Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Electronic Trip Units General Description OPTIM 750 OPTIM 1050 Cutler-Hammer offers the most comprehensive range of electronic trip units in the industry for power circuit breakers. The UL listed OPTIM electronic trip units are true RMS sensing and can be applied in any SPB or DSII breakers. Digitrip electronic trip units are ac devices that employ microprocessor-based technology that provides a true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. The primary function of the Digitrip electronic trip unit is to provide circuit protection. This is achieved by analyzing the secondary current signals received from the circuit breaker current sensors and initiating trip signals to the circuit breaker trip unit when pre-set current levels and time delay settings are exceeded. By sampling the current waveform at various points on the wave and calculating true RMS current, the Digitrip is able to reduce nuisance tripping events due to nonsinusoidal wave shapes. Electronic trip units are applied to distribution systems when high standards of protection and coordination are called for. In addition, electronic trip units can provide further enhanced features such as alarming, diagnostics, system monitoring and communications. Cutler-Hammer RMS sensing trip units for power breakers fall into two main categories: ● Front adjustable trip units: Digitrip RMS 510, 610, 810, 910 ● Programmable trip units: Digitrip OPTIM 750, 1050 Programmable Trip Units OPTIM trip units are electronic trip units that have up to ten time-current setting options that are programmed electronically by the use of a programming device. Trip units are readily accessible from the front of the breakers. Programmability means more settings, better accuracy, faster configuration, remote accessibility, higher system security, and the ability to apply limitless software. The application for programmable trip units would be high integrity distribution systems that require superior levels of system coordination coupled with system alarming, diagnostics and monitoring. Digitrip OPTIM for power breakers are available in three configurations: - Long time, short time, and instantaneous (LSI) - Long time, short time, instantaneous and ground fault protection (LSIG) - Long time, short time, instantaneous and ground fault alarm (LSIA) 212 ● ● ● ● ● ● RMS Sensing 10 Functions Programmable Load Monitoring Diagnostics Communications ● ● ● ● ● ● ● ● RMS Sensing 10 Functions Programmable Load Monitoring Diagnostics Communications Power and Energy Monitoring Harmonics For maximum selectability, OPTIM trip units allow the user to disable either short time or instantaneous functions, but not both. selectable on DS breakers and on SPB breakers are equal to the breaker frame rating. The plug value is referred to as In. Rating Plugs Time-Current Curve Shaping Rating plugs provide a means to establish the breaker’s continuous current rating. Rating plugs are unique to a particular breaker type, and are color coded to make it easy to match the correct rating plug with the correct circuit breaker type. Rating plugs are fixed type, and are interchangeable so that amp ratings can be changed simply by changing from one plug to another in a given breaker. The same rating plug can be applied to both 50 and 60 Hz distribution systems. SPB plugs are interlocked with the breaker frame to prevent putting the wrong plug into the wrong frame size. All Digitrip OPTIM settings are continuously adjustable, allowing virtually an infinite number of possibilities within setting ranges. Ranges are based on the plug rating In and the long delay pickup setting Ir. For ease of use all pickup values are programmed in amps rather than in multiples of In or Ir. Table 1 illustrates available setting ranges. For improved system coordination OPTIM features a new setting not available on previous models of Digitrip. The I4t long delay slope will provide superior coordination with upstream fuses and transformer damage curves. Rating plugs are available down to an ampere value of half the sensor rating. Sensors are Interchangeable rating plugs establish the circuit breaker’s continuous ampere rating. Different types and ratings are available to match the desired ampere rating and type of circuit breaker into which a Digitrip RMS trip unit is installed. The rating plugs are suitable for use on either 50 or 60 Hz system applications. Rating plugs may be applied as low as 50% of sensor rating. March 1996 Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Electronic Trip Units 10 Curve Shaping Adjustments Function 1 Multiplier/ Setting Setting Range Overload 1. Long Delay Pickup 2B 2A 2 XIn 0.4 - 1.0 2A. Long Delay Time I2t @6Ir 2 - 24 sec. 2B. Long Delay Time I4t @6Ir 1 - 5 sec. Short Circuit 3 Time 4B XIr 1.5 - S max.