Door Controls International PS17-TD2 Access Control Power Supply/Charger Rev. 062101 Overview: The PS17-TD2 is a power supply that will convert 115 VAC/60Hz input into two individually PTC protected 12VDC or 24VDC outputs (see specifications) and provide time delays to conform with both Delayed Egress and Access-controlled Egress provisions of the U.S. model building codes. It is intended for use in applications requiring UL Listing for Access Controls (UL294) and applications requiring an interface with Fire Alarm Control Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations. Specifications: • • • • • • • UL Listed for Access Control System (UL294). Switch selectable 12VDC or 24VDC power limited output. Input 115VAC/60Hz, 0.6 amp. 1.75 AMPS continuous supply current @ 12VDC or 24VDC. Filtered and electronically regulated output. Outputs are overload protected by PTC’s. Delay timing is reset (before, during, or after a delay) by dry contact closure (RES & GND). • An output is provided for unlocking devices (electric strikes). • An auxiliary output is provided which is not affected by the Fire Alarm Relay Terminals. • An AC Fail relay (Form “C” 1 A @ 28VDC) indicates AC is powering unit. • A green LED also indicates the AC is powering unit. • A red LED indicates the DC outputs are powered. • An output relay (Form “C” 1 A @ 28VDC) indicates the DC Lock+ terminal is powered and not the Strike+ terminal, or vice versa. • Field selectable: Delayed Egress, Access-controlled Egress, or no delays (a standard power supply). • Delay for delayed egress applications is 15 or 30 seconds field selectable. (Except factory shipped “UBCDE” model.) • Delayed egress has field selectable none or 1 second nuisance delay. • Delayed egress has alarm relay to switch on alarm power. • Delay for access-controlled applications is 30 or 45 seconds field selectable. • Delays are triggered by a dry contact closure (TR & GND). Enclosure Dimensions: 8.5”H x 7.5”W x 3.5”D Power Supply Output Specifications: Output Switch Max VDC Position Load DC 12VDC SW5 Open 1.75 amp 1.75 amp SW5 Closed 24VDC Battery Backup: 12VDC - One (1) 12VDC 7.2Ah battery will provide 4 hours of backup @ 1.25 AMPS. 24VDC - Two (2) 12VDC 7.2Ah batteries will provide 4 hours of backup @ 1.25 AMPS. Note: For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. When standby batteries are used, they must be lead-acid or gel type. Installation Instructions: The PS17-TD2 should be installed in accordance with The National Electrical Code and all applicable Local Regulations. See Terminal Identification Chart on page 3 for a description of each terminal function. 1. Mount the PS17-TD2 in desired location. 2. Connect 115VAC to the black and white flying leads of the transformer. 1 TR Secure green lead to earth ground. Use 18 AWG for all power connections (relay DC outputs). Use 22 AWG to 18 AWG for NC C NO NC AC FAIL ALARM NO C power limited PS17-TD2 Circuits (trigger inputs, SEE NOTE 7 AC FAIL ALARM MONITOR IF DESIRED (FOR DELAYED dry outputs). EGRESS ONLY) 3. Open SW5 for 12VDC ON DC SW5 SEE NOTE 6 output - Close SW5 for OPEN - 12V CLOSED - 24V OFF 24VDC output. 4. Measure output voltage AC *4 OFF LONG DELAY ON SHORT DELAY before connecting SEE NOTE 4 *3 OFF ACCESS - CONTROLLED EGRESS ON DELAYED EGRESS *2 OFF NUISANCE DELAY ON NO NUISANCE DELAY devices. This helps avoid OUTPUT potential damage. MONITOR IF DESIRED 5. Jumper TRG1 and TRG2 unless continuity L O C K + S T R I K E + C O M -- A U X + F A C P A U X --+ BAT --AC AC is provided through a fire alarm circuit as shown on page 5. To Electric Standby One Punchout To Access 6. Connect appropriate Locks and Battery for AC Entry Only. Control See Battery Request to Volatile Memory signaling notification Note Exit Switches if Required All other wires devices to AC Fail may be grouped in other punchouts. supervisory outputs marked [N.C., C, and N.O.] C is closed Black Lead to N.C. when AC 115VAC input 60 Hz, 0.6 A power is connected. XFMR C is closed to N.O. White Lead when AC power is off. Green Lead 7. When a delay is to be used install a N.O. Momentary Reset switch across terminals Fig. 1 marked [RES - GND]. 