INSTALLATION INSTRUCTIONS
CC62
REMOTE RELAY MODULE
The CC62 Remote Relay Module consists of six double-pole double-throw relays which are controlled by
way of IR commands from a Xantech RC68+ (or RC68) Programmer. The RC68+ commands are "taught"
to learning devices and passed to the CC62 IR IN (S) and G input terminals via Xantech IR receivers,
keypads, etc. The six relays give "dry contact" closures for a multitude of uses where simple contact
closures are needed. Any combination of one to six relays may be selected and operated in several ways
using the commands from the RC68+ Programmer.
CC62
REMOTE RELAY MODULE
+12V
GND
GND
IR IN
IR CONFIRM
RELAY
1
RELAY
2
RELAY
3
RELAY
4
RELAY
5
RELAY
6
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
12 VDC
1A
Fig. 1 The Model CC62 Remote Relay Module
• 2 normally open and 2 normally closed contacts per relay.
• Six 6-terminal screw-type plug-in connectors - one for each of the relays.
• Each relay and the relay poles are isolated from each other allowing use in circuits of differing potentials
and grounds.
• 4-terminal IR IN and +12V plug-in for Xantech IR Receivers, Smart Pads, connecting blocks and other
devices.
• IR Confirm LED lights with RC68+ and non RC68+ IR signals.
• RC68+ IR commands permit Pair, Toggle, Momentary and Group mode operations as well as different
IR codes for use of multiple CC62's.
• The CC62's Code Group number is 60.
• Universal mounting fits 19-inch racks or any 3-1/2" X 19" flat surface. Extends about 2-3/4" behind panel
with cables connected.
• Requires RC68+ (or RC68) Programmer and 782-00 Power Supply.
• Power: 12 VDC @ 300mA.
• Dimensions: 19" W x 3-1/2" H x 2-1/4" D
RC68+ PROGRAMMER / REMOTE CONTROL
The RC68+ Programmer (available separately) contains all commands necessary to operate the CC62 (see
Fig. 2).
• You will need it to program universal learning devices such as the Xantech URC-1 learning remote, the
Xantech Smart Pads, the 590 Controller, the 710 Fone Link, etc., with commands that operate the CC62.

1
Remote Control Switchers
FEATURES AND SPECIFICATIONS
• 6 double-pole double-throw relays rated at 5 Amps. 30 volts DC.
• NOTE: The RC68+ codes operate several other Xantech models as well, such as the RS41AV, CC12,
ZPR68, etc. Therefore, only the button descriptions that apply to the operation of the CC62 are
listed below. All others should be ignored.
CAUTION: While the RC68+ can be used as a handheld remote control, it is highly recommended it not
be given to the final user for the following reasons:
• Since it includes adjustable code groups, the user may inadvertently alter the installed configurations.
• Also, since the user will require IR commands from other brands of equipment to control the total system,
in addition to those of the CC62, all commands should be consolidated into one learning device, for ease
of use.
APPLICABLE RC68+ BUTTON DESCRIPTIONS (With the "D" Overlay. Refer to Fig. 2)
Relay Numbers (1 ~ 6).
These numbers identify the row of button commands that apply
to each relay on the CC62.
Relay
Numbers
(1 through 6)
Code Group Numbers.
The CC62 is capable of being set to 30 different IR code groups.
The code groups are identified by the numbers and letters that
are on the face of each button.
NOTE: When shipped from the factory, the CC62 is set to code
group number 60.
1
2
3
4
5
6
Code Group
Numbers
(on face of
each button)
Place the
"D" Overlay
on the RC68+
D
80
48
10
90
OFF
ON
TGL
MMT
00
C0
50
D0
OFF
ON
TGL
MMT
40
A0
30
B0
OFF
ON
TGL
MMT
20
E0
70
F0
OFF
ON
TGL
MMT
60
88
18
98
OFF
ON
TGL
MMT
08
A8
38
B8
OFF
ON
TGL
28
E8
78
01
41
21
61
09
29
MMT
F8
69
GP-ON
GP-ON
68
C8
58
Relay
Command
Modes
(for 6
relays)
D8
49
GP-OFF
Be sure to set the RC68+ (or RC68) to the same number!
It may be necessary to change the CC62 to a different code
RC68+
group if it is used in a common IR bus controlled system with
other Xantech CC62's, to avoid mutual interaction.
Refer to the RC68+ instructions for code group setting
Fig. 2 RC68+ Programmer
details and procedures!
Relay Command Modes.
Depending on the installation, you may want to have the CC62 respond to IR commands in different ways.
The basic modes of operation for each relay on the CC62 are as follows:
OFF - Activates the IR command that turns the selected relay OFF (the N/C position).
ON - Activates the IR command that turns the selected relay ON (the N/O position).
These dedicated OFF and ON (paired) commands are helpful when sending IR commands "blind"
from locations where you have no visual aid for status.
TGL - (Toggle Mode) - The first press of this button turns the selected relay ON (the N/O selection) - the
second press turns it OFF (the N/C selection).
MMT - (Momentary Mode) - Pressing this button causes the selected relay to go ON (the N/O selection)
but stays ON only as long as the MMT code is being sent. When released, the relay returns to the OFF
position (the N/C selection).
GP-ON - (group ON).
This button (labeled F8 on the button face) causes the CC62 to turn all 6 relays ON at the same time
(the N/O selections). GP-ON overrides all individual settings.
GP-OFF - (group OFF).
This button (labeled D8 on the button face) causes the CC62 to turn all 6 relays OFF (the N/C
selection). It also turns any relay(s) OFF that may have been set to ON with the ON command.
NOTE: OFF, ON and TGL (toggle) operation will still operate for any individual relay after Group ON
is executed.
2

