Facility Electrical Protection FACILITY ELECTRICAL PROTECTION Founded in 1903 as the Electric Railway Improvement Company, ERICO developed the CADWELD® exothermic welding process in 1938. CADWELD connections have found industry-wide acceptance as the ultimate grounding and bonding connection. During the 1970s, ERICO pioneered the copperbonded steel ground rod electrode. Today, ERICO’s range of facility electrical protection products includes ERITECH® ground rods, clamps, grounding and bonding assemblies, ground enhancement material, ground testers, structural lightning protection, equipotential mesh and mats, and signal reference grids; CRITEC® low-voltage TVSS devices; and CADWELD® exothermic connections. Facility Electrical Protection Lightning protection, grounding, equipotential bonding and surge protection are all interdependent disciplines and the focus of our Facility Electrical Protection product group. Reliable protection of personnel and structures demands a systematic and comprehensive approach to minimizing threats caused by transients and other system disturbances. For instance, no air terminal can safely capture and arrest the lightning energy without a dependable route to ground. Equally, even the most expensive Surge Protection Device (SPD) will not provide optimum protection if a low-impedance electrical connection to the ground is not present. Additionally, a lowimpedance ground system may create hazards to equipment and personnel alike if equipotential bonding is not in place. These interdependent disciplines are best applied when looking at a total facility rather than an individual piece of equipment or a portion of the facility. Since no single technology can eliminate the harmful effects of lightning or induced-surge transients, ERICO has developed the Six Point Plan of Protection. The concept behind this plan is a holistic and coordinated approach that embraces all aspects of effective facility electrical protection. The six interdependent disciplines that form the protection plan are: 1. Capture the lightning strike 2. Convey this energy to ground 3. Dissipate energy into the grounding system 4. Bond all ground points together 5. Protect incoming AC power feeders 6. Protect low voltage data/telecommunications circuits At ERICO, we offer innovative, efficient grounding and bonding products as well as engineering experience and technical support. With this experience, ERICO is a world-leading authority in the design and construction of permanent, low-impedance grounding systems. ERICO employs a quality-assurance program to help ensure that detailed procedures required for every step of the operation produce the best possible system for our clients. This attention to detail includes design, materials procurement, manufacturing, installation and testing. Our research and development capabilities provide continuous design improvement with new and improved products that preempt the challenging requirements of everevolving industry applications. Engineering expertise is shared among the other ERICO operations worldwide, to provide a comprehensive global knowledge pool. Trust ERICO for all of your facility electrical protection needs. www.erico.com FACILITY ELECTRICAL PROTECTION Table of Contents Technical Information ..................................................................................Pages 4-16 ERITECH® Lightning Protection ............................................................Pages 17-26 ERITECH® Conductors ................................................................................Pages 27-29 ERITECH® Grounding and Bonding ..................................................Pages 30-41 CRITEC® Surge Protection ........................................................................Pages 42-44 CADWELD®/CADWELD® PLUS/CADWELD® MULTI ..................Pages 45-56 Index ......................................................................................................................Pages 57-59 www.erico.com 1 CATALOGUE OVERVIEW LIGHTNING PROTECTION ERICO® Six Point Plan of Protection Point 1 - Capture the Effective lightning protection involves the integration of several concepts. ERICO® employs the Six Point Plan of Protection as a useful guide to ensure the highest level of system security. lightning strike PAGES 17 TO 19 PAGES 21 TO 22 Point 2 - Convey this energy to ground PAGES 23 TO 26 GROUNDING & BONDING Point 4 - Bond all ground points together Point 3 - Dissipate energy into the grounding system PAGES 27 TO 29 PAGES 31 TO 37 2 PAGES 38 TO 41 www.erico.com 6 surges and transients on incoming power lines to help prevent equipment damage and costly operational downtime. Protect low voltage data/telecommunications circuits. Protect equipment from surges and transients on incoming telecommunications and signal lines to help prevent equipment damage and costly operational downtime. CADWELD® PLUS W NE PAGES 46 TO 48 CADWELD® SURGE PROTECTION Point 5 - Protect incoming AC power feeders PAGES 43 TO 44 www.erico.com Point 6 - Protect low voltage data/ telecommunications circuits PAGES 43 TO 44 3 PAGES 48 TO 56 CADWELD® MULTI PAGE 49 TECHNICAL INFORMATION 3 energy to the ground via a purpose-designed downconductor. Dissipate energy into the grounding system. Dissipate energy into a low impedance grounding system. LIGHTNING PROTECTION 5 Protect incoming AC power feeders. Protect equipment from CONDUCTORS 2 Convey this energy to ground. Conduct the help eliminate ground loops and create an equipotential plane. GROUNDING & BONDING 4 Bond all ground points together. Bond all ground points to ning strike to a known and preferred attachment point using a purpose-designed air terminal system. SURGE PROTECTION 1 Capture the lightning strike. Capture the light- CADWELD CATALOGUE OVERVIEW TECHNICAL INFORMATION TECHNICAL INFORMATION ERITECH ® SYSTEM 3000 PROTECTION OF STRUCTURES AGAINST LIGHTNING There are 2 types of devices for the protection of structures against lightning: the conventional one, based only on passive components (copper, galvanized steel...), and the active protection system, The latter being based on advanced knowledge and more than 15 years of experience. AIR TERMINAL THE ERITECH DYNASPHERE ENHANCED AIR TERMINAL The patented ERITECH DYNASPHERE is an enhanced air terminal. • Non radioactive • Not externally powered • Has no moving parts • Responds dynamically to the approach of a lightning downleader. ACTIVE PROTECTION WHAT IS THE SYSTEM? PRINCIPLES OF THE ERITECH DYNASPHERE The ERITECH® SYSTEM 3000 is a technically advanced lightningprotection system. The unique features of this system allow the achievement of superior technical performance and hence provide more reliable lightning capture. The ERITECH® DYNASPHERE air terminal provides a preferred point for lightning discharges which would otherwise strike and damage an unprotected structure and/or its contents. The ERITECH DYNASPHERE is connected to an ERITECH® ERICORE downconductor and the ground system in such a way as to provide a totally integrated system. PROTECTION LEVEL Lightning is a statistical phenomena where 100% protection is virtually impossible to achieve, and certainly, is not economically practical. IEC 62305-3 defines 4 protection levels together with associated interception efficiencies. This information is used to determine the appropriate air terminal location and spacing. LEVEL I LEVEL II LEVEL III LEVEL IV 99% 97% 91% 84% Very high risk structures High risk structures Medium risk structures Low risk structures, e.g. Residential For more than 200 years little improvement was made in lightning protection systems. Modern research and recording methods have led to a better understanding of the lightning discharge process and various breakthroughs have been achieved in the simulation of lightning electric-field conditions. Two fundamental concepts have emerged from recent research into the lightning attachment process and air terminal performance: 1. Air terminals that produce copious quantities of corona (space charge) are likely to be less efficient in the interception of a lightning downward leader. 2. An optimum air terminal is one which launches an upward streamer when it is highly likely to convert into a stable, propagating leader (to intercept the downward leader) The ERITECH DYNASPHERE has been developed with these two concepts in mind. The ERITECH DYNASPHERE is an enhanced Franklin rod with a spherical dome which is capacitively coupled to the electric field of an approaching lightning downleader. This spherical conductive surface surrounds a central earthed lightning rod. The sphere is insulated from the rod but connected to ground via a high impedance with DC conduction. The ERITECH DYNASPHERE is isolated from the structure using an insulated support mast. The mast also enables the safe connection of the ERITECH ERICORE downconductor to the air terminal. 4 www.erico.com TECHNICAL AND DESIGN CHARACTERISTICS OF ERITECH ® ERICORE PLASTIC FILLER TO INCREASE EFFECTIVE DIAMETER OF CORE CONDUCTOR (Inductance-Skin effect) MAIN CONDUCTOR The ERITECH ERICORE downconductors have been designed to meet the criteria for an effective and reliable downconductor with the following key characteristics: COPPER TAPE SEMI-CONDUCTIVE STRESS CONTROL LAYER POLYETHYLENE H.V. INSULATION SEMI-CONDUCTIVE STRESS CONTROL LAYER • a low inductance per unit length • a low surge impedance • a carefully controlled internal electric field distribution to minimise field stresses under current impulse conditions • carefully designed, stress reducing upper termination. MAIN COPPER TAPE SCREEN SEMI-CONDUCTIVE OUTER SHEATH METAL SADDLES SECURE CABLE & BOND OUTER SCREEN TO STRUCTURE ERITECH ® SYSTEM 1000 ERITECH ® INTERCEPTOR SI ESE LIGHTNING TERMINALS • • • • Designed and tested to NFC17-102 and UNE-21186 Stainless steel design suitable for most environments Available in three models to suit specific site requirements Suitable for connection to a variety of downconductor systems including tape, cable, smooth-weave and ERICORE conductor • Fully compatible with the ERITECH® SYSTEM 3000 mast, ERITECH ERICORE cable and accessories ERITECH ® SYSTEM 2000 CONVENTIONAL PROTECTION Conventional protection of buildings or structures involves the use of suitably positioned air terminals (lightning rods) which are interconnected with a metal downconductor network (usually copper) to provide the most direct path from the air termination to a low impedance grounding system. This helps ensure a safe and effective dissipation of the lightning impulse. Comprehensive conventional systems are often referred to as Faraday Cages. Simple lightning rod www.erico.com 5 Faraday cage TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION For the efficient performance of a lightning protection system, it is essential that a low impedance ground be provided to facilitate the dissipation of the lightning energy into the earth mass. Because soil conditions and seasonal patterns vary from site to site, the methods of grounding need to be considered on an individual basis. GROUND RODS, TAPES AND CLAMPS ERITECH® copperbonded, galvanized and stainless steel earth rods facilitate the transfer of surges and fault currents into the earth, and provide a long service life due to superior construction and quality. GROUND ENHANCEMENT MATERIAL (GEM) Ground enhancing materials can be applied around the conductors in a grounding system to reduce the local soil resistivity and lower ground impedance. They are particularly useful in areas of moisture variation, sandy soils and rocky ground. GROUND POTENTIAL EQUALISATION ERICO’s range of equipotential ground bars, plates, pre-engineered grids, and Potential Equalization Clamps combine to create a safe equipotential ground plane for the protection of personnel and equipment. Polymeric Cover CADWELD®/CADWELD® PLUS MOLECULAR BONDING CADWELD PLUS Package Ignitor Strip Graphite Mould Tap Hole Conductor Connections are often the most critical element of grounding systems, and subsequently can become the weak point due to ageing and corrosion. The preferred method of connection is the CADWELD® exothermic welding process producing a molecular bond. The capacity of an earthing circuit to protect the safety of personnel depends on the quality of the connections made. Weld Cavity THE CADWELD MOULD COVER CRUCIBLE STARTING POWDER WELDING MATERIAL DISC SEAT TAP HOLE WELD CAVITY CONDUCTOR CONDUCTOR 6 www.erico.com TECHNICAL INFORMATION TECHNICAL INFORMATION GROUND ELECTRODES The ground electrode is a critical component of the grounding system. Many different types of electrodes are available, some "natural" and some "made”. The natural types include metal underground water pipe, the metal frame of a building (if effectively grounded), a copper wire or reinforcing bar in a concrete foundation or underground structures or systems. Consideration should be given to bonding of natural earths to ensure electrical continuity with a facilities’ other "earths". "Made" electrodes are specifically installed to improve the system grounding or earthing. These earth electrodes must ideally penetrate into the moisture level below the ground level to reduce resistance. They must also consist of metal conductors (or a combination of metal conductor types), which do not corrode excessively for the period of time they are expected to serve. Made electrodes include rods or pipes driven into the earth, metallic plates buried in the earth or a copper wire ring encircling the structure. Underground gas piping or aluminium electrodes are NOT permitted for use as ground electrodes. GROUND RODS Which ground rod should be used? Ground rods are often selected on the basis of their resistance to corrosion. The other major factor is cost. All too often, the cost of a product is seen as the initial up front price, but the real cost is determined by the serviceable life of the ground rod. Galvanized steel rods are one of the cheapest electrodes available. However, they are not the most cost effective since they have a relatively short service life. Solid copper and stainless steel rods have a long service life. However, they are considerably more expensive than galvanized steel rods. In addition to this, solid copper rods are not suited to deep driving or even driving short lengths into hard ground, without bending. As a compromise, steel cored ground rods, swaged in a copper or stainless steel sheath were developed. These ground rods are much less expensive than their solid counterparts. They are capable of being deep driven. However, the sheath of this rod type has been known to slip or tear, particularly the copper version. Once this sheath has been damaged, the integrity of the entire electrode is at risk. • Cost effective long service life Copperbonded coating: • Permanent molecular bond • Low resistance performance • High fault current capacity (IEEE® Std 80) • Will not slip or tear when driven • Will not crack if rod is bent Carbon Steel core and tip: • Greater tensile strength • Deep driving capability Ask for the ERICO® White Paper on Ground Rods – Copperbonded vs. Galvanized. Copperbonded ground rod versus Galvanized ground rod. www.erico.com COPPERBONDED GROUND ROD 7 GALVANIZED GROUND ROD • Lower purchase price - not as cost effective as Copperbonded Galvanized coating: • Relatively short service life • May crack if rod is bent Steel core and tip: • High tensile strength • Deep driving capability GROUND ELECTRODES The Stainless Steel Option The copperbonded ground rod has an electrolytic coating of copper deposited over a layer of nickel. This process ensures a long lasting, molecular bond between the copper layer and the steel core. ERICO® recommends copperbonded ground rods because the copper coating will not slip or tear when driven nor will it crack if the rod is bent. The tough, carbon steel core has good characteristics for deep driving. Copperbonded ground rods have a high resistance to corrosion and provide a low resistance path to ground. It is important to note that certain soils and land fill areas may not be compatible with copper. In these situations, stainless steel is a better proposition. Stainless steel may also be an alternative, where structures or components, such as steel towers, poles or lead sheathed cables are in close proximity to an array of ground electrodes. In these circumstances, consideration must be given to the consequence of galvanic corrosion. The high cost of stainless steel rods prohibits their widespread use. Above photo shows two ground rods subjected to the same pressure load test. The ERITECH® copperbonded ground rod, shown on the left, will bend without tears, cracks or folds, to the outer sheath. The inferior copperclad rod shown on the right, has developed cracks and creases to the outer sheath, which will significantly reduce its serviceable life and put the integrity of the entire electrode at risk. GROUND ROD ANNUAL COST Ga lva Zi niz nc ed Ste el Cop (10 pe mi rbo l/2 nd 54 ed μm Ste ) el Cop (13 pe mi rbo l/3 nd 30 ed μm ) Ga lva Zi niz nc ed Ste C o el (10 ppe mi rbo l/2 nd 54 ed μm Ste ) C el op (13 pe r mi bo l/3 nd 30 ed μm ) Sta inl e Ste ss el 8 Sta inl e Ste ss el COMPARATIVE COST GROUND ROD LIFE EXPECTANCY YEARS TECHNICAL INFORMATION TECHNICAL INFORMATION www.erico.com WHY IS GOOD GROUNDING IMPORTANT? Fig.1-A The transient nature of lightning with its associated fast rise times and large magnitude currents mean that special consideration needs to be given to grounding, for lightning protection to be effective. Many factors such as soil resistivity variations, installation accessibility, layout and existing physical features are all site specific and tend to affect decisions on grounding methods employed. The primary aim of a direct strike grounding system is to: • Efficiently dissipate lightning surge energy into the ground • Help ensure safety of equipment and personnel Distance from the electrode Earth Rod GROUNDING PRINCIPLES Low impedance is the key to lightning protection. All grounding connections should be as short and direct as possible to minimise inductance and reduce peak voltages induced in the connections. The ground electrode system must efficiently couple lightning surges into the ground by maximising capacitive coupling to the soil. The resistance of the ground itself to lightning currents must also be minimised. Only when all these factors are taken into account will maximum lightning protection be achieved. GROUND IMPEDANCE Soil resistivity is an important design consideration. It varies markedly for different soil types, moisture content and temperatures and gives rise to variations in ground impedances. Figure 1-B illustrates current flow from the injection point of a single ground electrode. As current flows out from the central injection point, a voltage gradient on the ground surface around the electrode is produced. This gradient levels off to a plateau at some distance from the electrode, as seen in Figure 1-A. The impedance seen by the current is determined by the soil particles in direct contact with the surface of the rod, and by the general impedance of the soil. Fig.1-B CHARACTERISTICS OF A GOOD GROUNDING SYSTEM • Good electrical conductivity • Conductors capable of withstanding high fault