8. When a delay is to be used install a N.O. Momentary triggering Switch across terminals marked [TR - GND]. 9. For monitoring the output relay governing terminals marked [Lock+ and Strike+] use the [C, N.C. and N.O.] terminals next to [TRG1 and TRG2]. C will be closed to N.C. when Lock+ is powered. 10. When a Delayed Egress is used, an alarm is required by all Codes. The alarm relay is used to switch on the alarm. C will close to N.C. when the alarm should sound: immediately at triggering with no nuisance delay, or after one continuous second of trigger with nuisance delay. If moderate power is required for the alarm it can be obtained by jumping [AUX+ to C] on the Alarm relay; and N.C. on the Alarm relay and [AUX ---] to the alarm. 11.See diagrams on following pages for Delayed Egress, Access-Controlled Egress, and Fire Alarm interface applications wiring suggestions. GND RES GND 1 2 3 4 TRG1 TRG2 C NC NO LED Diagnostics: RED (DC) ON OFF ON OFF 2 GREEN (AC) ON ON OFF OFF POWER SUPPLY STATUS Normal output, powered by AC No DC output, but AC is on Normal output, backup battery power only No AC nor battery backup Battery Backup. Use sealed lead-acid 12 volt secondary batteries only. Connect two in series for 24 volts. DCI supplies 5 Ah, 7.2 Ah, and 12 Ah sizes. Terminal Identification: Terminal Legend Function/Description TRG1 & TRG2 These input terminals are designed to connect to the closed C and N.O. terminals of an access control or fire alarm relay. These must be jumped otherwise. These terminals control LOCK+, and STRIKE+, as well as PS17-TD2 output relay contacts N.C., N.O., C. LOCK+ This terminal provides DC output voltage when TRG1 and TRG2 are shorted together and are typically used to power electromagnetic locks. Two locks may be connected in parallel on LOCK + and COM --- (Fig. 2, page 5). STRIKE+ This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and is typically used to power Electric Strikes. N.C., N.O., C (adjoining) TRG1 & TRG2 Isolated dry Form “C” contacts. Shorting TRG1 and TRG2 together causes these contacts to switch. They are typically used for controlling multiple power supplies with fire alarm tie-in (Figs. 7 and 8, page 7). AUX+ Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation. COM --- , AUX ---, BAT ---, GND (adjoining RES), GND (adjoining TR), and TRG2 All six are common (---) output (ground). FACP Spare wiring terminal used for fire alarm tie-in application (Fig. 7, page 7). BAT+, BAT- Battery backup connections. Apply proper voltage SLA batteries. Batteries are trickle charged with 13.6 or 26.6 volts. RES & GND Are normally open. To reset either time delay at any time-close momentarily. TR & GND Trigger either Delayed Egress or Access-controlled Egress by closing momentarily TR to GND. If nuisance delay is on in Delayed Egress Mode, trigger must be closed continuously for one full second. 3 Dip Switch Settings ALARM NO C NC C NO NC AC FAIL TR GND OPEN ON RES GND TRG1TRG2 C NC NO AC CLOSED 1 2 3 4 PS17-TD2 DC VR1 DOOR CONTROLS INTERNATIONAL DEXTER, MICHIGAN 48130 MADE IN U.S.A. AUX --- NOTES ON: SWITCH SELECTION TABLE: 1 NOT CONNECTED 2 OFF NUISANCE DELAY 3 OFF ACCESS - CONTROLLED EGRESS 4 OFF LONG DELAY + BAT --- 2 ON 3 ON 4 ON AC AC NO NUISANCE DELAY DELAYED EGRESS SHORT DELAY DELAYED EGRESS : IN THIS MODE #4 SWITCH SELECTS SHORT DELAY OF 15 SEC. OR LONG DELAY OF 30 SEC., AND #2 SWITCH SELECTS NONE OR A 1 SEC. NUISANCE DELAY. 