressure 75 % 3.4 Setting and operation 3.4.1 Setting level - Viewing and selecting parameters In order to access the setting level "Selecting and viewing parameters" press keys and together until the green "Operation" LED is extinguished (approximately 3 seconds). The first display line shows the parameter and the second line shows the parameter value. All parameters can now be displayed by repeatedly pressing the key or . 3.4.2 Setting level - Changing and saving parameters In order to access the setting level "Changing and saving parameters", press the middle key until the green "Operation" LED flashes (approximately 3 seconds). The parameter can now be changed by repeatedly pressing the key or . In order to save the value and return to the setting level "Selecting and viewing parameters", press the middle key until the green "Operation" LED is extinguished (approximately 3 seconds). 3.4.3 Return to operation level In order to access the operation level, press keys and together until the green "Operation" LED lights up (approximately 3 seconds). Operating instructions Typ 2200 Betriebsanleitung Typ 2200 13 / 34 3.5 List and description of parameters 3.5.1 P0 Filter type 3.5.2 Adjustable in steps of one Range 0 - 17 Factory setting Initial value 0 Text display, line 1 P0 filter type Text display, line 2 6.18/6.19/6.44 P1 Multiple flushing NOTE This parameter is only visible with filter type P0 = 6, 7, 8, 9, 10, 11, 12, 13, 14, 15. 3.5.3 3.5.4 14 / 34 Adjustable in steps of one Range 1 - 99 x Factory setting Initial value 1 Text display, line 1 P1 multiple fl. Text display, line 2 XXX chambers P2 Time-controlled backflushing Adjustable in steps of one hour Range 0 - 59 h Factory setting Initial setting 2 h Text display, line 1 P2 forced flush. Text display, line 2 XXX hours P3 Time-controlled backflushing Adjustable in steps of one minute Range 0 - 59 min Factory setting Initial value 0 min Text display, line 1 P3 forced flush. Text display, line 2 XXX minutes Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3.5.5 P4 Back-flushing time NOTE This parameter is not visible with filter type P0 = 1. 3.5.6 Adjustable in steps of one second Range 5 - 100 s Factory setting Initial value 20 s Text display, line 1 P4 flushing time Text display, line 2 XXX seconds P5 Filling time NOTE This parameter is not visible with filter type P0 = 0 and P0 = 1. 3.5.7 Adjustable in steps of 10 seconds Range 10 - 600 s Factory setting Initial value 180 s Text display, line 1 P5 Filling time Text display, line 2 XXX seconds P6 After-blowing time NOTE This parameter is only visible with filter type P0 = 4, 5, 8, 9, 14, 15. Adjustable in steps of one second Range 5 - 100 s Factory setting Initial value 30 s Text display, line 1 P6 After blow. t. Text display, line 2 XXX seconds Operating instructions Typ 2200 Betriebsanleitung Typ 2200 15 / 34 3.5.8 P7 Cartridge alarm delay time NOTE This parameter is only visible with filter type P0 = 4, 5, 8, 9, 14, 15. 3.5.9 Adjustable in steps of 10 seconds Range 10 - 600 s Factory setting Initial value 30 s Text display, line 1 P7 Cartridge al. Text display, line 2 XXX seconds P8 DP alarm (flushing frequency monitoring) NOTE This parameter is only visible with filter type P0 = 3, 5, 7, 9, 11, 13, 15, 17. Setting Off / On Factory setting Initial setting "On" Text display, line 1 P8 DP alarm Text display, line 2 Off or Text display, line 2 3.5.10 On P9 Motor fault NOTE This parameter is only visible with filter type P0 = 0, 6, 7, 8, 9, 12, 13, 14, 15. 16 / 34 Adjustable in steps of 0.01 A Range 0.10 to 0.99 A Factory setting Initial value 0.4 A Text display, line 1 P9 Motor fault Text display, line 2 0000 mA Operating instructions Typ 2200 Betriebsanleitung Typ 2200 3.5.11 P10 Back flushing time NOTE This parameter is only visible with filter type P0 = 1, type 6.21/6.22/6.23/6.24. Setting: ND 32 = 1 / ND 40 = 2 / ND 50 = 3 (ND = nominal diameter) A certain control time is selected from a table according to the nominal diameter. The parameter is not required if the setting is P0 1. NOTE For filter type 6.21/6.22, the backflushing time must generally be set to ND 50=3. 