Bluebook Planroom Document

advertisement
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
SECTION 28 31 00 - FIRE ALARM/SECURITY SYSTEM
PART 1 - GENERAL
1.1
SUMMARY
A.
Section includes
1.
Fire alarm/security system:
a.
b.
c.
d.
2.
1.2
The design drawing and subsequent installation drawings for the fire
alarm/security system shall include the main grocery store area as well as the Fred
Meyer Jewelry, the Little Clinic, and fuel center, as applicable.
Insure that each of the devices listed in this specification are incorporated into the
design of the fire alarm system and the security alarm system.
Provide one control panel for the fire alarm system and a separate control panel for
the security alarm system. Combining of the systems will not be permitted.
Provide fire alarm wiring to fire alarm system devices and wiring to make
connection between fire alarm panel and HVAC control system panel to shut down
all air handlers
Upgrade of Existing Fire and Security Systems: Any equipment or wiring to be reused
must be compatible with the new Bosch control panel. Reuse of any existing equipment
must be approved by Owner in writing prior to Bid Date.
SYSTEM DESIGN
A.
The design drawing and subsequent installation drawings of the fire alarm system shall be
designed to obtain the minimum compliance and installed in accordance with the latest edition
of NFPA 72. In addition, the design drawing and subsequent installation drawings shall meet
the requirements of this Section, the authority having jurisdiction and complete in all respects
and in operating condition including its supervision.
B.
The design drawing and subsequent installation drawings of the security system shall cover all
areas of the buildings and shall meet the requirements of this Section and be installed complete
in all respects and in operating condition including its supervision.
C.
In the absence of design drawings in the Construction Documents, the fire alarm and security
system shall be designed to obtain the minimum compliance and installed in accordance with
the latest edition of NFPA 72 and specifications Section 28 31 00. All components, materials,
and methods shall be in accordance with NFPA 72 and as listed by Underwriters Laboratories,
Inc. or FM Global, or the requirements of “The Kroger Co.”
D.
Construction Documents and Shop Drawings should include a floor plan with device locations
and room identification, a graphic symbol legend, a riser diagram, a matrix of operations,
applicable general notes, a description of the secondary power supply, and other data necessary
for the fabrication and installation of the fire alarm/security system, and any required changes or
revisions thereof necessary to obtain approval from the authority having jurisdiction.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 1
Jeffery A. Scott Architects, P.C.
E.
1.3
Kroger Store No. D-685
Birmingham, Michigan
No extra charges will be allowed for changes to drawings required to conform to NFPA 72, the
Owner’s requirements, of the authority having jurisdiction, the Owner's underwriter, or with
conflict with other trades. Design drawings become the property of the Owner.
STANDARDS
A.
The equipment and installation shall comply with the current applicable provisions of the
following standards:
1.
2.
NFPA 70, The National Electrical Code (including Article 760)
National Fire Protection Standards (including but not limited to):
a.
b.
c.
d.
3.
4.
5.
B.
Central Station Signaling Systems-Protected Premises Unit
National Fire Alarm and Signaling Code
Automatic Fire Detectors
Life Safety Code
Local and State building codes;
Requirements of the Local Authority Having Jurisdiction (AHJ);
Underwriters Laboratories, Inc.
The system and all components shall be listed by Underwriters Laboratories, Inc. for use in Fire
Protective Signaling Systems under the following standards as applicable. Not all of the
standards will apply to all projects, see Drawings for more information:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
1.4
NFPA 71
NFPA 72
NFPA 72
NFPA 101
UL 864
Control Units for Fire Protective Signaling Systems (including
UUKL sublisting)
UL 268
Smoke Detectors for Fire Protective Signaling Systems
UL 268A
Smoke Detectors for Duct Applications
UL 217
Smoke Detectors, Single and Multiple Station
UL 521
Heat Detectors for Fire Protective Signaling Systems
UL 228
Door Closers-Holders for Fire Protective Signaling Systems
UL 464
Audible Signaling Appliances
UL 1638
Visual Signaling Appliances
UL 1971
Signaling Devices for the Hearing Impaired
UL 38
Manually Actuated Signaling Boxes
UL 346
Water flow Indicators for Fire Protective Signaling Systems
UL 1481
Power supplies for Fire Protective Signaling Systems.
UL 609, 1610, 1635 Commercial Fire and Intrusion Alarm systems.
FIRE ALARM SYSTEM OPERATION
A.
When a fire alarm condition is detected by one of the system initiating devices, the following
functions shall occur simultaneously.
1.
2.
3.
System point shall be shown on the keypad by type of device, location and time of day.
The audio-visual alarm devices shall activate throughout out the building.
The digital dialer shall notify the monitoring company (as listed in the execution portion
of this specification) that an alarm condition exists.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 2
Jeffery A. Scott Architects, P.C.
4.
5.
B.
Kroger Store No. D-685
Birmingham, Michigan
Shut down all air handlers, unless specifically forbidden by the authority having
jurisdiction.
If the alarm is on an elevator related smoke detector, the elevator shall be captured and
returned to the predetermined floor. Refer to Division 14 Section "Hydraulic Elevators"
for further elevator-related requirements.
When a trouble or supervisory condition occurs, the following functions shall occur
simultaneously.
1.
2.
3.
System point shall be shown on the keypad by type of device, location and time of day.
A distinct trouble sound shall occur at the keypad.
The digital dialer shall notify the monitoring company (as listed in the execution portion
of this specification) that a trouble or supervisory condition exists.
