ESL-IE-97-04-36 VARIABLE FREQUENCY MOTOR DRIVES: HARMONICS, POWER FACTOR, AND ENERGY EFFICIENCY Gregory W. Massey, P.E. Electrical Engineer Federal Bureau of Prisons Kansas City, Kansas the energy used under partial load can be greatly reduced, compared to mechanical devices like inlet vanes or water valves. The primary benefit of VFD's is economic; significant energy savings result in a relatively quick payback on capital expenditures. An additional benefit is reduced wear and tear on motors, pumps, fans, pulleys, etc., which run at lower RPMs. ABSTRACT Variable frequency motor drives (VFD's) have been on the market for many years. Early versions were unreliable and prone to failure. Relatively recent developments in Pulse-Width Modulated (PWM) waveform technology have improved VFD reliability and efficiency. This paper provides an overview of PWM variable frequency drive theory and operation. The second portion of the paper provides an overview of the impact of installing VFD's within the electrical distribution system, including concerns regarding harmonics and power factor. NOTE: The views expressed in this paper do not necessarily represent the views of the United States of America, the U.S. Department of Justice, or the Federal Bureau of Prisons. Variable frequency motor drives are non-linear loads and can create problems within the electrical distribution system. Power quality for both the customer and the utility is a critical design consideration when installing VFD's. When the implications of installing variable frequency drives are fully considered, a proper balance between energy efficiency and power quality can be achieved. INTRODUCTION The use of variable frequency AC motor drives has grown at an exponential rate in recent years. VFD's increasingly have become an element of mechanical and electrical systems design in industrial and commercial projects. Some new and retrofit applications include conveyors, chemical processes, manufacturing, wastewater treatment, and HVAC systems. VARIABLE FREQUENCY DRIVES: AN OVERVIEW Motor speed is dictated by the frequency of the source. Typical 60 Hz AC motors display nominal nameplate speeds of 1,200 rpm, 1,800 rpm, and 3,600 rpm for six-, four-, and two-pole motors, respectively. Connection to a 60 Hz source will result in approximately these motor speeds under no­ load conditions. The characteristics of the load and the individual motor, however, will influence the actual speed that the motor will rotate under load. The development of advanced power electronic switching devices has enabled high-frequency switching operation and has improved the performance of PWM inverters for driving AC motors (5). Using solid-state technology provides an efficient, effective, and economical method for controlling motor speed. Variable frequency drives are solid-state power converters that can vary the voltage and frequency delivered to three-phase motors to produce specific motor speeds. To maintain the rated torque of the motor, voltage must be kept proportional to frequency (8). For example, if a motor is operated at 30 Hz, or one­ half speed, the voltage must also be reduced by one­ half of the rated value. If voltage is not reduced proportionately to frequency, the motor will overheat from excessive load currents. The result is that motor speed can be matched to the application requirements. For HVAC systems, this means varying motor speed to control the amount of water pumped through a pipe, air through a duct, or refrigerant through a compressor. In each case, Pulse Width Modulation is the present state-of­ the-art method used to control both voltage and frequency. PWM variable frequency drives consist of three sections; a rectifier, a DC bus, and an inverter. The AC source voltage is converted to DC Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 230 ESL-IE-97-04-36 by the rectifier. In the DC bus, large capacitors charge to the peak of the RMS voltage waveform of the source. where: BHP 1 is the initial horsepower, N. is the initial fan speed, BHPz is the reduced horsepower, and N z is the reduced fan speed. The DC is then "inverted," into a solid-state controlled square-wave output by the inverter. The logic programmed into the inverter determines the width and polarity of the DC pulses, thereby controlling the voltage and frequency, respectively, of the output. The inductance of the motor and motor branch circuit conductors resists the rapid switching of the voltage and smoothes out the DC voltage pulses. The motor accepts the inverter output as a three-phase sine wave. While fan speed is proportional to airflow, input power has a cubic relationship to motor speed. A 15% reduction in fan speed, for example, results in a 15 % reduction in airflow, while horsepower is reduced by 39 % to approximately 61 % of the original power required from the motor: BHP2 =BHP1 Variable frequency drives are typically classified according voltage and horsepower, based upon the motor they will serve (8). Small, low­ voltage motors generally are rated 250 horsepower or less and operate at or below 600 volts AC. Medium­ voltage motors are larger than 250 horsepower and operate above 600 volts AC. Where a motor is large but operates at low voltage, the horsepower rating typically dictates its classification. ( 0.85) 3 =BHP1 (0.614) 1.0 (2) Traditionally, mechanical means, such as guide vanes and dampers, have been employed in restricting airflow and reducing energy consumption. Because of