* XIr 0.1 - 0.5 sec. 4B. Short Delay Time I2t Response XIr 0.1 - 0.5 sec. 5. Instantaneous XIn 2.0 - M max.* Ground Fault 4 4A 6 3. Short Delay Pickup 4A. Short Delay Time Flat Response 6. Ground Fault Pickup XIn 0.25 - 1.0 (1200 A max) 7A. Ground Fault Delay Flat Response XIn 0.1 - 0.5 sec. XIn 0.1 - 0.5 sec. 7B. Ground Fault Delay I2t Response 5 In = Rating Plug Rating Ir = LDPU Setting * Varies with Breaker Type and Frame – See small table this page. 7B 7 7A Current in Amperes Breaker Type Frame S max. SPB SPB DSII 400A - 3000A 4000A - 5000A All 8 6 10 M max. 10 6 12 F Figure 1. OPTIM Trip Curve Settings Protective function settings are described below. See Figure 1. Long Delay (L) 1. Long Delay Pickup Determines the continuous ampere rating of the breaker. 2. Long Delay Time Determines the amount of time the breaker will carry a low level overload before tripping. 2A. I2t Response I2t in: For coordination with other circuit breakers with electronic trip devices and for coordination with thermal magnetic circuit breakers. 2B. I4t Response I4t in: For coordination with fuses and upstream transformer damage curves. Short Delay (S) 3. Short Delay Pickup Determine or set the level of fault current at which the short time trip delay countdown is actuated. 4. Short Delay Time Sets the amount of time the breaker will carry both low level and high level fault currents before tripping. 4A. Flat Response I2t out: For coordination with other circuit breakers with electronic trip devices. This setting is used when I4t Long Delay Time is selected. March 1996 4B. I2t I2t Response in: For coordination with fuses and thermal magnetic breakers. Instantaneous (I) 5. Instantaneous Pickup Determines the level of fault current which will actuate a trip with no time delay. Ground Fault (G) 6. Ground Fault Pickup Determines the level of fault current at which the ground fault trip delay countdown is actuated. 7. Ground Fault Delay Determines the amount of time the breaker will carry a ground fault before tripping. 7A. Flat Response I2t Out: For coordination with other circuit breakers with electronic ground fault settings. 7B. I2t Response I2t In: For coordination with zero sequence ground fault relays. dent curve shaping provides a wider range of available settings. OPTIM offers virtually infinite settings to allow the user to optimize coordination for a selectively coordinated distribution system. Time-current set points can be downloaded via a handheld programmer or a communication system from a central personal computer. Digitrip OPTIM is normally applied to electrical power systems where system integrity is very important. Zone Selective Interlocking Zone selective interlocking capabilities are available with Digitrip OPTIM 750 and 1050 trip units. Zone selective interlocking provides positive system coordination by allowing the breaker closest to the fault to trip without any preset time delays. This is achieved by setting up the distribution system as shown in Figure 2. The hard wired connection between the trip units sends a restraining signal upstream allowing the breaker closest to the fault to interrupt instantaneously, while the upstream breaker times out per its programmed settings. Zone selective interlocking reduces stress on the distribution system by isolating faults without time delays, and provides the ultimate in system selective coordination. Programmable Dependant Curve Shaping Digitrip OPTIM 750 and 1050 trip units offer programmable dependent curve shaping via ten curve shaping choices that are programmed electronically into the trip unit. The trip curves are interactive so that changing a long delay setting (Ir) moves the whole curve including the short time portion to provide closer protection for bus and cables. Depen213 Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Electronic Trip Units Figure 2. Zone Selective Interlocking made to close a breaker on a faulted circuit. The discriminator (or making current release) is set at 11 times the rating plug ampere rating and is enabled for approximately the first 10 cycles of current flow. Should a fault condition exist upon closing, the breaker will trip with no intentional time delay, protecting the user from a potentially unsafe condition. The discriminator function can be enabled or disabled by the user. In addition to a discriminator, an instantaneous override is present in all SPB insulated case circuit breakers to provide