currents • Long life - at least 40 years • Low ground resistance and impedance The basis philosophy of any grounding installation should be an attempt to maximise the surface area of electrodes or conductors with the surrounding soil. Not only does this help to lower the earth resistance of the grounding system, but it also greatly improves the impedance of the grounding system under lightning surge conditions. SHORT, DIRECT GROUND CONNECTIONS The voltage generated by a lightning surge depends primarily on the risetime of the surge current and the impedance (primarily inductance) of the path to ground. Extremely fast rise times result in significant voltage rises due to any series inductance resulting from long, indirect paths, or sharp bends in the routing of ground conductors. • Equipotential bonding COUPLING FROM THE ELECTRODE SYSTEM TO THE GROUND The efficiency of a ground electrode system in coupling a lightning surge current to ground is dependent on a number of factors, including the geometry of the ground electrode system, the shape of the conductors and the effective coupling into the soil. Equipotential bonding helps ensure that hazardous potential differences do not occur between different incoming conductors such as metallic water services, power systems, telecommunication systems and the local ground, and also minimises step and touch potentials. • Good corrosion resistance The ground electrode system should be corrosion resistant, and compatible with other conductors that are buried and bonded to the ground system. Copper is by far the most common material used for grounding conductors. In general, some form of maintenance or inspection procedure should be adopted to ensure the long-term effectiveness of a grounding system. DOWNCONDUCTOR GEM EARTH PIT • Electrically and mechanically robust and reliable A typical grounding system. Mechanical coupling can be used to join ground conductors, but suffers from corrosion effects when dissimilar metals are involved. As well as mechanical strength, CADWELD® connections provide excellent low impedance, long life electrical connections with excellent corrosion resistance. www.erico.com 9 TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION COMPONENTS OF A GROUNDING SYSTEM A grounding system for lightning protection serves to deliver the lightning current into ground. It consists of one or more ground electrodes (earthing rods) along with any interconnecting conductors. Components include: WITHOUT PROTECTION WITHOUT PROTECTION • Ground rods • Ground enhancing materials • CADWELD® exothermic welded connections • Ground connectors – tapes, stranded cables, rod clamps, mesh, plates etc • Ground pits - for access to the ground system Figure 2 DESIGNING A GROUND ELECTRODE SYSTEM A significant factor governing the choice of a grounding system are the applicable standards and codes: European American Australian IEC 10234-1, IEC 61364-5, ENV 61024-1, BS 1400, BS 7430, NFC 17100, NFC 17102 EN-50164-2 NFPA® 780, IEEE® STD80, IEEE 837, NFPA 70 AS1768 Other factors to consider include: • The needs and layout of the facility (location and space confinement issues) DIFFERENCE OF POTENTIAL Step and Touch Potential. Step potential is the voltage difference between a person’s feet caused by the dissipation gradient of a fault entering the earth. Touch potential is similar to “step potential” except that the fault current passes through the person’s arm and torso on the way to the ground. • Reducing ground impedance Resistivity of the soil varies markedly for different soil types, moisture content and temperatures, and this gives rise to variations in ground system impedance. The lower the resistivity, the easier it is to achieve an effective grounding system. Measures that can be used for reducing earth impedance include: • Connecting additional buried conductors to the ground electrode • Use of multiple interconnected ground electrodes • Use of flat tape rather than circular conductors • Use of spaced conductors connected in parallel • Use of equipotential mesh electrodes • Use of multiple short interconnected buried conductor • The ground environment of the facility itself (eg soil resistivity) • Existing grounding systems • Susceptibility to seasonal variations in soil moisture content and temperature • Exposure to pedestrian traffic • Step and Touch Potentials While it is clear that a low impedance grounding system will allow the lightning surge energy to be dissipated into the ground, this will not necessarily minimise hazards to personnel in close proximity to the grounding system. High voltage gradients on the surface of the ground give rise to undesirable step and touch potential hazards. In order to reduce the chance of injury to personnel, both step and touch potentials must be minimised. Figure 2 graphically illustrates the danger of such potentials. • Selecting the right connections The connections between the conductors and the main grid, and between the grid and ground rods, are as important as the conductors themselves in maintaining a permanent low-resistance path to ground. 10 • Use of ground enhancing compounds Electrically conductive ground enhancing compounds can be applied to help lower ground resistance and impedance. They are particularly useful for rocky ground, areas of moisture variation and sandy soils. These compounds are generally applied around electrodes in oversized drill holes and around horizontal buried conductors. • Use of mineral or chemical ground rods Mineral or chemical ground rods are also used to decrease ground impedance. These consist of a perforated hollow copper tube sealed at the bottom. A salt compound is placed inside the tube which gradually leaches out to maintain a conductive environment around the electrode. • Use of concrete slabs or footings The use of reinforced concrete slabs and footings is one of the most effective ways to provide a low impedance ground electrode system. If addressed at the design stage this method can provide a very stable, permanent distributed ground electrode system at very little additional cost to the civil works. www.erico.com TECHNICAL INFORMATION TECHNICAL INFORMATION GROUND POTENTIAL EQUALISATION Creating an equipotential earth plane under transient conditions is essential for equipment and personnel safety. However, separate earths are sometimes installed for lightning, mains power, computer and communications equipment in buildings and other installations. Although this may be desirable under normal operating conditions, when lightning or other transient voltages occur, potential differences between the separate earths are inevitable. These can enter buildings, destroying equipment and creating dangers for personnel. The PEC (Potential Equalization Clamp) usually operates as an effective open circuit. However, once the earth potential difference exceeds the breakdown voltage of the PEC (under transient conditions), the circuit closes immediately and the earth potential’s are equalised, thereby protecting equipment and people. TELECOM EARTH BAR POWER EARTH BAR MAINS POWER EARTH WIRE MAINS EARTH Estimated linear feet of ground conductor covering with each bag of GEM Total thickness of GEM Trench Width 2, 5 cm (1”) 5, 1 cm (2”) 7, 6 cm (3”) 10, 2 cm (4”) 10 cm (4”) 4.3 m (14.0’) 2.1 m (7.0’) 1.4 m (4.7’) 1.1 m (3.5’) 15 cm (6”) 2.8 m (9.3’) 1.4 m (4.7’) 0.9 m (3.1’) 0.7 m (2.3’) 20 cm (8”) 2.1 m (7.0’) 1.1 m (3.5’) 0.7 m (2.3’) 0.5 m (1.8’) 25 cm (10”) 1.7 m (5.6’) 0.9 m (2.8’) 0.6 m (1.9’) 0.4 m (1.4’) 30 cm (12”) 1.4 m (4.7’) 0.7 m (2.3’) 0.5 m (1.6’) 0.4 m (1.2’) LP EARTH Equipotential earth plane created by bonding all earths together with Potential Equalization Clamps (PEC). • Appropriate depth and separation of electrodes The length, number and placement of ground rods affects the resistivity of the path to ground. The most cost-effective depth to which an electrode should be driven is usually dependent on specific soil conditions. Soils are rarely homogeneous or uniform and it may be advantageous to install electrodes to a particular depth where a low resistivity soil layer, such as a clay base, is encountered. Electrode depths commonly used are in the range of 1 to 4 m. Electrodes should be separated by a distance of at least twice the depth to which they are installed. • Equipotential Bonding Potential equalisation ensures that any potential rise due to the injection of lightning current into the impedance of the grounding network, is experienced by all the conductive services in the building. Thus everything rises in potential together and hazardous potential differences are avoided. www.erico.com A superior conductive material that improves grounding effectiveness, especially in areas of poor conductivity (rocky ground, areas of moisture variation, sandy soils) : LIGHTNING DOWNCONDUCTOR EARTH PIT TELECOM EARTH GROUND ENHANCEMENT MATERIAL (GEM) Estimated bags of GEM for backfilling around ground rods to a density of 90 lb/cu ft (1442 kg/m3) Depth of hole (Feet) * Dia. of hole 7.5 cm 10.0 cm 12.5 cm 15.0 cm 17.5 cm 20.0 cm 22.5 cm 25.0 cm 11 (3”) (4”) (5”) (6”) (7”) (8”) (9”) (10”) 1.8 m 2.1 m 2.4 m 2.7 m 5.2 m 5.8 m 6.1 m (6’) (7’) (8’) (9’) (17’) (19’) (20’) 2 2 3 5 6 8 10 12 2 3 4 5 7 9 12 14 2 3 4 6 8 11 13 16 2 3 5 7 9 12 15 18 4 6 9 13 17 22 28 34 4 7 10 14 19 25 31 38 4 7 10 15 20 26 32 40 PROTECTION FROM POWER SURGES To meet the fundamental requirements of performance, longer service life and greater safety under real world conditions, ERICO® has developed a range of technologies covering all aspects of the Six Point Plan of Protection. In the field of surge protection, several technologies play a critical role in the provision of premium performance. The DINLINE Product range offers both shunt or series protection utilising differing technologies in compact DIN rail mounted products. A number of different options are available to suit your individual application or performance requirements. SHUNT SURGE PROTECTION DEVICES SERIES SURGE PROTECTION DEVICES For strategic or critical applications the DINLINE Surge Filter (DSF/TDF) provides, superior protection for sensitive electronic equipment. In addition to simply diverting the surge energy, the units filter the clamped waveform. The products should be installed prior to sensitive and valuable electronic equipment and installations utilising electronic and communications systems. Shunt Surge protection devices alone do not help modify the excessive wavefront characteristics of lightning. The high rate of current rise (dI/dt) and the rate of induced voltage rise (dV/dt) are properties of the lightning waveform which are often the principle causes of damage to sensitive electronic components and equipment. The DINLINE Surge Diverters (DSD) offer economical and reliable protection from transients on power lines with the convenience of easy installation on 35 mm DIN rail mountings. The DSF and TDF product range is therefore designed to provide suitable low pass filter technologies that act to limit and slow down the Output Voltage (or Let-through voltage under surge conditions). The figure below illustrates the fundamental performance difference between the DSD and DSF/TDF product lines under surge conditions. The DSD range includes the three phase DSD340 series for simple installation into TN-C, TN-S and TT systems. Alternatively multiple DSD1x units may be configured for TN-C, TN-S, TN-C-S, TT & IT systems with surge ratings ranging form 10kA to 150kA. OPEN CIRCUIT CLOSED CIRCUIT TEST WAVEFORM OUTPUT VOLTAGE (Volts) TECHNICAL INFORMATION TECHNICAL INFORMATION DSD SHUNT-ONLY PROTECTOR TIME (μs) DSF/TDF SURGE FILTER Internal thermal disconnect devices ensure safe isolation during sustained and abnormal events on the distribution network. Most units feature visual indication in the event of such operation. In addition, select units are available with voltage-free contacts for remote signaling if replacement is due. 12 www.erico.com PROTECTION OF COMMUNICATIONS EQUIPMENT Transients and surges caused by lightning, or switching of power equipment, affect communications signals carried on copper cables. Telecommunications lines, industrial process control, coaxial feeders and computer networks are all vulnerable to surges, which may be up to 20kA for some high-risk environments. In the field of communications surge protection, several product variations are required to ensure all applications are met. Therefore ERICO® offers protection products to meet a wide variety of applications, from telecommunication line protectors for either KRONE® or DIN connection to coaxial surge protectors suitable for either BNC or N type coax cables. The various product families and applications are summarised below: Subscriber Line Protection (SLP) and High Speed Digital Protection (HSP) Product family - High 20kA (8/20us) surge rating - KRONE LSA-Plus Termination - Both Single Stage and Multi-Stage models available Co-axial Surge Protectors (CSP) - Robust, plug-in style design - Range of connections types and operating voltages available - Wide operating frequency from DC up to 3GHz Data Line Protectors (DLP) / Data Equipment Protectors (DEP) / Local Area Network Protectors (LAN) - Range of connections types available, from DB to RJ45 and KRONE - Wide range of operating voltages and frequencies available - Surge Ratings from 500A to 20kA depending on product and application Universal Transient Barrier (UTB) - High 20kA (8/20us) surge rating - Premium three stage protection - Self-resetting, over-voltage and over-current protection Knowing where to install surge protection can be difficult. To ensure cost-effective protection is provided for data, signaling and control circuits, two issues need to be considered: WHAT TYPE OF SPD IS APPROPRIATE FOR EACH CIRCUIT TYPE AND LOCATION ? Five parameters must be considered to ensure that surge protection devices for use on data, signalling or control circuits are suitable and do not adversely affect operation of the circuit. 1) SPDs are designed to clamp the excess transient voltage to safe levels sustainable by the equipment, yet should not interfere with the normal signalling voltages. As a guide, the SPD clamping voltage should be selected to be approximately 20% higher than peak working voltage of the circuit. 2) The line current rating of the SPD should be sufficient to handle the maximum expected signalling current. 3) The SPD bandwidth should be sufficient to allow correct operation of the system without adverse attenuation. For most SPDs, frequency attenuation data or a maximum recommended baud rate is generally specified. www.erico.com 4) The connection termination, mounting method, number of lines to be protected and other physical aspects must be considered. 5) The SPD surge rating should be appropriate for the intended location. For circuits internal to the building, surge ratings of 1-5kA are generally sufficient. For the protection of circuits that connect to exposed lines entering or exiting the facility, 10-20kA is recommended. WHERE SHOULD THE SPDs BE INSTALLED ? Communications devices are at risk from transients being induced onto the interconnecting signal lines. The use of surge protection barriers, installed at either end of the lines, provides cost effective mitigation. Communication or signal lines that enter or exit the building pose the highest risk. In such circumstances, protection devices should be installed at the point of entry or at the equipment termination itself. 13 TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION TECHNICAL INFORMATION CADWELD ®/CADWELD ® PLUS THE MOLECULAR BOND THE CADWELD® MOULD USING CADWELD PLUS CADWELD® EXOTHERMIC CONNECTION A welding process that eliminates the connection by forming a molecular bond. Connections are the weak point of all electrical circuits and especially earthing circuits subjected to ageing and corrosion. The capacity of an earthing circuit to protect the safety of personnel depends on the quality of the connections made. BS 6651 (1992) STATES : "Any joint other than welded represents a discontinuity in the current conducting system and is susceptible to variation and failure.” THE CADWELD ® PROCESS Polymeric Cover CADWELD PLUS Package Ignitor Strip Graphite Mould Tap Hole Conductor The CADWELD® process provides a way to produce copper/copper, copper/galvanized or plain steel, copper/copper clad steel, copper/bronze/brass/stainless steel, steel/steel, molecular bonds with no external energy or heat source. Weld Cavity The principle consists of bringing together a welding filler material and ignition agent in a suitable graphite mould. The reduction of copper oxide by aluminium produces molten copper and aluminium oxide slag at extremely high temperatures. The shape of the mould, its dimensions, and the size of the weldmetal, are all dependent on the items to be welded and their size. 1 Installation Is Easy! 2 4 Simple Steps For Permanently Welded Electrical Connections CADWELD PLUS Control Unit initiates the reaction of the metal crucible. The standard unit includes a 6-foot (1.8 meter) high temperature control unit lead. The lead attaches to the ignition strip using a custom made, purpose-designed termination clip. After the termination clip is installed on the ignition strip, the installer pushes and holds the ignition button to start a charging and discharging sequence. Within a few seconds the control unit sends a predetermined voltage to the ignition strip and the reaction is initiated. Insert CADWELD PLUS package into mould 3 Press and hold control unit switch and wait for the ignition 14 Attach control unit termination clip to ignition strip 4 Open the mould and remove the expended steel cup – no special disposal required www.erico.com TECHNICAL INFORMATION TECHNICAL INFORMATION THE CADWELD® WELD • Will carry more current than the conductor. • Will not deteriorate with age. • Is a molecular bond that eliminates any risk of loosening or corrosion. • Will resist repeated fault currents • Can be quality controlled simply by visual inspection. RELIABILITY As the molecular bond eliminates the concept of surface contact, an electrolyte cannot penetrate between the conductors and cause oxidation and deterioration in the course of time. CORROSIVE ENVIRONMENTS This reliability is of particular interest for humid or chemical environments or for bonds directly buried in the ground. CORROSION TEST CONDUCTIVITY The CADWELD connections form a solid bond around the conductors assuring continuity. The cross sectional area of the weld has greater current carrying capacity than the conductors. CADWELD'S fine performance is due to its reliability resulting from the molecular bond. SET CABLE/CABLE 2 SAMPLES MECHANICAL 2 SAMPLES SET CABLE/CABLE 4 SAMPLES END 4 SAMPLES CADWELD CABLE/CABLE 3 SAMPLES CADWELD Comparison between CADWELD Bonded Connection and Mechanical Connection CADWELD Weld (Metal A) (Metal B). The CADWELD bonded connection provides permanent conductivity over the whole of the section due to molecular bonding between the metal surfaces. PERFORMANCE Standard CADWELD welds have a cross section greater than that of the conductors to be joined, which compensates for the difference in resistivity between the conductor and the weld material. Consequently, under fault conditions the weld will always remain cooler than the conductor. If special applications do not allow for the required increase in cross section to be employed, the use of the formula: R = p x l and V= R x l S will make it possible to define precisely the resistance of the CADWELD® weld. www.erico.com TIME IN YEARS The melting temperature of CADWELD filler material is higher than the melting temperature of copper (1082°C). For this reason, in the event of abnormal heating due to a high fault current, the conductor is destroyed before the connection. This accelerated ageing test, carried out in a saline atmosphere at a controlled temperature, demonstrates that CADWELD ® welds retain all their electrical properties during the period of the test whereas the resistance of mechanical connections increase with time and this alters their conductive properties. RELATIVE RESISTANCE ABILITY TO WITHSTAND HIGH CURRENT Comparison between CADWELD® Bonded Connection and Mechanical Connection CADWELD WELD (Metal A) (Metal B) The CADWELD bonded connection provides permanent conductivity over the whole of the section due to molecular bonding between the metal surfaces. 