UR Series Recovery Unit Data Sheet

advertisement
HEAT RECOVERY UNIT
UR...............................................................................................................................................................3
Heat recovery unit
URX CF.......................................................................................................................................................7
Heat recovery unit with refrigerant circuit(442-1947 cfm)
URHE CF.....................................................................................................................................................11
High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm)
UR
Heat recovery unit
These units allow to extract a certain amount of exhaust air from the room and supply an equivalent quantity of fresh air.
A crossflow aluminium plate exchanger assures an efficient heat exchange between exhaust and fresh air: therefore the fresh air is pre-heated or precooled according to the seasons.
The supply air is filtered before entering the heat recovery exchanger that is protected with a synthetic filter also at the exhaust air side.
The supply air can optionally be re-heated with a hot water coil or with an electric coil.
Features
• 7 sizes are available:
UR: standard version
UR W: same as standard version and equipped with water heating coil with copper
tubes and 3 rows aluminium fins. Not to be
used with chilled water
UR E: same as standard versions and equipped with electric heating coil with aluminium
fins and double safety thermostat
• Double suction centrifugal fans coupled
directly to the electric motors, equipped with
adjustable speeds via an electronic control to
vary the flow rate
cleaning or replacement
• G3 class synthetic filter on the air outlet
• Two versions available for horizontal and ver• Aluminium plate reheater housed in the contical installation (it is not possible to install
densate tray that is easily removed from the
the cooling coil accessories and silencers for
bottom
the vertical installation)
• G3 class synthetic filter on the fresh air intake • Electronic Regulator with Slave Application
• Self-bearing panels made of galvanized plate
allowing continuous variation of rotation
with injected polyurethane insulation and
speed and air flow rate
thickness 0.8 in.
• Galvanized condensate tray
• Fans can be inspected from the bottom
• Filters can be removed from the bottom for
3
Accessories
• BF: Water cooling coil.
coil and 1-row water post-heating coil.
• FGC: Circular flanges.
• MPX: Module with 4-row water cooling
• G4: High-efficiency filters on the fresh air
coil and electric post-heating coil with reinintake in class G4.
forced finned coils. Safety thermostat inclu• MPW: Module with 4-row water cooling
ded.
• SE: Free-Cooling control dampers.
• SU: Silencers.
Compatibility with the VMF system
For further system information please refer to
the specific documentation.
Compatibility of accessories
Horizontal installation:
BF 35
BF 55
BF 75
BF 100
BF 150
BF 210
BF 330
FGC 1
FGC 2
G4 35
G4 55
G4 75
G4 100
G4 150
G4 210
G4 330
MPW 35
MPW 55
MPW 75
MPW 100
MPW 150
MPW 210
MPW 330
MPX 35
MPX 55
MPX 75
MPX 100
MPX 150
MPX 210
MPX 330
SE 1
SE 2
SE 3
SE 4
SE 5
SU 1
SU 2
SU 3
SU 4
SU 5
UR 35
✔
UR 55
UR 75
UR 100
UR 150
UR 210
UR 330
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Vertical installation:
FGC 1
FGC 2
G4 35
G4 55
G4 75
G4 100
G4 150
G4 210
G4 330
SE 1
SE 2
SE 3
SE 4
SE 5
UR 35
✔
UR 55
✔
UR 75
✔
UR 100
UR 150
✔
✔
UR 210
UR 330
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
4
Technical data
Mod.
Air flow
Recoverer:
Efficiency
Heat capacity recovered
Cooling capacity recovered
Output temperature
Fan motor assembly:
Fans
Total input power
Fan speed variation
cfm
%
Btu/h
Btu/h
°F
UR 35
205.8
UR 55
323.4
52,1
5118.21
1364.86
46.4
55
8530.36
2388.50
47.66
Electrical protection
Insulation class
2
0,30
continous
UR Standard
0.5
UR E
0.46
UR W
IP
0.244
B
Filtres:
EN779 Classification
Efficiency
%
Available static pressure (in-w)
Water heating coil (UR W):
Geometry
Rows
Fin pitch
Frontal surface area
Heating capacity (1)
Air output temperature (1)
Heating capacity (2)
Air output temperature (2)
Heating capacity (3)
Air output temperature (3)
Electric heating coil (UR E):
Heating capacity
Air side pressure drop
Stages
Air output temperature (air 46.4°F)
n.
kW
n.
in
ft2
Btu/h
°F
Btu/h
°F
Btu/h
°F
Btu/h
inch-water
n.
