PA4 4 Zone Wired Intruder Alarm System MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 Zone 4 1 2 3 ARM 4 5 6 OMIT 7 8 9 RESET AWAY 0 ER HOME EXIT 1. 2. or 3. Check all windows and doors are closed. a) Fullguard - Press 'Away' then 'Arm'. b) Partguard - Press 'Home' then 'Arm'. Leave premises by entry/exit route. ENTRY 1. Enter premises by entry/exit route. 2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode. Installation & Operating Manual FOREWORD Your decision to purchase a Response PA4 Wired Intruder Alarm System represents a major and sensible step towards total protection of your premises, its contents and its occupants. All components are designed and manufactured to provide a high standard of security protection and long, reliable service. The PA4 Alarm System is designed for ease of installation using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual and plans the system before proceeding with the installation. During installation, it is important that the procedures described in this manual are followed in sequence. This manual should be retained in a safe place for future reference. IMPORTANT All components, with the exception of the External Siren, are suitable for mounting in dry interior locations only. Tools and Equipment Required: 3mm flat bladed screwdriver No.1 Philips screwdriver No.2 Philips screwdriver Wire Cutters & Strippers Drill 5 & 6mm Masonry Drill Bits Bradawl Hammer Small Spirit Level SAFETY WARNINGS Before proceeding with the installation, please note the following safety warnings: 1. Always follow the manufacturers advice when using power tools, steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes and hammering home cable clips etc. 2. Before drilling holes in walls, check for hidden cables and pipes. The use of a cable/pipe locator may be advisable if in any doubt. 3. When using ladders, ensure that they are positioned on a firm stable surface at the correct angle and suitably secured before use. 4. The use of ear defenders is advisable when working in close proximity to the Siren due to the high sound level produced by this device. SYSTEM SECURITY This system has been designed to both detect intruders and act as a strong deterrent to would-be intruders. Please remember that, given adequate knowledge and time, it is possible to overcome any alarm system and we therefore recommend that an Intruder Alarm is used in conjunction with good physical protection such as security windows and door locks. The system is operated from the Control Panel using a 4 digit User Access code. Care should be taken to ensure that your User Access code does not become known to other people as this will compromise the security of your system. In this event the User Access code should be changed as soon as possible. Additional Requirements: Terminal Strip or Insulating Tape 2 x 9 Volt PP3 Alkaline Back-up Batteries LOCAL AUTHORITY REGULATIONS Depending on your location within the country, you may be required by law to notify the Local Authorities and Police of your new alarm installation. Local Authority requirements differ from area to area, therefore, we recommend that you contact your Local Borough Environmental Officer to obtain full details of your area's requirements. Friedland PA4 Wired Intruder Alarm System CONTENTS Page No. Page No. INTRODUCTION & OVERVIEW Alarm Control Panel System Operation After Power Failure Passive Infra Red Movement Detectors Magnetic Contacts External Siren 2 2 2 2 2 KIT CONTENTS 3 SYSTEM FEATURES User Functions Arm/Disarm Quick Set Event Log Home and Zone Omit Reset Installer Functions Programming Zones 24 Hour Tamper Circuit Siren/Anti Tamper Monitoring Programmable Zone Options Entry/Exit Walk Through Zone General System Programmable Options Entry Time Exit Time Zone Omit Alarm Duration System Reset User Access Code Installer Access Code Keypad Security 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 INSTALLING THE MAGNETIC CONTACT DETECTORS Wiring the Magnetic Contacts Testing Magnetic Contacts at the Control Panel 14 15 INSTALLING THE EXTERNAL SIREN Fitting the External Siren Unit Wiring the Siren Unit 15 16 CONNECTING THE CONTROL PANEL MAINS ADAPTOR AND OPTIONAL BACK-UP BATTERIES 16 PROGRAMMING General 17 INSTALLER PROGRAMMING MODE Changing The Installer Access Code Exit Delay Time Adjustment Entry Delay Time Adjustment Alarm Duration Adjustment Selecting ‘Home’ Feature Zones Selecting Walk Through Zones Selecting ‘Code