Smart-UPS
On-Line 230 V
Unity output power factor single-phase,
double-conversion online UPS
with advanced management features
apc.com
apc.com
2
A versatile UPS developed
for unstable power
conditions worldwide
Smart-UPS On-Line provides high-density, double-conversion, online power
protection for servers, voice/data networks, medical labs, and light industrial
applications. The Smart-UPS On-Line is capable of supporting loads from
2.2 kVA – 10 kVA in a rack/tower convertible chassis. The 6 kVA, 8 kVA,
and 10 kVA models feature unity output power factor enabling them to support
power-hungry blade servers or heavily loaded equipment racks. When businesscritical systems require runtime in hours, not minutes, Smart-UPS On-Line can be
configured with multiple battery packs to meet aggressive runtime demands.
TM
The included PowerChute Network Shutdown management software provides
unattended graceful shutdown of network operating systems. Models 5 kVA
to 10 kVA include an integrated network management card for remote
management. The entire Smart-UPS On-Line family provides value to customers
with demanding power conditions, including a very wide input voltage window,
extremely tight output voltage regulation, frequency regulation, internal bypass,
and input power factor correction.
TM
apc.com
3
Smart-UPS On-Line
Industry-leading power factor maximizing UPS density
Rackmount and Tower SRT 2.2 kVA – 10 kVA
Standard Features
Best-in-class power density
More real power in watts, 0.9
pf on 2.2 kVA – 5 kVA, Unity
on 6 kVA – 10 kVA units.
High-efficiency “green mode”
Achieves 98 percent efficiency, which
saves utility and cooling costs without
compromising performance or reliability.
Graphical LCD display with
multicolor backlight
Intuitive interface provides detailed
and accurate information with ability
to configure locally.
Intelligent battery management
Temperature-compensated charging
extends life and advanced algorithms
recommend replacement date. The UPS
can inform user which batteries need
to be replaced and auto detect when
additional battery packs are added.
Built-in energy meter
Measures energy use and displays UPS
efficiency in various modes of operation
for easy energy tracking.
SRT6KXLI shown
Operate without battery
Ability to immediately protect equipment
when power returns after a complete
discharge of the battery.
Three-year warranty on electronics
Additional year of warranty protection
for electronics provides peace of mind.
apc.com
4
apc.com
5
apc.com
6
Smart-UPS On-Line
Proven performance with the world’s largest installed
base of single-phase, double-conversion products
Rackmount and Tower SRT 2.2 kVA – 10 kVA
Additional Features
Embedded network management card
with environmental monitoring
(5 kVA – 10 kVA models)
Remote monitoring and control of the
UPS and the environment via Ethernet
connection while freeing up the SmartSlot
so customers can add accessories for
additional communication options.
TM
Switched outlet group(s)
Ability to control a group of output load
receptacles independent from the main
UPS. Enables:
• Rebooting hung device without cycling
the entire UPS.
• Sequenced turn ON/OFF.
• Shedding of noncritical loads based on
a variety of parameters (battery time,
runtime remaining, and overload).
• Scheduled time OFF to conserve energy.
Emergency power off (EPO)
Remote UPS shutoff in the event of a fire
or other emergency. The UPS can accept
normally open (NO) or normally closed
(NC) contacts.
Communication ports
Serial, USB, Ethernet, and SmartSlot for
network accessory cards.
SRT10KXLT shown
Communication protocols
Modbus serial, USB PowerSummary, HTTP,
SNMP, and Telnet.
1:1, 3:1 input hard-wire options
Product can be wired for 3-PH or 1-PH input
(230 V, 8 kVA, and 10 kVA models only).
Dual input
Enables second input source to be
connected to UPS bypass (230 V, 8 kVA,
and 10 kVA models only).
apc.com
7
Smart-UPS On-Line display
Intuitive, easy-to-use LCD provides clear and accurate
information in multiple languages
Standard Features
LCD display screen
Accurately provides real-time status
updates in your choice of basic or
advanced menus.