F
UR 75
441
UR 100
588
UR 150
882
UR 210
1234.8
UR 330
1940
54,3
54,4
53,1
52,7
52
11601.28 15695.85 22861.35 31732.92 48793.63
3412.14
4435.78
6483.07
8871.57 14672.21
47.48
47.48
46.94
46.76
46.4
2
0,70
continous
0.56
0.52
2
0,70
continous
0.68
0.64
2
1,12
continous
0.6
0.56
2
1,12
continous
0.48
0.44
2
2,00
continous
0.48
0.44
4
4,00
continous
0.6
0.56
54
0.2
F
44
0.2
F
55
0.28
F
55
0.2
F
55
0.2
F
55
0.2
F
G3
80
G3
80
G3
80
G3
80
G3
80
G3
80
G3
80
P2519
3
0.07
P2519
3
0.07
P2519
3
0.07
P2519
3
0.07
P2519
3
0.07
P2519
3
0.07
P2519
3
0.08
0.29
0.5
16719.50
118.40
13989.78
106.16
8189.14
81.86
10.56
27638.35
122.00
22861.35
109.40
13648.57
83.66
8530.36
0.04
2
93.2
8530.36
0.04
2
77
Water cooling coil accessory with box to be positioned after the discharge fan:
Frontal surface area
ft2
0.81
0.81
Rows
n.
4
4
Cooling capacity (4)
Btu/h
6824.28
10236.43
Air side pressure drop
in-water
0.10
0.23
0.99
1.28
1.78
17060.71 17060.71
0.04
0.04
2
2
89.6
78.8
34121.42
0.04
3
82.4
1.21
2.29
2.29
4
4
4
13648.57 23543.78 30026.85
0.19
0.10
0.22
51182.13 85303.55
0.04
0.04
3
3
84.2
87.8
2.69
4
40945.70
0.30
Power supply = 1~ 220V 60Hz (3N~ 460V 60 Hz
Performance values refer to the following conditions:
- room air temperature 68 °F;
- ambient air temperature 23 °F.
(1)
(2)
(3)
(4)
5
2.55
36168.71 52888.20
76431.98 105776.40 146722.11
118.40
125.60
123.80 122.00
114.80
30026.85 44357.85 63807.06 88374.48 124884.40
106.34
113.00
110.48
109.40
103.10
17743.14 26273.49 38215.99 52546.99 75067.12
82.04
86.00
84.56
84.20
80.60
air temp. 46.4 °F - water temp. 176/158 °F
tair temp. 46.4 °F - water temp. 158/140 °F
air temp. 46.4 °F - water temp. 113/104 °F
air temp. 80.6 °F - HR 50% - water temp. 53.6/44.6 °F
2.69
4
59712.49
0.42
Lay-out (horizontal configuration)
Exaust air
Fresh air inlet
Supply air
Exaust air
Supply air
Return air
Return air
Fresh air inlet
Supply air
Exaust air
Return air
Fresh air inlet
Exaust air
Fresh air inlet
Supply air
Return air
Warning : the above diagrams refer to the unit in horizontal configuration only.
For the vertical configuration, please consult the manual.
Cod.: SURUY.05 / 1401
Dimensions (in)
Aermec reserves the right to make all modification deemed
necessary for improving the product at any time with any
modification of technical data.
Aermec S.p.A.
Via Roma, 996 - 37040 Bevilacqua (VR) - Italy
Tel. +39 04 42 63 31 11 - Telefax +39 044 29 35 66
www.aermec.com
6
NEW
URX CF
Heat recovery unit
with refrigerant circuit.
3/h.
Air flow from 750
442 to
to 3,300
1947 m
cfm
R410A
The URX_CF series is the mono-bloc solution designed for the installation requirements typical for public spaces like bars,
restaurants, offices, meeting rooms.
The URX_CF units combine in one mono-bloc unit, besides the fan, filter, and heat recovery sections, a heat pump refrigerant circuit
with scroll compressors of high output and low noise.
The supply air is heated or cooled, based on the season, through the heat pump refrigerant circuit located within the unit and
charged with refrigerant R410A. All this allows to have a complete unit, with the automatic operation in each season and capable of
combining the required space ventilation requirements with efficient heat recovery.
The careful design of the machine combines very compact dimensions, which permit easy installation in false ceilings, with an
excellent accessibility for maintaining all the internal components.
Characteristics
VERSIONS
ard.