additional protection for the breaker. The instantaneous override is factory set just below the breaker withstand rating to ensure rapid clearing under conditions of fault currents greater than the short time withstand rating of the breaker in which the trip unit is installed. Fault 1 There are no interlocking signals. The main breaker trip unit will initiate the trip instantaneously. Fault 2 The feeder breaker trip unit will initiate the trip instantaneously to clear the fault; and Zone 2 will send an interlocking signal to the Zone 1 trip unit. The Zone 1 trip unit will begin to time out, and in the event that the feeder breaker in Zone 2 would not clear the fault, the main breaker in Zone 1 will clear the fault in 0.5 seconds. Fault 3 The branch breaker trip unit will initiate the trip instantaneously to clear the fault; and Zone 3 will send an interlocking signal to the Zone 2 trip unit; and Zone 2 will send an interlocking signal to Zone 1. Zone 1 and Zone 2 trip units will begin to time out, and in the event that the branch breaker in Zone 3 would not clear the fault, the feeder breaker in Zone 2 will clear the fault in 0.3 seconds. Similarly, in the event that the feeder breaker in Zone 2 would not clear the fault, the main breaker in Zone 1 will clear the fault in 0.5 seconds. Digitrip OPTIM electronic trip units can operate reliably in ambient temperatures that range from -20C to + 95C. In the unlikely event that temperatures exceed this ambient, the trip unit has a built-in overtemperature trip to protect the trip unit from operating outside its design parameters. Non-Volatile Memory After an overcurrent trip operation, the trip unit retains information in E2 prom. Values indicating the cause of trip, currents through the breaker at time of trip, time when trip occurred, total number of times the trip unit has tripped the breaker, and voltage and power quality related data when applicable are automatically stored. The data will remain in memory even if 120 Vac control power to the power/relay module is lost. These values can be displayed when control power is restored prior to resetting the trip unit. Thermal Memory Digitrip OPTIM electronic trip units incorporate powered thermal memory. The units remember recent overcurrent events which may have initiated the trip timing sequence and then returned to nominal levels, halting the sequence prior to trip initiation. If a trip occurs, OPTIM remembers the heating effect of this overload. In the event that the current levels again exceed the pickup setpoint before the circuit has had time to cool from the original pickup, the unit's memory recalls the previous trip or near trip and automatically imposes a shorter delay time. In effect, the trip unit treats multiple time related events as a single continuous event thereby preventing system damage due to cumulative overheating. As a further enhancement, the trip units incorporate an unpowered thermal memory feature. In the event that current levels cause the breaker to trip and the breaker is then reclosed following a loss of control power, the trip unit remembers the previous overcurrent trip and again imposes a shorter delay time should a further overcurrent occur before a sufficient cool-down period has elapsed. Thermal Memory protects the distribution system from cumulative overheating caused by repeated overcurrent conditions. Both powered and unpowered thermal memory can be programmed in or out by the user. System Alarms Digitrip OPTIM electronic trip units offer a high load alarm capability but with more flexibility than was previously available. OPTIM trip units have a high load alarm that can be programmed to operate between 50% and 100% of Ir. In some cases users want to know when a ground fault exists, but want to continue to operate without tripping due to ground fault. Digitrip OPTIM electronic trip units incorporate a ground fault alarm capability. Units equipped with LSIA will alert the user to a ground fault condition without tripping the Additional Protection Features Digitrip RMS Electronic Trip Units are designed and built with safety and reliability in mind, both to protect the user and the equipment as well as making sure the trip functions within its design parameters. Following a trip, the OPTIM trip unit should be reset via the highly visible red “trip reset” button on the front of the unit. By providing a SURE Start discriminator circuit in Digitrip OPTIM 750 and 1050 trip units that do not have an instantaneous setting, the user is protected should an attempt be 214 Breaker Accessories Pictured From Left to Right: Power Relay Module, Potential