C.
Whenever a smoke, duct or heat detector is tripped, alarm verification shall function and a timer
shall start. After a program time delay compliant with prevailing codes, the horn strobes shall
sound if the detector is still in alarm.
D.
The system shall monitor for head sensitivity and give a warning message if the smoke or duct
detector needs cleaning.
E.
The system shall be fully field-programmable with the equipment on site or a programmer.
While programming, the system shall continue to operate, polling devices currently in the
program.
F.
Other features of the system shall include the following.
1.
2.
3.
4.
5.
6.
7.
8.
1.5
Walk test
Device Disabling: Feature pass code protected for use by manufacturer’s authorized
technician only. Pass code not available to end user.
Read status of any point.
Field programmable at keypad.
Multiple password protection (for remote programming).
Manual on/off for any output point.
Calibrated smoke detector test.
Low air pressure monitoring of air compressor of any dry pipe system.
SUBMITTALS
A.
General:
1.
2.
3.
Pay application fees and obtain approval of submittals in writing from the State Fire
Marshal’s office and/or the local authority having jurisdiction prior to submittal to
Owner’s Representative for review.
Submit fire alarm submittals to the Owner’s Representative within 30 calendar days after
award of Contract.
Permit Drawings and other Submittals shall be prepared by a fire alarm installer certified
by the approved manufacturer of the fire alarm system.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 3
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
B.
Product Data: Complete documentation for the fire alarm system showing the model number,
type, rating, size, style, manufacturer's names, and manufacturer's catalog data sheets for items
to ensure compliance with these specifications.
C.
Shop Drawings
1.
2.
3.
Complete set of permit drawings showing conduit sizes and number of conductors
required to components plus detailed wiring connections required at each type of device
based on the level of the fire alarm system indicated in the Contract Documents.
Detailed drawings showing the intended location of field devices and their connections to
the system along with room identification and a graphic symbol legend. Prepare
submittal drawings utilizing AutoCad Release 2009 or newer Computer Aided Drafting
system.
Detailed wiring diagrams and riser diagrams showing color-coding of wiring per
manufacturer recommendations. Include calculations showing adequate capacity of the
standby batteries, where applicable, as required by prevailing codes.
D.
Monitoring Data Form: Complete per the directions and in coordination with Owner and return
to the addresses shown a minimum of 30 days prior to system testing and activation.
E.
Technician Install/Conversion Form: Complete per the directions and return to the addresses
shown a minimum of 30 days prior to system testing and activation.
1.6
QUALITY ASSURANCE
A.
Installer Qualifications: A qualified firm that is approved, authorized, or licensed by fire
alarm/security system manufacturer to install manufacturer's product and that is eligible to
receive manufacturer's special warranty.
1.
Installing and programming technicians shall be individually certified by fire
alarm/security system manufacturer.
B.
The alarm control panel shall be supplied with all cards and future expansion slots needed for a
complete operating system.
C.
Provide system with a 3-year warranty for the control panel starting from the time this system is
operational.
1.7
PROJECT CONDITIONS
A.
Upgrade of Existing Fire and Security Systems:
1.
2.
3.
4.
Reuse as much existing wiring and equipment as possible.
Obtain Owner’s written permission for any existing fire and security alarm panels to
remain in use as part of final design incorporating separate panels.
Existing fire and security alarm systems should remain in operation during remodel
projects to insure protection.
Should a fire alarm system need to be shut down for more than an hour a standard fire
watch must be put in place until the system is reactivated. All system shut downs must
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 4
Jeffery A. Scott Architects, P.C.
5.
Kroger Store No. D-685
Birmingham, Michigan
have owner’s prior written permission and it will be the contractor’s responsibility to
notify the local fire department, authority having jurisdiction and KCAC prior to shut
down. Notify KCAC when systems are being reactivated.
Reuse only smoke detectors that are intelligent addressable duct mounted photoelectric
smoke detectors and compatible with new panel.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Manufacturer: Provide products identified in other Part 2 articles by Bosch Security Systems,
Inc. (Fire and Intrusion). Contact Bosch pre-sales at 800-289-0096 option 2 for questions
regarding the equipment and/or applications. For escalated issues please contact Christopher
Dunn: (585) 465-1229, chris.dunn@us.bosch.com or request to speak to the applicable regional
sales manager. No substitutions are allowed.
1.
This specification requires that a Bosch certified security dealer be contracted to install a
complete system, honor the warranty, provide the training and service the system after
the warranty period expires. Bosch should not be contacted for project bids or to provide
equipment to the electrical installers.
a.
2.
2.2
Installing and programming technicians shall be individually certified by fire
alarm/security system manufacturer.
Products (other than products by Bosch Security Systems, Inc.) identified as Basis of
Design in other Part 2 articles are identified to set the standard of quality for equipment
used.
APPROVED INSTALLERS
A.
Local installer certified by equipment manufacturer:
1.
2.
Equipment Manufacturer: Bosch Security Systems.
Certified Installer Locator:
a.
b.
B.
Web: //www2.boschsecurity.us/bcsd_locator.cfm
Phone: 1-800-289-0096, press 2 for Pre-Sales Support.
National Certified Installers:
1.
Carter Brothers LLC - A Certified Minority Business Enterprise.
a.
b.
2.
Steve Board: (404) 391-7176, sboard@carterbrothers.com.
Scott Dexter: (404) 227-5479, sdexter@carterbrothers.com.
CoLiant Solutions.
a.
b.