3 OFF ACCESS CONTROLLED EGRESS : IN THIS MODE #4 SWITCH SELECTS SHORT RELOCK DELAY OF 30 SEC. OR LONG RELOCK DELAY OF 45 SEC., #2 SWITCH IS DISABLED. 4 SW SW5 LOCK + STRIKE + COM -- AUX + FACP 3 ON SW5 CLOSED - 24V OPEN - 12V Fig. 2 - Typical Delayed Egress System: THESE ARE CODE - SPECIFIC TERMS. ONE OR MORE OF THESE RELAYS REQUIRED UNDER EVERY U. S. MODEL BUILDING CODE. FIRE - PROTECTIVE SIGNALING SYSTEM , FIRE ALARM SYSTEM , FIRE COMMAND CENTER , AUTOMATIC SPRINKLER SYSTEM , AUTOMATIC SMOKE - DETECTION SYSTEM, AND/OR AUTOMATIC FIRE - DETECTION SYSTEM RELAYS TO ALARM IN EXIT DEVICE (THRU DL - 418 ) OR TO LOCAL ALARM (REQUIRED) TO REMOTE ANNUNCIATOR (OPTIONAL) NEMA - 1 ENCLOSURE MONITOR AS DESIRED ALARM NO C NC C NO NC AC FAIL SW5 CLOSED - 24V OPEN - 12V TR GND SW5 DL - 418 DOOR LOOP MONITOR AS DESIRED (ALSO SEE FIG. 5) RES GND TRG1TRG2 C NC NO OPEN - 12V AC ON SW5 JUMPER DC CLOSED - 24V 1 2 3 4 4 OFF 3 OFF 2 OFF LONG DELAY ACCESS - CONTROLLED EGRESS NUISANCE DELAY L O C K + S T R I K E + C O M -- A U X + F A C P A U X --- 4 ON 3 ON 2 ON SHORT DELAY DELAYED EGRESS NO NUISANCE DELAY + BAT --- AC AC TRANSFORMER 115 VAC IN FROM ALARM NC TR F R O M F R O M F R O M F R O M T R G 1 R E S G N D L O C K + -1b 1 SWITCH BAR, PANIC HARDWARE, OR FIRE EXIT HARDWARE EXIT ELECTROMAGNETIC LOCK(S) HORN (IF PRESENT) PANNEX 120, 1200, or 1300 SERIES + + SPDT ALTERNATING 1a Ja le SECURITY SWITCH THE ALARM SOUNDS UNTIL RESET, THUS ITS DURATION IS WELL TO DISCUSS: TO MAKE ALARM CEASE UPON DOOR RELEASE MOVE THE JUMPER FROM AUX TO LOCK+. 1401 MAGNET BLACK WHT GRN RED 24V SHOWN 1401 MAGNET BLACK WHT GRN RED ON RESET/OFF DCI 210 - LED 5 Fig. 3 - Typical Access-Controlled Egress System: FIRE - PROTECTIVE SIGNALING SYSTEM , FIRE ALARM SYSTEM , FIRE COMMAND CENTER , AUTOMATIC SPRINKLER SYSTEM , AUTOMATIC SMOKE - DETECTION SYSTEM, AND/OR AUTOMATIC FIRE - DETECTION SYSTEM RELAYS THESE ARE CODE - SPECIFIC TERMS. IF ONE OR MORE OF THESE SYSTEMS IS PROVIDED, A RELAY TO UNLOCK IS REQUIRED FOR EACH SYSTEM. OTHERWISE JUMPER TRG1 TO TRG2 TO NO SPST RESET SWITCH (OPTIONAL) NEMA 1 ENCLOSURE NOT USED MONITOR AS DESIRED ALARM NO C NC C NO NC AC FAIL SW5 CLOSED - 24V OPEN - 12V TR GND SW5 MONITOR AS DESIRED RES GND TRG1TRG2 C NC NO OPEN - 12V AC ON DC CLOSED - 24V 1 2 3 4 4 OFF 3 OFF 2 OFF LONG DELAY ACCESS - CONTROLLED EGRESS NUISANCE DELAY LOCK + STRIKE + COM -- AUX + FACP SW5 4 ON 3 ON 2 ON SHORT DELAY DELAYED EGRESS NO NUISANCE DELAY + BAT --- AUX --- AC AC TRANSFORMER FOR VOLATILE MEMORY IF REQUIRED OPTIONAL LED "EXIT" SPST FORM A AND SPST FORM B MOMENTARY 1. 2. 3. 4. 5. 6 SW5 : Select 12VDC or 24VDC Dip SW1 : Any , has no effect. Dip SW2 : Any , has no effect. Dip SW3 : OFF (Access - Controlled Egress). Dip SW4 : OFF 45 sec. relock, ON - 30 sec. relock. INTERIOR ACCESS CONTROL V. M. EXTERIOR ACCESS CONTROL DEVICE OPTIONAL 1401 MAGNET ELECTRONICS ELECTROMAGNETIC LOCK(S) BLACK WHT GRN RED 24V SHOWN 1401 MAGNET BLACK WHT GRN RED 115 VAC IN Application Diagrams when used as a typical power supply not using delay features: Fig. 4 - Typical single mag lock or door strike installation with fire alarm tie-in using trigger controlled output: Fig. 6 - Typical mag lock with fire alarm tie-in using aux output installation: Fig. 7 - Latching fire alarm tie-in with manual reset: Fig. 5 - Typical dual mag lock installation with fire alarm tie-in using trigger controlled outputs: Fig. 8 - Multiple PS17-TD2 power supply connections: PS17-TD2 #1 PS17-TD2 #2 7 Enclosure Dimensions: 8”H x 7.25”W x 3.5”D TOP ONLY 1.25" TOP & BOTTOM FRONT 3.5" 3.5" 2.25" 0 0 7.25" 3.63" 0 .625" 3.63" 6.75" 0 2.25" 1.13" 4" FRONT FRONT 2" 4" 7" 8" 8 LEFT 7" BACK 8" Door Controls International 2362 Bishop Circle East, Dexter, MI 48130 Tel.: 800-742-3634, Fax: 800-742-0410 IIPS17-TD2 - Rev. 062101 RIGHT 3.5"