UPS status (scrolling)
• Output voltage
• Input voltage
• Output frequency
• Runtime
• Load
• Battery health
Control
• UPS and outlet group settings
• Bypass control
Configuration
• Output voltage, frequency
• Language, brightness, contrast
Backlight screens:
Amber: Indication of condition that
requires attention
• Alarm volume
Red: Indication of UPS alarm that
requires immediate attention
• IP address
Test and diagnostics
• Initiate battery and runtime
calibration tests
About
• UPS serial number, battery part number
• Battery install and suggested
replacement dates
apc.com
8
Product Accessories
SRT009: APC Smart-UPS SRT 5 M extension cable
for 72 VDC external battery pack 2.2 kVA UPS
Management cards
AP9630: UPS network management card
with PowerChute network shutdown
SRT010: APC Smart-UPS SRT 5 M extension cable
for 96 VDC external battery pack 3 kVA UPS
AP9631: UPS network management card
with PowerChute network shutdown
and environmental monitoring
Rail kits
SRTRK2: APC Smart-UPS SRT 19 inch rail
kit for Smart-UPS SRT 5/6/8/10 kVA UPS
AP9335TH: APC by Schneider Electric
temperature and humidity sensor
TM
TM
Management card
SRTRK3: APC 2-post mounting rail kit for
Smart-UPS SRT 2.2/3/5/6/8/10 kVA UPS
AP9810: APC dry contact I/O accessory
SRTRK4: APC Smart-UPS SRT 19 in. rail kit
for Smart-UPS SRT 2.2/3 kVA UPS
AP9624: UPS interface expander
AP9613: Dry contact I/O SmartSlot card
Backplate kit
SRT001: APC Smart-UPS SRT 5 kVA output HW kit
Battery packs
SRT192BP: APC Smart-UPS SRT 192 V
5 kVA and 6 kVA battery pack
SRT192RMBP: APC Smart-UPS SRT 192 V
5 kVA and 6 kVA RM battery pack
SRT192BP2: APC Smart-UPS SRT 192 V
8 kVA and 10 kVA battery pack
SRT192RMBP2: APC Smart-UPS SRT 192 V
8 kVA and 10 kVA RM battery pack
SRT72BP: APC Smart-UPS SRT 72 V 2.2 kVA
battery pack
SRT72RMBP: APC Smart-UPS SRT 72 V 2.2 kVA
RM battery pack
SRT96BP: APC Smart-UPS SRT 96 V 3 kVA
battery pack
SRT96RMBP: APC Smart-UPS SRT 96 V 3 kVA RM
battery pack
SRT002: APC Smart-UPS SRT 5 M Extension Cable
for 192 VDC External Battery Packs 5/6 kVA UPS
SRT003: APC Smart-UPS SRT 5 M Extension Cable
for 192 VDC External Battery Packs 8/10 kVA UPS
SRT012: APC Smart-UPS SRT 2.2/3 kVA
input/output HW kit
Battery pack
Transformers
SURT002: APC Smart-UPS RT 5,000 VA 230 V
isolation transformer
APTF10K W01: APC W W 10 kVA isolation transformer
Service bypass panels
SBP6KRMI2U: APC service bypass panel 230 V;
50 A; MBB; hardwire input; (4) IEC-320 C19 Output
SBP10KRMI4U: APC service bypass panel 230
V; 100 A; MBB; hardwire input; IEC-320 output (8)
C13 (2) C19
Rail kits
Other
SURT013: SURT Equipment Cart
Replacement Battery Cartridge
APCRBC140: RBC for SRT 5 kVA - 10 kVA UPS
APCRBC141: RBC for SRT 2.2 kVA UPS
APCRBC152: RBC for SRT 3 kVA UPS
Runtime estimates at half and full load (minutes)
SRT2200XLI (RM)
(990 W/1,980 W)
SRT3000XLI (RM)
SRT3000XLW-IEC (RM)
(1,350 W/2,700 W)
Internal
11.6/3.9
11.8/4.0
11.8/4
8.7/2.5
14.5/5.2
11.5/3.8
(1) Battery pack
45.7/20.2
46.4/20.5
46.2/20.5
36/15.5
34.5/14.7
28/11.6
(2) Battery packs
82.1/37.6
83.3/38.1
83/38
65.2/29.4
55.43/24.63
45.3/19.8
(3) Battery packs
119.9/55.6
121.6/56.3
121/56.4
95.5/43.8
77/34.84
63.1/28.2
(4) Battery packs
158.6/74.1
160.9/75.1
160.4/75.1
126.6/58.6
99.1/45.33
81.3/36.8