the cubic relationship between fan speed and power, energy savings from installing variable frequency drives surpasses guide vanes, dampers, and similar mechanical means of energy consumption. ENERGY EmCIENCY POWER QUALITY CONCERNS: HARMONICS AND POWER FACTOR The main reason that systems operate much more efficiently with the ability to vary motor speed is because mechanical systems are inherently oversized for their application. HVAC systems, for example, are based on an area's weather extremes. An HVAC system designed to handle extreme summer and winter temperatures requires only a portion of its full capacity on an average day. Harmonics are produced by VFD's because the current is not drawn from the source in a sinusoidal form, but in pulses. These pulses occur when the AC source is at a higher voltage than the DC bus of the drive, during which time the rectifier bridge diodes are forward biased and conduct (3). Actual air-volume requirements for any given HVAC system tend to follow a normal distribution curve (2). Approximately 87% of the time, any given HVAC system requires less than 70 % of its maximum air flow. VFD's can reduce motor speed and motor wear by more closely matching the actual load. Harmonic currents flow from the load toward the utility, seeking a low impedance path to ground, and causing a voltage drop through the distribution system according to Ohm's Law. Harmonic voltages combine with the fundamental source voltage producing voltage distortion throughout the power system. Other equipment is affected by the harmonic-laden system voltage and may inject even more harmonic currents into the system. Additionally, harmonic distortion can result in low power factor. Moreover, VFD's can result in significant energy savings by allowing fans and pumps to approach the ideal performance described by fan laws, which state that fan or pump horsepower, is reduced by the cube of the flow rate (2), as given by the following equation: Most variable frequency motor drives will have a negligible effect on displacement power factor because the current lag associated with a diode bridge is relatively small. Conversely, if significant harmonic currents are present and the utility measures true power factor, or the ratio of real power divided by the total apparent power comprised of real, Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 231 ESL-IE-97-04-36 TPF can be low due to high harmonic power consumption as well as high reactive power consumption. The resulting high apparent power in the denominator results in lower TPF. TPF is always lower than DPF when harmonics exist. With significant harmonic currents present, power factor can be improved by installing harmonic filters. Installing capacitor banks by themselves on a harmonically loaded distribution system may result in a resonant condition. reactive, and harmonic power, power factor will be lower than displacement power factor. Power Factor Based upon the Power Triangle model, real power, expressed as KW, reactive power, expressed as KV AR, and apparent power, expressed as KVA, are related through the Pythagorean Theorem as given below: KVA=JKW2+KVAR2 (3) Harmonic Resonance Inductance increases in proportion to frequency, as given by: Power factor is defined as the cosine of the power factor angle, but can also be determined through trigonometric identities: PF=Cos(8) = KW -KVA (6) where (4) XL is the inductive reactance, f is the fundamental frequency of the system in Hertz,and L is the finite, constant value of inductance in Henries. Power factor, in the classical power triangle representation, is more appropriately referred to as Displacement Power Factor (DPF). DPF is that portion of power factor that is attributable to phase displacement between source voltage and load current at the fundamental frequency. The Power Triangle models real and reactive power at the fundamental frequency of the electrical power system. Harmonic currents cannot be modeled vectorially along with the fundamental current. As such, displacement power factor does not consider that portion of power factor attributable to harmonic load current. Impedance due to inductive reactance increases with frequency, which tends to damp higher order harmonics. Meanwhile, capacitive reactance decreases in proportion to frequency as given by: X= 1 c 21tfC (7) where Xc is the capacitance, and C is the finite, constant value of the capacitance in Farads. True Power Factor True Power Factor (TPF) can be defined by revisiting the definition of power factor as the ratio of real power to apparent power. TPF is the ratio of real power to total power consumed in the system as given by: TPF= __KW __ KVAt;ot;al Impedance due to capacitive reactance decreases with frequency, which does not tend to attenuate higher order harmonics. At a specific frequency, the inductive reactance is equal to the capacitive reactance, which is the definition of resonance. During series resonance, the impedance of the composite transformer(s) and capacitor bank(s) is minimized, essentially cancelling each other. The only impedance to current flow is the pure resistance of the distribution circuit, which is normally low. Again, high magnitudes of harmonic currents at or near the resonant frequency can flow unimpeded through the distribution system. (5) where TPF is the true power factor, KW is the real power consumed by the electrical system, and KVA.c..J is the total apparent power composed of real, reactive, and harmonic power. Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 232 ESL-IE-97-04-36 During parallel resonance, the impedance of the composite transformer(s) and capacitor bank(s) is maximized and harmonic currents at or near the resonant frequency can create high harmonic voltages across the high parallel impedance. installation of capacitors on an electrical distribution system might lead to a resonant condition. The short circuit KVA available from the utility must be determined first, and is given by: Non-Linear Loads and Harmonics A resonant distribution circuit is aggravated because non-linear loads, such as variable frequency drives, generate harmonic currents, operating on the 60 Hertz source voltage and returning harmonic-rich load current to the distribution system (7). The load current is distributed across the harmonic spectrum by non-linear loads, significantly increasing the likelihood of a resonant circuit between inductance and capacitance within the distribution system. where KV A." is the available short circuit KVA from the utility, VL-L is the system operating voltage, and Isc is the available short circuit current. Next, the building or facility distribution system short circuit capacity must be calculated, as given by: Harmonic related problems are well documented in literature and include overheating equipment, blown fuses, and equipment failure. Excessive harmonic voltages and current in capacitors results in increased losses in iron, insulation, and conductors with a corresponding increase in temperature. Life expectancy of electrical equipment is reduced when exposed to excessive heat generated by harmonics. where KV A..:t. is the short circuit capacity of the secondary electrical system, KV A. is the KVA rating of the substation transformer(s), KVA." is the available short circuit KVA from the utility, and ~ is the impedance of the substation transformer(s). Unwanted harmonic currents can be prevented from flowing back through the power system by installing line impedance to "de-tune" the distribution circuit or by installing harmonic filters. Additional line impedance will increase the harmonic order of the resonant frequency. Since inductive reactance increases with frequency, the magnitudes of higher order harmonics are inherently attenuated by inductive reactance. Unfortunately, too much inductive reactance will increase voltage distortion to levels above those found in IEEE 519-1992 (4). Finally, the resonant harmonic of distribution system under analysis is given by: hI Alternatively, harmonic filters "capture" harmonic currents by diverting them through a specially designed series resonant, or low impedance, shunt path to ground. Harmonic filters are an effective and economical way of minimizing harmonic current and voltage distortion and to improve true power factor. = the (10) where h,. is the resonant harmonic, KV A..:t. is the available short circuit KVA from the distribution system, KV A.a: is the available short circuit KVA from motor contribution, and KV ARc is the sum of capacitor KVAR ratings. Under special circumstances, existing capacitor banks can be reconfigured into harmonic filters by adding series reactance, keeping the voltage, current, and reactive power limitations of the capacitor in When Equation 10 indicates a relatively low resonant harmonic, and spectrum analyses indicate that the magnitude of harmonic currents are significant at or near the resonant frequency, the most likely solution wi)) be to install harmonic filters. In fact, low true power factor may be entirely due to harmonic currents generated by the load (6). In those mind. The following series of equations, common in literature, are useful in determining whether the Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 233 ESL-IE-97-04-36 instances, TPF may be improved by installing filters or traps alone. In most cases, a combination of harmonic filters along with capacitors designed to operate at the fundamental frequency are required to improve TPF to acceptable levels in systems with harmonic currents present. 5 % will increase voltage distortion and voltage drop in accordance with Ohm's Law. The drive may not be able to operate under high harmonic distortion or low voltage, depending upon the sensitivity of the VFD. As such, a 3 % reactor is typically used for individual drive applications. Harmonic Mitigation/Improving Power Factor There are two schools of thought on dealing with power system harmonics. The first perspective is management of harmonic load currents. Conductors are oversized. Panelboards have double­ capacity neutrals. Transformers are derated or are K-rated. Motors, generators, and switchgear are oversized to compensate for harmonic currents. In short, equipment is oversized to handle harmonic­ induced heating effects. If harmonic load currents are significant, either in magnitude or harmonic order, it may be necessary to remove these currents from the distribution system for safe operation. Harmonic Filters Active filters have the ability to cancel harmonics in the current waveform by injecting energy into the gaps that are created by rectifier loads (3). In some cases special transformers or input choppers are used. This technology is still developing and not competitive for general use. The second perspective is removal of harmonic currents from the electrical system through filtering or cancellation technology. Large non-linear loads can be individually filtered to reduce or