Arming’ Reset System Defaults Lost Or Forgotten Installer Access Code 17 17 17 18 18 18 18 19 19 19 USER PROGRAMMING MODE Change The User Access Code 19 19 20 OPERATING INSTRUCTIONS ‘Away’ Arming All Zones ‘Home’ Arming Pre-Selected Zones Arming with Occasional Zones Omitted Quick Arm Disarming the System Event Log 20 21 21 21 21 22 MAINTENANCE Control Panel and Detectors Back-up Batteries Batteries 22 22 ALARM RECORD 22 TROUBLE SHOOTING 23 10 11 EXTENDING YOUR PA4 WIRED INTRUDER ALARM SYSTEM 24 11 COMPONENT SPECIFICATION Back Cover 6 6 6 6 6 7 INSTALLING THE CONTROL PANEL Testing the Control Panel Wiring the Detection Zones 8 9 PA4 Alarm 12 TESTING THE SYSTEM PLANNING THE INSTALLATION Locating the Control Panel Detector Wiring Magnetic Contact Detectors PIR Movement Detectors External Siren Installation Example INSTALLING THE PIR MOVEMENT DETECTORS Mounting the PIR Movement Detectors Wiring the PIR Movement Detectors Testing the PIR Movement Detectors at the Control Panel TYPICAL WIRING ARRANGEMENTS 1 INTRODUCTION INTRODUCTION & OVERVIEW The PA4 Alarm Package contains all components necessary to install a complete system. The items included in your Package are shown opposite. The main components are as follows:- correctly and during this period they effectively generate an alarm signal to the Control Panel. Note: Although optional, it is strongly recommended that backup batteries are fitted. ALARM CONTROL PANEL The Control Panel is the heart of the intruder alarm system and contains the microprocessor and electronic circuitry necessary to monitor the various detection circuits (Zones) and to initiate an alarm condition in the event of an intrusion into a protected area. All detectors and alarm circuits are wired from the Control Panel and operate at 12 Volts dc. The complete system operates at 12 Volts powered from the plug-in mains adaptor. In the event of a mains failure, the system will operate from the optional Back-up Batteries if these have been fitted. Passive Infra Red (PIR) detectors are designed to detect movement in a protected area by detecting changes in infra red radiation levels within its field of vision. If movement is detected the PIR detector will generating an alarm signal at the Control Panel, (if the system is armed). PIR detectors will also detect animals, so ensure that pets are not permitted access to areas fitted with PIR Movement Detectors when the system is armed. The Control Panel is operated via the push buttons on the front of the Control Panel allowing the user to ARM/ DISARM the system, Omit Zones, view the Event Log, Test the system or Program the various system functions. A four digit User Access Code ensures that only authorised users can operate the system. The Control Panel also contains a small speaker used to indicate various conditions by means of a variety of tones. The Control Panel incorporates a ‘Non Volatile Memory’, (NVM) which records all program settings indefinitely even when all power has been removed. The Control Panel will also remember which mode it was in when power was disconnected and revert to this mode when power is restored, e.g. if the panel was in Alarm Mode when the power was removed, the panel will continue to be in Alarm Mode when power is restored. SYSTEM OPERATION AFTER POWER FAILURE If a power failure occurs while the system is armed and backup batteries are not fitted (or flat) then when power is restored the system will be in its previously armed state. If there are any PIR detectors wired to any active zone then an alarm will initially occur. The siren will sound for the set alarm duration after the 3-4 minutes required for the PIR detectors to stabilise. This is because the PIR detectors require a period of 3-4 minutes to stabilise before they operate 2 PASSIVE INFRA RED MOVEMENT DETECTORS Additional Passive Infra Red Movement Detectors can be purchased separately, if required. MAGNETIC CONTACT DETECTORS Each Magnetic Contact Detector comprises two parts; a Magnetic Contact Switch and a Magnet. They are designed to be fitted to either doors or windows with the Magnet fixed to the moving/opening part and the Contact Switch fixed to the door or window frame. When the protected door or window is closed, the Contact Switch is held closed by the magnetic field from the Magnet. Opening the protected door or window will remove the magnetic field and allow the contact switch to open generating an alarm signal at the Control