3.5.12 Adjustable in steps of one Range 0 to 2 Factory setting Initial setting ND 32 = 1 s Text display, line 1 P10 flush.time Text display, line 2 ND=XX =XX sec P11 Language You can select from German, English, French and Spanish. Setting D German ES Spanish F French GB English Factory setting Initial setting D German Text display, line 1 P11 Language Text display, line 2 GB English Operating instructions Typ 2200 Betriebsanleitung Typ 2200 17 / 34 3.5.13 P12 Testcode NOTE This parameter is only visible with filter type P0 = 0. NOTE The test code switches the controller to a test mode which is provided for authorised persons only. 3.5.14 Adjustable in steps of one Range 0 to 250 Factory setting Initial value 0 Text display, line 1 P12 Testcode Text display, line 2 XXX P14 Pressure compensation time NOTE This parameter is only visible with filter type P0 = 12, 13, 14, 15. 18 / 34 Adjustable in steps of one second Range 0 to 99 s Factory setting Initial value 10 s Text display, line 1 P14 PET Text display, line 2 XXX seconds Operating instructions Typ 2200 Betriebsanleitung Typ 2200 4 Description and function of controller 4.1 Controller type 6.18 / 6.19 / 6.44 Inputs Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Outputs Motor Flushing valve Potential-free contacts 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Motor fault" alarm 3) "Motor fault" alarm Output A7, A8, A9 4) "Flushing active" message Output A10, A11, A12 Functional description 6.18, 6.19 and 6.44 See the operating instructions for the filter's function. Flushing is triggered by: 1) Key F 2) The forced flushing time elapsing 3) Pressure switch "DP reached, backflushing filter" Special attributes • All alarms are displayed and signalled and saved via potential-free contacts. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 19 / 34 4.2 Controllers of types 6.21/6.22/6.23 / 6.24 Inputs 6.21/6.22/6.23 and 6.24 Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Outputs 6.21/6.22/6.23 and 6.24 Flushing valve Potential-free contacts and messages 6.21/6.22/6.23 and 6.24 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) "Maximum DP reached" alarm Output A4, A5, A6 Functional description 6.21/6.22/6.23 and 6.24 See the operating instructions for the filter's function. Flushing is triggered by: 1) Key F 2) The forced flushing time elapsing 3) Pressure switch "DP reached, backflushing filter" Special attributes 20 / 34 • All alarms are displayed and signalled and saved via potential-free contacts. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 4.3 Controllers of type 6.60 Inputs 6.60 and 6.60 Alarm DP (flushing frequency monitoring) "Position reached" limit switch Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Additional inputs for 6.60.07 (flushing oil treatment) Pressure switch "DP too high, flushing oil treatment" 100 % Outputs 6.60 and 6.60 Alarm DP Flushing valve Chamber valve Additional outputs for 6.60.07 and 6.60.07 Alarm DP After-blowing valve Potential-free contacts and messages 6.60 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Maximum differential pressure reached" alarm Output A4, A5, A6 Potential-free contacts and messages 6.60 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Maximum differential pressure reached" alarm Output A4, A5, A6 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Potential-free contacts and messages 6.60.07 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) Operating instructions Typ 2200 Betriebsanleitung Typ 2200 21 / 34 Potential-free contacts and messages 6.60.07 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Functional description 6.60 See the operating instructions for the filter's function. Flushing is triggered by: 1) Switching on the power supply 2) Key F 3) The forced flushing time elapsing 4) Pressure switch "DP reached, backflushing filter" Additional functions for 6.60 Alarm DP (flushing frequency monitoring) If flushing is triggered by the "DP reached, back flushing filter" pressure switch before the forced flushing time elapses, a DP alarm is signalled (Flushing frequency alarm). Special attributes 22 / 34 • All alarms are displayed and signalled and saved via potential-free contacts. