Solar PV Modeling and Impacts on Distribution Systems Greg Shirek Milsoft Utility Solutions Outline • • • Generator Modeling Inverter Ratings and Operating Modes Step Voltage Regulators – Settings – Modes • Developing Solar Irradiance Generation Profiles – Plane of Array Levels – Tracking Systems • • • Generation and Feeder Load Coincidence Levels Solar Irradiance Variability Cases in WindMil – Large 1 MW PV Plant with Voltage Regulator Interactions and Inverter Modes – Feeder Distributed Roof-Top PV • Summary WindMil Generator Models • Rotating Type – Synchronous Generator (adjust kVAR by field winding). – Induction (needs external source of excitation). – Wind Turbines Types 1-4 machine based but coupled with grid via converters (Types 3-4). • Inverter based PV WindMil Generator Model Algorithms • Generators (Load Flow) – Negative load is a current source with real and reactive current injections. – Swing kVAR – Iterate until the level of reactive current (positive or negative) is found that is required to hold the specified voltage given the specified kW. • Generators (Fault Flow) – Simply a voltage source behind and impedance (Zsm). WindMil Generator Models Solar PV Plant Components • • • • • Panels – DC Ratings in Watts. Panels create collectors. Collectors mounted on tracking system. Inverters. Interconnect step-up transformer. Inverter Operating Modes • • • Converts DC to AC via solid state switches (IGBT’s or SCR’s) Fixed Power Factor (Unity, Q=0) Fixed Power Factor (Q≠0) – • Voltage Droop – • Maintain a Fixed PF at the POI, e.g. maintain between 0.98 lag and unity. Increase/Decrease Q linearly based on Voltage at POI within limits. Inverters rating based on voltage, so voltage decrease means can increase Q, and vice versa. Many times used in micro-grids with controllers with autonomous control. Voltage Control – Regulate a set point voltage at the POI by allowing inductive or capacitive Q within the limits of the inverter. q Traditional deployment is to size inverters for PV Array de-rated AC kW due to IEEE 1547 standard, and operate in Unity PF mode (Quadrant 1). Increasing Inverter Potential PPV = Max Total Power Output of Solar PV Plant PQinv = kVA Rating of Inverter Increase kVA rating by just 10% provides (100 kVA → 110 kVA): +/- 45 kVAR or (90% PF lead/lag PF) Step Voltage Regulator Operating Modes • SVR’s include up to 7 control settings to accommodate varying real and reactive power flow directions: 1. 2. 3. 4. 5. 6. 7. – – – – Locked forward Locked reverse Neutral idle Reverse idle Bi-directional Co-generation Reactive bi-directional Modes 1-3: One Direction Tap Changing Control regardless of power flow direction. Modes 5-7: Voltage Control on either primary or secondary side. Mode 7: Forward/Reverse reactive current direction determines if Forward/Reverse mode settings will be used, whereas Modes 1-6 use the real component of current. MODES 6 and 7 MOST COMMONLY USED FOR HIGH PENETRATION DG APPLICATIONS WITH DG GENERATION EXCEEDING MINIMUM CIRCUIT LOAD. Voltage Regulator Operating Modes Bi-Directional -V1 or V2 controlled based on real current component direction Co-Generation – V2 controlled during reverse active current flow Reactive Bi-Directional -V1 or V2 controlled based on reactive current direction WindMil Regulator Models • Defaulted to use co-generation mode during reverse power (power flowing opposite of parent-child connectivity) since the algorithm assumes the downline (child) side is the voltage control point. • Regulators with LDC during reverse power: – Still uses a co-generation mode. – With positive LDC values, will “buck” (lower voltage on child side). – With negative LDC values, will “boost” (raise voltage on child side). • Don’t use SET REGULATION analysis with DG or meshed circuits. • Overall, pay attention to regulator voltages during looped analysis (feeder/source ties, and/or DG) and reverse power. WindMil Regulator Mode Limitations • Limitations – WindMil regulators will not operate in a bi-directional mode with generators downline during reverse power. – Needed enhancements on the list • Bi-directional mode so that power flow direction will control the forward or reverse settings. • Reactive Bi-Directional modes. • Co-generation mode so that either parent or child side of regulator will be the control point. • User Defined Tap Number, similar to Locked Tap but independent of prior voltage drop run. Regulators – Forward with LDC Regulators – Reverse w/ (+) LDC & Gens Regulators – Reverse w/ (-) LDC & Gens PV Plant Array Types Fixed Tilt Fixed Tilt, one axis rotation Clear Sky Insolation Profiles at Site Source: National Renewable Energy Laboratory (NREL) METSTAT (Meteorological/Statistical) solar radiation model. Developed to support production of the NSRDB (National Solar Radiation Database. Estimates hourly values of direct normal, diffuse horizontal, and global horizontal radiation. Sample System 1 MW PV Plant Substation Regulator Line Regulator Contingency Substation Sample System Load Profiles A B C D E A. Peak = 3.6 MW, Used to Find LDC Settings B. Max kW 2.5 MW C. Net Max 1.5 MW D. Min kW 0.8 MW E. Net Min: -0.2 MW Case A – 6 p.m. peak, No PV (3.6 MW) Used to find LDC settings with load center at 120V at end of circuit Substation SVR 124V No LDC Line SVR 120V R=9, X=12 Case B – Max 12 p.m. , no PV (2.5 MW) Substation SVR 124V No LDC Line SVR 120V