Panel, (if the system is armed). Additional Magnetic Contacts can be purchased separately, if required. EXTERNAL SIREN The External Siren enclosure houses the Siren, which when assembled, installed and wired to the Control Panel will activate in the event of an intrusion with the system armed. In the event of the cable to the Siren Unit being deliberately cut an alarm will be generated at the control panel, provided that the tamper circuit to the Siren has been connected. PA4 Alarm KIT CONTENTS MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 Zone 4 1 2 3 ARM 4 5 6 OMIT 7 8 9 RESET AWAY 0 ER HOME INTRODUCTION The PA4 Wired Intruder Alarm System contains the following components. EXIT 1. 2. or 3. Check all windows and doors are closed. a) Fullguard - Press 'Away' then 'Arm'. b) Partguard - Press 'Home' then 'Arm'. Leave premises by entry/exit route. ENTRY 1. Enter premises by entry/exit route. 2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode. Control Panel 2 x Magnetic Contact Detectors External Siren External Siren Enclosure IMPORTANT 2 x PIR Movement Detectors 1 1 1 1 2 2 1 1 x x x x x x x x 4 Zone Control Panel Mains Adaptor Mains Adaptor External Siren External Siren Enclosure Passive Infra Red Movement Detectors Magnetic Contact Detectors 50 metres (approx) of 6 Core Cable Cable Clips and Fixings Also included:Installation & Operating Manual Window Warning Stickers Please check all items are present BEFORE breaking the packaging warranty seals. No claims for missing parts will be accepted unless pack seals are in place and intact. EXTENDING THE PA4 ALARM SYSTEM The following additional accessories are available to enhance your system and provide further protection and a higher level of security where required. Important: The PA4 system can be expanded to contain maximum of 7 PIR detectors. Component Order Code Accessory Pack comprising the following: 2 x Passive Infra Red Movement Detectors 2 x Magnetic Contact Detectors 25 metres (approx.) of 6 Core Cable PU1 Passive Infra Red Movement Detectors (Twin Pack) PU2 Full details of these accessories are given on page 24. PA4 Alarm 3 SYSTEM FEATURES INTRODUCTION USER FUNCTIONS ARM/DISARM The system has an easy arming facility. To fully arm the system simply press the AWAY button or to partially arm the system, omitting preselected Zones; press the HOME button. Then press ARM . The Magnetic Contacts on the front door would normally be connected to Zone 1. Other Detectors can be connected to Zones 2, 3 and 4 to protect the remaining areas within the property, as required. 24 HOUR TAMPER CIRCUIT QUICK SET The final arming of the system can be quicker. This is useful for night setting when the Entry/Exit sounder can be silenced after just a few seconds. EVENT LOG The Control Panel incorporates an Event Log memory capable of storing the last 4 alarm events. The Event Log replay will enable the user to establish which Zones have been activated if an alarm has occurred. Many system components incorporate tamper protection facilities and the associated wiring can be monitored on a 24 hour basis to generate an alarm condition if the equipment or wiring is interfered with. It is recommended that all system components with tamper facilities are monitored for tamper. SIREN ANTI TAMPER MONITORING HOME AND ZONE OMIT Wiring to the External Siren is monitored on a 24 hour basis. In the event of the wiring to the External Siren being damaged or deliberately cut, an alarm will be initiated at the Control Panel. The HOME button is used if you are remaining on the premises and require to arm the system while omitting pre-selected Zones. PROGRAMMABLE ZONE OPTIONS The OMIT button enables you to omit any Zone combination you require on a once only or temporary basis. Note: The Entry/Exit Zone cannot be omitted. RESET Pressing the RESET button clears any previously entered information at the keypad, e.g. incorrect buttons pressed and also clears Fault Lights, and resets the system after an alarm. INSTALLER FUNCTIONS PROGRAMMING When a valid installer code has been entered, access to programming the various system options will be permitted. ZONES The Control Panel incorporates four detection Zones for the connection of the system detectors. Zone 1 is intended for exclusive connection to the detector(s) which are located on the Entry/Exit route and will operate the Entry/Exit timers and associated tones. 