HEAT RECOVERY UNIT UR...............................................................................................................................................................3 Heat recovery unit URX CF.......................................................................................................................................................7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF.....................................................................................................................................................11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery unit These units allow to extract a certain amount of exhaust air from the room and supply an equivalent quantity of fresh air. A crossflow aluminium plate exchanger assures an efficient heat exchange between exhaust and fresh air: therefore the fresh air is pre-heated or precooled according to the seasons. The supply air is filtered before entering the heat recovery exchanger that is protected with a synthetic filter also at the exhaust air side. The supply air can optionally be re-heated with a hot water coil or with an electric coil. Features • 7 sizes are available: UR: standard version UR W: same as standard version and equipped with water heating coil with copper tubes and 3 rows aluminium fins. Not to be used with chilled water UR E: same as standard versions and equipped with electric heating coil with aluminium fins and double safety thermostat • Double suction centrifugal fans coupled directly to the electric motors, equipped with adjustable speeds via an electronic control to vary the flow rate cleaning or replacement • G3 class synthetic filter on the air outlet • Two versions available for horizontal and ver• Aluminium plate reheater housed in the contical installation (it is not possible to install densate tray that is easily removed from the the cooling coil accessories and silencers for bottom the vertical installation) • G3 class synthetic filter on the fresh air intake • Electronic Regulator with Slave Application • Self-bearing panels made of galvanized plate allowing continuous variation of rotation with injected polyurethane insulation and speed and air flow rate thickness 0.8 in. • Galvanized condensate tray • Fans can be inspected from the bottom • Filters can be removed from the bottom for 3 Accessories • BF: Water cooling coil. coil and 1-row water post-heating coil. • FGC: Circular flanges. • MPX: Module with 4-row water cooling • G4: High-efficiency filters on the fresh air coil and electric post-heating coil with reinintake in class G4. forced finned coils. Safety thermostat inclu• MPW: Module with 4-row water cooling ded. • SE: Free-Cooling control dampers. • SU: Silencers. Compatibility with the VMF system For further system information please refer to the specific documentation. Compatibility of accessories Horizontal installation: BF 35 BF 55 BF 75 BF 100 BF 150 BF 210 BF 330 FGC 1 FGC 2 G4 35 G4 55 G4 75 G4 100 G4 150 G4 210 G4 330 MPW 35 MPW 55 MPW 75 MPW 100 MPW 150 MPW 210 MPW 330 MPX 35 MPX 55 MPX 75 MPX 100 MPX 150 MPX 210 MPX 330 SE 1 SE 2 SE 3 SE 4 SE 5 SU 1 SU 2 SU 3 SU 4 SU 5 UR 35 ✔ UR 55 UR 75 UR 100 UR 150 UR 210 UR 330 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ Vertical installation: FGC 1 FGC 2 G4 35 G4 55 G4 75 G4 100 G4 150 G4 210 G4 330 SE 1 SE 2 SE 3 SE 4 SE 5 UR 35 ✔ UR 55 ✔ UR 75 ✔ UR 100 UR 150 ✔ ✔ UR 210 UR 330 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 4 Technical data Mod. Air flow Recoverer: Efficiency Heat capacity recovered Cooling capacity recovered Output temperature Fan motor assembly: Fans Total input power Fan speed variation cfm % Btu/h Btu/h °F UR 35 205.8 UR 55 323.4 52,1 5118.21 1364.86 46.4 55 8530.36 2388.50 47.66 Electrical protection Insulation class 2 0,30 continous UR Standard 0.5 UR E 0.46 UR W IP 0.244 B Filtres: EN779 Classification Efficiency % Available static pressure (in-w) Water heating coil (UR W): Geometry Rows Fin pitch Frontal surface area Heating capacity (1) Air output temperature (1) Heating capacity (2) Air output temperature (2) Heating capacity (3) Air output temperature (3) Electric heating coil (UR E): Heating capacity Air side pressure drop Stages Air output temperature (air 46.4°F) n. kW n. in ft2 Btu/h °F Btu/h °F Btu/h °F Btu/h inch-water n. F UR 75 441 UR 100 588 UR 150 882 UR 210 1234.8 UR 330 1940 54,3 54,4 53,1 52,7 52 11601.28 15695.85 22861.35 31732.92 48793.63 3412.14 4435.78 6483.07 8871.57 14672.21 47.48 47.48 46.94 46.76 46.4 2 0,70 continous 0.56 0.52 2 0,70 continous 0.68 0.64 2 1,12 continous 0.6 0.56 2 1,12 continous 0.48 0.44 2 2,00 continous 0.48 0.44 4 4,00 continous 0.6 0.56 54 0.2 F 44 0.2 F 55 0.28 F 55 0.2 F 55 0.2 F 55 0.2 F G3 80 G3 80 G3 80 G3 80 G3 80 G3 80 G3 80 P2519 3 0.07 P2519 3 0.07 P2519 3 0.07 P2519 3 0.07 P2519 3 0.07 P2519 3 0.07 P2519 3 0.08 0.29 0.5 16719.50 118.40 13989.78 106.16 8189.14 81.86 10.56 27638.35 122.00 22861.35 109.40 13648.57 83.66 8530.36 0.04 2 93.2 8530.36 0.04 2 77 Water cooling coil accessory with box to be positioned after the discharge fan: Frontal surface area ft2 0.81 0.81 Rows n. 4 4 Cooling capacity (4) Btu/h 6824.28 10236.43 Air side pressure drop in-water 0.10 0.23 0.99 1.28 1.78 17060.71 17060.71 0.04 0.04 2 2 89.6 78.8 34121.42 0.04 3 82.4 1.21 2.29 2.29 4 4 4 13648.57 23543.78 30026.85 0.19 0.10 0.22 51182.13 85303.55 0.04 0.04 3 3 84.2 87.8 2.69 4 40945.70 0.30 Power supply = 1~ 220V 60Hz (3N~ 460V 60 Hz Performance values refer to the following conditions: - room air temperature 68 °F; - ambient air temperature 23 °F. (1) (2) (3) (4) 5 2.55 36168.71 52888.20 76431.98 105776.40 146722.11 118.40 125.60 123.80 122.00 114.80 30026.85 44357.85 63807.06 88374.48 124884.40 106.34 113.00 110.48 109.40 103.10 17743.14 26273.49 38215.99 52546.99 75067.12 82.04 86.00 84.56 84.20 80.60 air temp. 46.4 °F - water temp. 176/158 °F tair temp. 46.4 °F - water temp. 158/140 °F air temp. 46.4 °F - water temp. 113/104 °F air temp. 80.6 °F - HR 50% - water temp. 53.6/44.6 °F 2.69 4 59712.49 0.42 Lay-out (horizontal configuration) Exaust air Fresh air inlet Supply air Exaust air Supply air Return air Return air Fresh air inlet Supply air Exaust air Return air Fresh air inlet Exaust air Fresh air inlet Supply air Return air Warning : the above diagrams refer to the unit in horizontal configuration only. For the vertical configuration, please consult the manual. Cod.: SURUY.05 / 1401 Dimensions (in) Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data. Aermec S.p.A. Via Roma, 996 - 37040 Bevilacqua (VR) - Italy Tel. +39 04 42 63 31 11 - Telefax +39 044 29 35 66 www.aermec.com 6 NEW URX CF Heat recovery unit with refrigerant circuit. 3/h. Air flow from 750 442 to to 3,300 1947 m cfm R410A The URX_CF series is the mono-bloc solution designed for the installation requirements typical for public spaces like bars, restaurants, offices, meeting rooms. The URX_CF units combine in one mono-bloc unit, besides the fan, filter, and heat recovery sections, a heat pump refrigerant circuit with scroll compressors of high output and low noise. The supply air is heated or cooled, based on the season, through the heat pump refrigerant circuit located within the unit and charged with refrigerant R410A. All this allows to have a complete unit, with the automatic operation in each season and capable of combining the required space ventilation requirements with efficient heat recovery. The careful design of the machine combines very compact dimensions, which permit easy installation in false ceilings, with an excellent accessibility for maintaining all the internal components. Characteristics VERSIONS ard. • Standard horizontal configuration 5 sizes complete with temperature controller REFRIGERANT CIRCUIT: and ready for installation. • Heat pump complete with high efficiency low noise scroll compressors, 4 way refrigerant PANELS: cycle reversing valve, evaporator coil, con• Self-supporting sandwich panel 0 .78 inch thick denser coil, liquid receiver, liquid separator, in galvanised steel for internal and external double thermostatic