R=9, X=12 Line SVR at Tap 8 Case C – Max 12 p.m. ,with PV (1.5 MW) Substation SVR 124V, No LDC Line SVR 120V R=9 , X=12 Less regulator LDC boost due to less current Meets ANSI Case D – Min 12 p.m., no PV (800 kW) Substation SVR 124V No LDC Line SVR 120V R=9, X=12 Notice Line Regulator actually bucks voltage Case E – Min 12 p.m., with PV (net -200 kW) • Need to establish cogeneration settings • For case study use 120 V with no LDC • Remember, WindMil gen model assumes co-gen mode • Notice Voltage Rise due to reverse power • Voltages meet ANSI Reverse Power Voltage Rise V = IZ I = DG Current Ø = PF Angle V = I * (R+jX) V ≈ Ir*R + Ix*X Vrise ≈ IRCosØ + IXSinØ Time-Frame Considerations • Previous cases were steady-state by allowing regulators to operate assuming necessary time constants were met to allow regulator step changes. • Overall, for all load cases both with and without PV, voltages appear to meet ANSI Standards. • However, with DER intermittent generation, small time-frame cases need to be considered due to cloud shading as well as the DER disconnecting during a temporary feeder fault to meet IEEE 1547 Standards. • Make use of WindMil regulators LOCKED setting. Ramping Rates from Solar PV Source: EPRI Distributed PV Monitoring Project. High Penetration PV Workshop, April 19, 2012. Ramping Rates from Solar PV Source: EPRI Distributed PV Monitoring Project. High Penetration PV Workshop, April 19, 2012. Voltage Changes due to Intermittency • Regulators have too long of a time delay to operate during intermittency. • From EPRI studies, the 1 MW PV plant will ramp up or ramp down completely within 30 seconds. • Need to check multiple cases at noon to see impacts and find worst case. 1. 2. 3. 4. Minimum feeder load with no PV transitioning to peak PV Maximum feeder load with no PV transitioning to peak PV Minimum feeder load with PV transitioning to no PV Maximum feeder load with PV transitioning to no PV • Worst case voltage change for case 2 (Max kW with No PV → w/ PV). WindMil Procedure for Ramping and/or DG Disconnect for Faults • No PV → PV 1. Run Voltage Drop with Regulators ON and NO generation. 2. Run Voltage Drop with Regulators LOCKED and turn generators ON. • PV → No PV 1. Voltage Drop with Regulators ON with Generation ON. 2. Run Voltage Drop with Regulators LOCKED with Generators OFF. DER Shall Cease to Energize Area EPS 1. 2. 3. 4. 5. 6. 7. 8. 9. A temporary fault occurs. A fault-detection device in the Area EPS detects the fault (i.e. substation recloser). The device opens isolating the Area EPS. The DR interconnection system detects the island, open-phase, or undervoltage condition. The DR ceases to energize the Area EPS. Fault was temporary, so substation device closes restoring power to the EPS. DR stays off-line due to industry standards. Regulators maintain tap settings before outage due to time delay (i.e. 30-45 seconds). Possible low or high voltages ensue on the Area EPS. Maximum feeder load with no PV → peak PV 2.5 MW, No PV 2.5 MW, with PV (1.5 MW Net) Note the Δ Voltage at end of feeder is ~ 4 V (124.5 – 120.5) Remediation Options • After ramping, voltage exceeds 127 volts. • Need to lower voltage downline of regulator to meet ANSI 126 volt standard. Leverage Swing kVAR Generation Mode. • Real-world case studies demonstrate making use of PV inverter operating modes for kVAR import or export may be very beneficial. • PV Inverters can use their reactive power kVAR capabilities “instantaneously.” • Further analyses are warranted to determine forward and co-generation mode settings. • WindMil Procedure: Lock Regulator Taps and Set Generator to Swing kVAR with 1 MW output at 1.016 p.u. voltage (122 V). Inverter Reactive Power Capability Generator Imports 800 kVAR to help increase the voltage “drop.” Regulator remains at tap 8. This 800 kVAR with 1000 kW at max irradiance means the inverter needs to have +/- 80% PF capability. More options need to be explored on how the regulator forward and co-gen modes should be set along with allowing the inverter to operate in reactive power mode. Rooftop Residential PV • Two ways to model – Method 1 – Consumer and Generator Elements. Consumer with actual demand along with separate generator with generated kW. – Method 2 – Just Consumer element. Calculated load tab value to be customer kW demand minus coincidental PV kW generation. Therefore may be negative kW at high irradiance periods. Rooftop Residential Modeling Method 1– With Generators Rooftop Residential Modeling – Method 1 Rooftop Residential Modeling – Method 2 Summary • • • • • • Demonstrated WindMil generator model modes – simple negative load versus swing kVAR. Demonstrated voltage regulator settings affects on line voltages during forward/ reverse power flow with and without Line Drop Compensation and based on parentchild relationship. When analyzing large PV integration, need to know the inverter capabilities and modes so they can be modeled correctly in WindMil. Investigated Solar Irradiance profiles and coincidence with feeder loads for a case study. Reviewed how to investigate ramping/intermittency with Solar PV in WindMil. For simple rooftop PV, customers preference to model generator element along with consumer, or simply use consumer with net load. Thanks for your attention! Questions/Comments? Greg Shirek, PE Lead Support Engineer greg.shirek@milsoft.com Milsoft Utility Solutions