15 MECHANICAL CRIMPED CONNECTION Line of current Actual Contact Surface The mechanical connection presents a significant difference between the apparent contact surface and the actual surface. TECHNICAL INFORMATION TECHNICAL INFORMATION Nominal Wire Size Cross AWG Sectional Area (mm2) #10 6 #8 10 #6 16 #4 25 #3 25 #2 #2 Solid 35 #1 #1 Solid 50 1/0 Solid 1/0 2/0 Solid 2/0 70 95 95 3/0 4/0 Solid 4/0 120 250 KCM 150 300 KCM 350 KCM 185 400 KCM 240 500 KCM 300 ERICO CADWELD Mould Reference 1B A7 1E W2 1H W3 1L Y1 1Q Y1 1V 1T Y2 1Y 1X Y3 2B 2C 2F 2G Y4 Y5 Y5 2L 2P 2Q Y6 2V Y7 3A 3D Y8 3H Y9 3Q Y0 Number Nominal of Strands Diameter of Strands (mm) 7 0.98 7 1.04 7 1.23 7 1.35 7 1.55 7 1.70 7 1.96 7 2.14 7 2.20 19 1.35 7 2.47 1 6.54 19 1.53 19 1.50 1 7.35 19 1.78 1 8.25 19 1.89 1 9.27 19 2.13 19 2.14 37 1.78 19 2.52 19 2.59 1 11.68 19 2.89 37 2.03 37 2.07 37 2.25 37 2.29 37 2.47 37 2.52 37 2.64 61 2.25 61 2.30 61 2.52 Nominal Nominal Cable Cable Diameter Diameter (mm) (inch) 2.95 0.12 3.12 0.12 3.71 0.15 4.05 0.16 4.67 0.18 5.10 0.20 5.89 0.23 6.42 0.25 6.60 0.26 6.75 0.27 7.42 0.29 6.54 0.26 7.65 0.30 8.43 0.33 7.35 0.29 8.90 0.35 8.25 0.32 9.46 0.07 9.27 0.36 10.65 0.42 10.70 0.42 12.46 0.49 12.60 0.50 12.95 0.47 11.68 0.46 13.41 0.53 14.21 0.56 14.61 0.58 15.75 0.62 16.00 0.63 17.30 0.68 17.64 0.69 18.49 0.73 20.25 0.80 20.65 0.81 22.68 0.89 Nominal Strand Area (mm2) 0.75 0.85 1.19 1.43 1.89 2.27 3.02 3.60 3.80 1.43 4.79 33.62 1.84 1.77 42.41 2.49 53.49 2.81 67.43 3.56 3.60 2.49 4.99 5.27 107.22 6.56 3.24 3.37 3.98 4.12 4.79 4.99 5.47 3.98 4.15 4.99 Nominal Wire Cross Sectional Area (mm2) 5.26 5.95 8.32 10.02 13.21 15.89 21.12 25.18 26.61 27.20 33.54 33.62 34.93 33.58 42.41 47.28 53.49 53.43 67.43 67.70 68.34 92.07 94.76 100.10 107.22 124.63 119.75 124.52 147.11 152.39 177.29 184.54 202.53 242.54 253.44 304.24 KCM was previously MCM, ie 1000 circular mils, a measure of the wire cross-sectional area. Note that KCM "overstates" the true cross sectional area (measured in sq. mils) of a conductor by 4/π (i.e. 1.273) 1 mil = 0.001 inch Square Inches x 1273 = KCM Square Millimeters x 1.974 = KCM KCM x 0.5607 = Square Millimeters 16 www.erico.com ERITECH® LIGHTNING PROTECTION ERITECH® SYSTEM 1000 ERITECH® SYSTEM 3000 CLT Terminal Inline Coupling Metallic Mast Support Mast ERITECH® ERICORE Insulated Downconductor Bare Downconductor 1 or 2 Required The ERITECH® SYSTEM 3000 is a technically advanced lightning protection system. The unique Collection Volume Method design (CVM), and features of this system allow the achievement of superior technical performance, and hence more reliable lightning capture. The ERITECH® SYSTEM 1000 SI Interceptor terminal is designed and tested to the French Standard NFC17-102 and Spanish norm UNE-21186. For applications up to 65 m tall, these standards provide simple placement rules and determination of protected area. The ERITECH® DYNASPHERE air terminal provides a preferred point for lightning discharges which would otherwise strike and damage an unprotected structure and/or its contents. The ERITECH DYNASPHERE is connected to a single insulated downconductor (ERITECH ERICORE) and the ground system in such a way as to provide a totally integrated system. www.erico.com The terminals are erected with conductive masts and dependant upon structure height and terminal location one or two bare downconductors are required. 17 LIGHTNING PROTECTION ESE Terminal FRP Insulated Mast ERITECH® LIGHTNING PROTECTION ERITECH® SYSTEM 3000 INLINE COUPLING ERITECH® DYNASPHERE AIR TERMINAL LIGHTNING PROTECTION 702085 702089 Ø 70 mm Reference code Part No. Description D/SMKIV-SS INTMKIV-SS 702085 702089 ERITECH® DYNASPHERE ERITECH® INTERCEPTOR 1 1 Unit weight kg 5 2 Reference code Part No. I/LCOUPL 701320 Unit weight kg 10,5 1 ALUMINIUM MASTS ERITECH® ERICORE DOWNCONDUCTORS Ø 60 mm Ø 68 mm Reference code Part No. Unit weight kg Length (mm) • • • Aluminium Reference code Part No. Section ERICORE/PER M 701875 50 mm2 Reference code Part No. • • • Terminations ERICORE/TRM/OS 701915 ERICORE/TRM/IS 701895 ERICORE/LT KITA 702005 ALUM 3ME ALUM 4M ALUM 5M ALUM 6M Unit weight kg 1,2 per meter 502000 701370 701380 701390 3000 4000 5000 6000 1 1 1 1 8,25 11 13 16 ALUMINIUM MASTS & BASES Unit weight kg Description Factory Upper Termination, outside drum Factory Upper Termination, inside drum Lower Termination 1 1 1 1,5 1,5 1,5 225 mm m 5m 22 Reference code INSULATED MASTS Part No. Length (mm) 502040 701340 701350 701360 3000 4000 5000 6000 Unit weight kg • • • Aluminium MBMAST3ME MBMAST4M MBMAST5M MBMAST6M 1 1 1 1 9,6 12 15 17 Ø 61,9 mm Ø 69,9 mm MAST BRACKETS 702065 10 mm 701460 r=38 Reference code Part No. Colour 87 mm Unit weight kg Length (mm) 90 mm • • • Fiberglass reinforced FRP/2M/WHITE FRP/2M/BLACK 702040 702030 White Black 2000 2000 1 1 31 mm 5 5 213 mm 195 mm 18 2 Reference code Part No. Description 7000250S4 UBOLT 702065 701460 Stainless steel mast bracket Pair of UBOLTs 1 1 pair Unit weight kg 1,12 0,4 www.erico.com ERITECH® LIGHTNING PROTECTION ERITECH® DYNASPHERE/ERITECH® INTERCEPTOR SI ADAPTORS 702297 702298 Reference code 701840 702299 701990 701410 701420 702296 702301 Reference code Part No. CONSAD/E2 CONSAD/FX CABTIE-SS 701990 701410 701420 Unit weight kg 0,19 0,01 0,05 5 100 1 LIGHTNING EVENT COUNTER 702306 Meets NFC-17100/NFC-17102 Part No. Unit weight kg Description ER1-ARCC-SS 101925 Adaptor to fix ARC to ER1-xxx-SS* THERMLUGCOUPL 701840 For bare downconductor INTCPT-ADBUTT 702296 For SI terminal to FRP INTCPT-ADF2BSPF 702297 SI terminal to 2” pipe. British thread INTCPT-ADF2NSP 702298 SI terminal to 2” pipe. USA thread INTCPT-ADM3/4UNC 702299 SI terminal to 3/4” pipe. USA thread INTCPT-ADM116UN 702301 SI terminal to ER2-xxxx-SS* INTCPT-ADM16 702306 16mm Conventional Rod to ER2-xxxx-SS* * See ERITECH® INTERCEPTOR SI Masts 1 1 1 1 1 1 1 1 0,1 0,1 0,05 0,1 0,1 0,1 0,1 0,1 Reference code Part No. LEC-IV 702050 Unit weight kg 2 1 ERITECH® SYSTEM 1000 ERITECH® INTERCEPTOR SI AIR TERMINAL GUY RING Reference code Part No. Description SI25 SI40 SI60 701535 701536 701537 ESE, 25μs ESE, 40μs ESE, 60μs 1 1 1 Unit weight kg 3 3 3 ERITECH® INTERCEPTOR SI MASTS Reference code Part No. in 701280 60 ø mm Unit weight kg out ERITECH INTERCEPTOR SI • • • Aluminium GUYRING 91 1 0,11 ER1 ER3 GUY KIT ER2 OR ER3-BASE ER2-BASE Reference code Part No. Unit weight kg Description • • • Stainless Steel Reference code Part No. Description GUYKIT 4MGRIP GUYKIT 7MGRIP 701305 701315 4m vertical guy 7m vertical guy www.erico.com 1 1 ER1-1000-SS ER1-2000-SS ER2-2000-SS ER2-3000-SS ER2-BASE ER3-2000-SS ER3-3000-SS ER3-BASE Unit weight kg 0,400 0,700 19 702255 702260 702265 702270 702290 702275 702280 702295 Upper Section, 1m Upper Section, 2m Mid Section, 2m Mid Section, 3m Base for ER2 mast Lower Section, 2m Lower Section, 3m Base for ER3 mast 1 1 1 1 1 1 1 1 3,5 6,2 4,9 7,3 5,2 5,3 7,9 5,6 LIGHTNING PROTECTION 101925 ERITECH® ERICORE FIXINGS ERITECH® LIGHTNING PROTECTION LIGHTNING PROTECTION ERITECH® SYSTEM 2000 PAGE 21 PAGE 25 PAGE 26 PAGE 24 PAGE 24 PAGE 21 PAGE 27 PAGE 25 PAGE 26 PAGE 21 PAGE 21 PAGE 23 PAGE 38 PAGE 26 PAGE 22 PAGE 22 PAGE 24 The ERITECH® SYSTEM 2000 lightning protection system is comprised of these principal components: • Air Termination Network • Downconductors • Grounding System • Bonding This Illustration is not drawn to scale, nor does it portray an actual or typical application. It is designed to illustrate some of the major components of the ERITECH® SYSTEM 2000 Lightning Protection System and their relationship with one another. 20 PAGE 26 PAGE 38 PAGE 22 PAGE 37 PAGE 38 PAGE 31-35 PAGE 24 PAGE 24 PAGE 24 PAGE 41 PAGE 23 Air terminal placement is designed using the computer aided design to BS6651, NFC 17-100, AS1768 or NFPA 780. This ensures the most effective placement of air terminations on the structure. Downconductors are positioned to provide the most direct path from the air termination to a low impedance grounding system, to help ensure safe and effective dissipation of the lightning impulse. Equipotential bonding of all circuits and conductors is necessary to reduce ground potential differences and to limit equipotential damage. www.erico.com ERITECH® LIGHTNING PROTECTION AIR TERMINAL TO TAPE COUPLING/BRACKETS Meets BS1432 C101/BS2897/AS1567 L 25mm 70 mm Meets BS1400/BS149 BS2897/AS1567 Ø 16.5mm M16 Ø 27mm TTR Series Reference code Part No. Unit weight kg ø mm L mm Reference code 711080 711090 711100 711110 711010 10 16 10 16 16 500 500 1000 1000 2000 1 1 1 1 1 0,480 0,750 1,100 1,510 3,000 711050 711060 710020 711070 10 10 16 16 500 1000 500 1000 1 1 1 1 0,190 0,380 0,265 0,530 Unit weight kg Material • • • Threaded rod to tape coupling • • • Copper CAR0510 CAR0515 CAR1010 CAR1015 CAR2015 • • • Aluminium AAR0510 AAR1010 AAR0515 AAR1015 Part No. TTRC16 711210 TTRA16 711200 • • • Rod brackets CBR015 711190 ABR015 711180 Copper Aluminium 1 1 0,230 0,080 Copper Aluminium 2 2 0,900 0,280 SIMPLE AIR TERMINAL Meets NFC-17100 Extension Masts Air Terminal Number height (m) of mast 2,40 0 4,15 1 (ER1) 5,90 2 (ER1+ER2) 7,65 3 (ER1+ER2+ER3) L 2m MULTIPLE POINT AIR TERMINAL 1 Meets BS1432 C101/BS1400 BS2897/BS2874/AS1567 2 3 Lightning Rod height • • • Chrome - nickel plated copper ASL-240-CC 101700 2,40 m Reference code Part No. Reference code Reference code Part No. CMPR 711120 ø mm L mm 16 500 1 Part No. Unit weight kg Ømm 30 1 3,750 Unit weight kg Ømm • • • Galvanized steel extension masts Unit weight kg 1,200 ER1-2000 ER2-2000 ER3-2000 101920 101930 101940 33 36 42 1 1 1 13,800 14,200 15,000 TRIPOD FOR MAST OR SIMPLE AIR TERMINAL AIR TERMINALS BASES ø int. maxi 50 mm A Meets BS1400/BS1471 AS1866/AS1567 A B Meets NFC-17100/NFC-17102 800 mm B 385 mm RSC ATBC/ATBA Reference code Reference code Part No. Unit weight kg A mm B mm www.erico.com 711150 711160 711170 10 16 16 25 25 31 1 1 1 0,500 0,500 1,700 711130 711140 10 16 25 25 1 1 0,160 0,160 Nr of masts 101950 0-3 Unit weight kg • • • Galvanized steel TFS 800 • • • Copper ATBC10 ATBC15 RSC115 • • • Aluminium ATBA10 ATBA15 Part No. 21 1 8,280 LIGHTNING PROTECTION AIR TERMINALS ERITECH® LIGHTNING PROTECTION WATERPROOF CONE/AERIAL SPARK GAP STRIKING RODS Meets NFC-17100 LIGHTNING PROTECTION 6-50mm Ø Reference code Part No. WPC SG-AERIAL-302 702230 702285 Unit weight kg 0,070 0,500 1 1 Reference code SET OF TWO 54 cm BRACKETS Meets NFC-17100/NFC-17102 550 mm 670 mm Lightning rod height Part No. • • • Chrome - nickel plated copper ARC-2205-CNC 101900 ARC-2210-CNC 101910 • • • Stainless steel ARC-2205-SS 102000 ARC-2210-SS 102010 Unit weight kg 0,50m 1m 1 1 0,550 0,800 0.50m 1m 1 1 0,500 0,750 AIR TERMINAL BASES AND FASTENERS 102350 102410 102400 38-77 mm Reference code Part No. LSEB 4554 702180 1 pair Unit weight kg 10,5 102460 102500 702165 BRACKETS FOR MAST OR AIR TERMINAL 102450 Meets NFC-17100 NFC-17102 280 mm 40 mm 90 mm Reference code Part No. ASB-TCA 102350 Base rod support and cross-over 1 Unit weight kg 0,250 ASP-100-TS ASA-TB ABFF-6530-TC ABFR-6530-TC 102400 102410 102450 102460 Support plate Angle support plate For flat conductor (30x2) For round conductor (8mmø) 1 1 1 1 0,430 0,200 0,070 0,050 ASFR-C TMC-SS 102500 702165 Cement block support Tape to Mast Clamp 10 1 1,000 0,200 Description 120 mm Ø 28-55mm Reference code Unit weight kg Part No. • • • Galvanized steel ALOF1-GS 702175 1 1,500 FASTENERS FOR AIR TERMINAL X-SHAPED BRACKET 102620 102600 Meets NFC-17100 Meets NFC-17100/NFC-17102 102610 ATR-10-SS 102600 M10 threaded rod, 100 mm long 10 Unit weight kg 0,080 ACB-10-SS 102610 10 0,060 AEM-10-SS 102620 Supporting anchor bolt* Angle support plate Expanding support pin, M10 85 mm long, drilling depth 60 mm 10 0,040 Reference code Reference code ACF-2-GS Part No. 103100 Description Set of 2 Fasteners Admissible ø mm 30 to 50 1 Unit weight kg 2,10 Part No. Description *Supplied with impermeable collar 22 www.erico.com ERITECH® LIGHTNING PROTECTION PUDDLE FLANGES NON METALLIC DC TAPE CLIPS Meets BS1432C101/BS2897 150 mm 3mm Meets BS1400/BS1471 150 mm Reference code Part No. Material PFC001 PFA001 710290 710295 Copper Aluminium 1 1 Unit weight kg - Reference code PDC253BN 711280 Brown PDC253GY 711290 Grey • • • For use with 50x6 bare Cu/Al tape PDC506BL 711360 Black • • • For use with 25x3 PVC covered Cu/Al tape PDC25WH 711350 White PDC25BN 711310 Brown PDC25BL 711300 Black PDC25GN 711320 Green PDC25GY 711330 Grey PDC25ST 711340 Stone Meets BS1400/BS1471/BS2874 BS2897/AS1567 Part No. 50 50 0,01 0,01 50 0,02 50 50 50 50 50 50 0,01 0,01 0,01 0,01 0,01 0,01 Unit weight kg Description SLATE HOLDFAST NON METALLIC DC CLIP & GLAZING BAR HOLDFAST • • • Copper DCC203 711630 DCC253 711220 DCC254 711640 DCC256 711230 DCC313 711650 DCC316 711660 DCC383 711670 DCC385 711680 DCC386 711690 DCC503 711700 DCC504 711710 DCC506 711240 DCC600 711250 DCC605 711260 DCC610 711270 • • • Aluminium DCA253 711730 DCA256 711740 DCA506 711750 DCA600 711760 Unit weight kg Colour • • • For use with 25x3 bare Cu/Al tape DC TAPE CLIPS Reference code Part No. for 20x3 bare copper tape for 25x3 bare copper tape for 25x4 bare copper tape for 25x6 bare copper tape for 31x3 bare copper tape for 31x6 bare copper tape for 38x3 bare copper tape for 38x5 bare copper tape for 38x6 bare copper tape for 50x3 bare copper tape for 50x4 bare copper tape for 50x6 bare copper tape for 25x3 PVC covered Cu tape for 25x6 PVC covered Cu tape for 50x6 PVC covered Cu tape 50 50 50 50 25 25 25 25 25 25 25 25 50 50 25 0,050 0,070 0,070 0,080 0,090 0,090 0,120 0,130 0,014 0,015 0,015 0,160 0,100 0,130 0,260 for 25x3 bare aluminium tape for 25x6 bare aluminium tape for 50x6 bare aluminium tape for 25x3 PVC covered Al. tape 50 50 25 25 0,030 0,080 0,050 0,040 Reference code Part No. Meets BS1400 BS2874 GB HF Unit weight kg Colour • • • For 25x3 bare tape HF250BN 711800 Brown HF250GY 711810 Grey • • • For 25x3 PVC covered tape HFP253BN 711820 Brown HFP253GY 711830 Grey HFP253ST 711840 Stone GLAZING BAR HOLDFAST Reference code 50 50 0,020 0,020 50 50 50 0,020 0,020 0,020 Meets BS1400/BS2874 Unit weight kg Part No. • • • Copper BARE TAPE CLIPS GBH C Meets BS2870/BS1471 GBH A w 710300 5 - 710305 5 - • • • Aluminium ONE HOLE CABLE CLIP Meets BS2879/BS1474 l W Reference code Part No. Description l w mm mm Unit weight kg A • • • Copper TAPC203 711560 for 20x3 bare copper tape clip TAPC253 711570 for 25x3 bare copper tape clip TAPC506 711590 for 50x6 bare copper tape clip • • • PVC Covered Copper TAPC254 711580 for 25x3 PVC covered copper 40 40 69 15 15 15 25 25 25 0,500 0,500 0,800 44.5 15 25 0,500 40 40 15 15 25 25 0,100 0,100 Reference code PC008C PC010C • • • Aluminium PC008A PC010A tape clip 711540 711550 www.erico.com for 20x3 bare aluminium tape clip for 25x3 bare aluminium tape clip ø mm A mm W mm Unit weight kg 711380 711390 8 10 28 42 10 15 50 50 0,01 0,01 711370 711040 8 10 28 42 10 15 50 50 0,01 0,01 • • • Copper • • • Aluminium TAPA203 TAPA253 Part No. 23 LIGHTNING PROTECTION 450 mm ø 5/8” ERITECH® LIGHTNING PROTECTION PLATE TYPE TEST CLAMP PROTECTIVE SLEEVE FOR DOWN CONDUCTOR ø 21mm 40 mm Meets BS1400 Meets BS1449-1 BS970 AS1397 NFC-17100 NFC-17102 PCF-40-GS 2m 10 mm PCR-27-GS 2m 100 mm LIGHTNING PROTECTION 25 mm AVG3.0 55 mm 3m Reference code Part No. Description 711450 26x12 mm Unit weight kg Reference code • • • Copper Part No. Unit weight kg Description • • • Galvanized PCT400 1 0,60 SQUARE TAPE CLAMP Meets BS1471/BS2874/BS1400 PCF-40-GS 102800 PCR-21-GS 102850 AVG3.0 711030 Protective sleeve for down conductors Protective sleeve for round down conductors Anti vandal guard 1 1 1 0,90 1 2,90 BRASS SUPPORT FOR DOWNCONDUCTOR 52 mm Reference code Part No. Unit weight kg Description 50 mm • • • Copper STC253 STC256-506 • • • Aluminium STA253 711410 711425 25x3 mm 25x6 mm to 50x6 mm 5 5 0,200 0,770 711400 25x3 mm 5 0,090 Meets NFC-17100/NFC-17102 17 mm Reference code Part No. SR 545260 50 Unit weight kg 0,027 BI-METALLIC CONNECTORS Meets BS970/BS1471/BS2874 711490 711500 711480 ANCHOR WITH LEAD PIN Reference code Part No. Unit weight kg Description • • • Stainless Steel BIM800 711490 BIM900 711500 • • • Copper / Aluminium BIM700 711480 25x3 mm Meets NFC17100/NFC-17102 102455 107500 round max 8 mm 5 5 0,200 0,200 25x3 mm 5 0,190 Reference code Part No. Description 107500 102455 with lead pin Unit weight kg • • • Galvanized SDH-3-GI PC302GS 50 1 0,021 0,010 MULTIPURPOSE CLAMP OBLONG TEST OR JUNCTION CLAMP Meets BS1471 BS2874/BS1400 Meets NFC-17100/NFC-17102 56 mm 8 mm 26 mm Reference code Unit weight kg Part No. Description 711440 26x8 mm 2 0,290 711430 26x8 mm 2 0,100 Reference code • • • Copper OCB268 • • • Aluminium OBA268 Part No. Unit weight kg Material • • • Round 8 mm max or tape 30 mm max CCFR-308 CCS-308 CCG-308 24 545270 545170 545180 Brass Stainless steel Galvanized steel 25 25 25 0,150 0,150 0,150 www.erico.com ERITECH® LIGHTNING PROTECTION SUPPORT FOR HIP OR RIDGE TILES Meets NFC-17100/NFC-17102 105400 r=93 Reference code Unit weight kg Part No. Reference code • • • For Round max 10 mm or flat max 30 mm CCJ-70-CA 102700 1 104350 Meets NFC-17100/NFC-17102 104450 Part No. Unit weight kg Conductor • • • Diameter 180-260 mm, plastic / stainless steel 0,4 SUPPORT HOOKS FOR ROOF TILES 105300 T1-SRL-25/6 T1-SFT-25 105300 105400 6 mm Ø 5-11 mm Ø or 30x2 mm 10 10 0,092 0,105 SUPPORT FOR ROUND CONDUCTOR 35 80 23 Reference code Part No. Unit weight kg Conductor Reference code • • • Plastic / Stainless steel 55 mm height R2-SRL-25 R2-SFT-25 104350 104450 Part No. Unit weight kg Conductor • • • Plastic 16 mm height 6 mm Ø 5-11 mm Ø or 30x2 mm 50 50 0,038 0,052 SRL-23-N6 SRL-23-N8 SRL-23-N10 103700 103710 103720 6 mm Ø 8 mm Ø 10 mm Ø 50 50 50 0,008 0,008 0,008 SUPPORTS WITH ADJUSTABLE FASTENING PLATE Meets NFC-17100/NFC-17102 23 PLASTIC SUPPORT BLOCK Ø6 106310 175 Meets NFC-17100/NFC-17102 106300 ø 110 35 106200 Reference code Part No. Unit weight kg Conductor Reference code • • • Plastic / Stainless steel 35mm height R1-SRL-25A6 R1-SFT-25 104200 104300 6 mm Ø 5-11 mm Ø or 30x2 mm 50 50 0,042 0,042 Part No. Conductor Unit weight kg Height • • • Plastic SFRR-SRL-45/6 SFRR-SFT-45 SFRR-SFT-65 FIXOBAND 106200 106300 106310 6 mm Ø 5-11 mm Ø or 30x2 5-11 mm Ø or 30x2 45mm 45mm 65mm 10 10 10 