Transformer Module, and Auxiliary Power Module. March 1996 Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Electronic Trip Units A peak demand exceeded alarm is available with OPTIM 1050. For ensuring a minimum degree of power quality, acceptable total harmonic distortion levels can be set with OPTIM 1050 and an alarming feature can be initiated should these levels be exceeded. ● Programmable high load phase and neutral alarm, adjustable between 50 and 100 percent of Ir (LDPU setting). ● Long delay trip alarm. ● Short-circuit trip alarm. ● Ground fault trip alarm (LSIG units) or neutral overcurrent alarm if breaker has provision for external neutral input. ● A ground fault alarm adjustable between 25 and 100 percent of In (rating plug) will alert user of a ground fault condition without tripping the breaker (LSIA units). ● Incom close contact for remote closing of breaker via IMPACC. System Diagnostics Systems Monitoring Whenever a circuit breaker trips it is imperative that the cause of trip be determined quickly, the faulty conditions rectified, and the breaker put back into service. Digitrip OPTIM electronic trip units incorporate a complete package of systems diagnostics to meet this challenge. Digitrip RMS and Digitrip OPTIM electronic trip units offer a complete menu of monitoring capability to include current, power and energy, power factor, power quality harmonics, and other related parameters with a high level of accuracy. breaker. Settings available for ground fault alarm are the same as for ground fault trip, adjustable from 25 to 100 percent of the rating plug value up to a maximum of 1200 amps. Once a ground fault alarm occurs both local and remote signal indication is available. OPTIM makes use of LED indicators on it faceplate to help the user easily determine the status of the circuit. A green LED blinks on and off once per second to indicate that the microprocessor is functioning normally. A red LED on the face of the trip unit is preset to flash on and off when an adjustable high load level is exceeded. A time delay is built in to avoid nuisance alarms. Four cause of trip LEDs are embedded in the front of the trip unit case indicating that the cause of trip was either a long delay, short delay, instantaneous or ground fault. A long-life lithium battery is included to provide power to the LED is following a breaker trip and simultaneous loss of control power to the power/relay module. The battery is located in the rating plug and can be easily replaced from the front of the unit. Its normal life expectancy would be between five and eight years. A battery check pushbutton and green LED are included to monitor battery status. Remote signal indication for cause of trip as well as magnitude of trip information is also available. The power/relay module, supplied with all breakers using OPTIM trip units, uses external control power (120Vac 50/60 Hz, 6VA➀) brought into the breaker’s secondary contacts to operate the communications circuitry and reason for trip LED indicators. Secondly, it acts to provide signal relay contact closures when conditions apply that warrant advance warning alerts to potential problems or actual trip conditions. Current Monitoring - OPTIM 750 and 1050 Digitrip OPTIM 750 and 1050 trip units are capable of monitoring currents in individual phases (A,B,C) as well as neutral and ground currents. Current values are displayed in kA on the hand held OPTIMizer, the Breaker Interface Module or on a remote personal computer via IMPACC. Accuracy of the current monitored values is ±2 percent of full scale sensor rating➁. Power and Energy Monitoring - OPTIM 1050 For the trip unit to calculate true power and energy values, a Potential Transformer Module is required. This PTM is included the power breaker and provides the voltage the trip unit requires. Digitrip OPTIM 1050 trip units are capable of monitoring peak power demand, present power demand, and reverse power flow in kW. Additionally, both forward and reverse energy consumption in kwh can be monitored. The accuracy of power monitored values is ±4 percent of full scale sensor rating (sensor x 600 volts). The accuracy of energy monitored values is ±5 percent of full scale sensor rating (sensor x 600 volts). Harmonics Monitoring Digitrip OPTIM 1050 trip units are capable of monitoring values of current harmonics. Percentage of total harmonic content can be monitored on three phases plus neutral line for each level of harmonic content up to the 27th harmonic. Additionally, a total harmonic distortion (THD) value can be calculated and displayed providing the user with total system current harmonic monitoring