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 4.4 Controllers of type 6.61 Inputs 6.61 and 6.61 Alarm DP (flushing frequency monitoring) "Position reached" limit switch Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Additional inputs 6.61.07 and 6.61.07 Alarm DP (flushing oil treatment) Pressure switch "DP too high, flushing oil treatment" 100 % Outputs 6.61 and 6.61 Alarm DP Flushing valve Motor Additional outputs for 6.61.07 and 6.61.07 Alarm DP After-blowing valve Potential-free contacts and messages 6.61 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Motor fault" alarm Potential-free contacts and messages 6.61 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Motor fault" alarm 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Potential-free contacts and messages 6.61.07 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm - "Motor fault" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) Operating instructions Typ 2200 Betriebsanleitung Typ 2200 23 / 34 Potential-free contacts and messages 6.61.07 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm - "Motor fault" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Functional description 6.61 See the operating instructions for the filter's function. Flushing is triggered by: 1) Switching on the power supply 2) Key F 3) The forced flushing time elapsing 4) Pressure switch "DP reached, backflushing filter" Special attributes 24 / 34 • When flushing is triggered by switching on the power and an open limit switch, a flushing cycle starts directly with the flushing valve. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 4.5 Controllers of type 6.62 Inputs 6.62 "Position reached" limit switch Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Outputs 6.62 Flushing valve Chamber valve supplied with pulse Potential-free contacts and messages 6.62 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Max differential pressure reached" alarm Output A4, A5, A6 Potential-free contacts and messages 6.62 Alarm DP (flushing frequency monitoring) 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Maximum differential pressure reached" alarm Output A4, A5, A6 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Functional description 6.62 See the operating instructions for the filter's function. Flushing is triggered by: 1) Switching on the power supply 2) Key F 3) The forced flushing time elapsing 4) Pressure switch "DP reached, backflushing filter" Special attributes • When flushing is triggered by switching on the power and an open limit switch, a flushing cycle starts directly with the flushing valve. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 25 / 34 4.6 Controllers of type 6.64 Inputs 6.64 and 6.64 Alarm DP (flushing frequency monitoring) "Position reached" limit switch Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Additional inputs 6.64.07 and 6.64.07 Alarm DP (flushing oil treatment) Pressure switch "DP too high, flushing oil treatment" 100 % Outputs 6.64 and 6.64 Alarm DP Flushing valve Motor Relief valve Additional outputs for 6.64.07 and 6.64.07 Alarm DP After-blowing valve Potential-free contacts and messages 6.64 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Motor fault" alarm Potential-free contacts and messages 6.64 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Motor fault" alarm 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Potential-free contacts and messages 6.64.07 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm - "Motor fault" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 26 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 Potential-free contacts and messages 6.64.07 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm - "Motor fault" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Functional description 6.64 See the operating instructions for the filter's function. Flushing is triggered by: 1) Switching on the power supply 2) Key F 3) The forced flushing time elapsing 4) Pressure switch "DP reached, backflushing filter" Special attributes • When flushing is triggered by switching on the power and an open limit switch, a flushing cycle with the flushing valve starts after expiry of the pressure compensation time. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 27 / 34 4.7 Controllers of type 6.72 Inputs 6.72 and 6.72 Alarm DP (flushing frequency monitoring) "Position reached" limit switch Pressure switch "DP reached, backflushing filter" 75 % Pressure switch "DP too high, backflushing filter" 100 % Additional inputs for 6.72.07 (flushing oil treatment) Pressure switch "DP too high, flushing oil treatment" 100 % Outputs 6.72 and 6.72 Alarm DP Flushing valve Chamber valve Additional outputs for 6.72.07 and 6.72.07 Alarm DP After-blowing valve Potential-free contacts and messages 6.72 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Maximum differential pressure reached" alarm Output A4, A5, A6 Potential-free contacts and messages 6.72 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Group fault: "Maximum differential pressure reached" alarm Output A4, A5, A6 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Potential-free contacts and messages 6.72.07 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 28 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 Potential-free contacts and messages 6.72.07 Alarm DP 1) "Control voltage monitoring" alarm Output A1, A2, A3 2) Collective fault, comprising: Output A4, A5, A6 - "Maximum differential pressure reached" alarm and - "Cartridge" alarm (DP alarm flushing oil treatment) 3) "Backflushing triggered by DP" alarm Output A7, A8, A9 Functional description 6.72 See the operating instructions for the filter's function. Flushing is triggered by: 1) Switching on the power supply 2) Key F 3) The forced flushing time elapsing 4) Pressure switch "DP reached, backflushing filter" Additional functions for 6.72 Alarm DP (flushing frequency monitoring) If flushing is triggered by the "DP reached, back flushing filter" pressure switch before the forced flushing time elapses, a DP alarm is signalled (Flushing frequency alarm). Special attributes • All alarms are displayed and signalled and saved via potential-free contacts. • If the controller is in parameterisation mode, flushing cannot be triggered manually. • If the "Controller type" parameter is changed, the functions are re-started. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 29 / 34 30 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 5 Appendix 5.1 Setting values Operating instructions Typ 2200 Betriebsanleitung Typ 2200 31 / 34 5.2 Worldwide sales and service network, subsidiaries and representatives If you require service or spare parts, please contact the main site or our subsidiaries, representatives or service points. Deutschland 1 2 3 BOLL & KIRCH Filterbau GmbH Croatia 1 Marine Trade d.o.o. Poland 1 TRIMOR sp. z o. o. Postfach 1420, D-50143 Kerpen Vladimira Nazora 6 ul. Andersa 17 Siemensstr. 10-14, D-50170 Kerpen HR - 47000 Karlovac PL-81-831 Sopot Tel.: +49/(0)2273/562-0 Tel.: +385/(0)47/ 61 19 07 Tel.: +48/(0)58 551 66 40 Fax: +49/(0)2273/562-223 Fax: +385/(0)47/ 43 12 61 Fax: +48/(0)58 555 19 29 E-Mail: info@bollfilter.com E-Mail: marine-trade@ka.t-com.hr E-Mail: trimor@trimor.com.pl www.bollfilter.com www.trimor.com.pl Cyprus 1 3 BOLL & KIRCH Filterbau GmbH 1 Geschäftsstelle Nord 124 Gladstonos Street Datschnyi prospekt, 2 CY - 3032 Limassol Geb. 1, Lit. A, Raum 23N Tel.: +49/(0)4102/4740-0 Tel.: +357/(0)25 889 999 RUS - 198207 St. Petersburg Fax: +49/(0)4102/4740-22 Fax: +357/(0)25 763 902 Tel.: + 7/(0)812-364-61-80 E-Mail: info@bollfilter.de E-Mail: info@mieserv.cy.net www.miegroup.com.cy Fax: + 7/(0)812-364-61-80 Denmark / Sweden / Norway / Iceland / Finland / Lithuania / Latvia / Estonia IVG Pumpen- und Filtrationstechnik Gera D - 07552 Gera Tel.:+49/(0)365/42 00 07 4 1 2 3 E-Mail: info@bollfilter.ru 1 2 3 Switzerland / Liechtenstein EIG CRUSTAG 120 Route de Frontenex BOLLFILTER Nordic ApS CH - 1208 Genève Fax: +49/(0)365/42 00 07 5 Hammerbakken 21 Tel.: +41/(0)22/73 59 50 0 E-Mail: ivg-neubert@superkabel.de DK - 3460 Birkerød