UPS
half/full loads
apc.com
SRT5KXLI (RM)
SRT5KRMXLW-HW
(2,250 W/4,500 W)
SRT6KXLI (RM)
(3,000 W/6,000 W)
SRT8KXLI (RM)
(4,000 W/8,000 W)
SRT10KXLI(RM)
(5,000 W/10,000 W)
9
Smart-UPS On-Line SRT 2200 VA and SRT 3000 VA
Technical specifications
Product feature
SRT2200XLI
SRT2200RMXLI
SRT3000XLI
SRT3000RMXLI
SRT3000XLW-IEC
SRT3000RMXLW-IEC
Output
Power rating
Nominal output voltage
Output frequency
2200 VA/1980 W
3000 VA/2700 W
50/60 Hz ± 3 Hz (auto sense) 50/60 Hz ± 0.1 Hz (user selectable)
Topology
Double-conversion online
Online efficiency at full load (typical)
Green mode efficiency at full load (typical)
230 V (208 V, 220 V, 240 V
user selectable)
230 V (220 V, 240 V user selectable)
92%
96%
97%
Output connections (switched groups)
(8) IEC 320 C13
(2) IEC 320 C19
(4) IEC320 C13
(2) IEC320 C19
230 V
230 V (208 V, 220 V, 240 V
user selectable)
Input
Nominal input voltage
Input voltage range full load (half load)
160 – 275 V (100 – 275 V)
Input frequency
40 – 70 Hz auto-selecting
Input connection
IEC-60320 C20, Schuko CEE 7/EU1-16P, British BS1363A
Batteries and runtime
Battery type
Maintenance-free sealed lead-acid battery with suspended electrolyte, leak proof
Typical backup time at ½ load (min)
11.6 min
11.8 min
Typical backup time at full load (min)
3.9 min
4.0 min
APCRBC141 (1)
APCRBC152 (1)
SRT72BP/SRT72RMBP
SRT96BP/SRT96RMBP
Replacement battery (quantity)
External battery pack (tower/rack mount)
Communication and management
Interface ports
Serial (RJ45), USB (Type A) and SmartSlot
Control panel
High resolution graphical LCD display
Emergency power off (EPO)
Yes (NO/NC connections)
Physical
Rack height
85 mm, 2U
Maximum width (RM)
432 mm
432 mm
Maximum depth (RM)
585 mm
636 mm
25 Kg
31 kg
CE, VDE, RCM, and EAC, IEC/EN
62040-1, IEC/EN 62040-2
CE, VDE, RCM, and EAC, IEC/EN 62040-1, IEC/EN 62040-2,
UL-1778, FCC Part 15 Class A, CSA
Net weight
Conformance
Regulatory
Warranty
apc.com
Three years electronics/two years battery
10
Smart-UPS On-Line SRT 5 kVA – 10 kVA
Product feature
SRT5KXLI
SRT5KRMXLI
SRT5KRMXLW-HW
SRT6KXLI
SRT6KRMXLI
SRT8KXLI
SRT8KRMXLI
SRT10KXLI
SRT10KRMXLI
Output
Power rating
Nominal output voltage
Output frequency
5,000 VA/4,500 W
6,000 VA/6,000 W
230 V (220 V, 240 V,
208 V user
selectable)
10,000 VA/10,000 W
230 V (220 V, 240 V user selectable)
50/60 Hz ± 3 Hz (auto sense)
50/60 Hz ± 0.1 Hz (user selectable)
Double-conversion online
Topology
Online efficiency at full load
(typical)
Green mode efficiency at full
load (typical)
Output connections
8,000 VA/8,000 W
94%
98%
Hardwire three-wire
(1 PH + N + G)
or (2 PH + G)
(6) IEC 320 C13
(4) IEC 320 C19
(6) IEC320 C13, (4) IEC320 C19, hardwire three-wire (1 PH + N + G)
Input
Nominal input voltage
208 V, 220 V, 230 V,
240 V
Input voltage range full load
(half load)
220 V, 230 V, 240 V
160 – 275 V (100 – 275 V)
Input frequency
Input connection
220 V/380 V, 230 V/400 V, 240 V/ 415 V
160/277 – 275/476 V (100/173-275/476 V)
40 – 70 Hz auto-selecting
Hardwire three-wire
(1 Ph+N+G) or
(2 PH + G)
Hardwire three-wire
(1 Ph+N+G)
Hardwire three-wire (1 Ph+N+G),
Hardwire five-wire (3 Ph+N+G)
Batteries and runtime
Battery type
Maintenance-free sealed lead-acid battery with suspended electrolyte, leak proof
Typical backup time at
1/2 load (min.)