0,014 0,028 0,029 SLIDE RAIL FOR ROOF TILE OR TILE SLATE Meets NFC-17100/NFC-17102 104950 104980 Reference code Part No. CEI20 FEI20 BEI20 42014 591080 591230 591280 591290 www.erico.com Description Stainless steel bonding 100 Stainless steel buckle 50 Stainless steel serrated buckle 100 Fixoband Tool 1 Unit weight kg 0,009 0,104 0,017 1,800 Reference code Part No. Unit weight kg Conductor • • • Plastic / stainless steel 40mm height R6-SRL-40/6 R6-SFT-40 25 104950 104980 6 mm Ø 5-11 mm Ø or 30x2 50 50 0,069 0,083 LIGHTNING PROTECTION EARTH TESTING CLAMP ERITECH® LIGHTNING PROTECTION PLASTIC SUPPORT FOR DOWNCONDUCTOR 104600 Meets NFC-17100/ NFC-17102 107660 52 107650 40 T CONNECTOR Meets NFC-17100 40 mm 45 mm LIGHTNING PROTECTION 25 Reference code Part No. Unit weight kg Conductor Reference code Part No. Material 101230 710030 710040 Galvanized Copper Aluminium Unit weight kg • • • 8 mm diam. • • • Plastic SFT-23-N SFTP-23-N R3SFT-25 107650 107660 104600 5-11 mm Ø or 30x2 mm 5-11 mm Ø or 30x2 mm 5-11 mm Ø or 30x2 mm 50 50 50 CTR-10 CTR-8CU CTR-8AL 0,020 0,020 0,037 25 10 10 0,12 - CROSS CONNECTOR STAINLESS STEEL CLIP 30X2 Meets NFC17100/ NFC-17102 38mm Meets NFC-17100/NFC-17102 28 mm 28 mm 18mm TAPS302 ALD-TAP302 Reference code Part No. TAPS302 ALD-TAP302 711620 711195 100 100 Reference code Unit weight kg 0,002 - Part No. Material 101250 101260 101265 Stainless steel Copper Galvanized steel Unit weight kg • • • 6-8 mm diam. CCR-68-S CCR-68-CU CCR-68-GS 25 25 25 0,48 0,54 - BLOCKS FOR ROUND OR FLAT CONDUCTORS Meets NFC-17100/NFC-17102 SLIDE FASTENER ROOFSTILE FOR CONDUCTORS Meets NFC-17100/NFC-17102 80mm 190mm Reference code SFR-BC-8 SFT-BC SFT-BE Part No. 106030 106080 106060 Conductor Unit weight kg Fill 8 mm Ø Concrete 20 5-11 mm Ø or 30x2 Concrete 20 5-10 mm Ø or 30x2 Empty 100 0,970 0,982 0,100 STRAIGHT CONNECTOR Reference code Part No. R7-SFT-20 702250 HOT STICKING STRIP Meets NFC-17100 101240 10 Unit weight kg 0,05 Meets NFC-17100/NFC-17102 35 mm 150 mm Reference code Part No. Unit weight kg Conductor • • • Galvanized steel CLR-10 101240 9 mm Ø 25 0,11 26 Reference code Part No. HSF 702240 10 Unit weight kg 0,02 www.erico.com ERITECH® CONDUCTORS BARE COPPER TAPE COPPER CABLE Width (A)mm TC-EC-1215-30 710460 12 TC-EC-1230-30 710470 12 TC-EC-2015-30 710480 20 TC-EC-2030-30 710490 20 TC-EC-2515-30 710500 25 TC-EC-2530-25 710515 25 TC-EC-2530-50 710510 25 TC-EC-2540-30 710520 25 TC-EC-2560-15 710535 25 TC-EC-3020-30 197650 30 TC-EC-3160-30 710540 31 TC-EC-3650-50 710545 36 TC-EC-3850-10 710555 38 TC-EC-3860-30 710560 38 TC-EC-5030-30 710570 50 TC-EC-5060-20 710580 50 Minimum Order Quantity to Consider Reference code WITHOUT INSULATION Reference code Part No. SC-EC-10 SC-EC-16 SC-EC-25 SC-EC-35 SC-EC-50 SC-EC-70 SC-EC-95 SC-EC-120 SC-EC-150 SC-EC-185 710880 710890 197900 197910 197920 197930 197940 710900 710920 197950 Strand Description 7x1,45 7x1,60 7x2,14 7x2,52 19x1,78 19x2,14 19x2,52 37x2,00 37x2,25 37x2,50 Section mm2 10 16 25 35 50 70 95 120 150 185 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m Unit weight kg 0,12/m 0,13/m 0,23/m 0,31/m 0,46/m 0,62/m 0,85/m 1,03/m 1,33/m 1,61/m Minimum Order Quantity to Consider Part No. Thick. (B)mm 1,5 3,0 1,5 3,0 1,5 3,0 3,0 4,0 6,0 2,0 6,0 5,0 5,0 6,0 3,0 6,0 30 m 30 m 30 m 30 m 30 m 25 m 50 m 30 m 15 m 30 m 30 m 50 m 10 m 30 m 30 m 20 m Unit weight kg 0,17/m 0,33/m 0,27/m 0,53/m 0,33/m 0,67/m 0,67/m 0,89/m 1,34/m 0,53/m 1,65/m 1,61/m 1,70/m 2,04/m 1,34/m 2,64/m TINNED COPPER TAPE Meets (IC-EC) CEI 1024-1 - Meets (IC-ECH) BS6004/6491X/AS1746/EN50164-2 Meets BS1432C101/BS6746/ AS1567/NFC 17100/ NFC 17102/EN50164-2 Reference code Part No. TC-ECT-2020-30 TC-ECT-2530-30 TC-ECT-3020-30 TC-ECT-3020-75 TC-ECT-4030-30 TC-ECT-4040-35 197700 197720 197710 545200 197970 197975 WITH GREEN / YELLOW INSULATION Strand Description Section mm2 198000 198010 198020 204x0,395 286x0,395 408x0,395 25 35 50 50 m 50 m 50 m 0,27/m 0,37/m 0,53/m 198130 198050 198060 198070 198080 198090 710980 710990 711000 710970 198100 7x1,60 7x2,14 7x2,52 19x1,78 19x2,14 19x2,52 37x2,03 37x2,25 37x2,52 61x2,25 61x2,52 16 25 35 50 70 95 120 150 185 240 300 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 0,26/m 0,36/m 0,52/m 0,72/m 0,98/m 1,16/m 1,54/m 2,10/m 2,50/m 3,13/m Reference code Part No. Unit weight kg ••• IC-EC-25 IC-EC-35 IC-EC-50 ••• IC-ECH-16 IC-ECH-25 IC-ECH-35 IC-ECH-50 IC-ECH-70 IC-ECH-95 IC-ECH-120 IC-ECH-150 IC-ECH-185 IC-ECH-240 IC-ECH-300 Width (A)mm 20 25 30 30 40 40 30 m 30 m 30 m 75 m 30 m 35 m Unit weight kg 0,36/m 0,67/m 0,53/m 0,53/m 1,06/m 1,42/m Minimum Order Quantity to Consider PVC COVERED COPPER TAPE Meets BS1432C101/BS6746/ AS1567/EN50164-2 CT Dimensions AmmxBmm CTBL253-25 710595 Black 25x3,0 CTBN253-25 710605 Brown 25x3,0 CTGN253-25 710616 Green 25x3,0 CTGY253-25 710645 Grey 25x3,0 CTST253-25 710655 Stone 25x3,0 CTWH253-25 710666 White 25x3,0 CTYGN253-25 710667 Yell./Green 25x3,0 CTGN256-30 710620 Green 25x6,0 CTGN506-20 710630 Green 50x6,0 Minimum Order Quantity to Consider Reference code Minimum Order Quantity to Consider Part No. Colour LSF COVERED COPPER TAPE Reference code Part No. 27 25 m 25 m 25 m 25 m 25 m 25 m 25 m 30 m 20 m Unit weight kg 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 1,55/m 2,95/m Meets BS1432 C101/BS6746/AS1567 Colour LSF-253 710615 Green Minimum Order Quantity to Consider www.erico.com Thick. (B)mm 2,0 3,0 2,0 2,0 3,0 4,0 Dimensions AmmxBmm 25x3,0 50 m Unit weight kg 0,77/m CONDUCTORS Meets BS1432 C101/AS1567/ NFC17-100/NFC17-102/ CEI1024-1/EN50164-2 Meets BS125/BS6360/AS1746/ CEI1024-1/EN50164-2 ERITECH® CONDUCTORS Meets BS1432 C101 LEAD COVERED COPPER TAPE Width (A)mm LCT-253 710625 25 Minimum Order Quantity to Consider Reference code Part No. Thick. (B)mm 3,0 COPPER PLATES AND LATTICES / GRIDS Unit weight kg 2,56/m 50 m WM PC Mesh: 115 x 55 mm PLAIN COPPER BARS EML Meets BS1433/BS2874 C101 SRGB CONDUCTORS Tape = 50 x 0,40 mm Reference code Part No. HDB2003 HDB2503 HDB2506 HDB3806 HDB5006 HDB5010 710670 710680 710690 710700 710710 550900 Dimensions mm 20x3x4000 25x3x4000 25x6x4000 38x6x4000 50x6x4000 50x10x4000 Unit weight kg 2,14 2,68 5,34 8,00 10,68 17,80 1 1 1 1 1 5 Meets BS1432 C101/EN50164-2 COPPER PLATES Minimum Order Quantity to Consider Reference code Part No. Dimensions mm PC1.5-0606 PC3-0606 PC1.5-0909 PC2.-1020 PC3-0909 710190 710200 710210 504550 504590 600 x 600 x 1,5 600 x 600 x 3,0 900 x 900 x 1,5 1000 x 2000 x 2 900 x 900 x 3 Reference code Part No. THDB5060 710730 Minimum Order Quantity to Consider Dimensions mm 50x6x4000 Unit weight kg 10,68 1 SOLID COPPER ROUND CONDUCTOR SC BARE SOLID COPPER ROUND CONDUCTOR Reference code Part No. RC-EC-6 RC-EC-8 RC-EC-8-3 198150 198160 545210 ø (D) mm 6 8 8 Cross Section 28,3 50,3 50,3 100 m 100 m 30 m Meets BS1432C101/ AS1567/ NFC17100/ NFC17102/ EN50164-2 Unit weight kg 0,25/m 0,45/m 0,45/m 1 1 1 1 1 5,000 9,600 11,510 35,600 21,630 Meets BS1432 C101 COPPER LATTICES AND GRIDS Meets BS1433/BS2874 C101 TINNED COPPER BAR Unit weight kg Part No. Dimensions mm EML663 710230 EML993 710240 WM3-2088-B 504500 WM2-1030-B 504510 WM3-1020-B 504520 WM2-1020-B 504530 • • • Galvanized steel WMS-1030-B 504540 600 x 600 x 3 900 x 900 x 3 8800 x 2000 x 3 3000 x 1000 x 2 2000 x 1000 x 3 2000 x 1000 x 2 1 1 1 1 1 1 Unit weight kg 3,980 7,200 54,000 5,000 5,400 4,000 3000 x 1000 x 3 1 8,700 Reference code SIGNAL REFERENCE GRIDS Unit weight kg Reference code Part No. Length (m) Width (m) Spacing (m) SRGBC120 SRGBD100 SRGBE100 SRGBF100 SRGBG100 167900 167901 167902 167903 167904 36,57 30,48 30,48 30,48 30,48 2,44 3,04 3,65 4,26 4,87 0,60 0,60 0,60 0,60 0,60 1 1 1 1 1 86,18 90,72 104,33 127,01 145,15 SIGNAL REFERENCE GRID CONNECTOR & BRACKET TINNED SOLID COPPER ROUND CONDUCTOR Meets BS1432 C101/AS1567/NFC 17100/NFC 17102/EN50164-2 Reference code Part No. RC-ET-6 RC-ET-8 198200 198210 ø (D)mm 6 8 Cross Section 28,3 50,3 100 m 100 m Unit weight kg 0,25/m 0,45/m PVC COVERED SOLID COPPER ROUND CONDUCTOR ø 8 mm Meets BS1432 C101/BS6746/AS1567/EN50164-2 Reference code Part No. Colours SCBL SCBN SCGY SCST 710800 710810 710820 710830 Black Brown Grey Stone Cross Section 50,3 50,3 50,3 50,3 50 m 50 m 50 m 50 m SRGC46BR SRGC46 Reference code Part No. Max. Size SRGC46 SRGC46BR 167905 167906 Up to 25 mm2 stranded 25 mm pedestal 50 10 Unit weight kg 0,10 0,13 Unit weight kg 0,49/m 0,49/m 0,49/m 0,49/m 28 www.erico.com ERITECH® CONDUCTORS BARE ALUMINIUM TAPE BARE ALUMINIUM ROUND CONDUCTOR Meets BS2898/1350/AS1866/EN50164-2* Reference code Part No. BAT-2030 FAT-253-50 BAT-2560 BAT-5060 710955 710740 710960 710965 Width A mm 20 25 25 50 Thick B mm 3 3 6 6 50 m 50 m 50 m 50 m Meets BS2898/1350/AS1866/EN50164-2 Reference code RAW-8 ASCO8 Unit weight kg 0,16/m 0,21/m 0,41/m 0,81/m Part No. 198250 711530 Cross-section mm2 50,3 50,3 D ø mm 8 8 300 m 50 m Unit weight kg 0,14/m 0,14/m Minimum Order Quantity to Consider PVC COVERED ALUMINIUM TAPE Meets BS2898/1350/AS1866/EN50164-2 Meets BS2898/1350/AS1866/EN50164-2 Reference code ATBL253 ATBN253 ATGY253 ATST253 ATWH253 Part No. 710750 710760 710770 710780 710790 Width Thick A mm B mm 25 3 25 3 25 3 25 3 25 3 Colours Black Brown Grey Stone White 50 m 50 m 50 m 50 m 50 m Unit weight kg 0,30/m 0,30/m 0,30/m 0,30/m 0,30/m Reference code SABL SABN SAGY SAST D Part No. Cross-section mm2 ø mm Colours 710840 50,3 8 Black 710850 50,3 8 Brown 710860 50,3 8 Grey 710870 50,3 8 Stone 50 m 50 m 50 m 50 m Unit weight kg 0,18/m 0,18/m 0,18/m 0,18/m BARE GALVANIZED STEEL TAPE Meets DIN 48801 /NFC 17100/NFC 17102/ EN50164-2 BARE GALVANIZED ROUND CONDUCTOR Meets NFC 17100/NFC 17102/EN50164-2 Reference code 30TC-HGSP-3035 70TC-HGSP-3035 Part No. 197810 197790 Width Thick A mm B mm 30 3,5 30 3,5 30 m 70 m Unit weight kg 0,82/m 0,82/m BLACK STEEL TAPE Reference code RSCC-8 RSCC-10 Meets EN50164-2 Reference code TC-BR-253 Part No. 140250 www.erico.com Cross-section Dimensions mm2 AxB mm 75 25x3 30 m Unit weight kg 0,590/m 29 Part No. 197860 197870 Cross-section mm2 50,3 78,5 D ømm 8 10 Unit weight kg 100 m 0,400/m 100 m 0,630/m CONDUCTORS PVC COVERED ALUMINIUM ROUND CONDUCTOR ERITECH® GROUNDING & BONDING PAGE 37 GROUNDING & BONDING PAGE 31-35 PAGE 28 PAGE 28 PAGE 38 PAGE 37 PAGE 49-53 PAGE 27 GROUNDING SOLUTIONS • High strength corrosion resistant ERITECH® Ground Rods, clamps and accessories • Prefabricated wire mesh • Ground Enhancement Material (GEM) greatly improves ground grid resistance and impedance • CADWELD® molecular bonding connections RADIAL DESIGN EQUIPOTENTIAL MESH ELECTRODES 30 www.erico.com ERITECH® GROUNDING & BONDING ERITECH® Copperbonded Pointed Ground Rods ERITECH solid copper and stainless steel threaded ground rods •A uniform copper thickness provides better corrosion resistance in most soil Type SCR (solid copper) •C101 to comply with BS2874 for solid copper ground rods. •For use in highly corrosive soil conditions. conditions. Copperbonded rods last longer, drive easier and will not crack. •Copper exteriors, molecularly bonded to nickel-sealed high-strength steel cores, exceed the requirements of ANSI®/UL® 467-1984 (ANSI C33.8-1972) and CSA®. Rod to Cable Lug (Split Clamps) •Copper Coating: standard copper plating thickness exceeds UL and ANSI specs. of 0.254mm, conforms to KEMA 83C and EN50164-2 Norms. •The rods exceed a tensile strength of 515,000 kPa and straightness tolerance of 8.3 x 10-4m/m. •Extending rods may be extended with use of threadless couplers. •Manufactured in Gunmetal (LG2) and Naval Brass to comply BS1400, CZ112, BS2874 •Rod to Cable Lug clamps (threaded and unthreaded) •Permits easy connection of ground conductors to both threaded and unthreaded ground rods Type SSR (Stainless steel) •BS 970 - (A2 grade) ERITECH® TYPE CC Threadless Couplings for Copperbonded Pointed Rods •Enables ground rods to be driven deep quickly and easily without the risk of rod separation. •Made of high-strength silicon bronze. •Tapered so that when the rod is driven into the coupling, ERITECH® Ground Rod Driver the two parts compress to form a conductive connection. Type DH Tempered steel Driving Heads Couplers This one tool enables driving of rods to ground level, without heavy sledge-hammers or ladders and without deforming the end of the rod. Heavy-duty steel construction provides robustness and excellent driving force, while the soft rubber ergonomic grip provides user comfort. GROUNDING & BONDING Earthrod Pigtail ERITECH Copperbonded Sectional Ground Rods •Copperbonded externally coupled ground rods have all the features of standard copperbonded rods plus cold-rolled threads at each end for joining with couplings. •The cold-rolled threads of ground rods with their continuous unbroken grain flows are stronger than cut-threads. •High-strength couplings are threaded bronze and chamfered at both ends for easy driving. •Threaded coupling design allows for full contact of rod point with butt end of preceding rod. These high strength, corrosion-resistant couplings ensure low resistance copper-to-copper connections. The ERITECH® Ground Rod Driver from ERICO® is the simple, effective and affordable way to install ground rods. Couplers for threaded rods The ERITECH® Ground Rod Driver includes driver body with soft rubber grip, insert for driving rods to ground level, and retaining collar which holds insert in place during storage. • Usable on all types of round ground rods: copperbonded, galvanized, stainless steel • 14,2 mm (5/8”) and 17,2 mm (3/4”) inserts are interchangeable with standard driver Steel driving studs for sectional ground rods www.erico.com body to enable easy driving of standard rods. driver will not deform the end of the rod, making connection of the ground conductor quick and easy • Integral insert prevents driver from slipping off the rod near ground level. • Convenient retaining collar holds the insert in the tool when not in use. • Self-contained and easy to store. • Saves time and money and dramatically reduces risks of employee injury. • The 31 ERITECH® GROUNDING & BONDING ERITECH® Galvanized steel ground rods •Zinc-coated exteriors are hot-dip galvanized for solid protection against corrosion. •Surfaces are rigidly inspected to eliminate seams, slivers and other defects. Galvanized steel compression coupler (threadless) Driving Points Type DH Tempered steel Driving head Connecting Clamp ERITECH Type CG (X-Shaped Non-extensible) •Steel quality DIN 17100 •Supplied with splice plate •Compliant with DIN 48-452 •Zinc coating: minimum 55 μm, (average minimum 70 μm) •Sections 50 x 50 x 3 and 50 x 50 x 5 ERITECH Type SG Round galvanized ground rods (Extensible) •Steel quality DIN 17100 •Compliant with CEI 7/6 •Zinc coating: minimum 78 μm, (average minimum 86 μm) •Resistance:> 70 daN/mm2 ERITECH® Type Cloverleaf profile European application only (Non-extensible) •Galvanized thickness 150 μm according to UTE 66-400. •Resistance: > 70 daN/mm2 •Supplied with fitted splice socket. Driving Head Driving Point Driving Accessories for SG ground rods •Steel quality DIN 17100 •Compliant with CEI 7/6 •Zinc coating: minimum 78 μm, (average minimum 86 μm) GROUNDING & BONDING •Resistance:> 70 daN/mm2 ERITECH Type SS Stainless steel ground rods (Extensible) •Stainless steel Z30 C13 •Resistance:> 90/100 daN/mm2 Extensible Rod Driving Head Type RG Round (Non-extensible) •Resistance: > 70 daN/mm2 •Supplied with fitted splice socket. GROUND ENHANCEMENT MATERIAL (GEM) Developed in 1992, GEM Ground Enhancement Material is a superior conductive material that solves your toughest grounding problems. EARTH RESISTANCE ANALYSER GEM improves grounding effectiveness regardless of soil conditions. It is the ideal material to use in areas of poor conductivity such as rocky ground, mountain tops and sandy soil. Reference code Part No. EARTH ANALYSER EST101 EST201 EST301 ESTREELKIT500 702100 702360 702370 702380 702350 1 1 1 1 1 GEM is also the answer in situations where ground rods can't be driven. Or where limited land area makes adequate grounding difficult with conventional methods. Unit weight kg 8,3 4,64 10,54 11,98 7,71 Once GEM is installed, it maintains its low resistance for the life of the project. GEM's performance is backed by rigorous independent tests and proven field experience. Technical data available upon request. 32 www.erico.com ERITECH® GROUNDING & BONDING ERITECH® COPPERBONDED GROUND RODS Meets BS6651/C33,8 STANDARD TYPE UL467/ASTM A37/ KEMA K83C/EN50164-2/BS7430 ERITECH COPPERBONDED GROUND RODS THREADED TYPE, EXTENDING, WITH THREADED COUPLER Meets BS6651/C33,8 UL467/ASTM A37/EN50164-2/BS7930 • Electrolytically copperbonded steel • Copper coating min. 250u according Reference Part No. code • • • Non extending 1,2M38 155000 1,5M38 155010 2,1M38 155030 3,0M38 155050 • • • Extending 1,2M12 155060 1,5M12 155070 2,1M12 155090 3,0M12 155110 1,2M58 155240 1,5M58 155250 2,1M58 155270 3,0M58 155290 1,2M34 155420 1,5M34 155430 2,1M34 155450 3,0M34 155470 to standard UL467 ø Nominal Length Approx. inches ø mm m feet Unit weight kg 3/8 3/8 3/8 3/8 9 9 9 9 1,2 1,5 2,1 3 4’ 5’ 7’ 10’ 5 5 5 5 0,650 0,800 1,100 1,600 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 3/4 3/4 3/4 3/4 12,5 12,5 12,5 12,5 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2 1,2 1,5 2,1 3 1,2 1,5 2,1 3 1,2 1,5 2,1 3 4’ 5’ 7’ 10’ 4’ 5’ 7’ 10’ 4’ 5’ 7’ 10’ 5 5 5 5 5 5 5 5 5 5 5 5 0,800 1,150 1,600 2,300 1,500 1,900 2,650 3,750 2,150 2,750 3,800 5,450 • Rolled thread to preserve copper coating Reference code S1,2M916 S1,5M916 S2,1M916 S3,0M916 S1,2M58 S1,5M58 S2,1M58 S3,0M58 S1,2M34 S1,5M34 S2,1M34 S3,0M34 Part No. 155180 155190 155210 155230 155300 155310 155330 155350 155480 155490 155510 155530 ø inches 9/16 9/16 9/16 9/16 5/8 5/8 5/8 5/8 3/4 3/4 3/4 3/4 Approx. ø mm 12,7 12,7 12,7 12,7 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2 Nominal Length m feet 1,2 4’ 1,5 5’ 2,1 7’ 3 10’ 1,2 4’ 1,5 5’ 2,1 7’ 3 10’ 1,2 4’ 1,5 5’ 2,1 7’ 3 10’ 5 5 5 5 5 5 5 5 5 5 5 5 Unit weight kg 0,800 1,150 1,600 2,300 1,500 1,900 2,650 3,750 2,150 2,750 3,800 5,450 COUPLERS FOR THREADED RODS Meets KEMA K83C/BS6651/UL467/EN50164-2 DRIVING HEADS FOR COPPERBONDED POINTED RODS Reference code Part No. Rod ø 158120 158130 158140 1/2” 5/8” 3/4” Unit weight kg • • • Tempered steel DH12 DH58 DH34 5 5 5 Reference code Rod ø 158030 158040 158050 9/16” 5/8” 3/4” SC916 SC58 SC34 5 5 5 Meets BS97/BS436 resistance 6 micro-Ohms • BZT-Copper couplers 99% Cu, typical mechanical strength 10kN, typical resistance 4 micro-Ohms Unit weight kg Part No. Rod ø 158000 158010 158020 1/2” 5/8” 3/4” 5 5 5 0,108 0,134 0,202 156650 1/2” 5 0,087 156720 1/2” 5 0,102 • • • Bronze CC12F CC58 CC34 • • • Brass BR12 • • • Copper BZT-12 Reference code Part No. DS916 DS58 DS34 Unit weight kg Rod ø • • • Tempered steel DT12 DT58 DT34 www.erico.com 158060 158070 158080 1/2” 5/8” 3/4” 5 5 5 Part No. Rod ø 158090 158100 158110 9/16” 5/8” 3/4” Unit weight kg • • • Tempered steel DRIVING POINTS FOR GROUND RODS Reference code 0,104 0,086 0,172 DRIVING STUD FOR THREADED RODS • BR-brass couplers 58% Cu, typical mechanical Reference code Unit weight kg • • • Brass 0,158 0,435 0,226 THREADLESS COUPLINGS FOR COPPERBONDED POINTED RODS Meets KEMA K83C/BS6651/UL467/EN50164-2 Part No. 0,110 0,156 0,272 33 5 5 5 0,052 0,074 0,126 GROUNDING & BONDING Meets KEMA K83C/BS6651/UL467/EN50164-2 ERITECH® GROUNDING & BONDING ERITECH EARTHROD PIGTAIL FOR GROUND RODS ERITECH SOLID COPPER OR STAINLESS STEEL GROUND RODS & ACCESSORIES Meets BS6651/EN50164-2/BS7430 Reference code PT-12-25/3000 PT-12-25/300 PT-58-25/300 PT-58-35/300 PT-58-50/300 rod ø 1/2” 1/2” 5/8” 5/8” 5/8” Part No. 158600 158610 158675 158690 158290 Cable Cable size mm2 lengh mm 25 3000 25 300 25 300 35 300 50 300 5 5 5 5 5 Unit weight kg 0,645 0,180 0,200 0,200 0,365 SCR15-710070 - Copper SCR20-710080 - Copper ERITECH® SOLID COPPER INTERNAL THREADED GROUND RODS TYPE SCR GROUNDING & BONDING ERITECH® HAMMERLOCK Reference Part No. code EHL12FCW3 166950 EHL12FCY1 166951 EHL12FCY2 166952 EHL12FCY3 166953 EHL12FCY4 166954 EHL12FC1G 166955 EHL12FC1G1G 166956 EHL12FC1H 166957 EHL12FC1K 166958 EHL12FC1K1K 166959 EHL12FC1L 166960 EHL12FC1T 166961 EHL12FC1V 166962 EHL12FC6MM 166963 EHL12FC8MM 166964 EHL58CW3 166965 EHL58CY1 166966 EHL58CY2 166967 EHL58CY3 166968 EHL58CY4 166969 EHL58C1G 166970 EHL58C1G1G 166971 EHL58C1H 166972 EHL58C1K 166973 EHL58C1K1K 166974 EHL58C1L 166975 EHL58C1T 166976 EHL58C1V 166977 EHL58C2G 166978 EHL58C6MM 166979 EHL58C8MM 166980 EHL34CW3 166981 EHL34CY1 166982 EHL34CY2 166983 EHL34CY3 166984 EHL34CY4 166985 EHL34C1G 166986 EHL34C1H 166987 EHL34C1K 166988 EHL34C1L 166989 EHL34C1T 166990 EHL34C1V 166991 EHL34C2G 166992 EHL34C6MM 166993 EHL34C8MM 166994 rod ø 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" Conductor 16 mm Stranded 25 mm2 Stranded 35 mm2 Stranded 50 mm2 Stranded 70 mm2 Stranded #6 Solid #6 Solid #6 Stranded #4 Solid #4 Solid #4 Stranded #2 Solid #2 Stranded 6 mm Solid 8mm Solid 16 mm2 Stranded 25 mm2 Stranded 35 mm2 Stranded 50 mm2 Stranded 70 mm2 Stranded #6 Solid #6 Solid #6 Stranded #4 Solid #4 Solid #4 Stranded #2 Solid #2 Stranded #2/0 Stranded 6 mm Solid 8 mm Solid 16 mm2 Stranded 25 mm2 Stranded 35 mm2 Stranded 50 mm2 Stranded 70 mm2 Stranded #6 Solid #6 Stranded #4 Solid #4 Stranded #2 Solid #2 Stranded #2/0 Stranded 6 mm Solid 8 mm Solid 2 Cond. Size Cross Sect. 