capability. With IMPACC, waveform capture gives the ability to view the waveform on the computer screen. System Communications The Westinghouse IMPACC monitoring, protection, and control communications system is the most highly reliable, cost effective communications system available. Digitrip OPTIM 750 and 1050 electronic trip units include a capability to communicate within an IMPACC System. IMPACC system communications are done over a shielded twisted pair communications cable that connects devices daisy chain style. OPTIM communications can be applied for variable levels of sophistication as described below. Features Control and monitoring features provided by Digitrip OPTIM 750 or 1050 trip units include: ● ● ● ● ● ● ● ● ● ● ● ● ● ● Breaker status (open, closed, tripped) Address and baud rate Trip event time Trip event counter View protection settings Change protection settings Load current values Power and energy values➂ Power Factor➂ Line to line voltage➂ Power quality current harmonic values➂ Waveform capture➂ Remote status messages Remote control-trip/close/reset-reset demand/energy/trip event Further Information I.L. 29C891 Instructions for OPTIM 750, 1050 Trip Units. Digitrip 1050 trip units have the additional capability of monitoring line to line voltage as well as system power factor. ➀ Optional 230 Vac available on SPB breakers. ➁ Accuracy applies when current is greater than 5% of the primary sensor rating. Accuracy is of the complete system which includes the sensors, auxiliary CTs and the OPTIM trip unit. When current is less than 2% of sensor ratings, no current reading is available. ➂ OPTIM 1050 only March 1996 215 F Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Electronic Trip Units Programming and Monitoring Digitrip OPTIMizer Hand-Held Programmer The OPTIMizer plugs into the front of the trip unit and is powered by a nine volt battery. The Digitrip OPTIMizer hand held programmer accesses, displays, and configures information from OPTIM Trip Units. Breaker Interface Module Panel Mounted User Interface The Breaker Interface Module can be mounted directly on the assembly or at a remote location and can be used to access, configure, and display information from OPTIM Trip Units. Stand Alone Digitrip OPTIM 750 and 1050 electronic trip units are programmable by the use of a Hand held programmer called a Digitrip OPTIMizer. The Digitrip OPTIMizer accesses, displays and configures trip settings and information. The portable programmer plugs into the front of the trip unit and is powered by a nine volt battery. A telephone type cord stretches up to eight feet away from the breaker. Sub-Network Digitrip OPTIM 750 and 1050 electronic trip units can also be connected as part of a sub-network system to a panel mounted user interface device called a Breaker Interface Module (BIM). A Breaker Interface Module accesses, configures, and displays OPTIM trip unit information and for Digitrip RMS 810 and 910 trip units and Energy Sentinels. The BIM communicates with up to 50 devices. The BIM, like the AEMII, is normally mounted on the front of an electrical assembly. Field Bus System Digitrip OPTIM 750 and 1050 electronic trip units can be connected into a field bus system which is called IMPACC. All control, monitoring and configuration of the trip units can be carried out from a central personal computer. See page 641 of this catalog for more information on IMPACC. Field Testing IMPACC Communications Programming and Other Capabilities from a Personal Computer All OPTIM programming, configuration, advance warning, diagnostic, monitoring, and control capabilities can be accessed from a central personal computer using IMPACC Series III software. Other software packages are available, including a Trip Curve Package that displays, configures, and coordinates time-current protection curves for OPTIM Trip Units and other devices that can be included on an IMPACC System. Custom Billing Software, a stand alone application specific software package, provides the capabilities to determine energy usage data by individual departments or tenants in a facility...and then creates “electric bills” based on this data. System maintenance is an extremely important part of any distribution system and the capability to test electronic trip units is an essential requirement. Digitrip OPTIM 750 and 1050 electronic trip units have an integral test capability and do not require a special external test set. Both phase and ground, trip and no trip, testing can be carried out with the breaker in the connected cell position using an OPTIMizer, a BIM or IMPACC. An Auxiliary Power Module can be provided for bench testing Digitrip OPTIM 750 and 1050 electronic trip units, or when the breaker is disconnected from the cell. The Auxiliary Power Module operates from a 120 Vac supply and provides control power to test the trip unit. Typical Specifications Waveform and harmonic display software is capable of performing a waveform capture of phase currents A, B, C as well as neutral or ground. In addition, total harmonic distortion (THD) and individual harmonic contents can be displayed. 