• Standard horizontal configuration
5 sizes complete with temperature controller REFRIGERANT CIRCUIT:
and ready for installation.
• Heat pump complete with high efficiency low
noise scroll compressors, 4 way refrigerant
PANELS:
cycle reversing valve, evaporator coil, con• Self-supporting sandwich panel 0 .78 inch thick denser coil, liquid receiver, liquid separator,
in galvanised steel for internal and external
double thermostatic expansion valve, liquid
surfaces with injected polyurethane insulasight glass (only for models 150, 210, 330),
tion (density 2.5 lb/ft3).
filter drier, high/low pressure pressostats.
HEAT RECOVERY:
ELECTRICAL PANEL:
• Cross flow plate heat exchanger in aluminium • The unit is provided with an electrical panel
with outputs over 50% in winter conditions.
complete with power and control section
(included the control for the 3 way valve for
FILTERS:
the supplementary hot water coil and associ• Class G3, 80% gravimetric efficiency, accordated actuators), ensuring the control of all the
ing to EN 779, thickness 1.89 inch located refrigerant circuit functions. Included are:
before the heat recovery both in the supply
NTC return air temperature sensor, external
and return air flow.
air temperature sensor, dampers and actuators
in the free-cooling version, pressure switch in
CENTRIFUGAL FANS:
the supply air filter. Supplied loose is a
• Double inlet forward curved blades with
remote mounted control terminal for autodirect drive motor. Single phase 220V-60Hz
matic control of the unit and an outlet to
single speed motor. The air flow is controlled,
power and control a light to conform with the
within +/- 15% of the nominal, through an
current regulation for smoking zones.
electronic speed controller supplied as stand-
7
CONDENSATE DRAIN TRAY:
• Condensate drain tray in aluminium.
ACCESSIBILITY:
• From below for the heat recovery, the filters,
the condensate drain tray and the fans.
Accessories
•
•
MBC casing with 2 row hot water coil to
•
install on the supply air. Includes the three
way valve and on-off actuator.
•
FCE free-cooling complete with controls
•
to be added to the existing. Free-cooling
operation only works in the summer mode,
if the external air temperature is at least
10K lower than the internal air temperature
and if the compressor safeties permit it.
FGC circular flanges. Each accessory
consists of a flange to be connected to
each unit's rectangular connection.
G4F filter efficiency G4
MBX casing with single stage electrical
heater with shrouded finned elements,
with double safety thermostat of manual
and automatic reset type, to install on the
supply air.
URX_CF
RS485
FCE
FGC
G4F
MBC
MBX
SUF
•
•
SUF silencer splitter module, in
appropriate casing. The accessory consists
of two modules: one for the supply and
one for the return.
RS485 board RS485
07
10
15
21
✔
✔
✔
✔
✔
07
07
07
07
07
07
10
10
10
10
10
10
15
15
15
15
15
15
21
21
21
21
21
21
33
33
33
33
33
Filters class G3 EN779 in
supply and return
Integrated heat pump refrigerant
circuit with scroll compressor
Reduced height for false
ceiling installations
Unit fitted with temperature controller
with unit mounted electrical panel
Electronic speed controller supplied as
standard, to calibration the fan speed
8
33
9
Dimensional data (in)
A
C
Cod.: SURXUY.01 / 1306
B
Aermec reserves the right to make all modifications deemed
necessary for improving the product at any time with any
modification of technical data .
Aermec S.p.A.
Via Roma, 996 - 37040 Bevilacqua (VR) - Italia
Tel. 0442633111 - Telefax 044293730
www.aermec.com
10
NEW
URHE CF
High efficiency heat recovery unit with
refrigerant circuit without an external unit.
Air flow from 588 to 1942 cfm
R410A
TECHNOLOGY
HIGH
EFFICIENCY
The units from the URHE_CF series represent the high efficiency solution to satisfy the temperature and humidity comfort and ventilation
requirements in air conditioning systems that serve public spaces and the commercial sector, such as offices, bars, restaurants, etc.
The URHE_CF units are particularly efficient machines in that they use a high efficiency cross flow plate heat exchanger of high
capacity combined with a heat pump refrigerant circuit operating with refrigerant R410A.
The use of a high capacity cross flow heat recovery unit permits a significant reduction in the operating time of the refrigerant circuit
throughout the year, thereby reducing to the minimum the electrical energy consumption.
The small unit dimensions allow an easy installation even in false ceilings, allowing excellent accessibility for the maintenance of all
the internal components.