DeeAnna Duncan: (678) 288-3811, deeanna.duncan@coliantsolutions.com.
Jeff Cullop: (678) 288-3810, jeff.cullop@coliantsolutions.com.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 5
Jeffery A. Scott Architects, P.C.
3.
Niscayah Group.
a.
4.
Steve Stigell: 513-200-9386, SStigall@simplexgrinnell.com
Tel-Aid
a.
2.3
Ross Balano: (913) 208-0899,ross.balano@niscayah.us.
SimplexGrinnell, a Tyco International company.
a.
5.
Kroger Store No. D-685
Birmingham, Michigan
Scott Patsiga: 770-903-6533; spatsiga@telaid.com.
GENERAL
A.
Incorporate each of the devices listed in this specification into the design of the Fire Alarm
System and the Security Alarm System.
B.
Provide a complete addressable fire alarm system throughout the building as shown on the
drawings and in accordance with NFPA 72 and authorities having jurisdiction. Equipment shall
be UL listed.
C.
Each smoke detector shall be addressable for the exact location in the building and provide
“dirty” maintenance type messages at the annunciator, central station and remote programming
software. Manual stations, sprinkler devices and all other "contact only" closing devices shall be
addressable.
D.
If existing raceways, cables and outlet boxes are suitable for re-use, they may be reused after
demonstrating to Owner’s representative that they have been tested and proven to be suitable.
Include existing cable used in three year warranty.
2.4
PANELS
A.
Main Fire Alarm Control Panel (FACP/FAP): Bosch
D7412GV4/D9412GV4 and shall be located in the ECR room.
1.
2.
3.
Security
Systems;
Model
Provide Bosch Security Systems; Model 7024FPD only where elevator recall is required
by authority having jurisdiction (AHJ).
Locate main fire alarm control panel in Network Equipment Room (ECR) room.
CPU (Central Processing Unit): Include the following:
a.
b.
c.
d.
e.
f.
Programming protection in the event of a power failure.
Addressable communication transmission.
History of the last 499 - 1000 activities.
LEDs for AC power, fire alarm, security alarm, supervisory signal, system trouble,
disabled points and alarm silenced.
Main power supply for the panel and for peripheral devices with 120VAC 60HZ
input power or transformer and an integral charger for batteries usable for
peripherals.
SIC data loop board(s) capable of handling 255 or 120 detectors/modules per
board.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 6
Jeffery A. Scott Architects, P.C.
g.
h.
i.
j.
4.
A serial interface board for printer or display terminal.
Battery backup shall comply with Section 1-5.2.6 of NFPA -72.
Local or remote programming.
Two different passwords required for programming.
DIA Display Interface Board:
a.
5.
32 or 16-character liquid crystal display command center.
Equip control panel to provide the following capacities:
a.
b.
c.
d.
e.
Data loops: 2
On-board points: 4 or 8
Addressable points: 255 or 238
Programmable horn circuits: 2 or 3
Integrated network communications capable, dialer capture module will not be
accepted
1)
f.
2.5
Kroger Store No. D-685
Birmingham, Michigan
Number of Boards (i.e. “cards”) determined by system designer.
Real Time clock
6.
Digital Communications: Provide system capable of communicating with a digital
receiver such as the Bosch/Radionics D6600 receiver.
7.
Remote programming access codes must remain at the factory default code. IT IS
FORBIDDEN FOR INSTALLERS TO INSERT THEIR OWN CODES.
CIRCUITS AND WIRING
A.
Provide a Class B wiring system.
B.
Provide 15 percent capacity for future expansion of A/V alarm device and data loop circuits.
C.
Separate alarm wiring from any open conductors or power, or Class 1 circuits. Do not place in
any conduit, junction box or raceway containing these conductors, per NEC Article 760-55.
D.
Wiring for 24 volt DC control, alarm notification, emergency communication and similar
power-limited auxiliary function may be run in the same conduit as initiating and signaling line
circuits. Provide circuits with transient suppression devices and design system to permit
simultaneous operation of all circuits without interference or loss of signals.
E.
Wire:
1.
2.
Provide new fire alarm system wiring except where existing alarm wiring in existing
facility is to remain in place.
Provide wiring meeting local, state and national codes (e.g., NEC Article 760) and as
recommended by the manufacturer of the fire alarm system. Provide number and size of
conductors as recommended by the fire alarm system manufacturer, but not less than 18
AWG (1.02 mm).
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 7
Jeffery A. Scott Architects, P.C.
a.
b.
3.
4.
5.
F.
2.6
Kroger Store No. D-685
Birmingham, Michigan
Line Voltage Circuits: Standard 14 gage copper wire with THHN insulation.
Low voltage Circuits: Twisted shielded 16 gage stranded copper wire.
Provide wire and cable listed and approved by a recognized testing agency for use with a
protective signaling system.
Provide wire and cable not installed in conduit with a fire resistance rating suitable for
the installation as indicated in NFPA 70 (e.g., FPLR).
Field wiring shall be electrically supervised for open circuit and ground fault.
Terminal Boxes, Junction Boxes and Cabinets: UL listed for use and purpose.
MANUAL PULL STATIONS
A.
Product: Bosch Security Systems; FMM-7045-D or FMM-462-D.
B.
Provide at customer service for building evacuation.
C.
The unit shall be dual action (i.e. requiring two motions to activate the station) and shall be
addressable for connections to the fire alarm control panel(s).
D.