remove harmonic load currents from the system. Zig-zag or multiple-secondary winding transformers cancel balanced harmonic load currents. Every electrical distribution system is unique. It is important to recognize that the most economical approach to dealing with harmonic load current may come from either perspective. The electrical system under consideration will prescribe its own cure. Passive harmonic filters are more commonly used. Passive filters are constructed of one or more tuned resonant circuits. The filters most commonly used with VFD applications consist of individual circuits tuned for the 5th, 7th, and 11th harmonics plus, in a few cases, a high pass filter tuned near the 17th harmonic (3). To compensate for capacitor aging over time, the actual resonant frequency of the harmonic filter is designed to be below the target harmonic. For this reason, a nominal 5th harmonic filter is normally designed for 4.7th harmonic. Inductive Reactance From the perspective of managing harmonics, harmonic currents can be controlled by placing additional line inductance ahead of the variable frequency drive (2). If the line impedance is too low, transient voltage spikes or interruptions can create excessive current spikes that will cause nuisance input fuse blowing and may cause damage to the drive power structure. To prevent the filter from trapping harmonics from the utility grid, a decoupling reactor should be installed as part of the filter. Technical literature is replete with examples of damage caused to harmonic filters installed without a decoupling reactor. Additionally, harmonic filters should have internal protection similar to capacitor banks, such as fuses, along with fault indicators for blown fuses or capacitor failure. Installing line reactors slows the rate at which the drive can draw current. Instead of drawing current in short, spike-like bursts with a high peak current, the drive draws current more slowly, with a much lower, broader peak. Line reactors or drive­ isolation transformers, if a voltage change is required, can be specified to provide the inductance required to achieve this. A harmonic analysis should be performed to determine the existing and potential harmonic currents and voltage levels resulting from installing variable frequency drives. Once a model is complete, an approach to mitigating harmonics and improving power factor can be developed. Harmonic filters on the market are designed as an assembly, although it is possible to specify components for field assembly into a harmonic filter. Upgrading an existing capacitor bank: to make a shunt filter can also be performed, provided several issues In most cases, line impedance should not exceed 5 % because of voltage distortion and voltage drop at the terminals of the drive. Impedance in excess of Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 234 ESL-IE-97-04-36 are addressed. Capacitors have definite limitations that must be taken into consideration during normal operation and during operation as an integral component of a harmonic filter. When a capacitor bank rated 240 volts is installed on a 208 volt system, for example, its reactive power rating must be derated to 75 %: Capacitor Ratings Two industry standards govern the characteristics of capacitors: ANSllIEEE Standard 18-1980, and NEMA CPI-1973 (9). Capacitor rating limitations include a maximum of 180% of rated current, a maximum of 110% of rated voltage, and a maximum of 135% of rated reactive power. KVARActual=KVARRated( (12) The margins dictated by the standards are required to allow for overvoltage due to harmonics, switching surges, and fundamental overvoltage at the capacitor terminals; for excessive reactive power demand due to harmonics, switching surges, overvoltage at the capacitor terminals; and for excessive capacitance from manufacturing tolerances. KVARAcual =KVARRaCed (0.75) (13) Applying a capacitor rated 240 volts on a 208 volt system without derating the KVAR capacity to 75 % may result in an improved power factor lower than expected. The system may require additional capacitance to improve power factor to satisfactory levels. Normally, the 180% of rated current limitation is less restrictive than the reactive power and voltage limitations outlined above (9). Observing capacitor ratings ensures a reasonable life expectancy, realizing that any increase in the applied voltage over the capacitor rating will result in shortened capacitor life. To account for this extra duty an additional 15­ 20 % increase in capacitor line-to-neutral voltage rating is recommended (1). The capacitors within a harmonic filter are typically rated for the next higher nominal voltage than the system to which it is connected. Capacitors installed as an integral harmonic filter component operate at a steady-state overvoltage due to the existence of harmonic voltages. Additionally, installing a capacitor bank on a system other than its nominal voltage requires derating of its rated reactive power to ensure adequate overload capacity for harmonics and surges. The following equation, common in literature, illustrates reactive power derating for any derivation from rated voltage: VTT7I D .I\. VTT7I D vn.n.Actual =.1\. v.ru;"Rated ( ~~~) 2 A capacitor bank with a nominal voltage rating and an actual operating terminal voltage of 480 V should not be upgraded into a harmonic filter because the steady-state overvoltage from harmonic currents will most likely exceed the 110% voltage limitation, and