nPANEL 4 4 Relay Cabinet

advertisement
nPANEL 4
RELAY & 0-10 VDC DIMMING CABINET
SPECIFICATIONS
FEATURES
Communicates w/ nLight Network
Four Relays
Four 0-10 VDC Dimming Ouputs
Integrated Power Supply Provides both Bus & Auxiliary Device Power
Remotely Configurable/Upgradeable
Push-Button Programmable
Heavy-Duty Terminal Blocks
UL 924 Recognized (ETL Listed) for Switching Emergency Cicuits
OVERVIEW
The nLight nPANEL 4 is targeted at rooms that require multiple relays be co-located in a cabinet
enclosure. Utilizing four 30 Amp rated relays, the nPANEL 4 can switch up to four 120/277/347
VAC loads. Further, as a standard feature, the nPANEL 4 pairs a 0-10 VDC dimming output
with each relay. This enables connected loads to be both switched and dimmed as necessary.
Each of the nPANEL 4’s relay/dimming channels can be independently programmed; enabling
custom multi-circuit control applications.
PHYSICAL SPECS
SIZE 8.375” W x 8.375” H x 3.125” D
(21.27 cm x 21.27 cm x 7.94 cm)
WEIGHT 6.0 lbs
ENCLOSURE TYPE NEMA 1
MOUNTING Surface mount, screw cover door
COLOR White
nLIGHT NETWORK CONNECTION
4 RJ-45 Ports (2 sets of 2)
RELAY TERMINAL SIZE
2 #8 AWG wires per lug
nLIGHT OPERATION
This panel is nLight-enabled, meaning it has the ability to directly communicate over an nLight
network. When daisy-chain wired, using CAT-5 cabling, with other nLight-enabled sensors,
power packs, or WallPods, an nLight control zone is created. Functionally the nPANEL 4
operates as two devices (each with two relays/dimming outputs and a unique network serial
number) that can be utilized together in a single zone or in separate zones. Once linked to a
Gateway, directly or via a Bridge, the zone becomes capable of remote status monitoring and
control via SensorView software.
ELECTRICAL SPECS
OPERATING VOLTAGE 120/277 VAC
RELAY TYPE Normally Closed Latching
RELAY LOAD
30A @ 277 VAC Ballast
20A @ 120 VAC Tungsten
20A @ 347 VAC Ballast
1.5HP@ 120 VAC Motor Load
3HP @ 277 VAC Motor Load
SCCR 18kA @ 277VAC
OPERATIONS
Rated for 250,000 Cycles @ 30A
DIMMING LOAD Sinks < 20 mA / output; ~40 Ballasts @ .5 mA each
AUXILIARY POWER OUPUT
200mA @ 28 VDC
ENVIRONMENTAL SPECS
OPERATING TEMP
32° to 105° F (0° to 41° C)
Non-condensing
SILICONE FREE
ROHS COMPLIANT
TITLE 24
MADE in U.S.A.
C
US LISTED
5 YEAR WARRANTY
The nPANEL 4’s onboard power supply provides up to 40 mA of power from each of its RJ-45
(bus) connections and 200 mA via its auxiliary power output. This enables other nLight devices
to connect directly to the nPANEL without any further consideration for device powering.
DEVICE SETTINGS
Several operation settings are available for assignment to each nPANEL relay/dimming pair
independently.
Override (On/Off/Normal)
Occupancy Tracking (Enable/Disable) Photocell Tracking (Enable/Disable) Switch Tracking (Enable/Disable) Switch Tracking Channel (1-16)
Occupancy Tracking Channel (1-16)
Photocell Tracking Channel (1-16)
Invert Relay Logic (Enable/Disable)
Several special modes of operation can also be assigned to each relay/dimming pair that
define the sequence of operation when connected with occupancy sensors or WallPods.