4 ENTRY/EXIT Zone 1 is programmed as Entry/Exit to allow the user a preselected (adjustable) time delay to exit and enter the premises without creating an alarm. During the Entry/Exit procedures, a low audible warning tone will be emitted from the Control Panel speaker. Normally the front door of the property would be the Entry/Exit route and would be connected to Zone 1. WALK THROUGH ZONE Zone 2 is programmed for a detector which is fitted between the Entry/Exit door and the Control Panel, e.g. in the downstairs hallway. When the Entry/Exit door is opened and the entry procedure begins, the ‘Walk Through Zone’ is inhibited for the duration of the entry time, allowing the system to be disarmed without creating an alarm. However, if the ‘Walk Through Zone’ is violated before the entry procedure is initiated, a full alarm will instantly occur. Note 1: It is advisable to change Zone 2 to an ‘Instant’ Zone if this facility is not required. Note 2: Zone(s) selected as ‘Walk Through’, cannot also be selected to operate on the ‘HOME’ feature. PA4 Alarm ENTRY TIME This is the time programmed to allow the user to reach the Control Panel to disarm the system before an alarm occurs. The Entry Time may be set between 01 - 99 seconds, depending on your own requirements. The default Entry Time is 30 seconds. If the system is not disarmed during the Entry delay period, a full alarm will occur when the Entry time expires. SYSTEM RESET (RETURN ALL OPTIONS TO FACTORY SETTINGS) If the User/Installer Access Codes have been lost or forgotten, or the installer is unsure of the programmed options, it is possible to return the Control Panel program to the factory default settings. All previously programmed options will be cleared and the system will require to be re-programmed to the user’s requirements. EXIT TIME This is the time programmed to allow the user to exit the premises before the system finally arms. The default Exit Time is 30 seconds however, this time may be set between 01 - 99 seconds, depending on your requirements. You will need to leave all protected areas and close protected doors/windows before the Exit time expires or a full alarm condition will occur. Note: If a Zone is open when the system is armed the Control Panel will emit a series of beeps (different to the Entry/Exit tone) to indicate which Zone is open, (i.e. 1 beep = Zone 1 open). It is not possible to Arm the system until the Zone is clear or omitted before arming. ZONE OMIT It is possible to pre-program a section of Zones for regular Zone omitting ie: night setting where ground floor Zones are armed whilst first floor Zones are omitted. Once programmed, the use of the HOME button will Arm the system omitting the selected Zones. It is also possible to omit a specified Zone(s) different to the ‘Home’ setting on a once only/temporary basis using the OMIT button. USER ACCESS CODE To Arm and Disarm the system and perform other functions, the user must enter a unique 4-digit User Access Code at the Control Panel keypad. The default User Access Code is 1 2 3 4 but this should be changed to your own unique code which only you and other system users know, once installation is complete. INSTALLER ACCESS CODE To allow programming of the system options, a unique Installer Access Code must be entered at the Control Panel keypad. If the user is installing the system, you may choose your own code. However, if the system has been installed for you by an approved installer, the installation code may not be available. The factory default Installer Access Code is 9 9 9 9 but this should be changed when the programming has been completed. KEYPAD SECURITY The Control Panel is protected from unauthorised disarming by means of initiating an alarm if more than 4 incorrect attempts to enter the User Access Code are made. In addition, if any button is pressed when the system is armed, the Entry timer will start. ALARM DURATION This is the time that the External Siren will sound for following an alarm activation. The program Alarm Duration time is 20 minutes, however this can be set to between 01 - 20 minutes, depending on individual requirements. Note: Most Local Authority noise pollution requirements set limits acceptable for alarm duration. You should therefore check your Local Authority requirements. PA4 Alarm 5 INTRODUCTION GENERAL SYSTEM PROGRAMMABLE OPTIONS PLANNING THE INSTALLATION GENERAL Before attempting to install any wiring or system components, it is recommended that a plan of the proposed installation is