PS17-TD2 Power Supply with Time Delay

advertisement
Door Controls International
PS17-TD2
Access Control Power Supply/Charger
Rev. 062101
Overview:
The PS17-TD2 is a power supply that will convert 115 VAC/60Hz input into two individually PTC protected
12VDC or 24VDC outputs (see specifications) and provide time delays to conform with both Delayed Egress and
Access-controlled Egress provisions of the U.S. model building codes. It is intended for use in applications
requiring UL Listing for Access Controls (UL294) and applications requiring an interface with Fire Alarm
Control Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations.
Specifications:
•
•
•
•
•
•
•
UL Listed for Access Control System (UL294).
Switch selectable 12VDC or 24VDC power limited output.
Input 115VAC/60Hz, 0.6 amp.
1.75 AMPS continuous supply current @ 12VDC or 24VDC.
Filtered and electronically regulated output.
Outputs are overload protected by PTC’s.
Delay timing is reset (before, during, or after a delay) by
dry contact closure (RES & GND).
• An output is provided for unlocking devices (electric strikes).
• An auxiliary output is provided which is not affected by the
Fire Alarm Relay Terminals.
• An AC Fail relay (Form “C” 1 A @ 28VDC) indicates AC is powering unit.
• A green LED also indicates the AC is powering unit.
• A red LED indicates the DC outputs are powered.
• An output relay (Form “C” 1 A @ 28VDC) indicates the DC Lock+ terminal is powered
and not the Strike+ terminal, or vice versa.
• Field selectable: Delayed Egress, Access-controlled Egress, or no delays (a standard power supply).
• Delay for delayed egress applications is 15 or 30 seconds field selectable.
(Except factory shipped “UBCDE” model.)
• Delayed egress has field selectable none or 1 second nuisance delay.
• Delayed egress has alarm relay to switch on alarm power.
• Delay for access-controlled applications is 30 or 45 seconds field selectable.
• Delays are triggered by a dry contact closure (TR & GND).
Enclosure Dimensions: 8.5”H x 7.5”W x 3.5”D
Power Supply Output Specifications:
Output
Switch
Max
VDC
Position
Load DC
12VDC
SW5 Open
1.75 amp
1.75 amp
SW5 Closed
24VDC
Battery Backup:
12VDC - One (1) 12VDC 7.2Ah battery will provide 4 hours of backup @ 1.25 AMPS.
24VDC - Two (2) 12VDC 7.2Ah batteries will provide 4 hours of backup @ 1.25 AMPS.
Note: For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the loss
of output voltage. When standby batteries are used, they must be lead-acid or gel type.
Installation Instructions:
The PS17-TD2 should be installed in accordance with The National Electrical Code and all applicable Local
Regulations. See Terminal Identification Chart on page 3 for a description of each terminal function.
1. Mount the PS17-TD2 in desired location.
2. Connect 115VAC to the black and white flying leads of the transformer.
1
TR
Secure green lead to
earth ground.
Use 18 AWG for all
power connections (relay
DC outputs). Use
22 AWG to 18 AWG for
NC C NO NC AC FAIL
ALARM NO C
power limited
PS17-TD2
Circuits (trigger inputs,
SEE NOTE 7
AC FAIL
ALARM
MONITOR IF DESIRED
(FOR DELAYED
dry outputs).
EGRESS ONLY)
3. Open SW5 for 12VDC
ON
DC
SW5
SEE NOTE 6
output - Close SW5 for
OPEN - 12V
CLOSED - 24V
OFF
24VDC output.
4. Measure output voltage
AC
*4 OFF LONG DELAY
ON SHORT DELAY
before connecting
SEE NOTE 4
*3 OFF ACCESS - CONTROLLED EGRESS
ON DELAYED EGRESS
*2 OFF NUISANCE DELAY
ON NO NUISANCE DELAY
devices. This helps avoid
OUTPUT
potential damage.