Manual On to Auto Off (Semi-Auto)
Manual to (Timed) Override On
Predictive Off
Auto to (Timed) Override On,
Manual On to Full Auto
DEFAULT SETTINGS
Relay/dimming output 1 => Switch Tracking Channel 1
Relay/dimming output 2 => Switch Tracking Channel 2
Relay/dimming output 3 => Switch Tracking Channel 3
Relay/dimming output 4 => Switch Tracking Channel 4
All relay/dimming outputs => Occupancy Tracking Channel 1
All relay/dimming outputs => Photocell Tracking Channel 1
All relay/dimming outputs => Normal Operational Mode (Auto On/Auto Off)
EMERGENCY POWER APPLICATIONS
Because the relays in the nPANEL 4 are normally closed and latching the unit can be configured
to switch emergency circuits as normal when primary power is present, but then override them
closed when primary power is lost. Note switching both primary and emergency circuits within
the same enclosure is not allowed.
ORDERING INFO
MODEL #
MODEL #
DESCRIPTION
PANEL 4nLight Cabinet - 4 Relays (120/277/347 VAC), 4 Dimming Outputs (0-10VDC)
n
277
120
Revised 2.17.11 © 2011 Sensor Switch
AUX
WIRING (DO NOT WIRE HOT)
CAT-5
Auxiliary Power Output < 200mA
(screw terminals )
N
Power
Supply
Power Supply Inputs
(Neutral, 120, 277) N
H1
Push-Button &
Feedback LEDs - 2 each
H2
0-10 VDC
nLight Nework Bus - 4 RJ45
(< 40 mA output power
supplied each)
Relays
H3
H4
LOAD1
LOAD2
LOAD3
LOAD4
Relay Connections - 4
(1 line and 1 load screw
terminal each)
Cmn (-)
Dim 1 (+)
Dim 2 (+)
Dim 3 (+)
Dim 4 (+)
0-10 VDC Dimming
Outputs - 4
(screw terminals)
Ground
(screw terminal)
nPanel 2 480
1 Zone Wiring Configuration
2 Zone Wiring Configuration
277
277
AUX
CAT-5
N
H1
H2
0-10 VDC
Relays
H3
H4
LOAD1
Zone 2
(Controls
Relay /
Dimmer 3, 4)
Zone 1
(Controls
Relay /
Dimmer 1, 2)
LOAD2
LOAD3
CAT-5
N Power
AUX
N
H1
CAT-5
H2
H3
0-10 VDC
LOAD4
Cmn (-)
Cmn (-)
Dim 1 (+)
Dim 1 (+)
Dim 2 (+)
Dim 2 (+)
Dim 3 (+)
Dim 3 (+)
LOAD1
LOAD2
LOAD3
0-10 VDC LOAD4
H4
Cmn (-)
Dim 1 (+)
Dim 2 (+)
Dim 4 (+)
Dim 4 (+)
INSTALLATION
Zone 1
(Controls
Relay /
Dimmer 1, 2)
• Remove lid screws and cabinet lid
• Mount cabinet using holes located in four inside corners of unit
• Connect non-switched Class 1 wires to power supply terminals and ground connection
• Connect Class 1 wires of circuits to be switched to appropriate relay terminals
• Connect Class 2 wires of dimming ballasts (0-10VDC only) or nLight devices to be powered via auxiliary power output
• Interconnect unit (via RJ-45 ports) with277
other nLight devices in lighting zone using CAT-5 cables (Note: middle two RJ-45s
will be connected at factory with CAT5 jumper.
120 If application calls for separating nPANEL between two zones, this CAT5
jumper must be removed.Power
N
Supply
AUX is applied, all
• Once power
connected devices in zone will automatically begin functioning together according to each
device’s defaults
CAT-5lid and secure with lid screws
• Restore
N
WARRANTY:
Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
LOAD1
H1period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LOAD2
LIMITATIONS
AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
H2warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
CAT-5
LOAD3
H3
9000-10
Northrop
Road, Wallingford, CT 06492
• 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
VDC
LOAD4
H4
Relays
Zone 2
(Controls
Relay /
Dimmer 3, 4)
Cmn (-)
120
Supply
CAT-5
Relays
AUX
Power
Supply
Relays
N
Power
Supply
277
120
120
TN-612-01
Phase A Lo
Phase A Li
Phase B Lo
Phase B Li
Phase A Lo
Phase A Li
Phase B Lo
Phase B Li
Download