prepared. This should help the installation to be completed using the most unobtrusive and effective methods. The following guidelines should be followed and used in conjunction with the example provided when preparing your own system plan. LOCATING THE CONTROL PANEL INSTALLATION The Control Panel should be located out of obvious sight of potential intruders and in a safe location, but easily accessible for system operation. Typically, the Control Panel may be located close to the main entry door or in a small cupboard under the stairs (or similar) close to a mains socket. An ideal mounting height would be the same as a household light switch or similar. If small children are in the household, a further consideration should be given to keeping the Panel out of reach. Also consider the user’s ability to hear the Entry/Exit Tone emitted by the Control Panel effectively when setting the system. It is preferable that the Exit Tone can be heard from outside the property when arming the system. The final position of the Control Panel will depend on the individual user requirements. Note: If using the Home Arm feature the Control Panel must not be located within an area protected by a PIR Movement detector unless this detector is not activated during Home Arm. DETECTOR WIRING Where only one detector per Zone is to be connected, the cable should be run directly to the detector. However, if more than one detector is to be connected to a Zone, either (a) run all cables back to the Control Panel or (b) run one cable to the Control Panel and link the detector contacts in ‘SERIES’ and power supplies in ‘PARALLEL’, (refer to example installation wiring diagrams on pages 15-16). MAGNETIC CONTACT DETECTORS The Magnetic Contact Detectors are suitable for mounting in dry interior locations only. 6 Decide which doors and windows are to be protected by fitting the Magnetic Contact Detectors. Normally the front and back doors will have Magnetic Contact Detectors fitted. Additional detectors may be fitted where required to other more vulnerable doors or windows, e.g. garage, patio and conservatory doors etc. Note: It is not recommended to connect more than four Magnetic Contacts to one Zone, as this may cause difficulty in wiring and hinder any attempt to remedy wiring faults efficiently. PIR MOVEMENT DETECTORS The PIR Detectors are suitable for mounting in dry interior locations only. When considering and deciding upon the mounting position for the detector the following points should be considered to ensure trouble free operation: 1. Ideally the detector should be positioned in a corner of the room to be protected where the logical path of an intruder would cut across the fan detection pattern of the device. PIR detectors respond more effectively to movement across the device than to movement directly towards it. 2. Do not position the detector facing a window or where it is exposed to direct sunlight. PIR detectors are not suitable for use in conservatories. 3. Do not position the detector where it is exposed to draughts. 4. Do not position the detector directly above a heat source, (e.g. fire, radiator, boiler, etc). 5. Do not position the detector in a position where it is subject to excessive vibration. Note: When the system is armed, household pets should not be allowed into an area protected by a PIR as their movement would trigger the PIR and activate the alarm. Alternatively a PIR protected Zone may be 'Omitted' to allow for pet movement. EXTERNAL SIREN The external housing should be located as high as possible in a prominent position so that it can be easily seen and heard. When running the cable to the siren, the cable should pass through a hole in the external wall and enter through the rear of the casing. PA4 Alarm FURTHER CONSIDERATIONS If the system is to be armed at night ie. (Zones omitted) while the occupants remain in the household, make sure that any detectors which are to be omitted are wired exclusively to those Zone(s). (Remember that a ‘Walk Through Zone’ cannot also be selected on the ‘Home’ setting). Pay particular attention to the most vulnerable points of entry to your property, which are the doors and windows to the side and rear of the property. Plan your cable runs for ease of installation and neatness of final appearance, allowing for concealing cables where necessary. INSTALLATION EXAMPLE The following example shows typical floor plans for a two storey domestic property incorporating