may exceed the 135 % reactive power limitation. Harmonic filter capacitors connected to a 480 V bus are typically rated for 600 V operation, a 25% increase in line-to-neutral voltage rating. VActual()lt1) V Rated where, KVAR Ratm is the KVAR rating of the capacitor, is the calculated KVAR KVARAduaJ capacity of the derated capacitor, V!laUd is the voltage rating of the capacitor, and VA<XlaI is the operating voltage of the capacitor as installed. Sizing for Reactive Power Requirements Sizing KVAR requirements for power factor improvement, either through the installation of capacitor banks or harmonic filters, is the similar (6). The magnitude of power factor problem can be ascertained from utility data. Once the target power factor is set, capacitor manufacturer tables can be used to calculate the KVAR requirement for the system. Generally, only a portion of the total KVAR Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 235 ESL-IE-97-04-36 required will be used for harmonic filtering. That portion will be determined when filters are sized to match the non-linear portion of the system load, including any adjustments to the capacitor ratings. derated in accordance with Equation 11 based upon the extent of steady-state overvoltage that the capacitor endures as a harmonic filter component. The capacitor provides the reactive power required by the reactor along with providing reactive power for the distribution system. As such, the addition of the reactor to the capacitor in making a filter further reduces the capacitor's reactive power output, as given by: Reference (6) recommends sizing harmonic filters between 0.30 and 0.40 times the drive horsepower rating for variable frequency drives with SCR front ends. For VFD's with diode bridge front ends, (most PWM drives), the filter should be sized between 0.25 and 0.30 times the drive horsepower. (17) Upgrading an Existing Capacitor into a Harmonic Filter The following series of equations can used to size an in-line reactor needed to upgrade an existing capacitor bank into a harmonic filter (1): Where KVARrow is the KVAR output of the filter, VL-L is the applied system voltage, Xc is the capacitive reactance of the filter, and XL is the inductive reactance of the filter. (14) CONCLUSIONS where Variable frequency drives can reduce an electrical system's energy consumption significantly. It is important to remember that a drive may affect other mechanical and electrical components in the system. If improperly applied, the drive can generate harmonic distortion that can have serious negative effects on components in a building's electrical distribution system and other equipment. Xc is the capacitive reactance of the filter, VL-L is the rated voltage of the capacitor bank, and KVAR}.pbue is the rated KVAR of the capacitor bank. (15) Harmonics and power factor become interrelated when non-linear loads are installed in the electrical environment. High harmonic currents result can result in low true power factor, although displacement power factor may be near unity. Proper application of capacitors, either alone or as harmonic filters, can safely improve power factor and mitigate harmonic distortion. where h is the tuned harmonic, and XL is the inductive reactance of the filter, Recall that capacitors experience terminal voltage in excess of rated voltage when installed as a harmonic filter component. The following equation expresses the percent of voltage rise that capacitors experience as a function of the harmonic number at which the filter is tuned (1): %VR=(~)Xl00 2 h -1 REFERENCES 1. (16) where %VR is the percent of voltage rise above nominal, and h is the tuned harmonic. 2. Andrews, D., Bishop, M., Witte, 1., "Harmonic Measurements, Analysis, and Power Factor Correction in a Modem Steel Manufacturing Facility," IEEE Transactions on Industry Applicmions, May/June 1996 Beck, P., "Adjustable-Frequency Drives Reduce HVAC Costs", Consulring-Specifying Engineer, June 1992. Recall that reactive power that a capacitor delivers is dependent upon terminal voltage. Actual reactive power generated by the capacitor must be Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 236 ESL-IE-97-04-36 3. 4. 5. 6. 7. 8. 9. Gray, J., Haydock, F., "Industrial Power Quality Considerations When Installing Adjustable Speed Drive Systems,· IEEE Transactions on Industry Applications, May/June 1996. IEEE Standard 519-1992: IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters. Jouanne, A., Enjeti, P., and Gray, W., •Application Issues for PWM Adjustable Speed AC Motor Drives, " IEEE Industry Applications Magazine, September/October 1996. Lowenstein, Michael Z., ·Power Factor Improvement for Non-Linear Loads,· 1991 Annual Technology Conference of the Textile, Fiber, and Film Industry Committee, the Industry Applications Society of the IEEE, Greenville, South Carolina, May 1991. Massey, G., ·Power Factor Improvement Capacitors: The Balance Between Power Quality and Energy Efficiency, • PowerSystems World, Power Quality '96, Imenec International, Las Vegas, Nevada, September 1996. Nicholas, D., ·Understanding the Twists and Turns of Adjustable-Frequency Drives, • Consulting-Specifying Engineer, November 1993. Rice, D., •Adjustable Speed Drives and Power Rectifier Harmonics - Their Effect on Power Systems Components,· IEEE Transactions on Industry Applications, JanuarylFebruary 1986. Proceedings from the Nineteenth Industrial Energy Technology Conference, Houston, TX, April 23-24, 1997 237