thermo king truck, trailer, cr, das, and dsr alarm codes

advertisement
THERMO KING TRUCK, TRAILER, CR, DAS, AND DSR ALARM CODES
THIS DOCUMENT SHOWS ALL CURRENT TRUCK, TRAILER, CR, DAS, AND DSR ALARM CODES. NOT ALL CODES ARE POSSIBLE ON ALL UNITS.
IF THE ALARM APPLIES TO A MULTI-TEMP ZONE, THAT ZONE WILL BE IDENTIFIED.
BE SURE TO RECORD ALL ALARMS THAT OCCUR. THEY ARE VALUABLE TO THE SERVICE TECHNICIAN.
ALARM CODE NUMBERS MARKED WITH PARTENTHESIS (XX) MAY EXIST WITH ALARM CODE 84 AND MAY CLEAR AUTOMATICALLY.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Num
00
02
03
04
05
06
07
08
(09)
(10)
11
12
13
14
15
16
(17)
(18)
(19)
(20)
(21)
(22)
23
24
25
(26)
(27)
28
29
30
31
32
33
34
35
(36)
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
61
62
(63)
64
65
66
67
68
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
Color
Description
Operator Action
No Alarms Exist
Check Evaporator Coil Sensor (Zone)
Check (Control) Return Air Sensor (Zone)
Check (Control) Discharge Air Sensor (Zone)
Check Ambient Temp Sensor
Check Coolant Temp Sensor
Check Engine RPM Sensor
Unit Running on Coil Sensor (Zone)
High Evaporator Temperature (Zone)
High Discharge Pressure (or Temperature)
Unit or Zone Controlling on Alternate Sensor (Zone)
Sensor or Digital Input Shutdown (Zone)
Sensor Check (Zone)
Defrost Terminated by Time
Check Glow Plugs or Intake Air Heater
Manual Start Not Completed
Engine Failed to Crank
High Engine Coolant Temperature
Low Engine Oil Pressure
Engine (Vapor Motor CR) Failed to Start
Cooling Cycle Check (Zone)
Heating Cycle Check (Zone)
Cooling Cycle Fault (Zone)
Heating Cycle Fault (Zone)
Alternator Check
Check Refrigeration Capacity (Zone)
Vapor Motor RPM High (CR)
Pretrip or Self Check Abort
Defrost Damper Circuit Check (Zone)
Defrost Damper Stuck Closed (Zone)
Check Oil Pressure Switch
Refrigeration Capacity Low (Zone)
Check Engine RPM
Check Modulation Circuit
Check Run Relay Circuit
Electric Motor Failed to Run
Check Engine Coolant Level
Electric Phase Reversed
Check Water Valve Circuit
Check High Speed Circuit
Check Engine Coolant Temp
Unit Forced to Low Speed
Unit Forced to Low Speed Modulation
Check Fuel System
Check Hot Gas or Hot Gas Bypass Circuit
Check Air Flow (Zone)
Remote Sensor Shutdown
Check Belts or Clutch
Check Spare Sensor 1
Reset Clock
Check Shutdown Circuit
Check Heat Circuit (Zone)
Check Economizer Valve Circuit
Test Mode Timeout
Check Engine Speeds
Check Evaporator Fan Low Speed (Zone)
Check Evaporator Fan High Speed (Zone)
Low Battery Voltage
Ammeter Out of Calibration
Engine or Vapor Motor Stopped
Pretrip Reminder
Abnormal Temperature Differential (Zone)
Low Engine Oil Level
Check Liquid Line Solenoid Circuit (Zone)
Internal Controller Fault Code
Hourmeter Failure
Hourmeter 4 Exceeds Set Time Limit
Hourmeter 5 Exceeds Set Time Limit
Hourmeter 6 Exceeds Set Time Limit
Controller Reset to Defaults
Controller RAM Failure
Controller EPROM Failure
Controller EPROM Checksum Failure
Data Log EPROM Failure
Internal Data Logger Overflow
Check Compressor Temp Sensor
High Compressor Temp
High Compressor Temp Shutdown
Low Engine Coolant Temp
Restart Null
Forced Unit Operation
Check Discharge Pressure Sensor
Check Suction Pressure Sensor
Reserved for CR
Check Electronic Throttling Valve (ETV) Circuit
Electric Overload
No action required.