Typical backup time
at full load (min.)
Replacement battery
(quantity)
External battery pack
(tower/rack mount)
11.8 min.
8.7 min.
14.5 min.
11.5 min.
4 min.
2.5 min.
5.2 min.
3.8 min.
APCRBC140 (1)
APCRBC140 (2)
SRT192BP/SRT192RMBP
SRT192BP2/SRT192RMBP2
Communication and management
Interface ports
Embedded network management with environmental monitoring
which includes an RJ-45 with status LEDs (10/100 Base-T),
Control panel
High-resloultion graphical LCD display
Emergency power off (EPO)
Yes (normally open, NO/ normally closed, NC connections)
Physical
3U
4U
6U
6U
Maximum height (RM)
130 mm
174 mm
263 mm
263 mm
Maximum width (RM)
432 mm
432 mm
432 mm
432 mm
Maximum depth (RM)
719 mm
719 mm
715 mm
715 mm
Net weight
54.5 kg
60 kg
112 kg
112 kg
Rack height
Conformance
Regulatory
Warranty
apc.com
UL-1778, FCC Part
15 Class A, CSA,
CE, VDE, RCM,
and EAC, IEC/EN
62040-1, IEC/EN
62040-2
CE, VDE, RCM, and EAC, IEC/EN 62040-1, IEC/EN 62040-2
Three years for electronics/two years for battery
11
You are here: Home > Products > Uninterruptible Power Supply (UPS) > Smart­UPS On­Line
APC Smart­UPS SRT 3000VA RM 230V
Part Number: SRT3000RMXLI
Technical Specifications
Product Overview
Documentation
Software & Firmware
Options
Output
Output Power Capacity
2700 Watts / 3000 VA
Max Configurable Power
2700 Watts / 3000 VA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains) 50/60Hz +/­ 3 Hz
Other Output Voltages
220, 240
Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform Type
Sine wave
Output Connections
(8) IEC 320 C13
(2) IEC 320 C19
(2) IEC Jumpers
Bypass
Internal Bypass (Automatic and Manual)
Input
Nominal Input Voltage
230V
Input Frequency
40 ­ 70 Hz (auto sensing)
Input Connections
British BS1363A
IEC­320 C20
Schuko CEE 7/EU1­16P
Cord Length
2.44 meters
Input voltage range for main
operations
160 ­ 275V
Input voltage adjustable range for 100 ­ 275 (half load)V
mains operation
Other Input Voltages
220, 240
Batteries & Runtime
Battery Type
Maintenance­free sealed Lead­Acid battery with suspended electrolyte : leakproof
Included Battery Modules
1
Typical recharge time
3 hour(s)
RBC Quantity
1
Nominal Battery Voltage
96V
Extended Run Options
APC Smart­UPS SRT 3000VA RM 230V
Runtime Graph
Curve
Part Number(s)
A
SRT3000RMXLI
B
SRT3000RMXLI + (1)SRT96RMBP
C
SRT3000RMXLI + (2)SRT96RMBP
D
SRT3000RMXLI + (3)SRT96RMBP
E
SRT3000RMXLI + (4)SRT96RMBP
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical
environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Energy Use/Efficiency
Load
Efficiency
25%
89.9%
50%
92.8%
75%
93.4%
100%
93.5%
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit of data measured in accordance with the ENERGY STAR Program Requirements Product
Specification for Uninterruptible Power Supplies (UPSs) ­ Eligibility Criteria Version 1.0. All measurements
taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced
resistive load (PF = 1.0) output.
