Spectra® RMS Circuit Breakers
™
with microEntelliGuard Trip Units
Greater system coordination, arc flash protection and reliability
for new equipment and retrofit applications
imagination at work
Spectra® RMS Circuit Breakers
™
with microEntelliGuard Trip Units
Enhanced performance for SG600 and SK1200
molded case circuit breakers
Spectra SG600 and SK1200 molded case circuit breakers
now feature microEntelliGuard trip units, which bring
improved system protection, coordination, selectivity,
performance and diagnostics.
Advanced interface and capabilities
Based on the EntelliGuard TU trip unit platform, microEntelliGuard delivers the same HMI
interface, advanced features and protective functions, including enhanced time-current curve
shaping capability, ground fault alarm, direct Modbus communications, reduced energy letthrough setting, zone selective interlock, neutral protection, waveform capture and
programmable output contacts.
Common accessories and backwards compatibility
The microEntelliGuard trip unit utilizes the same power management accessories offered for
the Spectra MicroVersaTrip trip unit, and adds a new advanced junction box, interconnect
cable and terminal boards. The footprint and interrupt ratings of the breakers are
unchanged, and they are backwards compatible with existing equipment and installations.
The microEntelliGuard trip unit uses the same universal rating plugs and test kit as the
EntelliGuard TU trip unit.
™
microEntelliGuard Trip Units
put you in control of your system
You get the flexibility to create the curve shape that
best suits your system’s need – not a one-size-fits-allsolution. Standard Long Time characteristics exactly
mimic the curve of a thermal magnetic circuit breaker
and closely match our new line of global Record Plus®
molded case circuit breakers. Optional fuse-like
Long Time and Ground Fault curves allow optimum
selectivity in systems that employ both fused and
circuit breaker devices, providing selectivity and
protection simultaneously.
You gain the ability to adjust to exactly what your
system needs. A wide range of continuous adjustment
Long Time delays ensure the circuit breaker can be
exactly dialed in to your selectivity and protection needs.
You can sustain load and protect optimally all the
time. Twelve Short Time bands allow you to set your
circuit breaker to sustain load requirements without
slowing your protection more than you absolutely must.
Broad range of
adjustments,
shapes, slopes,
delays
MVT I2t, thermal
CB & fuse I4t curves
Fine adjustment
exact delay
…No more
… No less
Fuse shaped GF
for enhanced
selectivity in all
systems
Flexible curve shaping adapts to every need. Multiple
Short Time diagonal bands tune your protection to
exactly where it needs to be.
You get selectivity and instantaneous clearing at the
same time.1 The Zone Selective Interlocking system
simultaneously provides short time, ground fault and
instantaneous selectivity.
ZSI
Current metering is standard, and optional power,
energy and reactive power metering and waveform
capture are available.
Flexible serial communications via Modbus RTU
makes programming easy for any power or building
management system.
ZSI
microEntelliGuard integrates directly into GE’s
EnerVista® Power Management System.
Restrained
Flexible programmable output contacts are useful for
such various needs as load shedding, ground fault
alarm, trip indication and many others.
A large, easy-to-see, backlit LCD screen makes it
easier to set up the trip unit in such environments as
a darkened electrical room.
1Instantaneous ZSI is available only as an output signal on
Spectra microEntelliGuard trip units
Unrestrained
Advanced ZSI allows Instantaneous ZSI to withstand ratings
Greater system coordination, enhanced protection and uptime
Standard features
• Adjustable Long-Time pickup and delay bands with three curve shapes (MVT I2t, CB and Fuse
I4t) for optimal system coordination (includes thermal memory for enhanced system protection)
• Adjustable Short-Time pickup with multiple delay bands, curve slopes, I2t IN/OUT, and OFF setting
• Adjustable Instantaneous pickup
• 3-Phase ammeter
• Backlit LCD display with five-button tactile keypad for function selection and set point adjustment;
and sealable, clear Lexan cover for tamper-resistant settings
• LED Status Indicator to show “health” of trip unit
• Trip Target indication and local pickup warning signal
• Interchangeable/universal rating plugs
• Test set jack for GTUTK20 test kit
• True RMS sensing for accurate response to high harmonic content waveforms
• EMI immunity per ANSI C37.90
Optional features
• Ground Fault (Trip or Alarm) pickup and delay bands with multiple slopes, I2t IN/OUT for optimal
system coordination
• Neutral Protection provides overload protection on the system neutral
• Zone Selective Interlocking (ZSI) capability on Short Time, Ground Fault and Instantaneous settings
for optimal system coordination and selectivity
• Reduced Energy Let-Through (RELT) setting for enhanced equipment and personnel protection
• Advanced metering option includes the ability to monitor current, voltage, energy, frequency,
power factor, power (real/reactive/apparent) and peak power demand
• Modbus communications system with user selectable address assignment for communication
directly with EnerVista Viewpoint power system monitoring software
• Waveform capture for enhanced system diagnostics
• Protective Relays for enhanced system protection
– Voltage Unbalance
– Current Unbalance
– Under Voltage
– Over Voltage
– Power Reversal
– Load Alarm
• Input relay for RELT signal or remote tripping of the breaker
• Two programmable output relays for enhanced signaling and diagnostics
• Control Power option provides connection capability for +24Vdc control power via the distribution
cable system
Other features
• UL Listed for reverse feed and HACR type (standard)
• UL Listed 100% continuous current rating (optional)
• UL Listed Current Limiting (optional on SG Frame)
• Internal Accessories (Shunt Trip, Undervoltage Release, Auxiliary Contacts, Bell Alarm) – UL
Listed for field installation and common across the entire line of Spectra RMS breakers
Feature summary
System / Asset LT/ST
Inst.