Fax: +41/(0)22/78 66 17 1 www.ivg-neubert.de Tel.: +45/(0)45/42 12 00 E-Mail: info@eig-crustag.ch Fax: +45/(0)45/42 12 99 www.eig-crustag.ch BOLL & KIRCH Filterbau GmbH E-Mail: info@bollfilter.dk Geschäftsstelle Süd www.bollfilter.dk 1 2 3 Spain / Portugal / Argentina / Rangaustraße 7a Chile / Peru / Uruguay D - 91639 Wolframs-Eschenbach BOLLFILTER España S.L. Greece / Bulgaria Tel.: +49/(0)9875/97899-0 FILTERKON Zona Cami Ral Paseo del Ferrocarril, 339 3ª – 2 a E-Mail: norbert.henkelmann@bollfilter.de Vas. Amalias 2 E - 08860 Castelldefels www.bollfilter.de GR - 14561 Kifissia Tel.: +34/(0)93/634 26 80 Tel.: +30/(0)210/92 17 671 Fax: +34/(0)93/665 22 79 Fax: +49/(0)9875/97899-29 1 2 3 Europe 1 2 3 000 BOLLFILTER Russland D - 22926 Ahrensburg Prehlis 13 A 1 1 2 3 An der Strusbek 34 www.bollfilter.de 1 Russia / Ukraine / Belarus M.I.E. Services Ltd. The Hawk Building Fax: +30/(0)210/92 42 242 E-Mail: info@bollfilter.es Austria / Czech Republic / Slovakia / Slovenia E-Mail: filterkon@filterkon.com www.bollfilter.com Schmachtl GmbH Great Britain / Ireland Lubrafil B.V. BOLLFILTER UK Limited Aalborg 2 A - 4020 Linz Unit 9 Station Road NL - 2993 LP Barendrecht Tel.: +43/(0)732/76 46 0 UK - Tolleshunt D'arcy, Essex CM9 8TY Tel.: +31/(0)180/55 62 55 Fax: +43/(0)732/78 50 36 Tel.: +44/(0)1621/86 21 80 Fax: +31/(0)180/55 62 65 E-Mail: g.oehler@schmachtl.at Fax: +44/(0)1621/86 92 57 E-Mail: lubrafil@lubrafil.nl www.schmachtl.at E-Mail: sales@bollfilter.co.uk www.lubrafil.nl Pummererstrasse 36 www.filterkon.com 1 2 3 The Netherlands 1 2 3 www.bollfilteruk.co.uk 1 Belgium / Luxembourg 1 2 3 1 2 Turkey ARES PLAKALI ESANJOR SAN. DE.CO.STA Spa Ve TIC. LTD. STI B - 2900 Schoten Via Bicetti de Buttinoni, 12 HSOSB ORDU CAD. NO:4 Tel.: +32/(0)3 646 61 80 I - 20156 Mailand 01350 ADANA, Türkei Fax: +32/(0)3 646 93 98 Tel.: +39/(0)0238/00 52 83 Tel.: +90/(0)322 / 394 3200 E-Mail: info@auximeca.be Fax: +39/(0)0238/00 36 31 Fax: +90/(0)322 / 394 3228 www.auximeca.com E-Mail: sales@decosta.it E-Mail: bollfilter@aresphe.com www.decosta.it www.aresphe.com Wijtschotbaan 3/3 32 / 34 Italy AUXIMECA N.V. Operating instructions Typ 2200 Betriebsanleitung Typ 2200 America Africa Middle East USA / Canada 1 2 3 2 3 1 2 South Africa Safe Technical Supply Co. L.L.C. 1 2 BOLLFILTER Corporation P.O. Box 4832 Afrifil Manufacturing (PTY) LTD 22635 Venture Drive UAE - Dubai Novi, MI 48375 - USA Tel.: +971/(0)4/32 43 24 0 ZA - Isando, 1600 Tel.: +1/(0)248/773-8200 Fax: +971/(0)/4/32 43 78 6 Tel.: +27 11 452 5444 8 Pressberg Road Modderfontein Fax: +1/(0)248/773-8201 E-Mail: info@safetechnical.com Fax: +27 11 609 9535 E-Mail: latorre@bollfilterusa.com www.bollfilterusa.com www.safetechnical.com E-Mail: sales@afrifil.co.za www.afrifil.co.za People's Republic of China incl. Hong Kong Motor-Services Hugo Stamp, Inc. USA - Ft. Lauderdale, Florida 33315 1 2 3 BOLLFILTER CHINA Ltd. Tel.: +1/(0)954/763 3660 2/F No. 178 South Riying Road Fax: +1/(0)954/763 2872 Waigaoquiao Free Trade Zone Shanghai 200131 China Asia Tel.: +86 21 5043 3328 Fax: +86 21 5043 3329 1 2 3 India E-Mail: grace.yip@bollfilterchina.com BOLLFILTER India Pvt. Ltd. www.bollfilterchina.com "Monarch Plaza", Office No. 106 Singapore / Malaysia / Indonesia Sector-11, CBD Belapur, IN - Navi Mumbai 400614 1 2 3 Tel.: +91/(0)22/27 56 01 47 1 2 3 IMI Corporation Pte. Ltd. 13 Joo Koon Crescent Fax: +91/(0)22/27 56 01 46 SGP - Singapur 629021 E-Mail: info@bollfilterindia.com Tel.: +65-68 61 42 22 www.bollfilter.com Fax: +65-68 62 42 22 E-Mail: imicorp@imicorp.com.sg Japan www.imicorp.com.sg BOLLFILTER Japan Ltd. South Korea Imon Kobe Bldg. 13F 95 Edo-machi, Chuo-ku JP - Kobe 650-0033 1 2 3 Blohm + Voss (Korea) Ltd. Room 1812, Ocean Tower Tel.: +81/(0)78/331 8031 760-3, U-Dong, Haeundae-gu Fax: +81/(0)78/331 8032 612-020 Pusan, Korea E-Mail: info@bollfilter.jp Tel.: +82-51-740 5700 www.bollfilter.jp Fax: +82-51-740 57 04/5/6 E-Mail: bvkorea@bvkorea.com 1 2 3 Verkaufsbüro Agency Lager Stockist Service Service Februar 2015 Operating instructions Typ 2200 Betriebsanleitung Typ 2200 33 / 34 34 / 34 Operating instructions Typ 2200 Betriebsanleitung Typ 2200