nPANEL 4 RELAY & 0-10 VDC DIMMING CABINET SPECIFICATIONS FEATURES Communicates w/ nLight Network Four Relays Four 0-10 VDC Dimming Ouputs Integrated Power Supply Provides both Bus & Auxiliary Device Power Remotely Configurable/Upgradeable Push-Button Programmable Heavy-Duty Terminal Blocks UL 924 Recognized (ETL Listed) for Switching Emergency Cicuits OVERVIEW The nLight nPANEL 4 is targeted at rooms that require multiple relays be co-located in a cabinet enclosure. Utilizing four 30 Amp rated relays, the nPANEL 4 can switch up to four 120/277/347 VAC loads. Further, as a standard feature, the nPANEL 4 pairs a 0-10 VDC dimming output with each relay. This enables connected loads to be both switched and dimmed as necessary. Each of the nPANEL 4’s relay/dimming channels can be independently programmed; enabling custom multi-circuit control applications. PHYSICAL SPECS SIZE 8.375” W x 8.375” H x 3.125” D (21.27 cm x 21.27 cm x 7.94 cm) WEIGHT 6.0 lbs ENCLOSURE TYPE NEMA 1 MOUNTING Surface mount, screw cover door COLOR White nLIGHT NETWORK CONNECTION 4 RJ-45 Ports (2 sets of 2) RELAY TERMINAL SIZE 2 #8 AWG wires per lug nLIGHT OPERATION This panel is nLight-enabled, meaning it has the ability to directly communicate over an nLight network. When daisy-chain wired, using CAT-5 cabling, with other nLight-enabled sensors, power packs, or WallPods, an nLight control zone is created. Functionally the nPANEL 4 operates as two devices (each with two relays/dimming outputs and a unique network serial number) that can be utilized together in a single zone or in separate zones. Once linked to a Gateway, directly or via a Bridge, the zone becomes capable of remote status monitoring and control via SensorView software. ELECTRICAL SPECS OPERATING VOLTAGE 120/277 VAC RELAY TYPE Normally Closed Latching RELAY LOAD 30A @ 277 VAC Ballast 20A @ 120 VAC Tungsten 20A @ 347 VAC Ballast 1.5HP@ 120 VAC Motor Load 3HP @ 277 VAC Motor Load SCCR 18kA @ 277VAC OPERATIONS Rated for 250,000 Cycles @ 30A DIMMING LOAD Sinks < 20 mA / output; ~40 Ballasts @ .5 mA each AUXILIARY POWER OUPUT 200mA @ 28 VDC ENVIRONMENTAL SPECS OPERATING TEMP 32° to 105° F (0° to 41° C) Non-condensing SILICONE FREE ROHS COMPLIANT TITLE 24 MADE in U.S.A. C US LISTED 5 YEAR WARRANTY The nPANEL 4’s onboard power supply provides up to 40 mA of power from each of its RJ-45 (bus) connections and 200 mA via its auxiliary power output. This enables other nLight devices to connect directly to the nPANEL without any further consideration for device powering. DEVICE SETTINGS Several operation settings are available for assignment to each nPANEL relay/dimming pair independently. Override (On/Off/Normal) Occupancy Tracking (Enable/Disable) Photocell Tracking (Enable/Disable) Switch Tracking (Enable/Disable) Switch Tracking Channel (1-16) Occupancy Tracking Channel (1-16) Photocell Tracking Channel (1-16) Invert Relay Logic (Enable/Disable) Several special modes of operation can also be assigned to each relay/dimming pair that define the sequence of operation when connected with occupancy sensors or WallPods. Manual On to Auto Off (Semi-Auto) Manual to (Timed) Override On Predictive Off Auto to (Timed) Override On, Manual On to Full Auto DEFAULT SETTINGS Relay/dimming output 1 => Switch Tracking Channel 1 Relay/dimming output 2 => Switch Tracking Channel 2 Relay/dimming output 3 => Switch Tracking Channel 3 Relay/dimming output 4 => Switch Tracking Channel 4 All relay/dimming outputs => Occupancy Tracking Channel 1 All relay/dimming outputs => Photocell Tracking Channel 1 All relay/dimming outputs => Normal Operational Mode (Auto On/Auto Off) EMERGENCY POWER APPLICATIONS Because the relays in the nPANEL 4 are normally closed and latching the unit can be configured to switch emergency circuits as normal when primary power is present, but then override them closed when primary power is lost. Note switching both primary and emergency circuits within the same enclosure is not allowed. ORDERING INFO MODEL # MODEL # DESCRIPTION PANEL 4nLight Cabinet - 4 Relays (120/277/347 VAC), 4 Dimming Outputs (0-10VDC) n 277 120 Revised 2.17.11 © 2011 Sensor Switch AUX WIRING (DO NOT WIRE HOT) CAT-5 Auxiliary Power Output < 200mA (screw terminals ) N Power Supply Power Supply Inputs (Neutral, 120, 277) N H1 Push-Button & Feedback LEDs - 2 each H2 0-10 VDC nLight Nework Bus - 4 RJ45 (< 40 mA output power supplied each) Relays H3 H4 LOAD1 LOAD2 LOAD3 LOAD4 Relay Connections - 4 (1 line and 1 load screw terminal each) Cmn (-) Dim 1 (+) Dim 2 (+) Dim 3 (+) Dim 4 (+) 0-10 VDC Dimming Outputs - 4 (screw terminals) Ground (screw terminal) nPanel 2 480 1 Zone Wiring Configuration 2 Zone Wiring Configuration 277 277 AUX CAT-5 N H1 H2 0-10 VDC Relays H3 H4 LOAD1 Zone 2 (Controls Relay / Dimmer 3, 4) Zone 1 (Controls Relay / Dimmer 1, 2) LOAD2 LOAD3 CAT-5 N Power AUX N H1 CAT-5 H2 H3 0-10 VDC LOAD4 Cmn (-) Cmn (-) Dim 1 (+) Dim 1 (+) Dim 2 (+) Dim 2 (+) Dim 3 (+) Dim 3 (+) LOAD1 LOAD2 LOAD3 0-10 VDC LOAD4 H4 Cmn (-) Dim 1 (+) Dim 2 (+) Dim 4 (+) Dim 4 (+) INSTALLATION Zone 1 (Controls Relay / Dimmer 1, 2) • Remove lid screws and cabinet lid • Mount cabinet using holes located in four inside corners of unit • Connect non-switched Class 1 wires to power supply terminals and ground connection • Connect Class 1 wires of circuits to be switched to appropriate relay terminals • Connect Class 2 wires of dimming ballasts (0-10VDC only) or nLight devices to be powered via auxiliary power output • Interconnect unit (via RJ-45 ports) with277 other nLight devices in lighting zone using CAT-5 cables (Note: middle two RJ-45s will be connected at factory with CAT5 jumper. 120 If application calls for separating nPANEL between two zones, this CAT5 jumper must be removed.Power N Supply AUX is applied, all • Once power connected devices in zone will automatically begin functioning together according to each device’s defaults CAT-5lid and secure with lid screws • Restore N WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a LOAD1 H1period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material Authorization number and repair or replace returned product. LOAD2 LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied H2warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses. CAT-5 LOAD3 H3 9000-10 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com VDC LOAD4 H4 Relays Zone 2 (Controls Relay / Dimmer 3, 4) Cmn (-) 120 Supply CAT-5 Relays AUX Power Supply Relays N Power Supply 277 120 120 TN-612-01 Phase A Lo Phase A Li Phase B Lo Phase B Li Phase A Lo Phase A Li Phase B Lo Phase B Li