Manually monitor temperature. Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
Manually monitor temperature. Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
Unit/zone cannot operate and is shut down. Repair immediately.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
Unit cannot operate and is shut down. Repair immediately. Switch to Diesel Mode
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Add fuel as necessary. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Clear alarm and restart unit.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
THERMO KING TK 40933-8-CH Rev 14 (02-25-15)
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Num
91
92
93
94
95
96
97
98
99
(100)
101
(102)
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
163
175
176
177
178
180
188
203
204
216
233
234
235
250
251
252
253
254
Color
Description
Operator Action
Check Electric Ready Input
Sensor Grades Not Set (Zone)
Low Compressor Suction Pressure
Check Loader #1 Circuit
Check Loader #2 Circuit
Low Fuel Level
Failed Remote Return Air Sensor (CR)
Check Fuel Level Sensor
High Compressor Pressure Ratio
Heater Fan Failure (CR)
Controlling on Evap Coil Outlet Temp (CR)
Low Evaporator Coil Temperature (CR)
Low Heater Fuel Level (CR)
Check Remote Fan Speed (Zone)
Check Receiver Tank Press Sol Circuit
Check Purge Valve Circuit
Check Condenser Inlet Sol Circuit
Door Open Timeout (Zone)
Check High Discharge Pressure Sensor
Check Suction Line Sol Circuit (Zone)
Unit Not Configured Correctly (Zone)
Check Remote Fans (Zone)
Check Electric Heat Circuit (Zone)
Multiple Alarms - Can Not Run (Zone)
Check High Pressure Cut Out Switch
Check High Pressure Cut In Switch
Auto Switch from Diesel to Electric
Auto Switch from Electric to Diesel
Reserved for CR
Check Alternator Excite Circuit
Check PMW Liquid Injection Circuit
Check Diesel/Electric Circuit
Check Evap Coil Inlet Temp Sensor (CR)
Check Evap Coil Outlet Temp Sensor (CR)
Check Tank Level Sensor (CR)
Check Back Pressure Regulator (CR)
Setpoint Not Entered (Zone)
Engine Run Time Maint Reminder #1/Service Due
Engine Run Time Maint Reminder #2
Electric Run Time Maint Reminder #1
Electric Run Time Maint Reminder #2
Total Unit Run Time Maint Reminder #1
Total Unit Run Time Maint Reminder #2
Controller Power On Hours
Check Spare Digital Inputs
Check Spare Digital Outputs
Check Damper Motor Heater Output
Log DAS Real Time Clock Battery Failure (DAS)
Abort Evacuation Mode
Not currently used
Auto Switch Diesel to Electric Disabled
Check Thermax Valve
Check Remote Drain Hose Heater Output (Zone)
Lost CAN Communications to Expansion Module
Lost Controller ON Feedback Signal
Software Version Mismatch
Check Multi-Temp Fan Speed Control Output (Zone)
Auto Switch Electric to Diesel Disabled
Alarm Not Identified
Sensor Out of Range Low (DAS and HMI) (Zone)
Sensor Out of Range High (DAS and HMI) (Zone)
DAS Failed Sensor (DAS)
Expansion Module Flash Load Failure
Low Suction Pressure Switch Failure
Lost CAN Communications to HMI
Check Suction/Liquid Heat Exchanger Bypass Valve
OptiSet Plus Profile Mismatch
Primary Software Failed to Load
Check Battery Condition
Lost CAN Communications to Radio Expansion Board
Log DAS Real Time Clock Invalid (DAS)
Emission Control Failure
Check Electronic Expansion Valve (CR)
Check Evaporator Pressure Sensor (CR)
Check CO2 Tank Pressure Sensor (CR)
Low CO2 Fuel Level (CR)
TriPac Compressor Alarm
Log DAS Microprocessor Fault (DAS)
Check Display Return Air Sensor (Zone)
Check Display Discharge Air Sensor (Zone)
Check DAS Digital Inputs (DAS)
REB Switching Off, Conservative to Full Null
Check Relative Humidity Sensor Circuit
High Engine Coolant Temperature Check
DAS Clock Time Reset (DAS)
Check Radio Expansion Board Configuration
Check Auto Fresh Air Exchange Circuit
REB On Back Up Battery, Alarms Disabled
Check Auxiliary Coolant Temp Sensor
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Add fuel as required.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Close doors. Report alarm at end of day.