MONITOR
IF DESIRED
5. Jumper TRG1 and
TRG2 unless continuity
L O C K + S T R I K E + C O M -- A U X + F A C P A U X --+ BAT --AC
AC
is provided through a
fire alarm circuit as
shown on page 5.
To Electric
Standby
One Punchout
To Access
6. Connect appropriate
Locks and
Battery
for AC Entry Only.
Control
See Battery
Request to
Volatile Memory
signaling notification
Note
Exit Switches
if Required
All other wires
devices to AC Fail
may be grouped
in other punchouts.
supervisory outputs
marked [N.C., C,
and N.O.] C is closed
Black Lead
to N.C. when AC
115VAC input
60 Hz, 0.6 A
power is connected.
XFMR
C is closed to N.O.
White Lead
when AC power is off.
Green Lead
7. When a delay is to be
used install a N.O.
Momentary Reset switch
across terminals
Fig. 1
marked [RES - GND].
8. When a delay is to be used install a N.O. Momentary triggering Switch across terminals marked
[TR - GND].
9. For monitoring the output relay governing terminals marked [Lock+ and Strike+] use the [C, N.C. and N.O.]
terminals next to [TRG1 and TRG2]. C will be closed to N.C. when Lock+ is powered.
10. When a Delayed Egress is used, an alarm is required by all Codes. The alarm relay is used to switch on the
alarm. C will close to N.C. when the alarm should sound: immediately at triggering with no nuisance delay, or
after one continuous second of trigger with nuisance delay. If moderate power is required for the alarm it can
be obtained by jumping [AUX+ to C] on the Alarm relay; and N.C. on the Alarm relay and [AUX ---] to the alarm.
11.See diagrams on following pages for Delayed Egress, Access-Controlled Egress, and Fire Alarm
interface applications wiring suggestions.
GND
RES GND
1 2 3 4
TRG1 TRG2 C
NC
NO
LED Diagnostics:
RED (DC)
ON
OFF
ON
OFF
2
GREEN (AC)
ON
ON
OFF
OFF
POWER SUPPLY STATUS
Normal output, powered by AC
No DC output, but AC is on
Normal output, backup battery power only
No AC nor battery backup
Battery Backup. Use sealed lead-acid 12 volt secondary batteries only. Connect two in series for 24 volts. DCI
supplies 5 Ah, 7.2 Ah, and 12 Ah sizes.
Terminal Identification:
Terminal
Legend
Function/Description
TRG1 & TRG2
These input terminals are designed to connect to the closed C and N.O. terminals of
an access control or fire alarm relay. These must be jumped otherwise. These
terminals control LOCK+, and STRIKE+, as well as PS17-TD2 output relay contacts
N.C., N.O., C.
LOCK+
This terminal provides DC output voltage when TRG1 and TRG2 are shorted together
and are typically used to power electromagnetic locks. Two locks may be connected
in parallel on LOCK + and COM --- (Fig. 2, page 5).
STRIKE+
This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and
is typically used to power Electric Strikes.
N.C., N.O., C
(adjoining) TRG1
& TRG2
Isolated dry Form “C” contacts. Shorting TRG1 and TRG2
together causes these contacts to switch. They are typically used
for controlling multiple power supplies with fire alarm tie-in (Figs. 7 and 8, page 7).
AUX+
Continuous positive (+) DC power output voltage. It is not affected by
TRG1, TRG2 operation.
COM --- , AUX ---,
BAT ---, GND
(adjoining RES),
GND (adjoining TR),
and TRG2
All six are common (---) output (ground).
FACP
Spare wiring terminal used for fire alarm tie-in application (Fig. 7, page 7).
BAT+, BAT-
Battery backup connections. Apply proper voltage SLA batteries.
Batteries are trickle charged with 13.6 or 26.6 volts.
RES & GND
Are normally open. To reset either time delay at any time-close momentarily.
TR & GND
Trigger either Delayed Egress or Access-controlled Egress by closing momentarily
TR to GND. If nuisance delay is on in Delayed Egress Mode, trigger must be closed
continuously for one full second.
