48x48 digital timer Type FMC01 Timers

advertisement
Timers
48x48 digital timer
Type FMC01
• 48 x 48 mm programmable timer
• 2-line LCD display with indicators for easy operation
and reading
• 9 programmable time ranges from 0.20 s to 99999 h
• 8 programmable timing functions
• 3 programmable activation modes
• Diplays text prompts to guide the user while programming
• Start and reset input voltage from 12 to 240 V AC/DC
• Output: 8 A SPST relay N.C. or N.O. selectable
• Power supply: replaceable lithium batteries
Product Description
Ordering Key
48 x 48 mm digital timer for
flush mounting with 2 lines
LCD display, with many indicators to show the set up of
the device. Wide time range
(up to 99999 h) and 8 timing
functions programmable via
front keys. Connection by
detachable screw-type connector.
Housing
Function
Type
Item number
Output
Input range
Mounting
Output
Housing
Input: 12 to 240 VAC/DC
Front panel
SPST
48 x 48 mm
FMC 01 C W24
FMC 01 C W24
Type Selection
Output Specifications
Time Specifications
Time ranges
Display selectable
Functions
ON DLY
OFF DLY
OS
SS
RC DLY
RC
RC DLY=
RC=
Accuracy
Repeatability
Reset
Manual reset
Time and reset inputs
Voltage
Pulse duration
Impedance
0.02 to 999.99 s
0.2 to 9999.9 s
1 to 99999 s
0.01 to 999.99 min
0.1 to 9999.9 min
1 to 99999 min
0.01 to 999.99 h
0.1 to 9999.9 h
1 to 99999 h
Delay on operate
Delay on release
One shot
Single shot
Asymmetrical recycler
OFF first
Asymmetrical recycler
ON first
Symmetrical recycler
OFF first
Symmetrical recycler
ON first
+50 / -20 ms or
±0.5% on set value
(higher value counts)
0.3% on set value
Output
Rated insulation voltage
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Response time
Dielectric strenght
Dielectric voltage
SPST relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 30 VDC
5 A @ 250 VAC
3.5 @ 30 VDC
≥ 50 x106 operations
≥ 105 operations
(at 8 A, cos ϕ= 1)
< 20 ms
≥ 1.5 kVAC (rms)
(contact/electronics)
Supply Specifications
Power supply
2 x 3V, 1/2 AA
replaceable lithium batteries
(lifetime ≥ 10 years or
≥ 50 x 104 relay operations)
Push the red key or close
the reset contact
Optoscouplers
12 to 240 VAC/DC ±10%
≥ 20 ms
180 kΩ
Specifications are subject to change without notice (03.01.06)
1
FMC01
General Specifications
Housing dimensions
Display
Number of digits
5 digits
2-line 7 segment LCD display
Time digit height
6.5 mm
Set time digit height
3.5 mm
Indicator for activated output
Present
Indicator for set function
Present
Indicator for set activation mode Present
Electrical lock of front keys
Present
Environment
IP 65 on front
Degree of protection
2
Pollution degree
-10 °C to +60 °C
Operating temperature
R.H. < 80%, up to 31 °C
R.H. < 50%, at 40 °C
Storage temperature
-25 °C to +70 °C
48 x 48 x 83 mm
(including rear connector)
45 x 45 +0.6 - 0 mm
Approx. 80 g
Screw-type, detachable
Max. 0.6 Nm
UL
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
Panel cut-out
Weight
Connector
Screw tightening torque
Approvals
CE Marking
EMC
Immunity
Emission
Front Panel Description
1. Time value display
2. Indicator for activated
output
3. Set time display
4. Selected time range
5.
6.
7.
8.
9.