expansion valve, liquid surfaces with injected polyurethane insulasight glass (only for models 150, 210, 330), tion (density 2.5 lb/ft3). filter drier, high/low pressure pressostats. HEAT RECOVERY: ELECTRICAL PANEL: • Cross flow plate heat exchanger in aluminium • The unit is provided with an electrical panel with outputs over 50% in winter conditions. complete with power and control section (included the control for the 3 way valve for FILTERS: the supplementary hot water coil and associ• Class G3, 80% gravimetric efficiency, accordated actuators), ensuring the control of all the ing to EN 779, thickness 1.89 inch located refrigerant circuit functions. Included are: before the heat recovery both in the supply NTC return air temperature sensor, external and return air flow. air temperature sensor, dampers and actuators in the free-cooling version, pressure switch in CENTRIFUGAL FANS: the supply air filter. Supplied loose is a • Double inlet forward curved blades with remote mounted control terminal for autodirect drive motor. Single phase 220V-60Hz matic control of the unit and an outlet to single speed motor. The air flow is controlled, power and control a light to conform with the within +/- 15% of the nominal, through an current regulation for smoking zones. electronic speed controller supplied as stand- 7 CONDENSATE DRAIN TRAY: • Condensate drain tray in aluminium. ACCESSIBILITY: • From below for the heat recovery, the filters, the condensate drain tray and the fans. Accessories • • MBC casing with 2 row hot water coil to • install on the supply air. Includes the three way valve and on-off actuator. • FCE free-cooling complete with controls • to be added to the existing. Free-cooling operation only works in the summer mode, if the external air temperature is at least 10K lower than the internal air temperature and if the compressor safeties permit it. FGC circular flanges. Each accessory consists of a flange to be connected to each unit's rectangular connection. G4F filter efficiency G4 MBX casing with single stage electrical heater with shrouded finned elements, with double safety thermostat of manual and automatic reset type, to install on the supply air. URX_CF RS485 FCE FGC G4F MBC MBX SUF • • SUF silencer splitter module, in appropriate casing. The accessory consists of two modules: one for the supply and one for the return. RS485 board RS485 07 10 15 21 ✔ ✔ ✔ ✔ ✔ 07 07 07 07 07 07 10 10 10 10 10 10 15 15 15 15 15 15 21 21 21 21 21 21 33 33 33 33 33 Filters class G3 EN779 in supply and return Integrated heat pump refrigerant circuit with scroll compressor Reduced height for false ceiling installations Unit fitted with temperature controller with unit mounted electrical panel Electronic speed controller supplied as standard, to calibration the fan speed 8 33 9 Dimensional data (in) A C Cod.: SURXUY.01 / 1306 B Aermec reserves the right to make all modifications deemed necessary for improving the product at any time with any modification of technical data . Aermec S.p.A. Via Roma, 996 - 37040 Bevilacqua (VR) - Italia Tel. 0442633111 - Telefax 044293730 www.aermec.com 10 NEW URHE CF High efficiency heat recovery unit with refrigerant circuit without an external unit. Air flow from 588 to 1942 cfm R410A TECHNOLOGY HIGH EFFICIENCY The units from the URHE_CF series represent the high efficiency solution to satisfy the temperature and humidity comfort and ventilation requirements in air conditioning systems that serve public spaces and the commercial sector, such as offices, bars, restaurants, etc. The URHE_CF units are particularly efficient machines in that they use a high efficiency cross flow plate heat exchanger of high capacity combined with a heat pump refrigerant circuit operating with refrigerant R410A. The use of a high capacity cross flow heat recovery unit permits a significant reduction in the operating time of the refrigerant circuit throughout the year, thereby reducing to the minimum the electrical energy consumption. The small unit dimensions allow an easy installation