3
Dip Switch Settings
ALARM NO C NC C NO NC AC FAIL
TR GND
OPEN ON
RES GND TRG1TRG2 C NC NO
AC
CLOSED
1 2 3 4
PS17-TD2
DC
VR1
DOOR CONTROLS INTERNATIONAL
DEXTER, MICHIGAN 48130
MADE IN U.S.A.
AUX ---
NOTES ON:
SWITCH SELECTION TABLE:
1
NOT CONNECTED
2 OFF NUISANCE DELAY
3 OFF ACCESS - CONTROLLED EGRESS
4 OFF LONG DELAY
+ BAT ---
2 ON
3 ON
4 ON
AC
AC
NO NUISANCE DELAY
DELAYED EGRESS
SHORT DELAY
DELAYED EGRESS : IN THIS MODE #4 SWITCH SELECTS SHORT
DELAY OF 15 SEC. OR LONG DELAY OF 30 SEC., AND #2 SWITCH
SELECTS NONE OR A 1 SEC. NUISANCE DELAY.
3 OFF ACCESS CONTROLLED EGRESS : IN THIS MODE #4 SWITCH SELECTS
SHORT RELOCK DELAY OF 30 SEC. OR LONG RELOCK DELAY OF
45 SEC., #2 SWITCH IS DISABLED.
4
SW
SW5
LOCK + STRIKE + COM -- AUX + FACP
3 ON
SW5 CLOSED - 24V
OPEN - 12V
Fig. 2 - Typical Delayed Egress System:
THESE ARE CODE - SPECIFIC TERMS.
ONE OR MORE OF THESE RELAYS REQUIRED
UNDER EVERY U. S. MODEL BUILDING CODE.
FIRE - PROTECTIVE SIGNALING SYSTEM ,
FIRE ALARM SYSTEM ,
FIRE COMMAND CENTER ,
AUTOMATIC SPRINKLER SYSTEM ,
AUTOMATIC SMOKE - DETECTION SYSTEM, AND/OR
AUTOMATIC FIRE - DETECTION SYSTEM RELAYS
TO ALARM IN EXIT DEVICE
(THRU DL - 418 )
OR TO LOCAL ALARM
(REQUIRED)
TO REMOTE
ANNUNCIATOR
(OPTIONAL)
NEMA - 1 ENCLOSURE
MONITOR
AS DESIRED
ALARM NO C NC C NO NC AC FAIL
SW5 CLOSED - 24V
OPEN - 12V
TR GND
SW5
DL - 418
DOOR LOOP
MONITOR
AS DESIRED
(ALSO SEE FIG. 5)
RES GND TRG1TRG2 C NC NO
OPEN - 12V
AC
ON
SW5
JUMPER
DC
CLOSED - 24V
1 2 3 4
4 OFF
3 OFF
2 OFF
LONG DELAY
ACCESS - CONTROLLED EGRESS
NUISANCE DELAY
L O C K + S T R I K E + C O M -- A U X + F A C P
A U X ---
4 ON
3 ON
2 ON
SHORT DELAY
DELAYED EGRESS
NO NUISANCE DELAY
+ BAT ---
AC
AC
TRANSFORMER
115 VAC IN
FROM
ALARM
NC
TR
F
R
O
M
F
R
O
M
F
R
O
M
F
R
O
M
T
R
G
1
R
E
S
G
N
D
L
O
C
K
+
-1b
1
SWITCH BAR,
PANIC HARDWARE, OR
FIRE EXIT HARDWARE
EXIT
ELECTROMAGNETIC
LOCK(S)
HORN
(IF PRESENT)
PANNEX 120, 1200, or 1300 SERIES
+
+
SPDT
ALTERNATING
1a
Ja le
SECURITY
SWITCH
THE ALARM SOUNDS UNTIL RESET, THUS
ITS DURATION IS WELL TO DISCUSS:
TO MAKE ALARM CEASE
UPON DOOR RELEASE
MOVE THE JUMPER FROM AUX TO LOCK+.