216 March 1996 Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Typical Specifications Table 1 Digitrip Optimizer Breaker Interface Module IMPACC Network Initial System Setup Select Breaker Addresses X Select System Frequency (50/60) Hz X X X Set System Baud Rate X X X Set System Password X X X X X X Configure the System Change Address Change Time-Current Setpoints X X X Select Protection Options X X X Select Alarm Levels X X X Breaker Information X X X Time-Current Setpoints X X X Metered Values X X X Trip Event Information X X X Display Information Test Trip Unit Performance Phase and Ground X X X Trip/No Trip X X X Set Addresses for Group Energy Monitoring X X Group Energy Readings X X Remote Indication/Alarming X X Breaker Status LED Indication X Expanded Energy Monitoring Local and Remote Indications Expanded Communications Communicates with: OPTIM Trip Units: X X X Digitrip 810 & 910 Trip Units X X IQ Energy Sentinel X X Up to 50 Devices X X Up to 1000 Devices X Expanded Capabilities Wave Form Analysis X Custom Billing Software X Trip Curve Software X Type DSII or SPB Circuit Breakers with Digitrip OPTIM 750 and 1050 Electronic Trip Units. Cutler-Hammer/Westinghouse power breakers with microprocessor-based RMS sensing trip units. Provide circuit breakers that are U.L. listed for application at 100% of their continuous ampere rating in their intended enclosure. Note to Specifier — For trip units with the functions of Digitrip OPTIM 750 for SPB or DSII circuit breakers, insert the following: Provide Cutler-Hammer/Westinghouse Digitrip OPTIM trip units for SPB or DS circuit breakers with the following features. Interchangeable rating plugs shall establish the continuous trip ratings of each circuit breaker. Rating plugs shall be fixed type as indicated. Rating plugs shall be unique to a given breaker frame, and interlocked such that a breaker cannot be closed and latched with the rating plug removed. System coordination shall be provided by the following microprocessor-based programmable time-current curve shaping adjustments. The short time pickup adjustment shall be dependent on the long time pickup setting. ● Programmable long time pickup ● Programmable long time delay with selectable I2t and I4t curve shaping ● Programmable short time pickup ● Programmable short time delay with selectable flat or I2t curve shaping and zone selective interlocking ● Programmable instantaneous pickup trip or alarm ● Programmable ground fault pickup ● Programmable ground fault delay with selectable flat or I2t curve shaping and zone selective interlocking The microprocessor-based trip unit shall have a powered/unpowered selectable thermal memory to provide protection against cumulative overheating should a number of overload conditions occur in quick succession. Provide zone interlocking for the short time delay and ground fault delay trip functions for improved system coordination. The zone interlocking system shall restrain the tripping of an upstream circuit breaker and allow the circuit breaker closest to the fault to trip with no intentional time delay. In the event that the downstream breaker does not trip, the upstream breaker shall trip after the pre-set time delay. When the instantaneous adjustment is not provided, a user selectable discriminator cir- March 1996 217 F Power Circuit Breakers Type DSII and SPB with OPTIM Trip Units Typical Specifications cuit shall be included to prevent the breaker being closed and latched onto a faulted circuit. The trip unit shall have an information system that utilizes battery backed-up LED's to indicate mode of trip following an automatic trip operation. The indication of the mode of trip shall be retained after an automatic trip. A trip reset button shall be provided to turn off the LED indication after an automatic trip. A test pushbutton shall energize an LED to indicate battery status. Circuit breakers shall be provided with a power/relay module to supply control power. Internal relays shall provide contacts for remote indication of the mode of trip (long delay, short circuit, ground fault) and high load. A red LED shall be provided on the face of the trip