View Enlarged Graph
Communications & Management
Interface Port(s)
RJ­45 Serial, SmartSlot, USB
Available SmartSlot™ Interface
Quantity
1
Control panel
Multi­function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Surge energy rating
340 Joules
Filtering
­­
Physical
Maximum Height
85.00 mm
Maximum Width
432.00 mm
Maximum Depth
635.00 mm
Rack Height
2U
Net Weight
31.30 KG
Shipping Weight
39.92 KG
Shipping Height
246.00 mm
Shipping Width
599.00 mm
Shipping Depth
871.00 mm
Color
Black
Units per Pallet
6.00
Environmental
Operating Environment
0 ­ 40 °C
Operating Relative Humidity
0 ­ 95% no%
Operating Elevation
0­3000 meters
Storage Temperature
­15 ­ 45 °C
Storage Relative Humidity
0 ­ 95% no%
Storage Elevation
0­15000 meters
Audible noise at 1 meter from
surface of unit
55.00 dBA
Online Thermal Dissipation
703.00 BTU/hr
Protection Class
IP 20
Conformance
Approvals
CE, CE Mark, EAC, EN/IEC 62040­1, EN/IEC 62040­2, ENERGY STAR (EU), RCM,
VDE
Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery
Sustainable Offer Status
RoHS
Compliant
REACH
REACH: Contains No SVHCs
Battery Directive
Compliant
Battery Notes
Contains Lithium Coin Cell
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
You are here: Home > Products > Uninterruptible Power Supply (UPS) > Smart­UPS On­Line
APC Smart­UPS SRT 3000VA 230V
Part Number: SRT3000XLI
Technical Specifications
Product Overview
Documentation
Software & Firmware
Options
Output
Output Power Capacity
2700 Watts / 3000 VA
Max Configurable Power
2700 Watts / 3000 VA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains) 50/60Hz +/­ 3 Hz
Other Output Voltages
220, 240
Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform Type
Sine wave
Output Connections
(8) IEC 320 C13
(2) IEC 320 C19
(2) IEC Jumpers
Bypass
Internal Bypass (Automatic and Manual)
Input
Nominal Input Voltage
230V
Input Frequency
40 ­ 70 Hz (auto sensing)
Input Connections
British BS1363A
IEC­320 C20
Schuko CEE 7/EU1­16P
Cord Length
2.44 meters
Input voltage range for main
operations
160 ­ 275V
Input voltage adjustable range for 100 ­ 275 (half load)V
mains operation
Other Input Voltages
220, 240
Batteries & Runtime
Battery Type
Maintenance­free sealed Lead­Acid battery with suspended electrolyte : leakproof
Typical recharge time
3 hour(s)
RBC Quantity
1
Extended Run Options
APC Smart­UPS SRT 3000VA 230V
Runtime Graph
Curve
Part Number(s)
A
SRT3000XLI
B
SRT3000XLI + (1)SRT96BP
C
SRT3000XLI + (2)SRT96BP
D
SRT3000XLI + (3)SRT96BP
E
SRT3000XLI + (4)SRT96BP
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical
environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Energy Use/Efficiency
Load
Efficiency
25%
89.9%
50%
92.8%
75%
93.4%
100%
93.5%
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit of data measured in accordance with the ENERGY STAR Program Requirements Product
Specification for Uninterruptible Power Supplies (UPSs) ­ Eligibility Criteria Version 1.0. All measurements
taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced
resistive load (PF = 1.0) output.