even in false ceilings, allowing excellent accessibility for the maintenance of all the internal components. The numerous accessories available on request, for example the high efficiency compact filters, the hot water coil or the silencers, complete the functions of the machine which is usually combined to an air conditioning system. Characteristics VERSIONS tained constant by the use of an electronic • 4 sizes available in horizontal configuration controller.. ENVIRONMENTALLY FRIENDLY: for ground or ceiling void installation. • Through the applied technology and the use • Unit complete with temperature controller REFRIGERANT CIRCUIT: of ozone friendly refrigerant R410A, the and ready for installation. • Heat pump with refrigerant R410A, complete URCHE_CF series is environmentally friendly. with high efficiency low noise rotary or scroll R410A is a refrigerant with high thermodySTRUCTURE AND PANELS: compressors (depending on size), 4 way namic efficiency and this allows, together • Structure in aluminium profiles with glass refrigerant cycle reversing valve, evaporator with the use of scroll compressors, to reduce fibre reinforced nylon corner pieces. coil, condenser coil, liquid receiver, thermoCO2 emissions. • Sandwich panel 1 in thick with galvanised static expansion valve, liquid sight glass, filter steel for the internal surface, prepainted for drier, high pressure pressostat, low pressure the external surface with injected polyurepressostat, safety valve, bypass valve (for the thane insulation (density 2.62 lb/ft3). smaller sizes). HEAT RECOVERY: ELECTRICAL PANEL: • Cross flow plate heat exchanger in aluminium • The unit is provided with an electrical panel optimised to ensure high outputs. complete with power and control section (including the control for the 3 way valve for PLEATED FILTERS: the supplementary hot water coil and associ• Class G4, 80% gravimetric efficiency accordated actuators), ensuring the control of all the ing to EN 779, thickness 1.9 in located refrigerant circuit functions. Included are: before the heat recovery both in the supply NTC return air temperature sensor, external and return air flow. air temperature sensor, dampers and actuators in the free-cooling version, pressure switch in CENTRIFUGAL FANS: the supply air filter. Supplied loose is a • High pressure forward curved impeller directremote mounted control terminal for autoly coupled to the motor. The air flow is mainmatic control of the unit. 11 Accessories • • • • • MBCH hot water coil module MBCX electric heater module • FCT high efficiency compact filters F7 • BIT base for floor mounting BIM base for floor mounting for additional • modules • TPE roof for external installation • TPM roof for external installation of addi- • tional modules • FCH free-cooling kit URHE_CF MBCH MBCX RS485 board RS485 MSS n° 1 silencer splitter module TPMSS roof for silencer splitter module FGE circular flanges 10 MBCH1 MBCX1 15 MBCH1 MBCX2 25 MBCH1 MBCX3 33 MBCH2 MBCX4 FCT FCT1 FCT1 FCT2 FCT3 BIT BIT1 BIT1 BIT2 BIT3 BIM BIM1 BIM1 BIM1 BIM1 TPE TPE1 TPE1 TPE2 TPE3 TPM TPM1 TPM1 TPM1 TPM2 FCH FCH1 FCH1 FCH2 FCH2 RS485 RS485 RS485 RS485 RS485 MSS TPMSS FGE MSS1 MSS1 MSS2 MSS2 TPMSS1 TPMSS1 TPMSS1 TPMSS2 FGE1 FGE1 FGE1 FGE1 High efficiency plate heat exchanger Filters class G4 EN779 in supply and return Remote panel (standard) Inverter for fans standard to maintain constant air flow High efficiency heat pump refrigerant circuit Unit fitted with temperature controller with unit mounted electrical panel 12 13 Dimensional data (in) A C Cod.: SURHECFUY.02 / 1309 B Aermec reserves the right to make all modifications deemed necessary for improving the product at any time with any modification of technical data . Aermec S.p.A. Via Roma, 996 - 37040 Bevilacqua (VR) - Italia Tel. 0442633111 - Telefax 044293730 www.aermec.com 14 AERMEC North America 1608 Bonhill Road Mississauga, Ontario L5T 1C7 Ph: 905‐564‐2221 Toll Free Canada: 1‐800‐567‐2221 Toll Free USA: 1‐888‐567‐2227 Fax: 905‐564‐2205 Email: help@aermec.us www.aermec.us www.aermec.ca