5 LCD digits, 6.5 mm high
5 LCD digits, 3.5 mm high
SEC (seconds)
MIN (minutes)
HRS (hours)
Front keys
5 keys to increase the set
time value
Reset key
To reset the unit when
timing up or the set time
when timing down;
to confirm the selected step
on the sub-routine program
Key for programming
To confirm the selected
phase
step on the routine
program
Selected activation mode LEVEL TRIG
EDGE TRIG
EDGE RETRIG
Selected function
ON DLY, OFF DLY, OS, SS,
RC DLY, RC, RC DLY=, RC=
Wiring Diagram
Keyboard inhibit
inhibit
Keyboard
Reset
Reset
36
11.Programming phase
annunciator
11
10
9
8
56
PROG
5 up
6 down
PROG
2
1
888.8.8
8 8 8.8 .8
ON OFF DLY
OSSS PW
=
=
RC +=
LEVEL EDGE RETRIG HRS MIN SEC
3
4
7
6
5
Accessories Included
L
Trigger
Trigger
10.Indicator for timing direction
7
+ -
m
The digital timer is supplied with the following accessories:
• screw terminal plug 7 poles, reference grid 5.08 mm;
• bezel for clip mount, panel cut-out 50 x 50 mm;
• bezel for screw mount, panel cut-out 50 x 50 mm;
• panel mounting clip.
5
2
1
4
N
2
Specifications are subject to change without notice (03.01.06)
FMC01
Operating Diagrams
Function OFF DLY - Delay on release
Function ON DLY - Delay on operate
LEVEL TRIG
TRIG
LEVEL
EDGE
EDGETRIG
TRIG
EDGE RETRIG
RETRIG
EDGE
LEVEL
LEVELTRIG
TRIG
Trigger
Trigger input
input
Trigger
Triggerinput
input
Reset
Reset
Reset
Reset
T
T
T
EDGE TRIG
TRIG
EDGE
T
T
T
Relay
Relay ON
ON
Relay ON
ON
Relay
Function OS - One shot
Function SS - Single shot
LEVEL
LEVEL TRIG
TRIG
EDGE TRIG
TRIG
EDGE
EDGERETRIG
RETRIG
EDGE
LEVEL
LEVELTRIG
TRIG
Trigger
Triggerinput
input
EDGE RETRIG
EDGE
RETRIG
EDGE
EDGE TRIG
TRIG
T
EDGE
EDGE RETRIG
RETRIG
Trigger
Triggerinput
input
Reset
Reset
pw
T
T
T
T
Relay
RelayON
ON
pw
Function RC DLY - Asymmetrical recycler OFF first
LEVEL TRIG
LEVEL
TRIG
EDGE
EDGE TRIG
TRIG
T
LEVEL
LEVELTRIG
TRIG
EDGE RETRIG
RETRIG
EDGE
Trigger
Triggerinput
input
Reset
Reset
Reset
Reset
T-
T+
T-
T+
T+
T
Function RC - Asymmetrical recycler ON first
Trigger
input
Trigger
input
T+
T
Relay ON
ON
Relay
pw
pw
Reset
Reset
T+
T+
T-
T-
EDGE
EDGETRIG
TRIG
T+
EDGE RETRIG
EDGE
RETRIG
T-
T+
T-
RelayON
ON
Relay
RelayON
ON
Relay
Function RC DLY= - Symmetrical recycler OFF first
Function RC= - Symmetrical recycler ON first
LEVEL
LEVEL TRIG
TRIG
EDGE
EDGETRIG
TRIG
EDGERETRIG
RETRIG
EDGE
Trigger
input
Trigger
input
LEVEL
LEVELTRIG
TRIG
EDGE TRIG
TRIG
EDGE
T+
EDGE RETRIG
EDGE
RETRIG
Trigger
Triggerinput
input
Reset
Reset
Reset
Reset
T=
T=
T=
T=
T=
T=
T=
T=
T=
RelayON
ON
Relay
Specifications are subject to change without notice (03.01.06)
T=
T=
T=
T=
T=
T=
RelayON
ON
Relay
3
FMC01
Dimensions
60 mm
60mm
(2.36")
63mm
(2.48")
S
12")
3mm (0.
3 mm
(0. 12")
3mm
6
4
75 mm
48mm 48mm
PGM S
(1.89”)
PGM
(1.89”)
63 mm
48 mm
48mm 48mm
(1.89")
48 mm
(1.89")
83 mm
83mm
(3.26")
83mm
(3.26")
(2.64”)
67mm
67 mm
67mm
(2.64”)
75mm
(2.95")
φ = 4.3 mm
(0.17") Ø
4.3mm
<12mm
(0.48")
< 12 mm
6
Specifications are subject to change without notice (03.01.06)
Download