GP-OFF
E1
89
C9
A9
71
19
59
39
E9
79
F1
99
D9
B9
F9
CC62
The CC62 should normally be plugged into an unswitched AC outlet. However, if the power to the CC62
is interrupted by a power failure or other reason, the internal memory will retain the last selected switched
condition for each of the relays.
IR RCVR INPUT CONNECTOR
This 4-terminal input has electrical connections for +12V, GND
(chassis ground), GND (IR signal ground) and IR IN (IR signal).
The GND terminal closest to the IR IN terminal is provided so that,
if needed, the IR signal ground can be isolated from the chassis
ground. This isolation may be necessary in some instances to
prevent ground loop problems, etc.
Jumper ON Position.
(Common ground
between GND and GND
terminals - factory
default setting)
A special jumper, inside the CC62, gives you the option to make
the grounds common or have them isolated. Refer to Fig. 3.
To gain access to this jumper, remove the eight screws that
secure the top cover to the metal chassis. Carefully lift the cover
off. When you have made the adjustment, reassemble in reverse
order.
NOTE: When shipped from the factory, the jumper is installed in
the ON (common) position.
PCB
Metal Chassis
JP1
JP1
LED1
LED1
PCB
Jumper OFF Position (Isolated Grounds).
No connection between the GND and GND terminals.
Fig. 3 Location and Adjustment of
Grounding Jumper
CAUTION: When powering IR receivers and keypads directly from the CC62, you must leave the jumper
installed in the ON position so that the two G terminals are connected in common. This provides the
needed ground return for the IR signal.
Change the jumper to the OFF position only when powering IR source devices separately from the
CC62 and there is a need for electrical isolation.
• To activate shade or drape pulls, projector lifts, screen drops, etc. Use Momentary On modes at
relay #1 to close and at relay # 2 to open, if such devices require two separate dry contacts to operate.
• To switch low voltage lighting or other devices: Use Toggle or the ON & OFF (pair) commands. Pair
commands allow a known ON/OFF status from remote rooms where visual status is not possible.
• Amplifier A/B switching: Each relay can be connected so that a stereo pair of speakers (in each remote
room) can be switched between two AV receivers. This effectively creates a simple 2-zone system
addressable from each room. Refer to Fig. 4.
Each remote control and keypad used in the system needs to be programmed with Toggle or Pair
commands from the RC68+ to do the A/B switching. In addition, each room needs a dedicated learning
remote or keypad having the RC68+ IR commands that operate the specific CC62 relay for each room.
NOTE: The CC62 is shown connected to Xantech 760-00 Match Maker room volume controls (Fig. 4)
for individual room control. When set correctly, the Match Makers will provide the proper impedance match
between the speakers and the amplifiers. See the 760-00 Installation Instructions for details.
• Another important application of the CC62 is to provide IR-to-switch closures for a 590 Programmable
Controller. This permits multiple sequenced commands to be generated from a single RC68+ IR
command or to convert RC68+ commands to other brand commands. Fig. 5 illustrates such a system.
Up to 16 independent closures are possible by using as many as three CC62's with a 590-00.
Use Momentary On programming.
CC62