Replaced by Alarm Code 86
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Unit/zone cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Normal operation – does not affect performance.
Normal operation – does not affect performance.
THERMO KING TK 40933-8-CH Rev 14 (02-25-15)
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Manually monitor load temperature. Report this alarm at the end of the day.
Be sure setpoint is adjusted to required temperature.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Manually monitor load temperature. Report this alarm at the end of the day.
Report alarm at end of day.
If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Unit cannot operate and is shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Manually monitor temperature. Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
THERMO KING PRECEDENT 500 SERIES ALARM CODES
The 500 Series Thermo King Alarm Codes shown below are used on Thermo King Precedent applications.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Num
Color
500
501
505
506
507
508
509
510
511
512
513
514
515
516
518
519
520
521
522
523
524
525
526
528
529
530
531
538
539
540
542
543
544
545
546
547
548
549
550
551
552
553
599
Description
Operator Action
Check Host Evaporator Blower Low Speed
Check Host Evaporator Blower High Speed
Check Roadside Condenser Fan Motor Speed Circuit
Check Curbside Condenser Fan Motor Speed Circuit
Check Digital Scroll Output Circuit (Scroll Only)
Speed Request Communication Error
ECU Failed to Enable
ECU Run Signal Failed
Engine Wait to Start Time Delay Expired
High Compressor Suction Pressure (Scroll Only)
Low Compressor Suction Ratio (Scroll Only)
Low Compressor Discharge Pressure (Scroll Only)
Minimum ETV Discharge Superheat Temp (Scroll)
I/O Controller to Application Controller Com Failure
Generator Ground Fault
Check Battery Charger Input Power
Check Battery Charger Output Power
Battery Charger External/Environmental Fault
Battery Temperature Sensor Alarm
Battery Charger Indicated Conditions
Generator Op Limit Vout to Frequency Ration
Generator Frequency Range Fault
Generator Operational Limit Output Current
Failed J1939 CAN Comm Base Controller/Charger
Check Fuel Pump Circuit
Low Pressure Differential (Scroll only)
Check Economizer Pressure Sensor (Scroll only)
Engine J1939 CAN Data Link Degraded
Engine J1939 CAN Data Link Failed
Illegal Engine Operating State
Battery Charger Fault – Unit Forced to Low Speed
Battery Charger Internal Short
Battery Charger External Short
Battery Charger Output Voltage Exceeded Limit
Battery Charger Operating Bulk Voltage Out of Range
AC Bus Phase Loss
Battery Charger Temperature Below Operating Range
Battery Charger AC Input Overvoltage
Battery Charger Internal Overvoltage Fault
Battery Charger Internal Temp Sensor Fault
Battery Charger Charging – Low Battery
Battery Charger Operating Derated Due to High temp
Engine Service Tool Connected
Not implemented
Not implemented
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
The unit is no longer able to operate and has been shut down. Repair immediately.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Maintenance information only. Report alarm at end of day.
Maintenance information only. Report alarm at end of day.
Maintenance information only. Report alarm at end of day.
Maintenance information only. Report alarm at end of day.
Maintenance information only. Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Maintenance information only. Report alarm at end of day.
Maintenance information only. Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Report alarm at end of day.
PRECEDENT 600 SERIES YANMAR DIAGNOSTIC TROUBLE CODES (DTC)
If the Yanmar Engine Control Unit (ECU) determines an engine related problem exists, one or more Yanmar Diagnostic Trouble Codes (DTC’s) will be set by the ECU. As a result,
one or more Thermo King 6xx codes will also be set and displayed on the HMI Control Panel and the ServiceWatch Data Logger as shown below.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Num
600
601
603
604
605
607
608
609
610
611
613
614
615
616
617
618
619
620
623
624
625
626
642
699
Color
Description
Operator Action
Check Crankshaft Speed Sensor
Check Camshaft Speed Sensor
Check Exhaust Pressure Sensor
Check Coolant Temp Sensor
Check Fresh Air Temp Sensor
Check Fuel Temperature Sensor
Check Rail Pressure Sensor
Check Intake Pressure Sensor
Check Atmospheric Pressure Sensor
Check Glow Plug Circuit
Check Injectors
Check High Pressure Fuel Pump
Rail Pressure Fault
Engine Overspeed
Internal ECU Fault
Check EGR System
ECU Main Relay Fault
No RPM Detected During Start Attempt
TRUCAN Message Timeout
Check EGR Temperature Sensor
Check Intake Air Temperature Sensor
Check Exhaust Temperature Sensor
ECU Forced Low Speed
Unknown ECU Fault
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately.