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2 13.3 mm2 13.3 mm2 13 mm2 21.2 mm2 21.2 mm2 21 mm2 30 mm2 33 mm2 28 mm2 50 mm2 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2 13.3 mm2 13.3 mm2 13 mm2 21.2 mm2 21.2 mm2 21 mm2 30 mm2 33 mm2 66 mm2 28 mm2 50 mm2 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2 13.3 mm2 13 mm2 21.2 mm2 21 mm2 30 mm2 33 mm2 66 mm2 28 mm2 50 mm2 Cond. Size Diam. 4,80 mm 6,40 mm 7,50 mm 8,90 mm 10,70 mm 4,70 mm 5,90 mm 6,50 mm 7,50 mm 6 mm 8 mm 4,80 mm 6,40 mm 7,50 mm 8,90 mm 10,70 mm 4,70 mm 5,90 mm 6,50 mm 7,50 mm 10,70 mm 6 mm 8 mm 4,80 mm 6,40 mm 7,50 mm 8,90 mm 10,70 mm 4,70 mm 5,90 mm 6,50 mm 7,50 mm 10,70 mm 6 mm 8 mm 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SCR16-710010 - Stainless steel Unit weight kg 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,21 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,20 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 0,24 34 Reference code Part No. SCR15 SCR20 710070 710080 Rod ø mm 15 20 Unit weight kg 1,64 3,34 L 1,20 m 1,20 m 5 5 ACCESSORIES FOR SOLID COPPER THREADED Meets BS2784 C101 GROUND RODS TYPE SCR See ground rods type SCR page 14 Reference code Rod ø mm Part No. Unit weight kg • • • Steel driving stud (15 mm) for SCR15 CDS15 710090 15 5 0,020 15 5 0,050 • • • Steel driving stud (20 mm) for SCR20 CDS20 710100 • • • M10 Phosphor bronze internal coupling Dowel (PB102) for SCR15 and SCR20 PBD10 710110 10 5 0,020 15 5 0,020 20 5 0,050 • • • Driving point for SCR 15 (15 mm) SPK15 710120 • • • Driving point for SCR 20 (20 mm) SPK20 710130 STAINLESS STEEL INTERNAL THREADED GROUND RODS TYPE SSR Reference code SSR16 Part No. 710010 diam. length mm m 16 1.20 Unit weight kg 1,640 5 ACCESSORIES FOR STAINLESS STEEL THREADED GROUND RODS TYPE SSR Reference code Part No. Rod ø mm Meets BS970 316-S12 Unit weight kg • • • Steel driving stud (15 mm) for SSR16 CDS15 710090 15 10 5 0,020 5 0,156 0,020 15 5 0,020 • • • M10 DT58Stainless steel internal 158070coupling Dowel 25 SSD10 710115 5 6.10 • • • Driving point for SSR16 SPK15 710120 www.erico.com ERITECH® GROUNDING & BONDING ERITECH® GALVANIZED STEEL GROUND RODS CLOVERLEAF PROFILE ERITECH GALVANIZED STEEL GROUND RODS TYPE CG (NON EXTENSIBLE) (X-SHAPED) Meets UTE C 66-400/DIN 48-452 Meets DIN 48-452 • • Supplied with splice plate Zinc coating: min 55 micron/ Average min. 70 micron • Supplied with fitted splice socket Reference code Part No. Length m 156340 156350 156360 1 1,5 2 Unit weight kg Reference code • • • Diameter 16 mm 1,0TG16TPWC 1,5TG16TPWC 2,0TG16TPWC Part No. Length m 158760 158770 158780 158790 158800 1 1,5 2 2,5 3 Unit weight kg • • • Section 50 x 50 x 3 5 5 5 1,0CG50/3 1,5CG50/3 2,0CG50/3 2,5CG50/3 3,0CG50/3 1,200 1,800 2,400 ERITECH GALVANIZED STEEL ROUND GROUND RODS • Meets UTE C 66-400/DIN 48-452 • 5 5 5 5 5 Meets DIN 48-452 Supplied with splice plate Zinc coating: min 78 micron/ Average min. 86 micron Reference code Part No. 2,340 3,510 4,680 5,850 7,020 Unit weight kg Length m 1,0CG50/5 1,5CG50/5 2,0CG50/5 2,5CG50/5 3,0CG50/5 Reference code Part No. Length m 156370 156380 156390 1 1,5 2 Unit weight kg 158710 158720 158730 158740 158750 1 1,5 2 2,5 3 5 5 5 5 5 3,900 5,850 7,800 9,750 11,750 • • • Diameter 16 mm 1,0RG16TPWC 1,5RG16TPWC 2,0RG16TPWC 5 5 5 1,700 2,500 3,400 ERITECH GALVANIZED STEEL GROUND RODS TYPE SG (EXTENSIBLE) Meets CEI 17/6 ERITECH STAINLESS STEEL GROUND RODS TYPE SS (EXTENSIBLE) • • Reference code Part No. 1,5SG20 1,5SG25 1,5SG30 158810 158820 158830 www.erico.com Length m 1,5 1,5 1,5 ø mm 20 25 30 5 5 5 Unit weight kg 3,705 5,600 8,600 35 Reference code Part No. 15SS20 158540 Stainless steel Z30 C13 Resistance: > 90 / 100 daN / mm2 Length m 1,5 ø mm 20 5 Unit weight kg 3,700 GROUNDING & BONDING • • • Section 50 x 50 x 5 • Supplied with fitted splice socket ERITECH® GROUNDING & BONDING ERITECH® DRIVING POINTS FOR GROUND RODS SG & SS ERITECH® GROUND ROD DRIVER FOR GROUND RODS SG Reference code Part No. Rod ø mm 158400 158390 158480 20 25 30 Unit weight kg • • • Tempered steel DT-P137-1-20 DT-P167-25 DT-P187-30 5 5 5 0,200 0,300 0,400 FOR GROUND RODS SS Reference code Part No. Rod ø mm 158550 20 Reference code Part No. EGRD58 158500 EGRD58L 158510 EGRD34 158520 EGRD34L 158530 1,5 m driver body with insert for up to 14,2 mm Replacement insert for 14,2 mm (5/8”) Driver body with insert for up to 17,2 Replacement insert for 17,2 mm (3/4”) 5 1 10,420 1 2,720 1 10,420 1 2,720 ERITECH® SADDLE AND ROD CLAMPS Unit weight kg Meets BS1400 • • • Tempered steel DT-P11-20-SS Unit weight kg Description range Reference code areaConductor (mm2) ø mm GUV16070 16-70 5,1-10,7 GUV70185 70-185 10,7-17,6 0,040 ERITECH DRIVING HEAD FOR GROUND RODS SG & SS Reference code Nominal Rod ø mm Part No. Unit weight kg • • • Gunmetal + Copper U bolt Reference code Part No. Rod ø mm 158380 20-30 UB16 UB20 UB25 GUV16070 GUV70185 Unit weight kg GROUNDING & BONDING • • • Tempered steel DH-TR167 5 Rod ø mm • • • Hot-galvanized steel - Tape capacity 40x3 MR127Z/20 158450 20 MR137/25 158460 25 MR187Z/30 158470 30 TO GROUND RODS SS Rod ø mm • • • Hot-galvanized steel - tape capacity 40x3 MR127Z/20 158450 20 Reference code Reference code Unit weight kg 5 5 5 5 0,200 0,200 0,210 0,390 0,390 Part No. Clamp capacity A mm B mm 158410 710345 710350 710360 26x12 31x10 51x12 26x10 Unit weight kg • • • Gunmetal RTC1 RTC3020 RTC2051 RTC2526 0,400 0,500 0,600 16 20 20 25 10 10 10 10 0,160 0,310 0,230 ERITECH® CONNECTING SOCKETS FOR CABLE TO GROUND ROD Unit weight kg Part No. 10 10 10 5 5 Meets BS1400 TO GROUND RODS SG Part No. 16 20 25 10-20 16-20 ERITECH® ROD TO TAPE DISCONNECT CLAMP (type A) 0,200 ERITECH® CONNECTING FLANGES FOR TAPE Reference code 710370 710380 710390 710400 710410 0,400 ERITECH CONNECTING CLAMP FOR CABLE TO GROUNG RODS SG & SS Reference code Rod ø mm Part No. Reference Part No. code • • • Cuproaluminium C142 158320 C162 158330 C174 158340 C205 158350 Unit weight kg • • • Copper/Steel - Cable capacity 70mm 2 S-136-20 158440 20 5 0,070 36 Rod ø mm Cable capacity mm2 14,2 16 17,2 20 95 95 95 95 Unit weight kg 5 5 5 5 0,072 0,068 0,068 0,098 www.erico.com ERITECH® GROUNDING & BONDING INSPECTION PITS ERITECH ROD® TO CABLE CLAMPS (type C) Meets BS2874/BS1400 Type C 103470 710180 Type CP Conductor Capacity Type C: Max 70 sq mm Type CP: Max 25 sq mm Reference code Part No. Rod ø in mm 158150 158260 158160 158170 156900 156910 158250 9,0-9,0 12,5-12,7 12,5-15,0 14,2-17,2 14,2-19,0 14,2-20,0 Unit weight kg • • • Gunmetal C38 C12 C58 C34 C19 C20 C1 • • • Bronze CP38 CP12 CP58 CP34 158155 158265 158165 158175 Cond. size cross section Max 16 sq mm Max 25 sq mm Max 25 sq mm Max 25 sq mm 5 5 5 5 5 5 5 0,026 0,040 0,084 0,086 0,085 0,125 0,110 50 50 50 50 0,04 0,09 0,10 0,13 103450 ø 180 mm 100 mm ø 140 mm Reference code PIT03 IP-900-C IP-R193x122MM IP-SQ-180-CI ERITECH® ROD TO TAPE LUG (SPLIT CLAMP) Meets BS2874/BS1400 Dimensions mm plastic 250x200x215 concrete 325x325x145 Cast iron 210x140x120 Cast iron ø180 Part No. Material 710180 103450 103470 103480 1 1 1 1 Unit weight kg 1,350 27 7 2,400 EARTH BARS FOR INSPECTION PITS Reference Part No. code • • • Gunmetal RCC10 710420 RCC16 710430 SRC15 710440 SRC20 Unit weight kg Description 9,5 mm plain split Clamp 16 mm split Clamp (threaded) 14,2-15 mm plain split Clamp (SCR) for solid copper rod 20 mm plain split Clamp (SCR) for solid copper rod 710450 10 10 0,090 0,340 Reference Part No. code • • • Copper BEP25x5x300MM 545140 10 0,330 BEP25x5x200MM 545135 10 0,300 BEP25x5x150MM 545530 Dimensions & No. of holes Designed to suit Earth Pit 25x5x300 mm 12 holes 25x5x200 mm 8 holes 25x5x150 mm 6 holes Concrete Earth Pit IP-900-C(103450) Plastic Earth Pit PIT03(710180) Cast Iron Earth Pit IPR193(103470) IP180(103480) GROUND ENHANCEMENT MATERIAL GEM Unit weight kg 1 0,300 1 0,260 1 0,150 TAPE METAL SUPPORT FOR FOUNDATIONS OR TRENCHES AND TAPE METAL WALL SUPPORT Refer to page 11 for further information Reference code Part No. GEM 163670 1 Unit weight kg 11,500 107600 107550 TAPE METAL SUPPORT FOR FOUNDATIONS OR TRENCHES PREFABRICATED CROWSFOOT • Keeps the tape in a vertical position Reference code Part No. Rod height mm Unit weight kg • • • Galvanized steel STBF-25-GS STBF-40-GS Reference code Part No. GF-302 503900 Rod ø in mm Tinned copper 30 x 2 1 Unit weight kg 5,500 250 400 25 25 TAPE METAL WALL SUPPORT Reference code Part No. 0,200 0,340 Unit weight kg Material • • • For tape below 6 mm thick SSF-6-GS SSF-6-C www.erico.com 107600 107610 37 107550 107560 Galvanized steel Copper 25 25 0,130 0,140 GROUNDING & BONDING RCC16 RCC10 SRC15 SRC20 ERITECH® GROUNDING & BONDING TOWER EARTH CLAMP PIPE COLLARS Meets BS1432 C101/BS970 M10x30 12 ø 6-11 mm 40 22 Reference code Part No. Unit weight kg ø min. / max. • • • Stainless steel - conductor, 6 to 11 mm Reference code SPC-5080-S 107000 SPC-70120-S 107010 SPC-130180-S 107020 • • • Copper - conductor, 6 to 11 mm SPC-5080-C 107050 SPC-70120-C 107060 SPC-130180-C 107070 Unit weight kg Part No. • • • Copper - ø 8mm TECLP-8-CU 710050 10 0,090 710060 10 0,058 • • • Aluminium - ø 8mm TECLP-8-AL B - BOND 50/80 70/120 130/180 10 10 10 0,147 0,170 0,214 50/80 70/120 130/180 10 10 10 0,165 0,191 0,240 FASTENERS FOR GUTTER RIM Meets NFC 17100/NFC 17102 Meets BS1471/BS2874 M10x35 33 33 25 mm max. Reference code Reference code • • • Copper - conductor, 6 to 10 mm Unit weight kg Part No. SGR-610-2 • • • Copper - suit 26 mm max tape width BBBC 710260 25 0,12 GROUNDING & BONDING 710250 25 0,60 107230 M10 0,067 25 100 Unit weight kg 0,102 0,008 VFST 40 WATER PIPE BOND 33 10 INSULATORS • • • Aluminium - suit 26 mm max tape width ABBC Unit weight kg Part No. Meets BS1400 33 ISO Reference code Part No. ISO40M10 VFST10x40 551520 593480 EQUIPOTENTIAL BARS Reference code Unit weight kg Part No. BWPB • • • Aluminium AWPB 710310 20 0,12 710270 20 0,08 160mm SEB • • • Copper 40mm ø 5mm l 171mm Cu 50x5mm w 173mm WATERMAIN PIPE BOND 52mm DLUNI Meets BS1400/BS1471 SEB-62-DL Reference code DLUNI SEB-06 SEB-06-DL SEB-10 SEB-10-DL SEB-62-DL SEB-GER-08 25 mm max. Reference code Part No. Unit weight kg ø mm • • • Copper WPB010 710320 Meets BS1433/BS2874 UL 94 NFF 1611 F2 5 0,26 SEB-GER-08 SEB-06-DL Nr of Disconnect L Part No. terminals links mm 545000 1 125 545010 6 0 400 545020 6 1 475 545030 10 0 600 545040 10 1 675 545130 6 2 550 545001 7 x 25 mm2 1 x tape 30 x 3,5 1 x 8 mm ø W L 100 100 100 100 100 100 94 94 94 94 94 94 1 1 1 1 1 1 10 Unit weight kg 1,192 1,642 2,400 2,312 2,800 3,200 0,314 NB: terminals do include Nuts and Bolts 38 www.erico.com ERITECH® GROUNDING & BONDING EQUIPOTENTIAL PLATE SET EARTH BOSS Meets UL 94/NFF 1611 F2 100 mm 710160 L. 200 mm 25 mm 10,5 mm • 16 connection points Reference code Unit weight kg Part No. • • • Tinned copper 100 x 5 SEP 545190 1 1,02 EARTH BLOCKS 500-10-E-BOSS 710160 Length mm 50 ø mm 50 1 Unit weight kg - 198400 198410 198420 5 ft = 1.5 m 10 ft = 3 m 20 ft = 6 m STATIC EARTHING 13 mm 50 mm 165620 165410 EBL08 - 6 x ø 5,2 mm - 2 x ø 6,5 mm 20 mm 88 mm Part No. EBL04 - 3 x ø 5,2 mm - 1 x ø 6,5 mm EBL04 20 mm Reference code 13 mm EBL08 B2610A Unit weight kg Part No. • • • Tinned brass EBL04 EBL08 711460 711470 10 10 B2671A 165400 710330 0,090 0,158 DOUBLE CONNECTING PLATE Supporting plate for the connection of round conductors, diameter 10 mm, or flat conductors up to 40 x 4 mm on rebars up to 24 mm ø. 10100 80 60 40 M10 Reference code Part No. Conductor Unit weight kg Rebar Reference code Part No. B2610A B2671A A822SA111C-5 A822SA111C-10 A822SA111C-20 B2618B SEB001 165410 165620 198400 198410 198420 165400 710330 • • • Galvanized steel CPD-2440 101100 10 mm dia or 40x4 24 mm dia 25 0,340 REBAR CLAMPS RC EK Reference code Part No. Conductor Rebar 8 mm dia 8 mm dia 25 mm2 25 mm2 8-18 mm 18-38 mm 25 mm-parallel 25 mm-perpendicular Unit weight kg • • • Galvanized steel RC70 RC100 EK16 EK17 710325 710335 710355 710365 www.erico.com 1 1 50 50 SEB001 B2618B 0,340 0,780 0,091 0,091 39 Description Spring Clamp Aircraft Grounding Clamp Orange Coiled Cable, 5 ft (1.5 m) Orange Coiled Cable, 10 ft (3 m) Orange Coiled Cable, 20 ft (6 m) Cable Reel Assembly Static Earth Bar 1 1 1 1 1 1 1 Unit weight kg 0,144 1,140 0,450 0,540 0,820 3,150 0,260 GROUNDING & BONDING Reference code ERITECH® GROUNDING & BONDING EYES BOLTS FOR COPPERBONDED GROUND RODS OXIDE INHIBITING COMPOUND Reference code W Part No. OXINHIBCOMP 710220 1 Unit weight kg 0,314 H ERITECH COPPER BONDING STRAPS Reference code Part No. ø inch W H EBR-58 EBR-34 710140 710150 5/8” 3/4” 68 68 96 96 5 5 Unit weight kg Part No. GROUNDING RECEPTACLES 165180 Meets BS1400 165220 165230 C A B These receptacles provide earth connections for the frames of planes, ships, tankers trucks, etc. eliminating their electrostatic charge and obtaining equipotentiality with the surrounding earth. GROUNDING & BONDING Parts are copper alloy, connections to the earth circuit can be made with CADWELD®. Reference code B165 B166 B167 Part No. 165180 165220 165230 Attachment Depth A Cast 3/4” ball 4 1/2” Cast 3/4” rod 6 1/4” Cast 1-1/2” rod 7 1/4” øB øC 2 3/4” 4 3/4” 3 7/8” 6 1/2” 4 3/4” 1 1 1 Unit weight kg 0,800 2,100 7,000 DENSO TAPE (DT) AND SILFOS TAPE (SFO) Reference code DT50 SFO50 Part No. 711520 710170 10 m x 50 mm 8 m x 50 mm 1 1 Unit weight kg 0,760 0,430 POTENTIAL EQUALIZATION CLAMP (PEC) Reference code PEC100 Part No. 702900 1 563540 556620 563550 556630 563300 556640 556650 563320 556660 556940 556670 556680 563340 556690 563430 556700 556710 556950 556720 556730 556740 556750 556760 556960 556770 556780 556790 556800 565000 556810 556970 556820 556830 563350 556840 563440 563360 563370 556850 556860 563390 563400 556980 563560 Thick. Section L Reference code Intensity A mm mm2 mm Ø mm J mm T mm MBJ 16-100-6 MBJ 16-100-8 MBJ 16-150-6 MBJ 16-150-8 MBJ 16-200-6 MBJ 16-200-8 MBJ 16-250-8 MBJ 16-300-6 MBJ 16-300-8 MBJ 16-500-8 MBJ 25-100-10 MBJ 25-150-10 MBJ 25-200-6 MBJ 25-200-10 MBJ 25-200-12 MBJ 25-250-10 MBJ 25-300-10 MBJ 25-500-10 MBJ 30-100-10 MBJ 30-150-10 MBJ 30-200-10 MBJ 30-250-10 MBJ 30-300-10 MBJ 30-500-10 MBJ 35-100-10 MBJ 35-150-10 MBJ 35-200-10 MBJ 35-250-10 MBJ 35-250-25 MBJ 35-300-10 MBJ 35-500-10 MBJ 50-100-10 MBJ 50-150-10 MBJ 50-200-6 MBJ 50-200-10 MBJ 50-200-12 MBJ 50-200-16 MBJ 50-200-18 MBJ 50-250-10 MBJ 50-300-10 MBJ 50-300-16 MBJ 50-300-18 MBJ 50-500-10 MBJ 50-500-12 6,5 8,5 6,5 8,5 6,5 8,5 8,5 6,5 8,5 8,5 10,5 10,5 6,5 10,5 12,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 25,5 10,5 10,5 10,5 10,5 6,5 10,5 12,5 16,5 18,5 10,5 10,5 16,5 18,5 10,5 12,5 15 15 15 15 15 15 15 15 15 15 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 40 23 23 28 28 28 28 28 28 28 28 28 28 28 28 28 25 25 25 25 25 25 25 25 25 25 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 50 33 33 38 38 38 38 38 38 38 38 38 38 38 38 38 120 120 120 120 120 120 120 120 120 120 150 150 150 150 150 150 150 150 180 180 180 180 180 180 197 197 197 197 197 197 197 250 250 250 250 250 250 250 250 250 250 250 250 250 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 16 16 16 16 16 16 16 16 16 16 25 25 25 25 25 25 25 25 30 30 30 30 30 30 35 35 35 35 35 35 35 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 150 150 200 200 250 300 300 500 100 150 200 200 200 250 300 500 100 150 200 250 300 500 100 150 200 250 250 300 500 100 150 200 200 200 200 200 250 300 300 300 500 500 Unit weight kg 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 0,018 0,018 0,035 0,035 0,033 0,033 0,040 0,05 0,05 0,082 0,027 0,039 0,052 0,052 0,052 0,064 0,077 0,013 0,032 0,047 0,062 0,075 0,092 0,155 0,037 0,054 0,072 0,089 0,089 0,110 0,180 0,052 0,077 0,12 0,120 0,120 0,11 0,11 0,127 0,153 0,15 0,14 0,255 0,255 Unit weight kg 0,500 40 www.erico.com ERITECH® GROUNDING & BONDING ERITECH® EARTH POINTS TYPE DB • FIG. 1: CADWELD® mould ref. 197130 can be used to make CADWELD welded connection of 1 or 2 conductors (cross-section up to 50 mm2 to the plate). • FIG. 2: Steel bar attached at right angles to shank of earth plate by CADWELD welding. 3 1 4 • FIG. 3: Steel bar attached to end of earth plate by CADWELD welding. • FIG. 4: 50 mm2 green: yellow insulated conductor attached to end of earth plate by CADWELD welding. 