LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED STATIC KWH METER WITH LCD DISPLAY INSTALLATION & OPERATION MANUAL FRONT VIEW 1. 2. 3. 4. 5. kWh Display CT Reverse Indication Calibration LED : 15000 imp/kWh for -/5A “D” key used for increment the value while setting Password & CT Ratio ↵” to confirm the entered value & to move “↵ the digit right to left 3Phase, 4Wire Electronic kWh Meter CT-2E 2 1 kWh CAL 4 Fig. 1 CUTOUT DETAILS WIRING DIAGRAM The Panel Meter is installed on the cabinet’s front panel and shall be secured firmly with cabinet using 4 transparent Clips. The meter shall be wired as per the following wiring Diagram : 2 Use 0.5 to 2.5mm Cable for Voltage 2 2 terminals & 3mm to 6mm cable for Current terminals. +0.8 92 -0.0mm 3Phase, 4Wire Electronic kWh Meter CT-2E 1 8 kwh 96mm -/5A 3x240V, 50Hz CL. 1.0 IEC 61036 CAL +0.8 92 -0.0mm 90mm P1 S1 FUSE 0 .5A L2 L3 N 15000 imp/ kWh P3 S3 REAR VIEW L1 kWh P2 S2 G S I1 I2 I3 S1 S2 S1 S2 S1 S2 1 PULSE = 1 kWh HPL-SOCOMEC 96mm Fig. 2 S, G = PULSE OUTPUT Fig. 3 CT PRIMARY PROGRAMMING Power ON the meter by giving voltage to the meter or after complete installation as per wiring diagram above Factory set CT ratio -/5A Appears on the LCD as CT - 5 CT Primary is selectable through push button on the front Panel CT ratio is password protected for security Password for setting CT Ratio is 123 CT PRIMARY SELECTION Screen shows kWh Press Push button “D” once HPL-SOCOMEC PVT. LTD, Code 18.0 _ _ 0 133, PACE CITY-I, SECTOR- 37, GURGAON - 122 001 N L1 L2 L3 Note : For selection the digits /Numerals move from Right to Left after pressing the “↵ ” Key COMMAND DISPLAY ON METER SCREEN Press “D” Code _ _ 0 Press “D” Code _ _ 1 Press “↵” Code _ 1 0 Press “D” Twice Code _ 1 2 Press “↵” Code 1 2 0 Press “D” Thrice Code 1 2 3 Press “↵ ↵” The password has now been feed in correctly and access is allowed to CT primary Selection After the entry of correct Password Ct _ _ _ 0 – - 5 CT Primary selection is explained with the help of two examples as below e.g. e.g. 1. 50/5A COMMAND DISPLAY ON METER SCREEN 2. 2205/5A COMMAND DISPLAY ON METER SCREEN Press “↵” Ct _ _ 0 0 –- 5 Press “D ” Ct _ _ _ 1 - 5 Press “↵” Ct _ 0 0 0 –- 5 Press “D ” Ct _ _ _ 2 - 5 Press “D ” Ct _ 0 0 1 –- 5 Press “↵ ↵” Ct _ _ 2 0 - 5 Press “D ” Ct _ 0 0 2 –- 5 Press “D ” Ct _ _ 2 1 - 5 Press “D ” Ct _ 0 0 3 –- 5 Press “D ” Ct _ _ 2 2 - 5 Press “D ” Ct _ 0 0 4 –- 5 ↵” Press “↵ Ct _ 2 2 0 - 5 Press “D ” Ct _ 0 0 5 –- 5 Press “↵ ↵” Ct 2 2 0 0 - 5 Press “↵ ↵” Ct _ 0 5 0 –- 5 Press “D ” Ct 2 2 0 1 - 5 Press “↵ ↵” Ct 0 0 5 0 –- 5 Press “D ” Ct 2 2 0 2 - 5 Press “D ” Ct 2 2 0 3 - 5 Press “D ” Ct 2 2 0 4 - 5 Press “D ” Ct 2 2 0 5 - 5 ↵”. Screen Blanks out for 2 to 3 second to confirm entry of CT Ratio. Then it displays the selected Press “↵ CT Ratio for 1 Second & then display the active energy IMPORTANT 1. Select the CT ratio as per the actual set of CTs installed 2. During Password entry & CT selection, if the required Push button is not pressed within 13-15 seconds, the display will switch to active energy mode. HPL-SOCOMEC PVT. LTD, 133, PACE CITY-I, SECTOR- 37, GURGAON - 122 001 LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED STATIC KWH METER WITH LCD DISPLAY TECHNICAL PARAMETER ENCLOSURE Compact Weight : : 96mm x 96mm x 90 mm 300 gms. : : : LCD with 6 digits 8mm x 4.8mm IP 54 A. CURRENT : Via Current Transformer with Primary Insulated secondary Current circuit burden Starting current Overload : : : : : Upto 6000A configurable in multiples of 5 5A < 0.5VA 10ma (for 5A Secondary) 7A B. VOLTAGE : Measurement range Voltage circuit burden : : 120V AC to 300V AC Phase to Neutral <1 W per phase : Self Powered, No Auxiliary Supply required : Class 1.0 : : : 100 msec minimum 1 Pulse = 1 kWh interrogated with an external DC Voltage of 5V to 24V : : -100C to +550C 95% FRONT PANEL Display Digit Height Protection Index INPUTS AUXILIARY SUPPLY ACCURACY Active Energy PULSE OUTPUT Pulse duration Pulse weight Potential free contact (Open collector type) OPERATING CONDITION Operating temperature Relative humidity SPECIAL FEATURES 1. Records energy accurately under the following Tamper conditions : a) One or Two phases are removed OR b) Neutral is Removed OR c) One Phase and neutral are removed OR d) Reverse current condition 2. Indication on LCD( ) in case of CT reverse connection 3. Finger touch-proof terminals for CT & Voltage connections. HPL-SOCOMEC PVT. LTD, 133, PACE CITY-I, SECTOR- 37, GURGAON - 122 001 HPL-SOCOMEC PVT. LTD. TEST CERTIFICATE ITEM : LT ac, Three Phase, Four Wire Panel Mounted Static kWh Meter with LCD Display (96mm x 96mm) METER SL. NO. : RATING : -/5A, 3x240V, 50Hz, Class 1.0 METER CONSTANT : 15000 Impulses per kWh for -/5A MODEL : CT-2E 1K 1K 10 The Meter tested as per IS 13779 & has passed following tests at reference conditions :TEST RESULT 01 No-Load Conditions Passed 02 AC Voltage Test Passed 03 Insulation Resistance Test Passed 04 Starting Test Passed 05 Meter Accuracy Test Passed Meter Accuracy observed within ± 1% WORKS : HPL-SOCOMEC PVT. LTD. Plot No. 133, Pace City-I Sector- 37 Gurgaon - 122 001 Haryana CERTIFIED OK Signature :__________ Dated : /02/07 1