unit and pre-set to flash on and off when an adjustable high load level is exceeded. A time delay shall be provided to avoid nuisance alarms. The microprocessor-based trip units shall be capable of monitoring the following data: ● Instantaneous value of phase, neutral and ground current ● Minimum and maximum current values ● Average demand current ● System diagnostic information such as alarms and cause of trip ● Approximate level of fault current that initiated an automatic trip operation The monitored data shall be displayed by a hand-held programmer, a breaker interface module or a remote computer. The trip unit shall be capable of two-way communication via a network twisted pair for remote monitoring and control. The trip unit shall be provided with a programmable address. Transmittable parameters shall include protection settings, individual phase, neutral and ground current, minimum and maximum currents, average demand current breaker status (open/closed/tripped), trip events and mode of trip; information on external trip net- 218 work commands, data or program memory test failure, missing or defective rating plug, test push-button operation, or communication failure. The breaker shall be capable of responding to open and close commands via the communication network. Where indicated, provide electrical operators which respond to a close command via the communication network. The trip unit shall contain test capability. Testing shall be carried out by using a hand-held programmer, a breaker interface module or a remote computer to select the values of test current within a range of available settings. The basic protection functions shall not be affected during test operations. The breaker may be tested in either the “Trip” or “No trip” test mode. Provide an optional auxiliary power module to allow the breaker trip unit to be bench tested with a 120 volt external power source. A hand held programming unit shall be provided to set/change the network communication breaker address for each device, set the system baud rate, distribution frequency, display breaker information and display monitored values. In addition, provide password protection for programming timecurrent set points and to perform functional testing of phase and ground trip characteristics. The programmer shall be self powered by an internal battery. Provide one hand-held programming unit when other means of programming the circuit breakers are not provided. Provide a local area network connecting each circuit breaker trip unit to a breaker interface module (BIM). The BIM shall be capable of changing the network communication breaker address for each device, setting the system baud rate and distribution frequency, displaying breaker information and displaying monitored values. In addition, provide password protection for programming time current set points, and to perform functional testing of phase and ground trip characteristics. The BIM shall have help message capabilities and shall communicate information for up to fifty devices including Digitrip OPTIM, 810, and 910 trip units and energy sentinels. Provide a 30-volt DC power supply for the BIM which is to be mounted within the assembly. Provide a product operated network interface (PONI) for the BIM to communicate via the IMPACC network to a remote computer. Provide Cutler-Hammer/Westinghouse Digitrip OPTIM 750 Trip Units Note to Specifier — For trip units with the additional functions of the Digitrip OPTIM 1050 for SPB or DSII circuit breakers, insert the following: The microprocessor-based trip units shall be capable of monitoring the following data: ● ● ● ● ● ● ● ● Peak demand (Megawatts) Present demand (Megawatts) Reverse power flow Energy consumption (Megawatt-hours) Reverse energy consumption Power Factor Percentage harmonic content Total harmonic distortion (THD) The monitored data shall be displayed by a hand-held programming unit, a breaker interface module or a remote computer. Circuit Breakers shall be provided with a potential transformer module, suitable for operation up to 600 volts. The primary of the potential transformer module shall be connected internally to the load side of the circuit breaker through a dielectric disconnect plug. The trip unit shall be capable of two-way communication via a network twisted pair for remote monitoring and control. Transmittable parameters shall include the addition of power and energy values, line-to-line voltage, power factor, total harmonic distortion, harmonic content and waveform capture, via the IMPACC communication network . Provide Cutler-Hammer/ Westinghouse Digitrip OPTIM 1050 Trip Units. March 1996