Unit shall meet UL 38, standard for manually actuated signaling boxes.
E.
Mount manual pull stations 48 inches (1220 mm) above the finished floor and in accordance
with local building codes and as called out in NFPA 72.
2.7
CEILING/WALL SMOKE DETECTORS
A.
Bosch Security Systems; D7050 with D7050-B6 base or F220 series smoke with F220-B6PM/S
POPIT bases.
B.
Provide base for all applications where auxiliary contacts are required.
2.8
DUCT SMOKE DETECTORS
A.
Intelligent Addressable Duct Mounted Photoelectric Smoke Detectors:
1.
Bosch Security Systems; D341P Series Duct Detector Housings.
a.
b.
2.
3.
4.
5.
If used with 9000 Series panel provide D9127U addressable single point module.
If used with the D7024 or FPD7024 provide D7044M addressable single point
module.
Provide UL 268A listed unit with two LEDs that will provide local alarm indication and a
remote alarm output will be required for use with auxiliary devices.
Operating Velocities: 300 to 4000 feet/minute (91 to 1219-m/minute).
Provide sampling tube per NFPA, test station and all other required accessories.
The shut down of air handlers shall occur via a signal from the Fire Alarm Panel should
any smoke detector be activated, unless specifically forbidden by the authority having
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 8
Jeffery A. Scott Architects, P.C.
6.
jurisdiction, in which case provide auxiliary contact as required to shut down equipment
and wire into the stop circuit of the associated air handler starter.
Provide remote key activated test station (with status/alarm/trouble indicating LEDs), on
the column or wall beneath the duct detector as indicated on Drawings or as determined
in field.
a.
b.
7.
Provide electrical conduit from duct detector to remote test station for column and
wall mounted applications. (Refer to Division 26 Section "Common Work Results
for Electrical.”)
Provide engraved (or approved machine-generated equivalent method) plate at
each remote station to read: “#### Duct Smoke Detector”, where #### is the RTU
or AHU identification number used on Drawings. Install test stations at 80-inches
(2032-mm) above finish floor (AFF).
Provide required power and control wiring so that upon detection of smoke, the following
sequence of operations occurs where applicable:
a.
b.
c.
2.9
Kroger Store No. D-685
Birmingham, Michigan
A supervisory signal is sent by the fire alarm control panel to the monitoring
central station.
All HVAC units shut down (including applicable dampers).
Associated smoke dampers close (wired to automatically re-open on duct detector
reset).
HEAT DETECTORS
A.
Addressable Heat Detectors:
1.
Products:
a.
b.
2.
2.10
A.
Provide both rate of rise and fixed temperature with 135 degrees F. (57 degrees C.) alarm
threshold.
FIRE ALARM NOTIFICATION DEVICES
General:
1.
2.
B.
For GV4 Systems: Bosch Security Systems; F220 series detectors with applicable
base.
For FPD-7024 Systems: Bosch Security Systems; D7050 heat detector with
D7050-B6 mux base.
Comply with requirements of NEC and NFPA-72.
Provide weather resistant back boxes for units installed in refrigerators and freezers to
diminish the risk of damage due to condensation.
Horn/Strobe Units
1.
Manufacturers:
a.
Cooper Industries; Wheelock Brand
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 9
Jeffery A. Scott Architects, P.C.
b.
2.
3.
4.
5.
C.
Mounting: Semi-flush mounting plates, ceiling or bottom of open steel structure
whenever possible, wall mounted (only when required) at 80-inches (2032-mm) as shown
on Drawings.
Manufacturers:
a.
b.
2.
3.
4.
5.
6.
Mounting: On ceiling or to the bottom of open steel structure whenever possible, Wall
mounted (only when required) at 80-inches (2032-mm) as shown on Drawings.
Remote Annunciators
3.
4.
Bosch model D1256RB
Locate remote annunciator in customer service area, exact location shall be coordinated
with Owner and local fire department.
Locate additional remote annunciator in or near the main entrance when required by the
local fire department.
Mount remote annunciator on wall 60 inches (1524 mm) above finish floor to center of
unit or as required by local fire department.
Sprinkler Devices
1.
C.
Main Sales Area: Minimum 75 candelas.
Smaller Areas: Minimum candela units as required to comply with ADA and the
equivalent NFPA 72 requirements resulting in the minimum number of devices.
ACCESSORY DEVICES
1.
2.
B.
Cooper Industries; Wheelock Brand
Gentex Corporation
Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction.
Synchronize strobe units.
Color: Red.
Luminous Intensity: ADA-compliant.
a.
b.
A.
Main Sales Area: Minimum 75 candela.
Smaller Areas: Minimum candela units as required to comply with ADA and the
equivalent NFPA 72 requirements resulting in the minimum number of devices.
Strobe-Only Units
1.
2.11
Gentex Corporation
Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction.
Synchronize strobe units.
Color: Red
Strobe Luminous Intensity: ADA-compliant.
a.
b.
6.
Kroger Store No. D-685
Birmingham, Michigan
Sprinkler tamper and flow switches will be provided by the fire protection installer.
Monitor Modules
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 10
Jeffery A. Scott Architects, P.C.
1.
Provide as required to interface "non-intelligent" devices into the system as shown on the
Drawings (i.e. Sprinkler Flow Switches, Tamper Switches, Pressure Switches, Kitchen
Hoods, etc. as applicable).
a.
D.
2.12
A.