3
Remote Control Switchers
INSTALLATION
Typical applications for the CC62 are as follows:
MAIN ROOM
SOURCE
COMPONENTS
SOURCE
AV RECEIVERS
(with built-in power amps)
Satellite Receiver
To Multiroom input jack
or emitter on AV receivers.
(depends on brand)
VCR
AV Receiver "A"
AV Receiver "B"
282M
or
283M
Laser Disc
R+
Mouse
Emitters
R– L–
L+
R+
R– L–
Common (or Gnd) bus for speaker
signals. Use the CB18 (or other
terminal strip) to make connections.
L+
To 120 V AC
(unswitched)
CD Changer
782-00
Power
Supply
CC62
R-
L-
Remote Relay Module
Cassette DecK
L+ ("A")
CC62
RELAY
1
REMOTE RELAY MODULE
L+
R+
("A")
R+
GND
GND
+12V
IR IN
IR CONFIRM
RELAY
2
RELAY
3
RELAY
4
RELAY
5
RELAY
6
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
R+
EMITTERS
("B")
12 VDC
1A
GND
791- 44
IR IN
+12 VDC
HIGH
IR
OUT
S TAT U S
791-44
Amplified
Connecting
Block
L+ ("B")
AMPLIFIED
CONNECTING BLOCK
IR
RCVR
12 VDC
3-Conductor Cables for IR
control signals (Home Runs).
Use a CB18 or other terminal
strip to handle the many
connections to the 791-44.
4-Conductor Speaker
Leads (Home Runs)
2-conductor lead carries +12V DC power to
the 791-44 and to the IR receivers & keypads
in the remote rooms.
S-62/64/66
Wall Speakers
L
R
780-10
760-00
"J" Box
Match Maker™
IR Receiver Vol. Control
REMOTE ROOM 1
L
480-00
R
760-00
Dinky Link ™ Match Maker™
Vol. Control
IR Receiver
REMOTE ROOM 2
L
R
Smart
Pad™
760-00
Match Maker™
Vol. Control
REMOTE ROOM 3
L
R
490DW-00
760-00
L
480-00
R
760-00
"J" Box Match Maker™
IR Receiver Vol. Control
Dinky Link ™ Match Maker™
IR Receiver
Vol. Control
REMOTE ROOM 4
REMOTE ROOM 5
L
R
Smart
Pad™
760-00
Match Maker™
Vol. Control
REMOTE ROOM 6
Fig. 4 A Typical Multiroom AV Receiver/Amp A/B Switching System
When using multiple CC62's or in combination with a 686-10 or other Xantech devices that respond to
RC68+
codes, keep the following items in mind:
1. Be sure each is set to a different IR Code Group to prevent mutual interaction. Refer to Fig. 2 and the
RC68+ Programmer Instructions for Code Group setting procedures.
2. To perform GROUP ON and OFF commands, it is necessary to sequence (macro) the different Group
ON and OFF codes for each CC62 in a learning device, such as the Xantech URC-1 Remote, a Smart
Pad™, or a 590-00 Controller.
3. A CB18 Strip-IR Connecting Block is used in Fig. 5 to make the many parallel connections from the
IR devices to the 791-44 Connecting Block. In this example, 8 IR devices are shown connected to the
4

CC62
CONTROLLED COMPONENTS
+12V DC
CC62
Remote Relay Module
782-00
Power
Supply
Satellite Receiver
CC62
or
To 120 V AC
(unswitched)
IR CONFIRM
IR IN
283M
Laser Disc
RELAY
2
Mouse
Emitters
GND
GND
+12V
VCR
RELAY
1
REMOTE RELAY MODULE
282M
RELAY
3
RELAY
4
RELAY
5
RELAY
6
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
12 VDC
1A
CD Changer
Wire size typically AWG 20-24
AV Receiver
Model 590 (rear panel)
2-conductor lead
carries +12V DC
power to the
791-44 and to the
IR receivers &
keypads connected
to the CB18.
RES DEL SEQ PGM ON
+
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 O G
12VDC
– +
1234
BANK
GND
791-44
791- 44
IR IN
+12 VDC
HIGH
IR
OUT
S TAT U S
EMITTERS
AMPLIFIED
CONNECTING BLOCK
IR
RCVR
12VDC
–
Amplified
Connecting
Block
12 VDC
IR Output
Ground or "–"
return wires.
CB18
786-00
Power Supply
(included)
8
V G G S
7
V G G S
6
V G G S
5
V G G S
4
V G G S
3
V G G S
2
V G G S
1
V G G S
V G G S
Strip-IR
Parallel
Connecting
Block
(see text,
item 3)
To 120 V AC
(unswitched)
3-conductor IR Control Leads
to IR receivers and Keypads
in Remote Rooms
(Home Runs)
9
Fig. 5 Using a CC62 to provide switch closures for a 590 Programmable Controller
• • • IMPORTANT • • •
1. Power Supply Considerations. Because of the relatively high current required to drive the relays
in the CC62, the Xantech Model 782-00 High Current Regulated Power Supply must be used. In Fig.
4, all of the system IR control devices are also powered from the 782-00 through the CC62.
To be sure you have sufficient power supply capability in your particular system, calculate the total
current required using the method shown in the 791-44 instructions, then add 300 mA for the CC62.
If the total exceeds 1 Amp, use a second supply to power the IR devices separately through the 79144.
2. The devices to be switched are connected to the Model CC62 by the six-terminal plug-in connectors.
The actual relays used in a given system are not important (if all six are not used). For instance, devices
will work just as well connected to relays 5 and 6 as they would connected to relays 1 and 2.
3. The Model CC62 is intended to be mounted on a flat surface or onto a standard 19-inch rack.
2-6-01
Rev.C
CC62

5
Remote Control Switchers
CB18. If more are needed, you could "double-up" on each connector or use an additional CB18.