System
Diagnostics /
Arc Flash
Protection
Coordination Selectivity
Performance Reliability
Feature
Benefit
Enhanced adjustability
& flexibility of time current curve shape, slope,
and delay bands
Enhanced system protection via
tight coordination with upstream
and downstream devices
including fuses
✓
Ground Fault Trip or
Alarm*
Enhanced system and asset
protection - especially for process
driven applications
✓
✓
✓
✓
Zone Selective Interlock
System protection
(ST/GF)*
✓
Zone Selective Interlock Maximum system protection,
(INST)*
coordination, and selectivity
✓
✓
✓
Reduced Energy
Let-Through*
Enhance system and personnel
protection
✓
✓
✓
Protective Relay
Functions*
Enhanced system and asset
protection via a suite of
protective relays
✓
Neutral Protection*
Protection on heavy harmonic loads
✓
Prevents unauthorized trip unit
Sealable Lexan Trip Unit setting changes for maximum
system, personnel, and asset
Cover
protection.
✓
Long Time Thermal
Memory
Enhanced system protection
✓
Input Relay*
System and asset protection via
remote trip (dedicated if RELT
enabled)
✓
Programmable Output
Contacts*
Advanced Metering*
Maximize system uptime via
signaling on GF alarm, overcurrent
trip, protective relay trip, load
alarm or health status
System performance monitoring
and diagnostics of critical current,
voltage, and power characteristics
✓
✓
✓
✓
✓
✓
✓
✓
Modbus
Communications*
System performance monitoring,
reporting and diagnostics
(compatible with EnerVista
Viewpoint power system
monitoring software)
Test Set Jack for
GTUTK20 Test Kit
Maximize system uptime and
enhanced diagnostics
✓
Trip Indication Targets
Visual Trip indication for quick
diagnostic evaluation
✓
Event Log
Record last 10 trip events
✓
Waveform Capture*
Enhanced diagnostic feature to
maximize system uptime
✓
HMI - Backlit LCD
Display & 5-Button
Keypad
Ease of programming and
viewing status/metering displays
✓
LED Status Indicator
Enhanced diagnostic feature to
maximize system uptime (visual
display of trip unit’s “health”)
✓
✓
Visual Pickup Warning
Signal
For quick diagnostics and
pre-trip detection
✓
✓
* Optional feature
✓
Capabilities by equipment for Spectra RMS circuit breakers
with microEntelliGuard
Spectra microEntelliGuard
Long Time/Short Time/
Instantaneous
Ground Fault
Ground Fault Alarm
Neutral Protection
ZSI (ST/GF)
Advanced
Protection
ZSI (ST/GF/INST)
RELT
Modbus Communications
Advanced
Advanced Metering
Features &
Communications Waveform Capture
Protective Relays
Standard
Protection
A-Series Busway Spectra Panelboard Switchboard
AV-3
Motor Control
Main Bus Plug
Main
Feeder Main1 Feeder Main Feeder Main Feeder
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
-
✓
✓
✓
-
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
-
✓
✓
✓
-
✓2
✓
✓
✓
✓
1Main or service disconnects
2RELT available on individually mounted feeders only (not on group mounted)
Spectra and Record Plus are registered trademarks and microEntelliGuard is a trademark of the General Electric Company.
Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under
laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.