DIGITAL COMMUNICATOR (“DIALER”)
Description: Programmed to report to the Owner’s UL LISTED CENTRAL STATION via two
dedicated POTS telephone lines for fire alarm systems and one dedicated POTS telephone line
for the burglar alarm system. Do not install network module unless directed by Kroger Central
Alarm Control. Phone lines will be set up to allow long distance calling.
2.
3.
2.13
A.
Product: Bosch D9068 DACT.
Provide one duplex telephone outlet connected to a non-dedicated telephone line (with two
RJ31X connecting block jacks) within two feet (610-mm) of the Fire Alarm Panel/Digital
Communicator for back up connection to telephone system.
SECURITY ALARM SYSTEM
Security Alarm Control Panel
1.
2.
B.
UL station will be the Owner’s central alarm control monitoring company (KCAC
04002/31A). COMPLETE THE CENTRAL ALARM CONTROL MONITORING
DATA FORM INCLUDED AT THE END OF THIS SPECIFICATION.
The dialer and/or network module will be UL listed for fire alarm use.
Mounting: Mount in single equipment housing containing battery charger and battery
with coupler cable.
Equip fire alarm systems that are being upgraded with a new communicator and tie to (KCAC).
1.
C.
Provide electrical conduit for wall mounted applications, and for ceiling mounted
applications if the above-ceiling space acts as a plenum return. (Refer to Division
26 Section "Common Work Results for Electrical.”)
Provide required relays for auxiliary devices including door closures and supervised control
functions such as air handler shut-downs.
1.
B.
Kroger Store No. D-685
Birmingham, Michigan
Main Control Panel: Bosch Security Systems; D7412GV4/D9412GV4.
Configure system to accommodate the needs of this store. Supply panel with all security
modules and future expansion slots needed for a complete operating system.
Keypads: Pharmacy and customer service office locations.
1.
2.
3.
4.
Product: Bosch Security Systems; D1255.
Provide separate keypads for each area of the system.
Keypad installation shall be located customer service office, exact location field verified
with Owner. Mount keypads 48 inches (1220 mm) above finished floor to center of
keypad.
Provide an additional keypad inside the pharmacy beyond reach from the security grille
to control the pharmacy alarm, verify exact location with Owner.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 11
Jeffery A. Scott Architects, P.C.
C.
Keypads: Freight Receiving Driver Entry (DSD) door location.
1.
2.
D.
Product: Bosch Security Systems; 1255.
Mount 48 inches (1220 mm) above finished floor to center of keypad near the Driver
Entry door.
Door Switch
1.
Basis of Design:
a.
b.
2.
3.
Install wiring for door switch in conduit to a junction box adjacent to door jam. Install
wiring from junction box to door switch in surface raceway or flexible conduit depending
on the installation.
Bosch Security Systems; Model D116
Provide one remote security sounder at each door, grille or roof hatch.
Locate sounder just below roof deck.
When emergency exit door is equipped with a delayed egress device delete remote
security sounder.
Motion Sensors
1.
2.
Bosch Security Systems; ISC-PDL1-WA18G wall-mount motion, DS9360 (up to 17 feet)
and DS9370 (above 17 feet) ceiling mount motions.
Install on ceiling or on wall 80 inches (2032 mm) above finished floor to provide a
curtain of protection just inside the potential access point in locations shown on the
Drawings. Typical areas include but are not limited to the following:
a.
b.
c.
d.
G.
Auxillary customer entrances such as at outdoor seating areas and Starbucks.
Remote Security Sounder:
1.
2.
3.
4.
F.
Rolling Doors: UTS Fire and Security, GE Security; Sentrol 2300 Series, track
mounted contacts.
Other Doors: UTS Fire and Security, GE Security; Sentrol 1078T Series, recessed
contact.
Provide at doors that enter the space. When door is equipped with a delayed egress device
utilize activation contact and delete door switch. Typical areas include but are not limited
to the following:
a.
E.
Kroger Store No. D-685
Birmingham, Michigan
Pharmacy: Provide sensors above and below ceiling to detect motion.
Entrance vestibule.
Accounting room (with safe).
Front main aisle of sales floor.
Contact Switch
1.
2.
Basis of Design: GE Security; Sentrol.
Install on other areas where operation of entry gates/grilles may be desired. Typical
locations would include but are not limited to the following:
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 12
Jeffery A. Scott Architects, P.C.
a.
H.
Kroger Store No. D-685
Birmingham, Michigan
Pharmacy rolling gate (drop down or horizontally rolling), one on each gate. If
gate is wider than 8 feet (2438 mm), provide one contact at each end. Wire
contacts to the same point.
Security System Monitoring Devices
1.
2.
Basis of Design: GE Security; Sentrol.
Provide in selective equipment as indicated. The equipment typically monitored using
the security system include but are not limited to the following (security system
monitoring devices not required in elevators):
a.
b.
c.
d.
3.
CPC refrigeration failure.
Generator fault indicator.
Sump pumps.
Elevators.
Monitoring of the specialized equipment will require coordination with the equipment
manufacturers. Provide supplemental equipment needed to monitor this equipment for a
complete and operational system.
PART 3 - EXECUTION
3.1
GENERAL
A.
3.2
The Authority Having Jurisdiction (AHJ) shall be notified prior to installation [or alteration] of
equipment and wiring.
INSTALLATION
A.
General:
1.
2.
3.
4.
Install equipment in accordance with the NEC, NFPA 72, local and state codes, as shown
on the Drawings, and as recommended by the manufacturer. Refer to Section 26 05 19
"Low Voltage Electrical Power Conductors and Cables" for additional recommendations.