View Enlarged Graph
Communications & Management
Interface Port(s)
RJ­45 Serial, Smart­Slot, USB
Available SmartSlot™ Interface
Quantity
1
Control panel
Multi­function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Surge energy rating
340 Joules
Filtering
­­
Physical
Maximum Height
432.00 mm
Maximum Width
85.00 mm
Maximum Depth
635.00 mm
Net Weight
31.30 KG
Shipping Weight
36.74 KG
Shipping Height
246.00 mm
Shipping Width
599.00 mm
Shipping Depth
871.00 mm
Color
Black
Units per Pallet
6.00
Environmental
Operating Environment
0 ­ 40 °C
Operating Relative Humidity
0 ­ 95% no%
Operating Elevation
0­3000 meters
Storage Temperature
­15 ­ 45 °C
Storage Relative Humidity
0 ­ 95% no%
Storage Elevation
0­15000 meters
Audible noise at 1 meter from
surface of unit
55.00 dBA
Online Thermal Dissipation
703.00 BTU/hr
Protection Class
IP 20
Conformance
Approvals
CE, CE Mark, EAC, EN/IEC 62040­1, EN/IEC 62040­2, ENERGY STAR (EU), RCM,
VDE
Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery
Sustainable Offer Status
RoHS
Compliant
REACH
REACH: Contains No SVHCs
Battery Directive
Compliant
Battery Notes
Contains Lithium Coin Cell
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
You are here: Home > Products > Uninterruptible Power Supply (UPS) > Smart­UPS On­Line
APC Smart­UPS SRT 2200VA RM 230V
Part Number: SRT2200RMXLI
Technical Specifications
Product Overview
Documentation
Software & Firmware
Output
Output Power Capacity
1980 Watts / 2200 VA
Max Configurable Power
1980 Watts / 2200 VA
Nominal Output Voltage
230V
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains) 50/60Hz +/­ 3 Hz
Other Output Voltages
220, 240
Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform Type
Sine wave
Output Connections
(8) IEC 320 C13
(2) IEC 320 C19
(2) IEC Jumpers
Bypass
Built­in Bypass
Input
Nominal Input Voltage
230V
Input Frequency
40 ­ 70 Hz (auto sensing)
Input Connections
IEC­320 C20
Options
Schuko CEE 7 / EU1­16P
British BS1363A
Cord Length
2.44 meters
Input voltage range for main
operations
160 ­ 275V
Input voltage adjustable range for 100 ­ 275 (half load)V
mains operation
Other Input Voltages
220, 240
Batteries & Runtime
Battery Type
Maintenance­free sealed Lead­Acid battery with suspended electrolyte : leakproof
Included Battery Modules
1
Typical recharge time
3 hour(s)
RBC Quantity
1
Extended Run Options
APC Smart­UPS SRT 2200VA RM 230V
Runtime Graph
Curve
Part Number(s)
A
SRT2200RMXLI
B
SRT2200RMXLI + (1)SRT72RMBP
C
SRT2200RMXLI + (2)SRT72RMBP
D
SRT2200RMXLI + (3)SRT72RMBP
E
SRT2200RMXLI + (4)SRT72RMBP
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical
environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Energy Use/Efficiency
Load
Efficiency
25%
87.1%
50%
91.1%
75%
92.0%
100%
92.2%
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit of data measured in accordance with the ENERGY STAR Program Requirements Product
Specification for Uninterruptible Power Supplies (UPSs) ­ Eligibility Criteria Version 1.0. All measurements
taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced
resistive load (PF = 1.0) output.
View Enlarged Graph
Communications & Management
Interface Port(s)
RJ­45 Serial, Smart­Slot, USB
Available SmartSlot™ Interface
Quantity
1
Control panel
Multi­function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Surge energy rating
340 Joules
Filtering
­­
Physical
Maximum Height
85.00 mm
Maximum Width
432.00 mm
Maximum Depth
584.00 mm
Rack Height
2U
Net Weight
25.00 KG
Shipping Weight
34.02 KG
Shipping Height
246.00 mm
Shipping Width
599.00 mm
Shipping Depth
810.00 mm
Color
Black
Units per Pallet
12.00
Environmental
Operating Environment
0 ­ 40 °C
Operating Relative Humidity
0 ­ 95% no%
Operating Elevation
0­3000 meters
Storage Temperature
­20 ­ 50 °C
Storage Relative Humidity
0 ­ 95% no%
Storage Elevation
0­15000 meters
Audible noise at 1 meter from
surface of unit
55.00 dBA
Online Thermal Dissipation