1401
MAGNET
BLACK
WHT
GRN
RED
24V SHOWN
1401
MAGNET
BLACK
WHT
GRN
RED
ON
RESET/OFF
DCI 210 - LED
5
Fig. 3 - Typical Access-Controlled Egress System:
FIRE - PROTECTIVE SIGNALING SYSTEM ,
FIRE ALARM SYSTEM ,
FIRE COMMAND CENTER ,
AUTOMATIC SPRINKLER SYSTEM ,
AUTOMATIC SMOKE - DETECTION SYSTEM, AND/OR
AUTOMATIC FIRE - DETECTION SYSTEM RELAYS
THESE ARE CODE - SPECIFIC TERMS.
IF ONE OR MORE OF THESE SYSTEMS
IS PROVIDED, A RELAY TO UNLOCK
IS REQUIRED FOR EACH SYSTEM.
OTHERWISE JUMPER TRG1 TO TRG2
TO NO SPST
RESET SWITCH
(OPTIONAL)
NEMA 1 ENCLOSURE
NOT USED
MONITOR
AS DESIRED
ALARM NO C NC C NO NC AC FAIL
SW5 CLOSED - 24V
OPEN - 12V
TR GND
SW5
MONITOR
AS DESIRED
RES GND TRG1TRG2 C NC NO
OPEN - 12V
AC
ON
DC
CLOSED - 24V
1 2 3 4
4 OFF
3 OFF
2 OFF
LONG DELAY
ACCESS - CONTROLLED EGRESS
NUISANCE DELAY
LOCK + STRIKE + COM -- AUX + FACP
SW5
4 ON
3 ON
2 ON
SHORT DELAY
DELAYED EGRESS
NO NUISANCE DELAY
+ BAT ---
AUX ---
AC
AC
TRANSFORMER
FOR VOLATILE
MEMORY IF
REQUIRED
OPTIONAL
LED
"EXIT"
SPST FORM A
AND
SPST FORM B
MOMENTARY
1.
2.
3.
4.
5.
6
SW5 : Select 12VDC or 24VDC
Dip SW1 : Any , has no effect.
Dip SW2 : Any , has no effect.
Dip SW3 : OFF (Access - Controlled Egress).
Dip SW4 : OFF 45 sec. relock, ON - 30 sec. relock.
INTERIOR
ACCESS CONTROL
V. M.
EXTERIOR
ACCESS CONTROL
DEVICE OPTIONAL
1401
MAGNET
ELECTRONICS
ELECTROMAGNETIC
LOCK(S)
BLACK
WHT
GRN
RED
24V SHOWN
1401
MAGNET
BLACK
WHT
GRN
RED
115 VAC IN
Application Diagrams when used as a typical power supply not using delay features:
Fig. 4 - Typical single mag lock or door strike installation
with fire alarm tie-in using trigger controlled output:
Fig. 6 - Typical mag lock with fire alarm tie-in using
aux output installation:
Fig. 7 - Latching fire alarm tie-in with manual reset:
Fig. 5 - Typical dual mag lock installation with fire alarm
tie-in using trigger controlled outputs:
Fig. 8 - Multiple PS17-TD2 power supply
connections:
PS17-TD2 #1
PS17-TD2 #2
7
Enclosure Dimensions:
8”H x 7.25”W x 3.5”D
TOP
ONLY
1.25"
TOP & BOTTOM
FRONT
3.5"
3.5"
2.25"
0
0
7.25"
3.63"
0
.625"
3.63"
6.75"
0
2.25"
1.13"
4"
FRONT
FRONT
2"
4"
7"
8"
8
LEFT
7"
BACK
8"
Door Controls International
2362 Bishop Circle East, Dexter, MI 48130
Tel.: 800-742-3634, Fax: 800-742-0410
IIPS17-TD2 - Rev. 062101