Conceal wiring, cabling, conduit, junction boxes, conduit supports and hangers from
view in finished ceiling areas and remain exposed in open structure areas. Place alarm
wiring in conduit when installed down a column and unfinished walls in backroom areas.
Do not install smoke detectors prior to the system programming and test period. If
construction is ongoing during this period, protect smoke detectors from contamination
and physical damage.
Flush mount fire detection and alarm system devices, control panels and remote
annunciators when located in finished areas. Devices may be surface mounted when
located in unfinished areas.
B.
Connect 120VAC power for fire alarm equipment to emergency panels where applicable.
C.
Provide required 20A/120VAC power as required to energize components of the security and
fire alarm system. Include home-runs for fire alarm control panels as well as home-runs and
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 13
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
wiring for any accessory devices such as remote power supplies/panels, printer, dialer, etc. as
applicable.
1.
2.
3.
D.
Smoke or Heat Detector Locations:
1.
2.
3.
E.
F.
1.
Duct smoke detectors are typically shown schematically at the respective air handling
unit on the Drawings, but shall actually be installed maximizing the distances between
ductwork offsets, and installed ahead of the first branch duct take-off. Coordinate with
HVAC installer and fire alarm manufacturer’s representative in field.
2.
In fully ducted systems, install duct smoke detectors in the appropriate side of air
handling equipment as required by the authority having jurisdiction. Where more than
one detector is indicated associated with a particular piece of air handling equipment,
there are special reasons for the additional detectors (i.e. split returns, return risers
serving multiple floors, etc.); coordinate all locations for same with the HVAC installer.
Digital Communicator (Dialer) Installation
2.
Connect each jack to a separate phone line and install as the first in-house device tied to
the respective phone line. Do not connect the jacks to a party line or a “ground start”
telephone circuit.
Connect digital communicator to operate from three sets of dry contacts on fire alarm
control panel; one set each for alarm, trouble and supervisory (existing conventional fire
panels only).
Delayed Egress Electronic Exit Door Locking System Connection
1.
3.3
Do not exceed the rated coverage of the detector.
Install no more than 15-feet (4.6-m) from a wall or 30-feet (9-m) apart.
Do not install within 3-feet (1-m) of a supply air diffuser.
Duct Smoke Detector Installation:
1.
G.
This requirement applies whether or not such power work is shown on the Drawings.
Dedicate branch circuits serving fire alarm equipment to fire alarm equipment only.
Label circuit at the main power distribution panel as FIRE ALARM. Ground control
panel cabinet securely to either a cold water pipe or a grounding rod.
Provide machine generated label at FACP and intrusion control panel indicating location
of breaker box and circuit number.
Connect wiring to each door control to automatically unlatch the lock instantly in the
event of a fire alarm activation.
FIELD QUALITY CONTROL
A.
Manufacturer's Field Service:
Engage a factory-authorized service representative to
inspect, test, and adjust field-assembled components and equipment installation, including
connections, and to assist in field testing.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 14
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
B.
Upon completion of installation, the system shall be checked and tested by a fire alarm
inspector that is State-Licensed, NICET Level II Certified, or approved equivalent. Contact
system manufacturer for this service if installer cannot provide on their own.
C.
After making tests and corrections, conduct a system demonstration for Owner and the authority
having jurisdiction.
3.4
ADJUSTING
A.
Occupancy Adjustments: When requested within 12 months of date of Substantial Completion,
provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to
two visits to Project outside normal occupancy hours for this purpose.
B.
Follow-Up Tests and Inspections: After date of Substantial Completion, test the fire alarm
system complying with testing and visual inspection requirements in NFPA 72. Perform tests
and inspections listed for three monthly, and one quarterly, periods.
3.5
DEMONSTRATION
A.
Engage a manufacturer certified service representative to train Owner's personnel to operate the
fire alarm system.
1.
Provide onsite training and User Guide documentation at no cost to Owner. Training
includes but is not limited to:
a.
b.
c.
d.
e.
f.
g.
2.
How to arm and disarm the Intrusion system.
How to check point status and identify faults on the Intrusion system.
How to silence a trouble signal on the Intrusion or Fire system.
How to silence the horns on the Fire system.
How to reset the smoke and/or duct detectors on the Fire system.
How to reset a pull station on the Fire system.
How to identify phone line, A/C power, and battery fails on the Intrusion or Fire
system.
Provide 24 hour/7 days per week/365 days per year technical support at no cost to Owner.