2 TYPE B161 - B164 TYPE B162 7 6 9 5 11 10 12 8 Fig. No. 1 2 3 4 Reference code Part No. øA DB-8A DB-10A DB-12A DB-16A DB-8K DB-10K DB-12K DB-16K DB-8KS DB-10KS DB-12KS DB-16KS DB-10-C5005 DB-10-C501 DB-10-C502 166090 166120 166150 166180 166100 166130 166160 166190 166110 166140 166170 166200 166480 166490 166500 M8 M10 M12 M16 M8 M10 M12 M16 M8 M10 M12 M16 M10 M10 M10 TYPE B161-B164 5 6 7 8 Reference code Part No. B161-8A B161-10B B164-12A B161-8K B161-10KA B164-12K B161-8KS B161-10KM B164-12KS B161-10-C5005 B161-10-C501 B161-10-C502 166000 166030 166060 166010 166040 166070 166020 166050 166080 166510 166520 166530 øA 4xM8 4xM10 4xM12 4xM8 4xM10 4xM12 4xM8 4xM10 4xM12 4xM10 4xM10 4xM10 TYPE B162 9 10 11 12 Reference code Part No. øA B-162-12A B-162-12K B-162-12KS B-162-12-C5005 B-162-12-C501 B-162-12-C502 166210 166220 162230 166540 166550 166560 2xM12 2xM12 2xM12 2xM12 2xM12 2xM12 www.erico.com øB øC øD F L mm mm mm mm mm 12,7 16 16 16 12,7 16 16 16 12,7 16 16 16 - 12 19 19 19 12 19 19 19 50mm2 50mm2 50mm2 30 50 50 50 30 50 50 50 30 50 50 50 50 50 50 50 55 55 55 50 55 55 55 50 55 55 55 55 55 55 500 500 500 500 500 500 500 500 500 1000 2000 øB øC øD F G L mm mm mm mm mm mm 14 14 10,7 14 14 10,7 14 14 10,7 - 12 12 12 12 12 12 50mm2 50mm2 50mm2 65 65 85 65 65 85 65 65 85 65 65 65 42 42 75 42 42 75 42 42 75 - 30 30 44,5 30 30 44,5 30 30 44,5 30 30 30 500 500 400 500 500 400 500 1000 2000 øB øC D E F G L mm mm mm mm mm mm mm 10,7 10,7 10,7 - 12 12 50mm2 50mm2 50mm2 45 45 45 45 45 45 85 85 85 85 85 85 75 75 75 75 75 75 44,5 44,5 44,5 44,5 44,5 44,5 400 400 500 1000 2000 41 5 5 5 5 1 1 1 1 1 1 1 1 1 1 1 Unit weight kg 0,090 0,300 0,305 0,400 0,450 1,520 1,535 1,560 0,440 1,520 1,505 1,540 0,740 0,960 1,440 1 1 1 1 1 1 1 1 1 1 1 1 Unit weight kg 0,435 0,455 0,770 1,980 1,040 1,080 1,980 0,850 1,100 0,840 1,100 1,600 5 1 1 1 1 1 Unit weight kg 0,400 0,700 0,700 0,820 1,060 1,560 GROUNDING & BONDING TYPE DB CRITEC® SURGE PROTECTION PAGE 44 PAGE 44 PAGE 44 SURGE PROTECTION PAGE 44 PAGE 44 COLOUR CODE Power Protection device Telecommunication and Dataline Protection device. PAGE 43 Power line Telecoms and Data Earthing network 42 www.erico.com CRITEC® SURGE PROTECTION DINLINE DECOUPLING INDUCTORS (DDI) DINLINE SURGE DIVERTERS 150kA Reference code DSD1150 2SR 275 Part No. Description 702420 150kA, 275V 1 Part No. Description 702460 702466 702478 702480 702510 702436 702491 702521 702496 702530 702506 702560 702566 60kA, 275V, Relay 60kA, 275V Module 40kA, 75V 40kA, 150V 40kA, 150V, Relay 40kA, 150V Module 40kA, 275V 40kA, 275V, Relay 40kA, 275V Module 40kA, 440V, Relay 40kA, 440V Module 10kA, 275V 10kA, 275V Module Unit weight kg 0.12 0.10 0.12 0.12 0.12 0.10 0.12 0.12 0.10 0.12 0.10 0.12 0.10 1 1 1 1 1 1 1 1 1 1 1 1 1 Part No. Description 700465 700475 35A 63A 1 1 Unit weight kg 0.5 1.0 1 Unit weight kg 0.2 DINLINE SURGE COUNTER DINLINE SURGE DIVERTERS 100-10kA Reference code DSD160 1SR 275 DSD160 M 275 DSD140 1S 75 DSD140 1S 150 DSD140 1SR 150 DSD140 M 150 DSD140 1S 275 DSD140 1SR 275 DSD140 M 275 DSD140 1SR 440 DSD140 M 440 DSD110 1S 275 DSD110 M 275 Reference code DDI35 DDI63 Unit weight kg 0.33 Reference code TDS SC Part No. Description 701250 TRANSIENT DISCRIMINATING FILTER (TDF) Reference code TDF3A120V TDF3A240V TDF10A120V TDF10A240V TDF20A120V TDF20A240V DINLINE SURGE DIVERTERS THREE PHASE Part No. Description 700001 700002 700003 700004 700005 700006 3A, 120V 3A, 240V 10A, 120V 10A, 240V 20A, 120V 20A, 240V 1 1 1 1 1 1 Unit weight kg 0.35 0.35 0.75 0.75 0.8 0.8 1 1 1 Unit weight kg 0,200 0,200 0,200 Reference code DSD340 TNC 275 A DSD340 TNS 275 A DSD340 TT 275 A Part No. 702581 702591 702601 Description 40kA, 275V TN-C, Modular 40kA, 275V TN-S, Modular 40kA, 275V TT, Modular 1 1 1 Unit weight kg 0.4 0.4 0.4 Reference code DSF6A 30V DSF6A 150V DSF6A 275V DINLINE SPARK GAP DIVERTER (SGD) Part No. Description 702090 701000 701030 6A, 30V 6A, 150V 6A, 275V REMOTE TRANSMITTER PROTECTOR (RTP) Reference code SGD1100 2S NE SGD112 1S NE www.erico.com Part No. Description 702400 702402 100kA 10/350 12kA 10/350 1 1 Unit weight kg 0.3 0.12 Reference code RTP 30 34 43 Part No. Description 700865 30V, 145mA 3/4” NPT SS pipe 1 Unit weight kg 0,340 SURGE PROTECTION DINLINE SURGE FILTER (DSF) CRITEC® SURGE PROTECTION TELECOMMUNICATION PROTECTORS (SLP/DLP/DLT) UNIVERSAL TRANSIENT BARRIER (UTB) Reference code UTB5 UTB15 UTB15EX UTB30 UTB30EX UTB60 UTB110 UTBSA Part No. Description 702800 702810 702811 702820 702821 702830 702840 702860 5V, 1.5A 15V, 1.5A 15V, EX approved 30V, 1.5A 30V, EX approved 60V, 1.5A 110Vac, 1.5A Analog Telephone Unit weight kg 0,100 0,100 0,100 0,100 0,100 0,100 0,100 0,100 1 1 1 1 1 1 1 1 Reference code SLP10K1F HSP10K12 HSP10K36 HSP10K72 HSP10K230 DLT Part No. Description 701540 700815 700805 700850 700860 702721 12V, high speed 36V, high speed 72V, high speed 230V, high speed 2.5mm2 terminal block Unit weight kg 0,100 0,100 0,100 0,100 0,100 0,150 1 1 1 1 1 1 COAXIAL PROTECTORS - TV AND VIDEO DATA EQUIPMENT PROTECTORS (DEP) Reference code DEP RS232 25 25 DEP RS232 9 9 DEP RS422 9 9 Part No. Description 700630 700640 700650 25 wire, 15V 9 wire, 15V 9 wire, 9V 1 1 1 Reference code CATV F CATV MF CCTV 12 Unit weight kg 0,050 0,050 0,050 Part No. Description 702535 702525 703000 Cable TV Protector Antenna TV Protector CCTV protector (video) Unit weight kg 0,100 0,100 0,200 1 1 1 COAXIAL SURGE PROTECTORS (CSP) DINLINE DC PROTECTORS SURGE PROTECTION 702750 Reference code DSD120 1S 12 DSD120 1S 24 DSD140 2BR 24/48 Part No. Description 702670 702680 702750 12V, 10kA 24V, 10kA 24-48V, 40kA 1 1 1 Reference code CSP BNC 90 CSP BNC 600 CSP NMF 90 CSP NMF 600 CSP NB 90 CSP NB 600 Unit weight kg 0,100 0,100 0,150 LOCAL AREA NETWORK PROTECTORS (LAN) Reference code LAN RJ45 1 LAN RJ45 24 Part No. Description 700526 700527 1 x RJ45 circuit 24 x RJ45 circuits 1 1 Unit weight kg 0,100 Description 700360 700405 700310 700355 700410 700455 BNC, 90V BNC, 600V NMF, 90V NMF, 600V NB, 90V NB, 600V 1 1 1 1 1 1 Unit weight kg 0,200 0,200 0,200 0,200 0,200 0,200 LOADCELL PROTECTORS (LCP) Reference code LCO01A 44 Part No. Part No. 701610 1 Unit weight kg 0,274 www.erico.com CADWELD® / CADWELD® PLUS / CADWELD® MULTI XA PC BY LE PG PA THE CADWELD® MOULD NUMBERING SYSTEM BD TA XXX-XXXX Mould type Mould Price Key EXAMPLES : www.erico.com Code for Main or Run Conductor Code for Tap Conductor TA C - Y6 Y4 GT C - P143 Y6 SS C - Y4 VS C - Y2 - V76 • • • • • Type GT • Price Key C • 14,2 mm Copper Clad Ground Rod • 120 mm2 Tap • Type SS • Price Key C • 2 x 70 mm2 cables • • • • • Type TA Price Key C 120 mm2 Run 70 mm2 Tap 45 Type VS Price Key C Cable 35 mm2 Vertical Pipe 76 mm Diameter Pipe CADWELD The CADWELD Mould Part Number code gives the complete information of the mould ie: - type of connection, mould price key, and conductor size(s). ® CADWELD PLUS CADWELD PLUS connections offer all the benefits of conventional CADWELD® connections: ® W NE • Withstand repeated fault currents without failing during operation • Exceed requirements of “IEEE® Std 837- Std. for Qualifying Permanent Connections Used In Substation Grounding” • Join copper to copper, copper to galvanized or plain steel, copper to copper clad steel, copper to bronze/ brass/stainless steel, steel to steel, etc. • Current carrying capacity equal to or greater than that of the conductor • Permanent, molecular bond that will not loosen or corrode, resulting in a connection with a lifetime equal to that of the installation The ultimate welded connection that will never loosen, corrode or increase in resistance just got BETTER. CADWELD PLUS is the latest advancement in the continuing evolution of ERICO’s exothermic products. Since it’s development in 1938, CADWELD electrical connections have become recognized as the ultimate connection for rail, cathodic, power and grounding applications. ERICO® has established itself as the worldwide connections leader. CADWELD PLUS continues this tradition of technical leadership. The revolutionary CADWELD PLUS System is a simplified method of performing exothermically welded electrical connections. The CADWELD PLUS integrated welding material package has streamlined the installation process by eliminating ignition materials – reducing set up time. The tamper proof, integrated welding material package consists of a steel cup containing CADWELD patented welding material alloys and ignition source. This new welding material package is designed for use in all standard CADWELD moulds including CADWELD® MULTI. Once placed in the CADWELD mould, the welding material is electronically ignited using a simple battery-powered control unit with six (6) foot lead. • No external power or heat source required • Quality Assurance Inspection is easy and visual • Minimal installation training required Polymeric Cover CADWELD PLUS Package • Consists of a tamper proof, disposable, moisture-resistant welding material cup. The welding material, disk and ignition source are incorporated into the self-contained package • Virtually unlimited shelf life Ignitor Strip Graphite Mould Tap Hole Conductor • Completes welds at distances of up to 6 ft/1.8 meters (up to 15 ft/4.6 meters with optional lead) Weld Cavity • Requires minimum components – no starting material, no disks, no flint igniters • Easy to handle, store and transport – by air, land or sea in unlimited quantities CADWELD® PLUS • Reduces installation time by 20% • Has colour-coded welding material containers – by size and alloy type – for easy identification CADWELD • Has electronic ignition with a CE/UL® battery powered controller box that is designed for 600 connections with one set of 8 standard AA batteries (included) – requiring no special batteries or chargers • Designed for use in standard CADWELD® moulds including CADWELD® MULTI Feature Benefits Integrated Welding Material Package • Simplifies training and set up • Saves labour • Simplifies cleaning Colour Coded Welding Material • Reduces risk of misapplication • Simple visual verification of correct welding material size Electronic Control Unit • No starting material required • Easy ignition Six Foot Control Unit Lead • Increased flexibility in hard to reach areas 46 www.erico.com ® CADWELD PLUS Installation Is Easy! W NE 4 Simple Steps For Permanently Welded Electrical Connections 2 1 Insert CADWELD® PLUS package into mould Attach control unit termination clip to ignition strip CADWELD PLUS for Grounding Applications CADWELD PLUS Reference Code Part No. Size Identification Ring Color Traditional Welding Material Part Number (Clear Cap) 15PLUSF20 25PLUSF20 32PLUSF20 45PLUSF20 65PLUSF20 90PLUSF20 115PLUSF20 150PLUSF20 200PLUSF20 250PLUSF20 300PLUSF20 400PLUSF20 500PLUSF20 165700 Black Red White Light Blue Dark Green Gray Orange Dark Blue Yellow Purple Light Green Brown Light Brown 15 25 32 45 65 90 115 150 200 250 use 2 x 150 use 2 x 200 500 165701 165702 165703 165704 165705 165706 165707 165708 165709 165710 165711 165712 3 4 Press and hold control unit switch and wait for the ignition Open the mould and remove the expended steel cup – no special disposal required CADWELD PLUS for Cathodic Applications CADWELD PLUS Reference Code Part No. Size Identification Ring Color Traditional Welding Material Part Number (Green Cap) CA15PLUSF33 CA25PLUSF33 CA32PLUSF33 CA45PLUSF33 CA65PLUSF33 165713 165714 165715 165716 165717 Black Red White Light Blue Dark Green CA15/CA15S CA25 CA32 CA45 CA65 CADWELD PLUS Reference Code Part No. Size Identification Ring Color Traditional Welding Material Part Number (Orange Cap) CA25PLUSXF19 CA32PLUSXF19 CA45PLUSXF19 CA65PLUSXF19 165722 165723 165724 165725 Red White Light Blue Dark Green CA25XF19 CA32XF19 CA45XF19 CA65XF19 CADWELD PLUS for Cast Iron Applications Part No. 25PLUSXF19 32PLUSXF19 45PLUSXF19 65PLUSXF19 165718 165719 165720 165721 Traditional Welding Size Identification Material Part Number (Orange Cap) Ring Color Red White Light Blue Dark Green Gram weight PLUS welding material type i.e. 45PLUSF20 25XF19 32XF19 45XF19 65XF19 Accessories Reference Code Part No. PLUSCU Baffle Cover Kit CADWELD PLUS Patent Numbers PLUSCULD 6,553,911 6,835,910 6,703,578 CADWELD PLUS Control Unit initiates the reaction of the metal crucible. The standard unit includes a 6-foot (1.8 meter) high temperature control unit lead. The lead attaches to the ignition strip using a custom made, purpose-designed termination clip. www.erico.com PLUSCU PLUSCU15L PLUSCULD PLUSCULD15 MC2X2KIT MC25X3KIT MC3X3KIT MC4X4KIT 165738 165745 165739 165746 165740 165744 165741 165742 Description CADWELD PLUS Control Unit CADWELD PLUS Control Unit with 15 ft. (4.6 meters) Lead CONTROL UNIT Replacement Lead 6 ft. (1.8 meters) CONTROL UNIT Replacement Lead 15 ft. (4.6 meters) Kit, Baffle Cover, Graphite - 2” X 2” Mould Kit, Baffle Cover, Graphite - 21⁄2” X 3” Mould Kit, Baffle Cover, Graphite - 3” X 3” Mould Kit, Baffle Cover, Graphite - 4” X 4” Mould After the termination clip is installed on the ignition strip, the installer pushes and holds the ignition button to start a charging and discharging sequence. Within a few seconds the control unit sends a predetermined voltage to the ignition strip and the reaction is initiated. 47 CADWELD CADWELD PLUS Reference Code ® ® CADWELD AND CADWELD PLUS Traditional CADWELD® & CADWELD® PLUS Welding Material W NE Welding Material Size Traditional CADWELD Reference code Part No. CADWELD PLUS Unit Weight kg Disk Type* Reference code Part No. Unit Weight kg 15PLUSF20 25PLUSF20 32PLUSF20 45PLUSF20 65PLUSF20 90PLUSF20 115PLUSF20 150PLUSF20 200PLUSF20 250PLUSF20 300PLUSF20 400PLUSF20 500PLUSF20 165700 165701 165702 165703 165704 165705 165706 165707 165708 165709 165710 165711 165712 20 20 20 20 20 10 10 10 10 10 10 10 10 0,049 0,063 0,065 0,086 0,104 0,158 0,185 0,217 0,267 0,353 0,376 0,480 0,585 F20 Alloy - Clear Cap - Copper/Copper - Copper/Steel - Steel/Steel 15 25 32 45 65 90 115 150 200 250 300 400 500 15 25 32 45 65 90 115 150 200 250 use (2) 150 use (2) 200 500 163590 163000 163010 163020 163030 163040 163050 163060 163070 163080 20 20 20 20 20 10 10 10 10 10 0,015 0,025 0,032 0,045 0,065 0,090 0,115 0,150 0,200 0,250 19 19 19 19 19 25 25 38 38 38 163090 10 0,500 38 20 20 20 20 20 10 10 10 0,015 0,025 0,032 0,045 0,065 0,090 0,115 0,150 19 19 19 19 19 25 25 38 CA15PLUSF33 CA25PLUSF33 CA32PLUSF33 CA45PLUSF33 CA65PLUSF33 165713 165714 165715 165716 165717 20 20 20 20 20 0,049 0,063 0,065 0,086 0,104 20 20 20 20 10 10 0,025 0,032 0,045 0,065 0,090 0,115 19 19 19 19 25 25 25PLUSXF19 32PLUSXF19 45PLUSXF19 65PLUSXF19 165718 165719 165720 165721 20 20 20 20 0,063 0,065 0,086 0,104 CA25PLUSXF19 CA32PLUSXF19 CA45PLUSXF19 CA65PLUSXF19 165722 165722 165722 165722 20 20 20 20 0,063 0,065 0,086 0,104 F33 Alloy - Green Cap - Cathodic protection - Steel pipe 15 25 32 45 65 90 115 150 CA15 CA25 CA32 CA45 CA65 CA90 CA115 CA150 163200 163210 163220 163230 163240 163250 163260 163270 XF19 Alloy - Orange Cap - Cast Iron application 25 32 45 65 90 115 25XF19 32XF19 45XF19 65XF19 90XF19 115XF19 163280 163290 163300 163310 163320 163330 CADWELD XF19 Alloy - Orange Cap - Cathodic protection - Cast Iron pipe *Disk Type: Welding Material Disk Type size (Diameter - mm) Welding material disks are supplied with “Traditional CADWELD” 15-65 19 welding material. However, spare disks can be ordered as follows: 90-115 150-500 48 25 38 Reference Code Part No. DISC PACK21/19 DISC PACK11/25 DISC PACK11/38 141154 141156 141157 www.erico.com ® CADWELD MULTI CADWELD® MULTI Connection Capabilities Copper Cable/Solid to Copper Cable/Solid steps for multiple, permanently welded, electrical connections 4 Easy Unit batting and variable Step Step Layer conductor sizes to be 2 1 welded into dry mold • Copper cable/solid sizes up to 1/0 (50 mm2) stranded or .40” (10 mm) diameter Close mold and drop metal disk in place • Copper cable/solid sizes up to #3 (25 mm2) stranded or .26” (6,5 mm) diameter Copper Cable/Solid/Strip to Rebar welding material Step Deposit and tap bottom of 3 container to release • Copper conductor sizes up to 1/0 (50 mm2) stranded or .40” (10 mm) diameter • Copper or steel strip/lug sizes up to 1” x .138” (30 x 3,5 mm) • Rebar sizes up to #3 (10 mm) the cover and ignite Step Close with flint ignitor. Open 4 the mold after 10 seconds starting material Copper Cable/Solid to Copper or Steel Strip/Lug • Copper conductor sizes up to 1/0 (50 mm2) stranded or .40” (10 mm) diameter • Copper or steel strip/lug sizes up to 1” x .138” (30 x 3,5 mm) Copper Strip to Copper Strip The CADWELD MULTI combines a versatile mold block and a range of gaskets (batting) to allow numerous different welded connections to be produced without the need to change the mold for each connection type. The process is similar to the traditional CADWELD with one distinct difference... there is no need to change the mold for different connection types. The whole process is complete in about one minute. The connection table details the gasket quantities required for each weld. Galvanized Steel Strip to Galvanized Steel Strip • Galvanized steel strip sizes up to 1” x .138” (30 x 3,5 mm) * in KITCDM01 = Traditional CADWELD MULTI Kit ** in KITCDM01PLUS = CADWELD PLUS MULTI Kit www.erico.com CADWELD MULTI Available Items Description Reference Code Part No. Kit for 20 welds, in metallic box KITCDM01 167780 14” x 13” x 6” (360 x 330 x 160 mm) Kit for 20 welds using CADWELD PLUS, KITCDM01 167781 in metallic box (Control Unit sold separately) PLUS 14” x 13” x 11” (360 x 330 x 280 mm) Made from the following items which can be ordered separately: Mould Handle Clamp Set of 33 battings/gaskets Welding material 90* CADWELD PLUS Welding Material** Toolset TS-6A, including: • gloves • cardcloth brush • soft brush • flint ignitor 49 CDM01 FMCDM01 SCDM01 90 90PLUSF20 TS6A 234720 120882 120886 163040 165705 169930 1 Unit Weight (kg) 10.00 1 11.50 1 1 1 10 10 1 1.000 1.100 0.200 0.090 0.158 0.490 Qty. in Kit 1 1 2 2 boxes of 10 2 boxes of 10 1 CADWELD • BB and CG 1” x (.020” - .118”), (30 x 3,5 mm) • BG and EB 1” x (.020” - .079”), (30 x 3 mm) CADWELD Mould A B SS A B TA A B XA A B PG A B PT PC LJ LW A HA A LE VG VS A CADWELD Reference code SSC-W6 SSC-W8 SSC-Y1 SSC-Y2 SSC-Y3 SSC-Y4 SSC-Y5 SSC-Y6 TAC-Y1 TAC-Y2 TAC-Y2-Y1 TAC-Y3 TAC-Y4 TAC-Y4-Y2 TAC-Y5 TAC-Y5-Y6 TAC-Y6 TAC-Y6-Y4 TAC-Y7 TAC-Y8 XAC-Y1 XAC-Y2 XAC-Y3 XAC-Y4 XAC-Y5 XAC-Y6 PGC-Y1 PGC-Y2 PGC-Y3 PGC-Y4 PGC-Y4-Y1 PGC-Y5 PGC-Y6 PTC-Y1 PTC-Y2 PTC-Y3 PTC-Y4 PTC-Y5 PTC-Y6 PCC-Y1 PCC-Y3 PCC-Y6 LJP-Y1-BAK LJP-Y2-BAK LJP-Y3-BAK LJC-Y3-FAM LWP-Y3-BAK HAA-Y1 HAA-Y1-CA HAA-Y2 HAA-A3 HAA-Y3 HAA-Y4 HAA-B3-CA HBA-B3 LEP-Y3-BAK Part No. 221008 221011 221004 221006 221009 221021 221013 221014 221025 221028 221063 222459 221035 221075 222461 225026 222463 221094 221051 221053 221135 221138 221142 221148 221153 221159 237901 232556 232648 231342 236084 223943 231692 221268 226545 221265 221258 221256 222115 223550 222560 230199 234737 234738 234739 232933 234782 221609 221466 221607 222689 221603 221534 240228 223044 234759 Diameter Amm Bmm 8,0 8,0 10,0 10,0 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 7,6 6,4 9,0 9,0 11,0 11,0 11,0 7,6 12,5 12,5 12,5 14,2 14,2 14,2 14,2 11,0 15,9 15,9 17,7 17,7 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 11,0 6,4 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 9,0 9,0 14,2 14,2 6,4 7,6 9,0 9,0 9,0 6,4 6,4 7,6 8,0 9,0 11,0 4,9 4,9 9,0 Section Bmm2 Amm2 50 50 78,5 78,5 25 25 35 35 50 50 70 70 95 95 120 120 25 25 35 35 35 25 50 50 70 70 70 35 95 95 95 120 120 120 120 70 150 150 185 185 25 25 35 35 50 50 70 70 95 95 120 120 25 25 35 35 50 50 70 70 70 25 95 95 120 120 25 25 35 35 50 50 70 70 95 95 120 120 25 25 50 50 120 120 25 60 35 60 50 60 50 250 50 60 25 25 35 40 50 70 14,5-16 14,5-16 50 60 Sizes mm 30x2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Unit weight kg 1,37 1,37 1,37 1,37 1,37 1,37 1,75 1,75 1,37 1,37 1,37 1,37 1,37 1,37 1,37 1,37 1,57 1,57 1,57 1,57 1,37 1,37 1,37 1,37 1,57 1,75 1,37 1,37 1,37 1,37 1,37 1,57 1,57 1,75 1,75 1,75 1,75 1,97 1,97 1,37 1,75 1,97 0,70 0,70 0,70 1,37 0,70 0,31 0,31 0,31 0,31 0,31 0,45 0,19 0,31 0,60 30x2 25x3 25x3,5 25x3/30x2 30x2 30x2 25x3 25x3,5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1,37 1,37 1,75 1,75 1,97 1,97 1,57 1,57 1,57 1,57 0,87 0,87 0,87 0,60 0,87 0,85 0,58 0,58 30x2 30x2 30x2 50x5 30x2 Remarks Solid core cable horizontal splice Multi -strand cable to cable splice Horizontal + cable to cable connection Horizontal X cable to cable connection, one cable cut Parallel horizontal conductors cable to cable Parallel vertical conductors cable to cable Cable to cable Cable to tape Horizontal round or cable conductor to flat steel surface or top of horizontal pipe Sleeve : H105 Tape to cable B A B BM A EB ® B VGC-Y1 VGC-Y2 VGC-Y3 VGC-Y4 VGC-Y5 VGC-Y6 VSC-Y3 VSC-Y4 VSC-Y5 VSC-Y6 BMP-BAK BMP-CAJ G-BMP-DAJ BMP-CAJ-BAK EBP-BAK EB-BGP-BAK EBP-CAJ G-EBP-DAJ 228521 224815 222939 228347 223076 223609 221407 221405 221404 221403 234429 234426 224123 234736 225788 234398 234991 223432 6,4 7,6 9,0 11,0 12,5 14,2 9,0 11,0 12,5 14,2 25 35 50 70 95 120 50 70 95 120 60 75 87,5 75 60 60 75 87,5 60 75 87,5 60 60 60 75 87,5 50 Cable through connections on vertical flat steel surface Cable to vertical steel surface Tape to tape Tape to tape www.erico.com ® Weld metal size required 45 65 32 32 45 65 90 115 32 45 45 90 90 45 115 150 150 90 200 200 45 65 90 115 150 200 45 65 90 115 90 150 200 45 65 90 115 200 250 45 90 200 65 65 90 90 90 45 32F33 45 45 45 65 15F33 25 65 Frame Page 53 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-161 L-161 L-161 L-160 L-161 M-129 M-129 M-129 M-129 M-129 M-129 M-129 M-129 L-161 Toolset Page 55 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST Scraper tools Page 55 TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-7A TP-7A TP-3B TP-3B TP-3B TP-7A TP-7A TP-3B TP-7A TP-2A TP-2A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-3B TP-7A TP-2A TP-5B TP-5B TP-5B TP-7A TP-5B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-5B 45 45 115 115 150 150 90 90 115 115 65 65 65 90 90 90 65 65 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-161 L-161 L-161 L-161 L-161 L-161 L-161 L-161 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-7A TP-7A TP-7A TP-7A TP-5B TP-5B TP-5B TP-2A TP-5B TP-5B TP-5B TP-5B www.erico.com CADWELD® PLUS Control Units PLUSCU Reference code Part No. PLUSCU PLUSCU15L PLUSCULD PLUSCULD15 165738 165745 165739 165746 Description Control Unit with 1,80 m lead Control Unit with 4,60 m lead Replacement Lead 1,80 m long Replacement Lead 4,60 m long 1 1 1 1 Unit weight kg 0,907 1,088 0,146 0,306 FLINT IGNITOR T320 AND SPARE FLINTS T320A T320 Reference code Part No. T320 T320A 165000 165010 1 10 Unit weight kg 0,090 0,015 BRUSHES T314A T314 KIT-120-3/4 T313 Reference code Part No. T313 T314 T314A KIT-120-3/4 165040 165130 165270 165260 1 1 1 1 Unit weight kg 0,070 0,375 0,070 0,040 BAFFLE MOULD COVER 51 Reference code Part No. MC2X2KIT MC2.5X3KIT MC3X3KIT MC4X4KIT 165740 165744 165741 165742 1 1 1 1 Unit weight kg 0,113 0,113 0,227 0,227 CADWELD CADWELD CADWELD ® Reference code CHP-BAK Mould Part No. Diameter Amm Bmm Section Bmm2 Sizes mm 30x2 1 Unit weight kg 0,70 Lug or tape to horizontal surface Remarks 234733 Amm2 60 CGP-BAK 234732 60 30x2 1 0,70 Lug or tape to horizontal surface CCP-BAK 234734 60 30x2 1 0,70 Lug or tape to vertical surface CFP-BAK CFP-CAJ G-CFP-DAJ BWP-BAK 232003 233366 225147 239887 60 75 87,5 60 30x2 25x3 25x3,5 30x2 1 1 1 1 0,52 0,70 0,70 0,90 Lug or tape to vertical surface Lug or tape to vertical surface B GRC-P172-Y3 B-GRC-P143-Y3 226567 238039 17,2 14,2 9,0 9,0 232,4 160,6 50 50 1 1 1,75 1,75 Single stranded cable to top of ground rod 14,2 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2 17,2 19 14,2 17,2 12,8 14,2 12,8 14,2 160,6 160,6 160,6 160,6 160,6 232,4 232,4 232,4 232,4 232,4 283,5 160,6 232,4 128,7 158 25 35 50 70 95 25 35 50 70 95 66,5 60 60 128,7 158 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1,75 1,75 1,75 1,57 1,57 1,75 1,75 1,57 1,57 1,57 1,57 0,70 0,68 1,75 1,97 Single stranded cable to top of ground rod B 233901 229737 225814 232996 223520 228682 226670 226083 227687 227549 223138 234735 239694 232537 237727 6,4 7,6 9,0 11,0 12,5 6,4 7,6 9,0 11,0 12,5 10,7 A GE GTC-P143-Y1 GTC-P143-Y2 GTC-P143-Y3 GTC-P143-Y4 GTC-P143-Y5 GTC-P172-Y1 GTC-P172-Y2 GTC-P172-Y3 GTC-P172-Y4 GTC-P172-Y5 GTC-P190-2G CPP-P143-BAK CPP-P172-BAK GEC-P128 GEC-P143 A GF B GFC-P143-Y3 GFC-P165-G2-B 238544 238556 14,2 16,5 9,0 9,5 160,6 214 50 50 1 1 1,75 1,75 Horizontal stranded cable to ground or other rod splice LAC-Y1-BAH LAC-Y1-CAJ LAC-Y2-BAH LAC-Y2-CAJ LAZ-Y3-BAK LAC-Y3-BAH LAC-Y3-BAJ LAC-Y3-CAJ LAC-L9-EAK-A BJC-BAK-CROW 224800 222501 224150 221443 234740 239534 222122 221455 233795 234770 6,4 6,4 7,6 7,6 9,0 9,0 9,0 9,0 10,0 25 25 35 35 50 50 50 50 60 60 40 75 40 75 60 40 50 75 120 60 20x2 25x3 20x2 25x3 30x2 20x2 25x2 25x3 30x4 30x2 1 1 1 1 1 1 1 1 1 1 1,37 1,37 1,37 1,37 0,70 1,37 1,37 1,37 1,75 2,20 Stranded cable to lug or tape BYC-BAK-CROW 234760 60 60 30x2 1 1,60 Crowsfoot with flat tape RCP-Y1 RCP-Y2 RCP-Y3 RCP-Y4 RCP-Y5 RCP-Y6 RTP-Y1 RTP-Y2 RTP-Y3 RTP-Y4 RTP-Y5 RTP-Y6 234581 234585 234582 234588 234592 234593 234441 234444 234445 234447 234453 234454 S-2904B S-2904B S-2904B S-2904B S-2904B S-2904C S-2904B S-2904B S-2904B S-2904B S-2904A S-3121 Batting 25 35 50 70 95 120 25 35 50 70 95 120 1 1 1 1 1 1 1 1 1 1 1 1 0,68 0,68 0,68 0,68 0,68 0,68 0,62 0,62 0,62 0,62 0,62 0,62 Single stranded cable to rebar CH CG CC A CF BW GR A B A GT B CP A A B LA 30x2 30x2 Tape to ground rod Horizontal ground round to ground rod splice Crowsfoot with edgewise tape CROWS FOOT edgewise CROWS FOOT horizontal B RC B 6,4 7,6 9 11 12,5 14,2 6,4 7,6 9 11 12,5 14,2 Single stranded cable to rebar CADWELD A RT A 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 52 www.erico.com Weld metal size required 90 Frame Page 53 L-161 ® Toolset Page 55 TS CST Scraper tools Page 55 TP-5B FRAMES L160 90 L-161 TS CST TP-5B 90 L-161 TS CST TP-5B 65 65 65 65 L-161 L-161 L-161 L-161 TS CST TS CST TS CST TS CST TP-5B TP-5B TP-5B TP-5B 90 115 L-160 L-160 TS CST TS CST TP-7A TP-7A 90 90 90 115 115 90 90 115 115 115 115 90 115 150 150 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-161 L-161 L-160 L-160 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-7A TP-5B TP-3B TP-7A TP-2A 90 115 L-160 L-160 TS CST TS CST TP-7A TP-7A 32 45 32 45 90 45 45 65 90 115 L-160 L-160 L-160 L-160 L-161 L-160 L-160 L-160 L-160 L-160 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TP-3B TP-3B TP-3B TP-3B TP-5B TP-3B TP-3B TP-3B TP-7A TP-2A 200 L-160 TS CST TP-2A 45 45 65 90 90 90 45 45 90 90 90 115 L-161A L-161A L-161A L-161A L-161A L-161A SMK 21 SMK 21 SMK 21 SMK 21 SMK 21 SMK 21 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B TP-5B 161000 161740 Clamp for frame L160 161020 L159 B135 161780 Clamp for frame L159 161010 L161 L160V 161660 L161A 161090 SMK21 161080 SKK1 162070 Chain support clamp for C & R moulds M129 161030 M32 161060 Clamp for frame L160 Reference code L160 L159 L161 B134 B135 L161A L160V M129 M32 SMK21 SKK1 www.erico.com B134 53 Part No. 161000 161020 161010 161740 161780 161090 161660 161030 161060 161080 162070 1 1 1 1 1 1 1 1 1 1 1 Unit weight kg 1,185 1,325 0,380 0,360 0,414 1,010 1,775 0,315 0,880 0,670 0,500 CADWELD CADWELD CADWELD ® RASP BATTING FOR P MOULD 185030 - 185020 - 185010 Used with CADWELD® “P” moulds Reference code Part No. T321C (complete) T321 (holder) T321A (blade) 162630 162420 162430 1 1 1 Unit weight kg 0,740 0,455 0,285 Reference code S2904C S2904B S2904A CABLE CLAMP B265 Sizes mm 50x60x12 50x60x20 50x60x25 Part No. 185030 185020 185010 25 25 25 Unit weight kg 0,005 0,008 0,009 COPPER SLEEVES Reference code Part No. B265 165020 1 Unit weight kg 0,348 Available on Request C B A CADWELD MOULD SEALER Reference code T403 1 Unit weight kg 0,910 1 1 Unit weight kg 0,260 0,100 Part No. 165280 Reference code H101 H102 H103 H104 H105 H107 H108 H109 H113 H115 H117 Part No. 180140 180170 180180 180190 180230 180690 180010 180020 180350 180700 180430 A mm 8 6,4 7,7 19 5 11 20 14 10 6,35 9 B mm 6 4,3 5,3 17 3 9 18 12 8 4,83 7 C mm 26 25 25 26 23,5 26 26 26 26 25 25 50 50 50 50 50 50 50 50 50 50 50 Unit weight kg 0,005 0,004 0,006 0,013 0,003 0,008 0,014 0,010 0,007 0,003 0,006 BLOWLAMP SOUDO 360 AND VALVED CARTRIDGE CADWELD 11200327 11200300 Reference code Part No. 11200327 11200330 140160 140180 54 www.erico.com CADWELD ® SLEEVES TOOL BOXES Length + flair B T322 Available on Request A Plywood Box 400 x 190 x 190 mm 300 x 155 x 500 mm C Reference code H101F H102F H103F H104F H106F H107F H108F H109F H111F H112F H113F H114F H116F H117F H104BF H106AF H109AF H111AF H113AF Part No. 180150 180390 180380 180200 180250 180270 180280 180300 180320 180340 180360 180040 180740 180080 180220 180260 180310 180330 180030 A mm 8 6,4 7,7 19 17 11 20 14 15 12 10 25 13 9 19 17 14 15 10 B C mm mm 6 25 4,3 25 5,3 25 17 25 15 25 9 25 18 25 12 25 13 25 10 25 8 25 21 25 11,5 25 7 25 17 34 15 34 12 34 13 34 8 34 Length + flair 26 26 26 26 26 26 26 26 26 26 26 26 26 26 35 35 35 35 35 Unit weight kg 0,005 0,004 0,006 0,013 0,009 0,008 0,014 0,010 0,011 0,008 0,007 0,032 0,007 0,006 0,018 0,012 0,013 0,014 0,009 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 TP2A TP4A TP5A TP6A TP7A TP3B TP5B B136A B136B B136F 182030 182040 182010 182050 182020 182060 182070 182125 182130 182135 Equivalent Ref. Code B136B B136F B136A B136A B136B B136A B136A T322 Plywood box 165110 4572 1 1 Unit weight kg 2,540 3,995 25 Unit weight kg 0,001 1 Unit weight kg 0,450 WRAP SLEEVE Reference code Part No. B140 165610 Dimensions mm 76x25x0,20 Equivalent Part No. 182130 182135 182125 182125 182130 182125 182125 1 1 1 1 1 1 1 1 1 1 Unit weight kg 0,144 0,172 0,116 0,126 0,132 0,045 0,060 0,045 0,077 0,080 Reference code Part No. TS-CST 197290 CADWELD Part No. Part No. TOOLSET SCRAPER TOOLS Reference code Reference code www.erico.com 55 ® CADWELD KITS CADWELD® MULTI Kit and CADWELD® PLUS MULTI Kit Description GROUND NETWORK KITS FOR RAISED ACCESS FLOORS Reference Part No. Code Unit Weight (kg) Kit for 20 welds, in metallic box KITCDM01 167780 14” x 13” x 6” (360 x 330 x 160 mm) 1 10.00 Kit for 20 welds using CADWELD PLUS KITCDM01 167781 in metallic box (Control Unit sold separately) PLUS 14” x 13” x 11” (360 x 330 x 280 mm) Made from the following items which can be ordered separately: Qty. in Kit 1 11.50 Mould Handle Clamp CDM01 234720 FMCDM01 120882 1 1 1.000 1.100 Set of 33 battings/gaskets Welding Material 90* CADWELD PLUS Welding Material** Toolset TS-6A, including: • gloves • cardcloth brush • soft brush • flint ignitor SCDM01 90 90PLUSF20 TS6A 120886 2 1 163040 2 boxes of 10 10 165705 2 boxes of 10 10 169930 1 1 0.200 0.090 0.158 0.490 1 1 546330 + 546340 546330 546330 + 546320 Reference Part No. Description code • • • Connections on lifting jack feet BK-CCR-2 546330 Basic kit, 200 welds 1 RK-CCR-2 546300 Consumable item, kit 200 welds 1 • • • Additional connections (for braid 5 to 16 mm2 and tape 30 x2) BB-CCR 546320 Braid/braid accessory 1 BF-CCR 546340 Braid/tape accessory 1 Unit weight kg 6,000 3,000 0,200 0,100 CATHODIC PROTECTION KITS * in KITCDM01 = Traditional CADWELD MULTI Kit ** in KITCDM01PLUS = CADWELD PLUS MULTI Kit CADWELD® KITS GT RT CADWELD DIRECT 1 10 mm Reference Cable cross Part No. code section mm2 • • • Basic CADWELD kit 20 welds KIT CPD 2,5/16 167260 2,5 to 16 KIT CPD-25 167280* 25 KIT CPD-35 167300* 35 • • • Consumable item CADWELD kit 20 welds CPD 2,5/16 PACK 167270 2,5 to 16 CPD-25 PACK 167290* 25 CPD-35 PACK 167310* 35 *Available upon request. 35 mm2 RC Reference code GY Part No. GY LA Welds Figure per kit A 15 mm Unit weight kg CADWELD • • • Compact kit (20 welds) GT-P128 169310 PG-25/29 168050 PG-35 168060 VG-25/29 168090 VG-35 168100 GY-35 168180 GY-50 168190 • • • Maxi kit (60 welds) PG-25/29-Z 168380 PG-35-Z 168390 PG-50-Z 168400 PG-70-Z 168410 VG25/29-Z 168440 VG35-Z 168450 VG50-Z 168460 VG70-Z 168470 RT-25-Z-10 169990 RT-35-Z-10 168830 RT-50-Z-10 168850 RC-35-Z-10 168890 RC-50-Z-10 168910 GY-35-Z 168630 GY-50-Z 168640 GY-95-Z 168660 LA-Y2-FAK 169600 GYV-35-Z-10 169890 1 2 2 3 3 6 6 20 20 20 20 20 20 20 1 1 1 1 1 1 1 2,110 2,015 2,225 2,265 2,265 2,320 2,600 2 2 2 2 3 3 3 3 4 4 4 5 5 6 6 6 7 8 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6,700 7,450 8,545 8,630 6,525 6,785 7,200 11,00 7,525 7,525 8,695 6 8,225 7,050 7,465 10,560 16,750 6,745 Unit weight kg 1 1 1 5,760 5,700 5,650 1 1 1 1,025 0,925 0,945 CADWELD BRAZE Reference Cable cross Part No. code section mm2 • • • Basic CADWELD kit 20 welds KIT CPB 2,5/16 167200 2,5 to 16 KIT CPB-25 167220* 25 KIT CPB-35 167240* 35 • • • Consumable item CADWELD kit 20 welds CPB 2,5/16 PACK 167210 2,5 to 16 CPB-25 PACK 167230* 25 CPB-35 PACK 167250* 35 *Available upon request. 56 Unit weight kg 1 1 1 6,185 6,095 6,110 1 1 1 1,425 1,320 1,325 www.erico.com INDEX OF PART NUMBERS IN NUMERICAL ORDER Part No. 4572 101100 101230 101240 101250 101260 101265 101700 101900 101910 101920 101925 101930 101940 101950 102000 102010 102350 102400 102410 102450 102455 102460 102500 102600 102610 102620 102700 102800 102850 103100 103450 103470 103480 103700 103710 103720 104200 104300 104350 104450 104600 104950 104980 105300 105400 106030 106060 106080 106200 106300 106310 107000 107010 107020 107050 107060 107070 107230 107500 107550 107560 107600 107610 107650 107660 120882 120886 140160 140180 140250 155000 155010 155030 155050 155060 155070 155090 155110 155180 155190 155210 155230 155240 155250 155270 155290 155300 155310 155330 155350 155420 155430 155450 155470 155480 155490 155510 155530 156340 156350 156360 156370 156380 156390 Reference code Plywood box CPD-2440 CTR-10 CLR-10 CCR-68-S CCR-68-CU CCR-68-GS ASL-240-CC ARC-2205-CNC ARC-2210-CNC ER1-2000 ER1-ARCC-SS ER2-2000 ER3-2000 TFS 800 ARC-2205-SS ARC-2210-SS ASB-TCA ASP-100-TS ASA-TB ABFF-6530-TC PC302GS ABFR-6530-TC ASFR-C ATR-10-SS ACB-10-SS AEM-10-SS CCI-70-CA PCF-40-GS PCR-21-GS ACF-2-GS IP-900-C IP-R193x122MM IP-SQ-180CI SRL23-N6 SRL-23-N8 SRL-23-N10 R1-SRL-25A6 R1-SFT-25 R2-SRL-25 R2-SFT-25 R3SFT-25 R6-SRL-40/6 R6-SFT-40 T1-SRL-25/6 T1-SFT-25 SFR-BC-8 SFT-BE SFT-BC SFRR-SRL-45/6 SFRR-SFT-45 SFRR-SFT-65 SPC-5080-S SPC-70120-S SPC-130180-S SPC-5080-C SPC-70120-C SPC-130180-C SGR-610-2 SDH-3-GI SSF-6-GS SSF-6-C STBF-25-GS STBF-40-GS SFT-23-N SFTP-23-N FMCDM01 SCDM01 11200327 11200330 TC-BR-253 1,2M38 1,5M38 2,1M38 3,0M38 1,2M12 1,5M12 2,1M12 3,0M12 S1,2M916 S1,5M916 S2,1M916 S3,0M916 1,2M58 1,5M58 2,1M58 3,0M58 S1,2M58 S1,5M58 S2,1M58 S3,0M58 1,2M34 1,5M34 2,1M34 3,0M34 S1,2M34 S1,5M34 S2,1M34 S3,0M34 1,0TG16TPWC 1,5TG16TPWC 2,0TG16TPWC 1,0RG16TPWC 1,5G16TPWC 2,0RG16TPWC www.erico.com Page Part No. 55 39 26 26 26 26 26 21 22 22 21 19 21 21 21 22 22 22 22 22 22 24 22 22 22 22 22 25 24 24 22 37 37 37 25 25 25 25 25 25 25 26 25 25 25 25 26 26 26 25 25 25 38 38 38 38 38 38 38 24 37 37 37 37 26 26 49 49 54 54 29 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 35 35 35 35 35 35 156650 156720 156900 156910 158000 158010 158020 158030 158040 158050 158060 158070 158080 158090 158100 158110 158120 158130 158140 158150 158155 158160 158165 158170 158175 158250 158260 158265 158290 158320 158330 158340 158350 158380 158390 158400 158410 158440 158450 158450 158460 158470 158480 158500 158510 158520 158530 158540 158550 158600 158610 158675 158690 158710 158720 158730 158740 158750 158760 158770 158780 158790 158800 158810 158820 158830 161000 161010 161020 161030 161060 161080 161090 161660 161740 161780 162000 162010 162070 162230 162420 162430 162630 163000 163010 163020 163030 163040 163040 163050 163060 163070 163080 163090 163200 163210 163220 163230 163240 163250 163260 163270 163280 163290 163300 Reference code BR12 BZT-12 C19 C20 CC12F CC58 CC34 SC916 SC58 SC34 DT12 DT58 DT34 DS916 DS58 DS34 DH12 DH58 DH34 C38 CP38 C58 CP58 C34 CP34 C1 C12 CP12 PT-58-50/300 C142 C162 C174 C205 DH-TR167 DT-P167-25 DT-P137-1-20 RTC1 S-136-20 MR127Z/20 MR127Z/20 MR137/25 MR187Z/30 DT-P187-30 EGRD58 EGRD58L EGRD34 EGRD34L 15SS20 DT-P11-20-SS PT-12-25/3000 PT-12-25/300 PT-58-25/300 PT-58-35/300 1,0CG50/5 1,5CG50/5 2,0CG50/5 2,5CG50/5 3,0CG50/5 1,0CG50/3 1,5CG50/3 2,0CG50/3 2,5CG50/3 3,0CG50/3 1,5SG20 1,5SG25 1,5SG30 L160 L161 L159 M129 M32 SMK21 L161A L160V B134 B135 S3015 S3054 SKK1 B-162-12KS T321 (holder) T321A (blade) T321C (complete) 25 32 45 65 90 90 115 150 200 250 500 CA15 CA25 CA32 CA45 CA65 CA90 CA115 CA150 25XF19 32XF19 45XF19 Page Part No. 33 33 37 37 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 37 37 37 37 37 37 37 37 37 34 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 35 36 34 34 34 34 35 35 35 35 35 35 35 35 35 35 35 35 35 53 53 53 53 53 53 53 53 53 53 54 54 53 41 54 54 54 48 48 48 48 48 49 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 163310 163320 163330 163590 163670 165000 165010 165020 165040 165110 165130 165180 165220 165230 165260 165270 165280 165400 165410 165610 165620 165700 165700 165701 165701 165702 165702 165703 165703 165704 165704 165705 165705 165705 165706 165706 165707 165707 165708 165708 165709 165709 165710 165710 165711 165711 165712 165712 165713 165713 165714 165714 165715 165715 165716 165716 165717 165717 165718 165718 165719 165719 165720 165720 165721 165721 165722 165722 165722 165722 165722 165723 165724 165725 165738 165738 165739 165739 165740 165740 165741 165741 165742 165742 165744 165744 165745 165745 165746 165746 166000 166010 166020 166030 166040 166050 166060 166070 166080 166090 166100 166110 166120 166130 166140 57 Reference code 65XF19 90XF19 115XF19 15 GEM T320 T320A B265 T313 T322 T314 B165 B166 B167 KIT-120-3/4 T314A T403 B2618B B2610A B140 B2671A 15PLUSF20 15PLUSF20 25PLUSF20 25PLUSF20 32PLUSF20 32PLUSF20 45PLUSF20 45PLUSF20 65PLUSF20 65PLUSF20 90PLUSF20 90PLUSF20 90PLUSF20 115PLUSF20 115PLUSF20 150PLUSF20 150PLUSF20 200PLUSF20 200PLUSF20 250PLUSF20 250PLUSF20 300PLUSF20 300PLUSF20 400PLUSF20 400PLUSF20 500PLUSF20 500PLUSF20 CA15PLUSF33 CA15PLUSF33 CA25PLUSF33 CA25PLUSF33 CA32PLUSF33 CA32PLUSF33 CA45PLUSF33 CA45PLUSF33 CA65PLUSF33 CA65PLUSF33 25PLUSXF19 25PLUSXF19 32PLUSXF19 32PLUSXF19 45PLUSXF19 45PLUSXF19 65PLUSXF19 65PLUSXF19 CA25PLUSXF19 CA25PLUSXF19 CA32PLUSXF19 CA45PLUSXF19 CA65PLUSXF19 CA32PLUSXF19 CA45PLUSXF19 CA65PLUSXF19 PLUSCU PLUSCU PLUSCULD PLUSCULD MC2X2KIT MC2X2KIT MC3X3KIT MC3X3KIT MC4X4KIT MC4X4KIT MC2.5X3KIT MC25X3KIT PLUSCU15L PLUSCU15L PLUSCULD15 PLUSCULD15 B161-8A B161-8K B161-8KS B161-10B B161-10KA B161-10KM B164-12A B164-12K B164-12KS DB-8A DB-8K DB-8KS DB-10A DB-10K DB-10KS Page Part No. 48 48 48 48 37 51 51 54 51 55 51 40 40 40 51 51 54 39 39 55 39 47 48 47 48 47 48 47 48 47 48 47 48 49 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 47 48 48 48 48 47 47 47 47 51 47 51 47 51 47 51 47 51 51 47 47 51 47 51 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 166150 166160 166170 166180 166190 166200 166210 166220 166480 166490 166500 166510 166520 166530 166540 166550 166560 166950 166951 166952 166953 166954 166955 166956 166957 166958 166959 166960 166961 166962 166963 166964 166965 166966 166967 166968 166969 166970 166971 166972 166973 166974 166975 166976 166977 166978 166979 166980 166981 166982 166983 166984 166985 166986 166987 166988 166989 166990 166991 166992 166993 166994 167200 167210 167220 167230 167240 167250 167260 167270 167280 167290 167300 167310 167780 167781 167900 167901 167902 167903 167904 167905 167906 168050 168060 168090 168100 168180 168190 168380 168390 168400 168410 168440 168450 168460 168470 168630 168640 168660 168830 168850 168890 168910 169310 Reference code DB-12A DB-12K DB-12KS DB-16A DB-16K DB-16KS B-162-12A B-162-12K DB-10-C5005 DB-10-C501 DB-10-C502 B161-10-C5005 B161-10-C501 B161-10-C502 B-162-12-C5005 B-162-12-C501 B-162-12-C502 EHL12FCW3 EHL12FCY1 EHL12FCY2 EHL12FCY3 EHL12FCY4 EHL12FC1G EHL12FC1G1G EHL12FC1H EHL12FC1K EHL12FC1K1K EHL12FC1L EHL12FC1T EHL12FC1V EHL12FC6MM EHL12FC8MM EHL58CW3 EHL58CY1 EHL58CY2 EHL58CY3 EHL58CY4 EHL58C1G EHL58C1G1G EHL58C1H EHL58C1K EHL58C1K1K EHL58C1L EHL58C1T EHL58C1V EHL58C2G