The numerous accessories available on request, for example the high efficiency compact filters, the hot water coil or the silencers,
complete the functions of the machine which is usually combined to an air conditioning system.
Characteristics
VERSIONS
tained constant by the use of an electronic
• 4 sizes available in horizontal configuration
controller..
ENVIRONMENTALLY FRIENDLY:
for ground or ceiling void installation.
• Through the applied technology and the use
• Unit complete with temperature controller REFRIGERANT CIRCUIT:
of ozone friendly refrigerant R410A, the
and ready for installation.
• Heat pump with refrigerant R410A, complete
URCHE_CF series is environmentally friendly.
with high efficiency low noise rotary or scroll
R410A is a refrigerant with high thermodySTRUCTURE AND PANELS:
compressors (depending on size), 4 way
namic efficiency and this allows, together
• Structure in aluminium profiles with glass
refrigerant cycle reversing valve, evaporator
with the use of scroll compressors, to reduce
fibre reinforced nylon corner pieces.
coil, condenser coil, liquid receiver, thermoCO2 emissions.
• Sandwich panel 1 in thick with galvanised
static expansion valve, liquid sight glass, filter
steel for the internal surface, prepainted for
drier, high pressure pressostat, low pressure
the external surface with injected polyurepressostat, safety valve, bypass valve (for the
thane insulation (density 2.62 lb/ft3).
smaller sizes).
HEAT RECOVERY:
ELECTRICAL PANEL:
• Cross flow plate heat exchanger in aluminium • The unit is provided with an electrical panel
optimised to ensure high outputs.
complete with power and control section
(including the control for the 3 way valve for
PLEATED FILTERS:
the supplementary hot water coil and associ• Class G4, 80% gravimetric efficiency accordated actuators), ensuring the control of all the
ing to EN 779, thickness 1.9 in located
refrigerant circuit functions. Included are:
before the heat recovery both in the supply
NTC return air temperature sensor, external
and return air flow.
air temperature sensor, dampers and actuators
in the free-cooling version, pressure switch in
CENTRIFUGAL FANS:
the supply air filter. Supplied loose is a
• High pressure forward curved impeller directremote mounted control terminal for autoly coupled to the motor. The air flow is mainmatic control of the unit.
11
Accessories
•
•
•
•
•
MBCH hot water coil module
MBCX electric heater module
•
FCT high efficiency compact filters F7
•
BIT base for floor mounting
BIM base for floor mounting for additional •
modules
•
TPE roof for external installation
•
TPM roof for external installation of addi- •
tional modules
•
FCH free-cooling kit
URHE_CF
MBCH
MBCX
RS485 board RS485
MSS n° 1 silencer splitter module
TPMSS roof for silencer splitter module
FGE circular flanges
10
MBCH1
MBCX1
15
MBCH1
MBCX2
25
MBCH1
MBCX3
33
MBCH2
MBCX4
FCT
FCT1
FCT1
FCT2
FCT3
BIT
BIT1
BIT1
BIT2
BIT3
BIM
BIM1
BIM1
BIM1
BIM1
TPE
TPE1
TPE1
TPE2
TPE3
TPM
TPM1
TPM1
TPM1
TPM2
FCH
FCH1
FCH1
FCH2
FCH2
RS485
RS485
RS485
RS485
RS485
MSS
TPMSS
FGE
MSS1
MSS1
MSS2
MSS2
TPMSS1
TPMSS1
TPMSS1
TPMSS2
FGE1
FGE1
FGE1
FGE1
High efficiency plate heat
exchanger
Filters class G4 EN779 in
supply and return
Remote panel
(standard)
Inverter for fans standard to maintain
constant air flow
High efficiency heat pump
refrigerant circuit
Unit fitted with temperature
controller with unit mounted
electrical panel
12
13
Dimensional data (in)
A
C
Cod.: SURHECFUY.02 / 1309
B
Aermec reserves the right to make all modifications deemed
necessary for improving the product at any time with any
modification of technical data .
Aermec S.p.A.
Via Roma, 996 - 37040 Bevilacqua (VR) - Italia
Tel. 0442633111 - Telefax 044293730
www.aermec.com
14
AERMEC North America
1608 Bonhill Road
Mississauga, Ontario
L5T 1C7
Ph: 905‐564‐2221
Toll Free Canada: 1‐800‐567‐2221
Toll Free USA: 1‐888‐567‐2227
Fax: 905‐564‐2205
Email: help@aermec.us
www.aermec.us
www.aermec.ca
Download