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 15
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
Kroger Central Alarm Control
Monitoring Data Form
Call KCAC toll free 1-800-982-2749
To schedule Conversion & Programming call 503-797-5411
All fields marked with * must be completed to enable monitoring service
*Store Name:_____________________________
*Division #:________
*Address: ________________________________
*Zone/District_______ *Time Zone
*City:____________________________________
*State:____________
*Store Main Phone Number: __________________
*Alarm Panel Type
*Does your jurisdiction require an alarm permit? _____ If Yes, permit #
*Store #: ___________
*Zip Code:
_______________________
*Pharmacy Phone #:
*RX Dr.’s line _____________________________
*Fuel kiosk direct phone #
*Local Police Dispatch phone # (Not 911):
_________
_____________________
*Is this store using Best Practices? ______________
*Local Fire Dispatch phone # (Not 911):
________
____________________
________________
_______________________________________________
_____________________________________________
Secondary Police and/or Fire Dispatch # if available:
*Business Hours: ___________________________
______________________________________
*Are Associates inside 24 hours a day? _______
Emergency Call List: These people will be notified if no one is contacted at the store or in an emergency
*Store Manager Name:___________________________________________
EUID: _______________
Home # __________________________________ Cell #: ____________________________________
*1st Responder (Name & Position)___________________________________ EUID: _______________
Home # __________________________________ Cell #: ____________________________________
*2nd Responder (Name & Position) _____________________________ ___
EUID: _______ _________
Home # __________________________________ Cell #: _____________________________________
*3rd Responder (Name & Position) _________________________________
EUID: _______________
Home # ___________________________________ Cell #: _____________________________________
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 16
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
Call KCAC toll free 1-800-982-2749
To schedule Conversion & Programming call 503-797-5411
4th Responder (Name & Position) ___________________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
5th Responder __________________________________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
*Pharmacy Manager______________________________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
*2nd Pharmacy Responder________________________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
*3rd Pharmacy Responder________________________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
Additional Responder (Name & Position) ____________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
Additional Responder (Name & Position) ____________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
Additional Responder (Name & Position) _____________________________ EUID: ________________
Home # _________________________________
Cell #: _____________________________________
Additional Responder (Name & Position) _____________________________ EUID: ________________
Home # __________________________________ Cell #: _____________________________________
IF NEEDED, ADDITIONAL RESPONDERS CAN BE ADDED ON A SEPARATE SHEET
Authorized Contact List These additional people will also be able to contact KCAC Please TYPE/Print
*Name__________________________________
Position_____________ EUID: ________________
*Name__________________________________
Position_____________ EUID: ________________
*Name__________________________________
Position_____________ EUID: ________________
Name__________________________________
Position_____________ EUID: ________________
Name__________________________________
Position_____________ EUID: ________________
Name__________________________________
Position_____________ EUID: ________________
IF NEEDED, ADDITIONAL CONTACTS CAN BE ADDED ON A SEPARATE SHEET
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 17
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
Call KCAC toll free 1-800-982-2749
To schedule Conversion & Programming call 503-797-5411
Please indicate the arm/disarm schedule for all areas monitored on the burglary system. PLEASE TYPE/PRINT
Area
Time ON
(ARM)
Time OFF
(Disarm)
Day(s) of the Week
EXAMPLE: Premise (All Customer Doors)
2330 hours (11:30 PM)
0600 hours (6:00 AM)
Every Day
*
*Do you want KCAC to notify you if system is not armed on time? ________
PLEASE NOTE:
Fire Systems are monitored 24 hours a day. The fire department is dispatched immediately on all fire alarms. If
your system is being serviced or needs to be disregarded for any period of time, call KCAC prior to servicing.
Special Instructions (if any)
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
*Name of person completing form Please TYPE/Print: _______________________________________
*Position of person completing form Please TYPE/Print: _______________________________________
Date______________________
Please E-mail this completed form to:
alarmcontrol@kroger.com
For Additional Information Contact:
Joy or Lindy, Program & Conversion Coordinating....503-797-5411
Carroll Wall, KCAC Manager………………………..503-797-7715
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 18
Jeffery A. Scott Architects, P.C.
Kroger Store No. D-685
Birmingham, Michigan
Kroger Central Alarm Control
Technician Install/Conversion Form
Call KCAC 503-797-3160 or toll free 1-800-982-2749
To schedule Conversion & Programming call 503-797-5411, Fax #503-797-3172
To be completed by service company completing install or conversion
Entire form must be completed & submitted to KCAC
a minimum of 48 hours prior to scheduled install with KCAC
Store Name:_____________________________
Division #:___________ Store #: _____________
Address: _______________________________
Zone/District__________ Time Zone ___________
City:______________________________________ State:_______________ Zip Code: _____________
Company Name: _________________________
Phone #
Installer’s Name:_________________________
Cell #
________________________________
__________________________________
Panel Manufacturer: ________________________ Panel Model #:________ Format: ______________
Primary Panel Phone #: ____________________
AREA
POINT #
Secondary Panel Phone #:
Type of Alarm
Description
Jewelry Area 2
1
Interior 60 sec delay
Entry Gate
Jewelry Area 2
2
Interior instant
Center Gate
Jewelry Area 2
3
Interior instant
End Gate
Jewelry Area 2
4
Interior Follower
Front motion
Teller/Cashroom
Area 3
5
Interior instant
Front motion or door
Pharmacy Area 4
6
Interior 30 sec delay
Entry door or Gate
Pharmacy Area 4
7
Interior follower
front motion
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
___________________
28 31 00 - 19
Jeffery A. Scott Architects, P.C.
AREA
POINT #
Kroger Store No. D-685
Birmingham, Michigan
Type of Alarm
Description
Pharmacy Area 4
8
24hr silent & invisible
Hold up alarm
Perimeter Area 1
9
Perimeter 60 sec delay
Employee Entry or Main Customer Entry door
Perimeter Area 1
10
Perimeter instant
Customer Entry/Exit door or motion
Perimeter Area 1
11
Perimeter instant
Customer Entry/Exit door or motion
Perimeter Area 1
12
Perimeter instant
Customer Entry/Exit door or motion
Perimeter Area 1
13
Perimeter instant
Electrical Control Room door (ECR)
Perimeter Area 1
14
24 Hour point
Electrical room or Generator room
Perimeter Area 1
15
24 hour point
Emergency exit door
Perimeter Area 1
16
24 hour point
Emergency exit door
Perimeter Area 1
17
24 hour point
Emergency exit door
Perimeter Area 1
18
24 hour point
Emergency exit door
Perimeter Area 1
19
24 hour point
Emergency exit door
Perimeter Area 1
20
24 hour point
Emergency exit door
Perimeter Area 1
21
24 hour point
Emergency exit door
Perimeter Area 1
22
24 hour point
Emergency exit door
Perimeter Area 1
23
24 hour point
Emergency exit door
Perimeter Area 1
24
24 hour point
Emergency exit door
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 20
Jeffery A. Scott Architects, P.C.