the suggested positions for the Control Panel, External Siren and Detectors, for optimum security. Use this as a guide for your installation in conjunction with the recommendations for planning your intruder alarm system. In this example, the front door is the Entry/Exit route to the property and is connected to Zone 1. The side door is also fitted with a Magnetic Contact and is connected to Zone 2. The Living Room and Dining Room are fitted with PIR Movement Detectors detecting entry into the rooms from any angle and are connected to Zone 3. An additional PIR has been fitted on the upstairs landing. The upstairs PIR Movement Detector will detect entry into the first floor and is connected to Zone 4 (This is the Zone which will be intentionally omitted when the system is armed at night). PIR Movement Detector PIR Movement Detector Dining Room (Zone 3) (Zone 3) Living Room Magnetic Contact Detector Hallway TYPICAL GROUND FLOOR PLAN Front Door (Entry/Exit Zone 1) Back Door (Zone 2) Kitchen Control Panel Magnetic Contact Detector MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 1 2 3 ARM 4 5 6 OMIT 7 8 9 RESET AWAY 0 ER HOME Zone 4 Control Panel EXIT 1. Check all windows and doors are closed. 2. a) Fullguard - Press 'Away' then 'Arm'. or b) Partguard - Press 'Home' then 'Arm'. 3. Leave premises by entry/exit route. PIR Movement Detector ENTRY 1. Enter premises by entry/exit route. 2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode. Bedroom 2 (Zone 4) (omitted during night setting) Bedroom 1 Landing External Siren PA4 Alarm Bedroom 3 TYPICAL FIRST FLOOR PLAN 7 INSTALLATION Surface wiring to the External Siren is not recommended unless it is mechanically protected, e.g. in steel tubing or equivalent. However, if surface wiring is unavoidable, the 24 hour monitoring will activate the Control Panel sounder if damage occurs. However, if the system is armed at the time a full alarm will occur. INSTALLING THE CONTROL PANEL Choose a suitable position to locate the Control Panel as described in ‘Planning The Installation’. Important: Do not drill the fixing holes with the Control Panel in position, as the resulting dust could seriously affect the system electronics and invalidate the guarantee. Note: The Control Panel should be mounted on an even flat surface to prevent the possibility of distortion to the Control Panel casing. TESTING THE CONTROL PANEL INSTALLATION 1. There is no need to completely remove the front cover screws, simply loosen the screws, then hinge open and lift the cover from the top lip and place safely to one side. The Control Panel is factory fitted with small wire links inserted to the Zone and 24Hr Tamper connections. These can be removed, then replaced when testing the Control Panel to simulate a detector switch opening and closing. 2. Hold the Control Panel in position and mark the location of the three mounting holes on the wall. A small spirit level placed on the casing will ensure a perfect level. Note: If the front cover tamper switch is not bypassed, the Control Panel will indicate a 24 hour fault, indicated by the 24 Hr LED and internal sounder activating. To temporarily bypass the Control Panel Anti Tamper Switch, connect a short piece of the alarm cable (approx. 100 mm) between terminals 11 and 21, while you test the Zones. Leave this wire connected throughout the installation and whilst you connect the detectors to the Control Panel. Note the position of the cable entries that you may require before fixing the Control Panel. The final use of cable entries will depend on the individual installation requirements. 3. Remove the Control Panel, drill 3 x 6mm holes and insert the 30mm plastic wall plugs supplied. Using the 30mm No. 8 screws fix the Control Panel loosely onto the two slotted holes at the top. The top screws may be tightened and the remaining bottom screw inserted when the installation is complete. Detection and Alarm Wiring Terminal Blocks Should the panel speaker sound during testing, press RESET followed by 1 2 3 4 to silence or Current User Access Code the tone, followed by NVM Reset Pins and Link RESET , then continue. Top Keyhole Fixings 1 Z1 2 3 Z2 Z3 6 7 Z4 NVM RESET 4 5 Speaker Leads 2 3 ARM 4 5 6 OMIT 7 8 9 RESET AWAY 0 ER HOME Keypad 8 11 1 24Hr 14 17 18 21 SPEAKER D BELL B 12 13 Bottom Cover AUX 22 Cover Tamper Switch Cover Fixing Screws Leads and Connectors for Optional Back-up Batteries Bottom Fixing Hole Mains Adaptor Socket Control Panel Internal Physical Layout 8 PA4 Alarm WIRING THE DETECTION ZONES 1. Connect the plug in Mains Adaptor and switch on the supply. AWAY . The clear LED will 3. Remove the factory fitted link from Zone 1 terminals. The Zone 1 LED will flash and the internal speaker will intermittently beep once. Refit the link to extinguish the Zone 1 LED and silence the tone. Red Black 4. Repeat this procedure for Zones 2, 3 and 4. The Control Panel will intermittently beep twice for Zone 2, three times for Zone 3 and four times for Zone 4. 