535.00 BTU/hr
Protection Class
IP 20
Conformance
Approvals
CE, CE Mark, EAC, EN/IEC 62040­1, EN/IEC 62040­2, ENERGY STAR (EU), RCM,
VDE
Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery
Sustainable Offer Status
RoHS
Compliant
REACH
REACH: Contains No SVHCs
Battery Directive
Compliant
Battery Notes
Contains Lithium Coin Cell
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
SERBIA AND MONTENEGRO [ Change ]
Home
Sign in
Products and Services
Solutions
✉
Share:
Support

Your Business
Company
Subscribe
to our
Channel
APC Smart­UPS SRT 6000VA 230V
SRT6KXLI
APC Smart­UPS SRT 6000VA 230V
Includes: CD with software , Documentation CD , Installation guide , Removable support feet ,
Temperature Probe , USB cable , Warranty card , Web/SNMP Management Card
Locate a Partner
Related Products, Accessories & Services
Rack PDU, Metered, Zero U, 10A, 230V,
(16) C13
Product Overview
Technical Specifications
View all optional accessories for this product
Power Cord Kit (6 Ea), C19 To C20 (90
Degree), 0.6m
Documentation
Software & Firmware
Output
Output power capacity
6.0 KWatts / 6.0 kVA
Max Configurable Power (Watts)
6.0 KWatts / 6.0 kVA
Nominal Output Voltage
230V
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60Hz +/­ 3 Hz
Other Output Voltages
220, 240
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Output Connections
Bypass
(6) IEC 320 C13 (Battery Backup)
(4) IEC 320 C19 (Battery Backup)
Internal Bypass (Automatic and Manual)
Input
Nominal Input Voltage
230V
Input frequency
40 ­ 70 Hz (auto sensing)
Input Connections
Hard Wire 3 wire (1PH+N+G)
Input voltage range for main
operations
160 ­ 275 V
Rack PDU 2G, Switched, ZeroU,
20A/208V, 16A/230V, (7) C13 & (1) C19
Options
Input voltage adjustable range for
mains operation
100 ­ 275 (half load) V
Other Input Voltages
220, 240
Batteries & Runtime
Battery type
Maintenance­free sealed Lead­Acid battery with suspended electrolyte : leakproof
Typical recharge time
1.5 hour(s)
Replacement Battery
APCRBC140
RBC Quantity
1
Extendable Run Time
1
Battery Volt­Amp­Hour Capacity
902
Extended Run Options
APC­Smart­UPS­SRT­6000VA­230V
Runtime
View Runtime Graph
Efficiency
View Efficiency Graph
View Runtime Chart
Communications & Management
Interface Port(s)
RJ­45 10/100 Base­T , RJ­45 Serial , Smart­Slot , USB
Control panel
Multi­function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Available SmartSlot™ Interface
Quantity
1
Surge Protection and Filtering
Surge energy rating
480 Joules
Physical
Maximum Height
432 , 43.2 CM
Maximum Width
174 , 17.4 CM
Maximum Depth
719 , 71.94 CM
Net Weight
60.0 KG
Shipping weight
67.0 KG
Shipping Height
370 , 37.0 CM
Shipping Width
610 , 61.0 CM
Shipping Depth
960 , 96.0 CM
Color
Black
Units per Pallet
6.0
Environmental
Operating Environment
0 ­ 40 °C
Operating Relative Humidity
0 ­ 95% no %
Operating Elevation
0­3000 meters
Storage Temperature
­15 ­ 45 °C
Storage Relative Humidity
0 ­ 95% no %
Storage Elevation
0­15000 meters
Audible noise at 1 meter from surface
of unit
55.0 dBA
Online thermal dissipation
1300.0 BTU/hr
Protection Class
IP 20
Conformance
Approvals
CE, CE Mark, EAC, EN/IEC 62040­1, EN/IEC 62040­2, ENERGY STAR (EU), IRAM, RCM, VDE
Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery
Sustainable Offer Status
RoHS
Compliant
REACH
Home
Solutions
REACH: Contains No SVHCs
Products and Services
Support
Your Business
Company
©APC by Schneider Electric Privacy Policy
Contact
Schneider Electric
132 Fairgrounds Road
West Kingston, RI 02892
Phone: 401-789-5735
www.apc.com
October 2015
©2015 Schneider Electric. All Rights Reserved. Schneider Electric, APC, Smart-UPS, PowerChute,
SmartSlot, and Life Is On Schneider Electric are trademarks owned by Schneider Electric Industries SAS or its affiliated
companies. All other trademarks are the property of their respective owners.• 998-1243569_GMA-US_A
This document has been
printed on recycled paper