EHL58C6MM EHL58C8MM EHL34CW3 EHL34CY1 EHL34CY2 EHL34CY3 EHL34CY4 EHL34C1G EHL34C1H EHL34C1K EHL34C1L EHL34C1T EHL34C1V EHL34C2G EHL34C6MM EHL34C8MM KIT CPB 2,5/16 CPB 2,5/16 PACK KIT CPB-25 CPB-25 PACK KIT CPB-35 CPB-35 PACK KIT CPD 2,5/16 CPD 2,5/16 PACK KIT CPD-25 CPD-25 PACK KIT CPD-35 CPD-35 PACK KITCDM01 KITCDM01PLUS SRGBC120 SRGBD100 SRGBE100 SRGBF100 SRGBG100 SRGC46 SRGC46BR PG-25/29 PG-35 VF-25/29 VG-35 GY-35 GY-50 PG-25/29-Z PG-35-Z PG-50-Z PG-70-Z VG25/29-Z VG35-Z VG50-Z VG70-Z GY-35-Z GY-50-Z GY-95-Z RT-35-Z-10 RT-50-Z-10 RC-35-Z-10 RC-50-Z-10 GT-P128 Page 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 56 56 56 56 56 56 56 56 56 56 56 56 49 49 28 28 28 28 28 28 28 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 INDEX OF PART NUMBERS IN NUMERICAL ORDER Part No. 169600 169890 169930 169990 180010 180020 180030 180040 180080 180140 180150 180170 180180 180190 180200 180220 180230 180250 180260 180270 180280 180300 180310 180320 180330 180340 180350 180360 180380 180390 180430 180700 180740 180960 182010 182020 182030 182040 182050 182060 182070 182125 182130 182135 185010 185020 185030 197290 197650 197700 197710 197720 197790 197810 197860 197870 197900 197910 197920 197930 197940 197950 197970 197975 198000 198010 198020 198050 198060 198070 198080 198090 198100 198130 198150 198160 198200 198210 198250 198400 198410 198420 221004 221006 221008 221009 221011 221013 221014 221021 221025 221028 221035 221051 221053 221063 221075 221094 221135 221138 221142 221148 221153 221159 221256 Reference code LA-Y2-FAK GYV-35-Z-10 TS6A RT-25-Z-10 H108 H109 H113AF H114F H117F H101 H101F H102 H103 H104 H104F H104BF H105 H106F H106AF H107F H108F H109F H109AF H111F H111AF H112F H113 H113F H103F H102F H117 H115 H116F H107 TP5A TP7A TP2A TP4A TP6A TP3B TP5B B136A B136B B136F S2904A S2904B S2904C TS-CST TC-EC-3020-30 TC-ECT-2020-30 TC-ECT-3020-30 TC-ECT-2530-30 70TC-HGSP-3035 30TC-HGSP-3035 RSCC-8 RSCC-10 SC-EC-25 SC-EC-35 SC-EC-50 SC-EC-70 SC-EC-95 SC-EC-185 TC-ECT-4030-30 TC-ECT-4040-35 IC-EC-25 IC-EC-35 IC-EC-50 IC-ECH-25 IC-ECH-35 IC-ECH-50 IC-ECH-70 IC-ECH-95 IC-ECH-300 IC-ECH-16 RC-EC-6 RC-EC-8 RC-ET-6 RC-ET-8 RAW-8 A822SA111C-5 A822SA111C-10 A822SA111C-20 SSC-Y1 SSC-Y2 SSC-W6 SSC-Y3 SSC-W8 SSC-Y5 SSC-Y6 SSC-Y4 TAC-Y1 TAC-Y2 TAC-Y4 TAC-Y7 TAC-Y8 TAC-Y2-Y1 TAC-Y4-Y2 TAC-Y6-Y4 XAC-Y1 XAC-Y2 XAC-Y3 XAC-Y4 XAC-Y5 XAC-Y6 PTC-Y5 Page Part No. 56 56 49 56 54 54 55 55 55 54 55 54 54 54 55 55 54 55 55 55 55 55 55 55 55 55 54 55 55 55 54 54 55 54 55 55 55 55 55 55 55 55 55 55 54 54 54 55 27 27 27 27 29 29 29 29 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 28 28 28 28 29 39 39 39 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 221258 221265 221268 221403 221404 221405 221407 221443 221455 221466 221534 221603 221607 221609 222115 222122 222459 222461 222463 222501 222560 222689 222939 223044 223076 223138 223432 223520 223550 223609 223943 224123 224150 224800 224815 225026 225147 225788 225814 226083 226545 226567 226670 227549 227687 228347 228521 228682 229737 230199 231342 231692 232003 232537 232556 232648 232933 232996 233366 233795 233901 234398 234426 234429 234441 234444 234445 234447 234453 234454 234581 234582 234585 234588 234592 234593 234720 234732 234733 234734 234735 234736 234737 234738 234739 234740 234759 234760 234770 234782 234991 236084 237727 237901 238039 238544 238556 239534 239694 239887 240228 502000 502040 503900 504500 Reference code PTC-Y4 PTC-Y3 PTC-Y1 VSC-Y6 VSC-Y5 VSC-Y4 VSC-Y3 LAC-Y2-CAJ LAC-Y3-CAJ HAA-Y1-CA HAA-Y4 HAA-Y3 HAA-Y2 HAA-Y1 PTC-Y6 LAC-Y3-BAJ TAC-Y3 TAC-Y5 TAC-Y6 LAC-Y1-CAJ PCC-Y3 HAA-A3 VGC-Y3 HBA-B3 VGC-Y5 GTC-P190-2G G-EBP-DAJ GTC-P143-Y5 PCC-Y1 VGC-Y6 PGC-Y5 G-BMP-DAJ LAC-Y2-BAH LAC-Y1-BAH VGC-Y2 TAC-Y5-Y6 G-CFZ-DAJ EBP-BAK GTC-P143-Y3 GTC-P172-Y3 PTC-Y2 GRC-P172-Y3 GTC-P172-Y2 GTC-P172-Y5 GTC-P172-Y4 VGC-Y4 VGC-Y1 GTC-P172-Y1 GTC-P143-Y2 PCC-Y6 PGC-Y4 PGC-Y6 CFZ-BAK GEC-P128 PGC-Y2 PGC-Y3 LJP-Y3-FAM GTC-P143-Y4 CFZ-CAJ LAC-L9-EAK-A GTC-P143-Y1 EB-BGP-BAK BMP-CAJ BMP-BAK RTZ-Y1 RTZ-Y2 RTZ-Y3 RTZ-Y4 RTZ-Y5 RTZ-Y6 RCZ-Y1 RCZ-Y3 RCZ-Y2 RCZ-Y4 RCZ-Y5 RCZ-Y6 CDM01 CGZ-BAK CHZ-BAK CCZ-BAK CPZ-P143-BAK BMP-CAJ-BAK LJP-Y1-BAK LJP-Y2-BAK LJP-Y3-BAK LAZ-Y3-BAK LEP-Y3-BAK BYC-BAK-CROW BJC-BAK-CROW LWP-Y3-BAK EBP-CAJ PGC-Y4-Y1 GEC-P143 PGC-Y1 B-GRC-P143-Y3 GFC-P143-Y3 GFC-P165-G2-B LAC-Y3-BAH CPZ-P172-BAK BWZ-BAK HAA-B3-CA ALUM 3ME MBMAST3ME GF-302 WM3-2088-B Page Part No. 50 50 50 50 50 50 50 52 52 50 50 50 50 50 50 52 50 50 50 52 50 50 50 50 50 52 50 52 50 50 50 50 52 52 50 50 52 50 52 52 50 52 52 52 52 50 50 52 52 50 50 50 52 52 50 50 50 52 52 52 52 50 50 50 52 52 52 52 52 52 52 52 52 52 52 52 49 52 52 52 52 50 50 50 50 52 50 52 52 50 50 50 52 50 52 52 52 52 52 52 50 18 18 37 28 504510 504520 504530 504540 504550 504590 545000 545001 545010 545020 545030 545040 545130 545135 545140 545170 545180 545190 545200 545210 545260 545270 545530 546300 546320 546330 546340 550900 551520 556620 556630 556640 556650 556660 556670 556680 556690 556700 556710 556720 556730 556740 556750 556760 556770 556780 556790 556800 556810 556820 556830 556840 556850 556860 556940 556950 556960 556970 556980 563300 563320 563340 563350 563360 563370 563390 563400 563430 563440 563540 563550 563560 565000 591080 591230 591280 591290 593480 700001 700002 700003 700004 700005 700006 700310 700355 700360 700405 700410 700455 700465 700475 700526 700527 700630 700640 700650 700805 700815 700850 700860 700865 701000 701030 701250 58 Reference code WM2-1030-B WM3-1020-B WM2-1020-B WMS-1030-B PC2.-1020 PC3-0909 DLUNI SEB-GER-08 SEB-06 SEB-06-DL SEB-10 SEB-10-DL SEB-62-DL BEP25x5x200 BEP25x5x300 CCS-308 CCG-308 SEP TC-ECT-3020-75 RC-EC-8-3 SR CCFR-308 BEP25x5x150 RK-CCR-2 BB-CCR BK-CCR-2 BF-CCR HDB5010 ISO40M410 MBJ 16-100-8 MBJ 16-150-8 MBJ 16-200-8 MBJ 16-250-8 MBJ 16-300-8 MBJ 25-100-10 MBJ 25-150-10 MBJ 25-200-10 MBJ 25-250-10 MBJ 25-300-10 MBJ 30-100-10 MBJ 30-150-10 MBJ 30-200-10 MBJ 30-250-10 MBJ 30-300-10 MBJ 35-100-10 MBJ 35-150-10 MBJ 35-200-10 MBJ 35-250-10 MBJ 35-300-10 MBJ 50-100-10 MBJ 50-150-10 MBJ 50-200-10 MBJ 50-250-10 MBJ 50-300-10 MBJ 16-500-8 MBJ 25-500-10 MBJ 30-500-10 MBJ 35-500-10 MBJ 50-500-10 MBJ 16-200-6 MBJ 16-300-6 MBJ 25-200-6 MBJ 50-200-6 MBJ 50-200-16 MBJ 50-200-18 MBJ 50-300-16 MBJ 50-300-18 MBJ 25-200-12 MBJ 50-200-12 MBJ 16-100-6 MBJ 16-150-6 MBJ 50-500-12 MBJ 35-250-25 CEI20 FEI20 BEI20 42014 VFST10x40 TDF3A120V TDF3A240V TDF10A120V TDF10A240V TDF20A120V TDF20A240V CSP NMF 90 CSP NMF 600 CSP BNC 90 CSP BNC 600 CSP NB 90 CSP NB 600 DDI35 DDI63 LAN RJ45 1 LAN RJ45 24 DEP RS232 25 25 DEP RS232 9 9 DEP RS422 9 9 HSP10K36 HSP10K12 HSP10K72 HSP10K230 RTP 30 34 DSF6A 30V DSF6A 275V TDS SC Page Part No. 28 28 28 28 28 28 38 38 38 38 38 38 38 37 37 24 24 39 27 28 24 24 37 56 56 56 56 28 38 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 25 25 25 25 38 43 43 43 43 43 43 44 44 44 44 44 44 43 43 44 44 44 44 44 44 44 44 44 43 43 43 43 701280 701305 701315 701320 701340 701350 701360 701370 701380 701390 701410 701420 701460 701535 701536 701537 701540 701610 701840 701875 701895 701915 701990 702005 702030 702040 702050 702065 702085 702089 702090 702100 702165 702175 702180 702230 702240 702250 702255 702260 702265 702270 702275 702280 702285 702290 702295 702296 702297 702298 702299 702301 702306 702350 702360 702370 702380 702400 702402 702420 702436 702460 702466 702478 702480 702491 702496 702506 702510 702521 702525 702530 702535 702560 702566 702581 702591 702601 702670 702680 702721 702750 702800 702810 702811 702820 702821 702830 702840 702860 702900 703000 705506 705560 710010 710020 710030 710040 710050 710060 710070 710080 710090 710090 710100 Reference code GUYRING GUYKIT 4MGRIP GUYKIT 7MGRIP I/LCOUPL MBMAST4M MBMAST5M MBMAST6M ALUM 4M ALUM 5M ALUM 6M CONSAD/FX CABTIE-SS UBOLT SI25 SI40 SI65 SLP10K1F LCO01A THERMLUGCOUPL ERICORE/PER M ERICORE/TRM/IS ERICORE/TRM/OS CONSAD/E2 ERICORE/LT KITA FRP/2M/BLACK FRP/2M/WHITE LEC-IV 7000250S4 D/SMKIV-SS INTMKIV-SS DSF6A 30V EARTH ANALYSER TMC-SS ALOF1-GS LSEB 4554 WPC HSF R7-SFT-20 ER1-1000-SS ER1-2000-SS ER2-2000-SS ER2-3000-SS ER3-2000-SS ER3-3000-SS SG-AERIAL-302 ER2-BASE ER3-BASE INTCPT-ADBUTT INTCPT-ADF2BSPF INTCPT-ADF2NSP INTCPT-ADM3/4UNC INTCPT-ADM116UN INTCPT-ADM16 ESTREELKIT500 EST101 EST201 EST301 SGD1100 2S NE SGD112 1S NE DSD1150 2SR 275 DSD140 M 150 DSD160 1SR 275 DSD160 M 275 DSD140 1S 75 DSD140 1S 150 DSD140 1S 275 DSD140 M 275 DSD140 M 440 DSD140 1SR 150 DSD140 1SR 275 CATV MF DSD140 1SR 440 CATV F DSD110 1S 275 DSD110 M 275 DSD340 TNC 275 A DSD340 TNS 275 A DSD340 TT 275 A DSD120 1S 12 DSD120 1S 24 DLT DSD140 2BR 24/48 UTB5 UTB15 UTB15EX UTB30 UTB30EX UTB60 UTB110 UTBSA PEC100 CCTV 12 DSD140 M 440 DSD110 1S 275 SSR16 AAR0515 CTR-8CU CTR-8AL TECLP-8-CU TECLP-8-AL SCR15 SCR20 CDS15 CDS15 CDS20 Page 19 19 19 18 18 18 18 18 18 18 19 19 18 19 19 19 44 44 19 18 18 18 19 18 18 18 19 18 18 18 43 32 22 22 22 22 26 26 19 19 19 19 19 19 22 19 19 19 19 19 19 19 19 32 32 32 32 43 43 43 43 43 43 43 43 43 43 43 43 43 44 43 44 43 43 43 43 43 44 44 44 44 44 44 44 44 44 44 44 44 40 44 43 43 34 21 26 26 38 38 34 34 34 34 34 www.erico.com INDEX OF PART NUMBERS IN NUMERICAL ORDER Part No. 710110 710115 710120 710120 710130 710140 710150 710160 710170 710180 710190 710200 710210 710220 710230 710240 710250 710260 710270 710290 710295 710300 710305 710310 710320 710325 710330 710335 710345 710350 710355 710360 710365 710370 710380 710390 710400 710410 710420 710430 710440 710450 710460 710470 710480 710490 710500 710510 710515 710520 710535 710540 710545 710555 710560 710570 710580 710595 710605 710615 710616 710620 710625 710630 710645 710655 Reference code PBD10 SSD10 SPK15 SPK15 SPK20 EBR-58 EBR-34 500-10-E-BOSS SFO50 PIT03 PC1.5-0606 PC3-0606 PC1.5-0909 OXINH1BCOMP EML663 EML993 ABBC BBBC AWPB PFC001 PFA001 GBH C GBH A BWPB WPB010 RC70 SEB001 RC100 RTC3020 RTC2051 EK16 RTC2526 EK17 UB16 UB20 UB25 GUV16070 GUV70185 RCC10 RCC16 SRC15 SRC20 TC-EC-1215-30 TC-EC-1230-30 TC-EC-2015-30 TC-EC-2030-30 TC-EC-2515-30 TC-EC-2530-50 TC-EC-2530-25 TC-EC-2540-30 TC-EC-2560-15 TC-EC-3160-30 TC-EC-3650-50 TC-EC-3850-10 TC-EC-3860-30 TC-EC-5030-30 TC-EC-5060-20 CTBL253-25 CTBN253-25 LSF-253 CTGN253-25 CTGN256-30 LCT-253 CTGN506-30 CTGY253-25 CTST253-25 www.erico.com Page Part No. 34 34 34 34 34 40 40 39 40 37 28 28 28 40 28 28 38 38 38 23 23 23 23 38 38 39 39 39 36 36 39 36 39 36 36 36 36 36 37 37 37 37 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 28 27 27 27 710666 710667 710670 710680 710690 710700 710710 710730 710740 710750 710760 710770 710780 710790 710800 710810 710820 710830 710840 710850 710860 710870 710875 710880 710890 710900 710920 710940 710955 710960 710965 710970 710980 710990 711000 711010 711030 711040 711050 711060 711070 711080 711090 711100 711110 711120 711130 711140 711150 711160 711170 711180 711190 711195 711200 711210 711220 711230 711230 711240 711250 711260 711270 711280 711290 711300 Reference code CTWH253-25 CTYGN253-25 HDB2003 HDB2503 HDB2506 HDB3806 HDB5006 THDB5060 FAT-253-50 ATBL253 ATBN253 ATGY253 ATST253 ATWH253 SCBL SCBN SCGY SCST SABL SABN SAGY SAST SC-EC-06 SC-EC-10 SC-EC-16 SC-EC-120 SC-EC-150 SC-EC-400 BAT-2030 BAT-2560 BAT-5060 IC-ECH-240 IC-ECH-120 IC-ECH-150 IC-ECH-185 CAR2015 AVG3.0 PC010A AAR0510 AAR1010 AAR1015 CAR0510 CAR0515 CAR1010 CAR1015 CMPR ATBA10 ATBA15 ATBC10 ATBC15 RSC115 ABR015 CBR015 ALD-TAP302 (10x4.8x2) TTRA16 TTRC16 DCC253 DCC256 DCC256 DCC506 DCC600 DCC605 DCC610 PDC253BN PDC253GY PDC25BL Page Part No. 27 27 28 28 28 28 28 28 29 29 29 29 29 29 28 28 28 28 29 29 29 29 27 27 27 27 27 27 29 29 29 27 27 27 27 21 24 23 21 21 21 21 21 21 21 21 21 21 21 21 21 21 21 26 21 21 23 23 23 23 23 23 23 23 23 23 711310 711320 711330 711340 711350 711360 711370 711380 711390 711400 711410 711425 711430 711440 711450 711460 711470 711480 711490 711500 711520 711530 711540 711550 711560 711570 711580 711590 711620 711630 711640 711650 711660 711670 711680 711690 711700 711710 711730 711740 711750 711760 711800 711810 711820 711830 711840 59 Reference code PDC25BN PDC25GN PDC25GY PDC25ST PDC25WH PDC506BL PC008A PC008C PC010C STA253 STC253 STC256-506 OBA268 OCB268 PCT400 EBL04 EBL08 BIM700 BIM800 BIM900 DT50 ASCO8 TAPA203 TAPA253 TAPC203 TAPC253 TAPC254 TAPC506 TAPS302 DCC203 DCC254 DCC313 DCC316 DCC383 DCC385 DCC386 DCC503 DCC504 DCA253 DCA256 DCA506 DCA600 HF250BN HF250GY HFP253BN HFP253GY HFP253ST Page 23 23 23 23 23 23 23 23 23 24 24 24 24 24 24 39 39 24 24 24 40 29 23 23 23 23 23 23 26 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 WARNING ERICO products shall be installed and used only as indicated in ERICO's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death. WARRANTY ERICO products are warranted to be free from defects in material and workmanship at the time of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCTS. Claims for errors, shortages, defects or nonconformities ascertainable upon inspection must be made in writing within 5 days after Buyer's receipt of products. All other claims must be made in writing to ERICO within 6 months from the date of shipment or transport. Products claimed to be nonconforming or defective must, upon ERICO's prior written approval in accordance with its standard terms and procedures governing returns, promptly be returned to ERICO for inspection. Claims not made as provided above and within the applicable time period will be barred. ERICO shall in no event be responsible if the products have not been stored or used in accordance with its specifications and recommended procedures. ERICO will, at its option, either repair or replace nonconforming or defective products for which it is responsible or return the purchase price to the Buyer. THE FOREGOING STATES BUYER'S EXCLUSIVE REMEDY FOR ANY BREACH OF ERICO WARRANTY AND FOR ANY CLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR INJURY CAUSED BY THE SALE OR USE OF ANY PRODUCT. LIMITATION OF LIABILITY ERICO excludes all liability except such liability that is directly attributable to the willful or gross negligence of ERICO's employees. Should ERICO be held liable its liability shall in no event exceed the total purchase price under the contract. ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIME OR DELAY, LABOR, REPAIR OR MATERIAL COSTS OR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER. Due to a policy of continuing product development, specifications are subject to change without notice. ANSI is a registered trademark of American National Standards Institute CSA is a copyright of Canadian Standard Association International IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc Krone-LSA is a registered trademark of Krone GmbH. NEC is a registered trademark of, and National Electrical Code (NEC) standard is a copyright of the National Fire Protection Association NFPA is a registered trademark of National Fire Protection Association UL is a registered trademark of Underwriters Laboratories, Inc. 60 www.erico.com ERICO® Facility Electrical Protection Literature Facility Electrical Protection Solutions Brochure Discusses effective facility electrical protection. The catalog details the ERICO® Six Point Plan of Protection and goes on to cover lightning protection, grounding, bonding and surge protection in depth. Products and detailed drawings are included, as are industries to which the technologies are most applicable. ERITECH® Lightning Protection Catalogs ERITECH® SYSTEM 2000 Lightning Protection Products catalog highlights products used in conventional lightning protection. Products detailed include conductors, ground rods and plates, clamps, splices, points and accessories. ERITECH® SYSTEM 3000 Lightning Protection Products catalog details the active lightning protection process. Information on air terminals, downconductors and design software is included. ERITECH® Grounding Products Catalog Details ERICO’s extensive offering of ground rods and accessories, ground mesh and mats, signal reference grids, ground bars, ground receptacles, transient earth clamps, ground enhancement materials, and other grounding materials. CADWELD® Welded Electrical Connections Catalog Covers the range of hardware required to make a CADWELD connection as well as detailed ordering information for molds, weld materials, fence and gate jumpers and the smokeless CADWELD® EXOLON process. CRITEC® Surge Protection Products Catalog Details the extensive range of CRITEC Surge Protection Devices for industries such as commercial & industrial, process control & automation and telecommunications. It includes information on AC protection products, data control and signal protection products, as well as point-of-use protection products. www.erico.com AUSTRALIA GERMANY POLAND 6 Chilvers Road P.O. Box 148 Thornleigh (Sydney) NSW 2120 Australia Phone 61-2-9479-8500 Fax 61-2-9484-9188 66851 Schwanenmühle Germany Phone 49-6307-918-10 Fax 49-6307-918-150 ul. Krzemieniecka 17 54-613 Wroclaw Poland Phone 48-71-374-40-22 Fax 48-71-374-40-43 BELGIUM HONG KONG SINGAPORE Postbus 33 3110 Rotselaar Belgium Phone 32-14-69-96-88 Fax 32-14-69-96-90 Unit 1, 2nd Floor, Block A Po Yip Building 62-70 Texaco Road Tsuen Wan, New Territories Hong Kong Phone 852-2764-8808 Fax 852-2764-4486 Jurong Industrial Estate 16 Wan Lee Road Singapore 627 946 Phone 65-6-268-3433 Fax 65-6-268-1389 BRAZIL HUNGARY SPAIN R. Dom Pedro Henrique de Orleans E Braganca, 276 Vila Jaguara São Paulo CEP 05117-000 Brazil Phone 55-11-3621-4111 Fax 55-11-3621-4066 P.f. 184 1476 Budapest Hungary Phone 31-13-58-34-547 Fax 31-13-58-35-499 C /Provenza 288, Pral. 08008 Barcelona Spain Phone 34-93-467-7726 Fax 34-93-467-7725 CANADA INDONESIA SWEDEN P.O. Box 170 Mississauga, Ontario Canada L5M 2B8 Phone 1-800-677-9089 Fax 1-800-677-8131 Sudirman Square Tower B 19th Fl. Jalan Jend. Sudirman Kav. 45-46 Jakarta 12930 Indonesia Phone 62-21-575-0941 Fax 62-21-575-0942 Box 211 201 22 Malmö Sweden Phone 46-40-611-13-60 Fax 46-40-611-94-15 CHILE ITALY SWITZERLAND Alcantara 200, piso 6 Of. 17 Las Condes, Santiago Chile Phone 56-2-370-2908 Fax 56-2-370-2914 A&B Business Center Via Valla 16, nr. 17 20141 Milano Italy Phone 39-02-8474-2250 Fax 39-02-8474-2251 Postfach 54 3280 Murten Switzerland Phone 00-800-5000-1090 Fax 00-800-6000-1090 CHINA MEXICO THAILAND Room 1204 Tomson Commercial Building No. 710 Dongfang Road Pudong, Shanghai P.R. China 200122 Phone 86-21-5081-3900 Fax 86-21-5831-8177 Melchor Ocampo 193 Torre A piso 13 Col. Veronica Anzures 11300 Mexico D.F. Mexico Phone 52-55-5260-5991 Fax 52-55-5260-3310 163 Ocean Insurance Bldg. 16th Fl. Unit B Surawongse Road Bangrak Bangkok 10500 Thailand Phone 66-2-634-1692 Fax 66-2-634-1694 DENMARK NETHERLANDS UNITED KINGDOM Box 211 201 22 Malmö Sweden Phone 46-40-611-13-60 Fax 46-40-611-94-15 Jules Verneweg 75 5015 BG Tilburg Netherlands Phone 31-13-58-35-400 Fax 31-13-58-35-499 52 Milford Road Reading, Berkshire RG1 8LJ United Kingdom Phone 44-118-958-8386 Fax 44-118-955-0925 FRANCE NORWAY UNITED STATES Rue Benoît Fourneyron Z.I. Sud Boîte Postale 31 42161 Andrezieux Cedex France Phone 33-4-77-36-56-56 Fax 33-4-77-55-37-89 Postboks 148 1366 Lysaker Norway Phone 47-67-53-12-00 Fax 47-67-12-42-68 34600 Solon Road Solon, Ohio 44139 U.S.A. Phone 1-440-248-0100 Fax 1-440-248-0723 Copyright ©2005 ERICO International Corporation. All rights reserved. CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation. E515C-EN E1686CT06EN 0127M6