AREA
POINT #
Kroger Store No. D-685
Birmingham, Michigan
Type of Alarm
Description
Perimeter Area 1
25
Perimeter instant
Main store motion
Perimeter Area 1
26
Perimeter instant
Main store motion
Perimeter Area 1
27
Perimeter instant
Main store motion
Perimeter Area 1
28
Perimeter instant
Main store motion
Perimeter Area 1
29
Perimeter instant
Main store motion
Perimeter Area 1
30
Perimeter instant
Main store motion
Perimeter Area 1
31
Perimeter instant
Main store motion
Perimeter Area 1
32
Perimeter instant
Main store motion
Perimeter Area 1
33
Perimeter instant
Roof hatch
Freight Area 5
34
Perimeter instant
Overhead door or man door
Freight Area 5
35
Perimeter instant
Overhead door or man door
Freight Area 5
36
Perimeter instant
Overhead door or man door
Freight Area 5
37
Perimeter instant
Overhead door or man door
Freight Area 5
38
Perimeter instant
Overhead door or man door
Perimeter Area 1
39
Perimeter instant
Cart overhead door
Additional Freight
Area 6 (If applicable)
40
Perimeter instant
Overhead door or man door
Additional Freight
Area 6 (If applicable)
41
Perimeter instant
Overhead door or man door
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 21
Jeffery A. Scott Architects, P.C.
AREA
POINT #
Kroger Store No. D-685
Birmingham, Michigan
Type of Alarm
Description
Additional Freight
Area 6 (If applicable)
42
Perimeter instant
Overhead door or man door
Additional Freight
Area 6 (If applicable)
43
Perimeter instant
Overhead door or man door
Perimeter Area 1
44
Perimeter instant
Compactor door
Perimeter Area 1
45
24 hour supervisory
Generator Supervision
Perimeter Area 1
46
24 hour supervisory
Gate Keeper (Anti-theft cart system)
Perimeter Area 1
47
Perimeter instant
Cart overhead door
Perimeter Area 1
48
Perimeter instant
Cart overhead door
Jewelry Area 2
49
Interior follower
Rear motion
Jewelry Area 2
50
Interior instant
Stockroom motion
Teller/Cash room
Area 3
51
Interior instant
Rear motion
Pharmacy Area 4
52
Interior instant
Drop off/Pick up counter top gate
Pharmacy Area 4
53
Interior follower
Interior motion
Pharmacy Area 4
54
Interior follower
Interior motion
Pharmacy Area 4
55
Interior follower
Interior motion
Pharmacy Area 4
56
24 hour
Motion above ceiling
Refrigeration Area 7
57
24 hour supervisory
Refrigeration leak detection or spill
Refrigeration Area 7
58
24 hour supervisory
Refrigeration supervision
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 22
Jeffery A. Scott Architects, P.C.
AREA
POINT #
Kroger Store No. D-685
Birmingham, Michigan
Type of Alarm
Description
Refrigeration Area 7
59
24 hour supervisory
Refrigeration supervision (If applicable)
Fuel Area 8
60
24hr silent and invisible
Kiosk Hold up alarm
Fuel Area 8
61
Perimeter 30 sec delay
Kiosk entry door
Fuel Area 8
62
Interior follower
Kiosk Interior motion
Fuel Area 8
63
24 hour
Kiosk Panel tamper
Fuel Area 8
64
24 hour
Fuel dispenser doors pumps 1 & 2
Fuel Area 8
65
24 hour
Fuel dispenser doors pumps 3 & 4
Fuel Area 8
66
24 hour
Fuel dispenser doors pumps 5 & 6
Fuel Area 8
67
24 hour
Fuel dispenser doors pumps 7 & 8
Fuel Area 8
68
24 hour
Fuel dispenser doors pumps 9 & 10
Liquor Area 9
70
24 hour silent/ invisible
Hold up alarm
Liquor Area 9
71
Interior 30 sec delay
Entry door or gate
Liquor Area 9
72
Interior follower
Interior motion
Liquor Area 9
73
Interior instant
Overhead door or man door
Liquor Area 9
74
Interior instant
Overhead door or man door
Liquor Area 9
75
Interior instant
Extra liquor point if needed
Gun storage Area 10
76
Interior instant
Cabinet door or safe door
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 23
Jeffery A. Scott Architects, P.C.
AREA
Gun storage Area 10
Kroger Store No. D-685
Birmingham, Michigan
POINT #
Type of Alarm
Description
77
Interior instant
Cabinet door or safe door
100% of Fire Initiating Devices have to be tested at time of conversion
Don't forget to program the daily timer test for every 24 hours
Attach additional sheet if necessary
END OF SECTION 28 31 00
FIRE ALARM/SECURITY SYSTEM
283100_FireAlarmSecuritySystem_04-17-14.doc
28 31 00 - 24
Download