If unit is shut down repair immediately.
If unit is shut down repair immediately.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately.
THERMO KING TK 40933-8-CH Rev 14 (02-25-15)
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
PRECEDENT 800 SERIES PEUGEOT DIAGNOSTIC TROUBLE CODES (DTC)
If the Peugeot Engine Control Unit (ECU) determines an engine related problem exists, one or more Peugeot Diagnostic Trouble Codes (DTC’s) will be set by the ECU. As a result,
one or more Thermo King 8xx codes will also be set and displayed on the HMI Control Panel and the ServiceWatch Data Logger as shown below.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Num
Color
800
801
804
807
808
809
810
811
813
815
818
819
820
825
826
827
828
829
830
832
833
834
836
838
839
840
841
842
843
844
845
846
847
853
854
899
Description
Operator Action
Crankshaft Position Sensor Error
Camshaft Position Sensor Error
Engine Coolant Temperature Sensor Error
Fuel Temperature Sensor Error
Rail Pressure Sensor Error
Intake Air Pressure Sensor Error
Atmospheric Pressure Sensor Error
Glow Plug Circuit Error
General Injector Error
Fuel Pressure Regulator Error
EGR Valve Actuator Error
ECU Power Relay Error
Main ECU Relay Error
T1 Air Intake Temperature Sensor Error
T2 Air Intake Temperature Sensor Error
EGR Valve Position Sensor Error
Lambda System Error
Engine Communication Error
Air Flow Meter Error
Engine Power Supply Error
High Pressure Pump Fuel Metering Unit Error
Water in Fuel Sensor Error
Major ECU Failures
Intake Air System Error
Engine Speed Error
Fuel Injection Energizing Error
High Pressure Pump Wear
Engine Running in Safe Mode – Low Speed
Fuel Injection System Error
Engine Failed to Crank
Starter Relay Error
T50 Switch Error
Variant Coding Error
Engine Overspeed (No DTC)
Engine Protection Self Shutdown
Unknown ECU Fault
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately.
If unit is shut down repair immediately.
If unit is shut down repair immediately.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
Otherwise, report alarm at end of day.
DIRECT SMART REEFER (DSR) ALARM CODES
The DSR Series Thermo King Alarm Codes shown below are used on Thermo King Direct Smart Reefer applications.
COLOR CODE DEFINITIONS
OK TO RUN
CHECK AS SPECIFIED
TAKE IMMEDIATE ACTION
THESE ARE SUGGESTIONS ONLY. ALWAYS CONSULT YOUR COMPANY FOR FINAL DECISIONS.
Code
P1E
P2E
OL
bAt
HP
LP
PSE
tEP
tP4
dr1
dr2
tCO
SOF
-C-
Color
Description
Operator Action
Return Air Temperature Sensor Fault
Remote Return Air Temperature Sensor Fault
Electric Standby Overload
Low Battery Voltage
High Discharge Pressure
Low Suction Pressure
High Pressure Sensor Fault
Electric Standby Motor Thermal Protection Alarm
Power Supply Thermal Protection Alarm
Door 1 Open/Door Switch 1 Failure
Door 2 Open/Door Switch 2 Failure
Electronic Control Module Internal Temperature
Exceeds Limit
Microprocessor Software Failure
Communications Failure, Microprocessor to In-Cab
Control Box
Report alarm at end of day.
Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Close door. Report alarm at end of day.
Close door. Report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
THERMO KING TK 40933-8-CH Rev 14 (02-25-15)
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Download
Study collections