5. To test the 24 Hr Zone, first ensure the temporary link is removed between the terminals 11 and 21. Make sure you hold down the panel tamper switch spring, press RESET . Remove the factory link between terminals 11 and 12 to activate the internal speaker. Replace the link, then enter 1 2 3 4 . Check the 24 Hr Zone LED is illuminated, then press RESET . Replace the temporary link between terminals 11 and 21. RESET +ve supply to each PIR Movement Detector 0V -ve supply to each PIR Movement Detector Yellow Blue Normally closed detector contact alarm Zone circuit Green White 24 Hr normally closed Tamper Circuit The power supply to each PIR Movement Detector should ideally be taken direct from the Control Panel to each detector, so that a break in the cable only results in one detector being out of service. However, the power supply can be taken from one detector to the next if required, up to a maximum of four detectors or 50 metres of cable per Zone. or Current User Access Code 6. To end the test sequence, press 12V All Zone and Tamper circuit wiring must be wired in a ‘SERIES’ loop from the appropriate terminals in the Control Panel. Where ‘Series’ connections are made terminal blocks or insulating tape must be used to prevent bare wires touching each other. . 7. The plug in Mains Adaptor must now be disconnected, but will be re-connected when testing each detector as it is installed. Surface cabling should be clipped at 1m intervals using the clips supplied. Please refer to the appropriate circuit wiring diagrams for typical wiring arrangements for the detectors supplied. 2 3 1 Z1 4 5 Z2 6 7 Z3 Zones 8 11 Z4 12 13 24Hr Tamper Circuit 14 17 18 21 SPEAKER D BELL B External Siren 22 AUX PIR Detector Power Supply Mains Adaptor Factory Links Note: Remove factory wire links before connecting circuit wiring. Leave the factory wire links in place where a zone/circuit is unused. Control Panel Schematic Wiring Diagram Showing Factory Links Fitted PA4 Alarm 9 INSTALLATION 2. Press RESET then press illuminate. In order to keep wiring consistent and aid installation/connections, it is recommended that the following wiring code is adhered to throughout the installation:- INSTALLING THE PIR MOVEMENT DETECTORS The Passive Infra Red (PIR) Movement Detectors supplied with this kit are suitable for mounting in dry interior locations only. It is recommended that the PIR Detector is mounted in the corner of a room, approximately 2.2m above floor level. At this height the detector will have a 12m range with a 90º spread. If required the detector may be mounted at an 8° angle to tilt downwards and reduce the detection pattern range. INSTALLATION Before fitting the detector, observe the environmental considerations as described in ‘Planning The Installation’. Note: A maximum of 7 PIR Movement Detectors can be connected to the system in total. 1. Having chosen a suitable position to locate the PIR Detector, run the required length of 6-core cable back to the Control Panel. Do not make any connections at this stage. 2. Slightly loosen the cover retaining screw on the PIR and remove the cover. Carefully remove the PCB by un-clipping the PCB retaining clip at the bottom left of the PCB. Important: Do not touch the PIR sensor in the middle of the PCB as any marking may impair the unit’s performance. If accidentally touched, clean with a lint-free cloth. Top Mount 3. The unit can be mounted for the standard 12m range by using the top two side holes, or tilted down by 8° using the bottom two side holes. Alternatively, the unit can be ceiling mounted using the two holes at the extreme top of the casing. Cable entry cut outs are provided top and bottom, as required. 8° 4. Carefully cut (or drill) out the required mounting holes and cable entry. Only remove the minimum required number of screw or cable holes, to avoid insects entering the detector and causing false triggering. Mount the unit using two 18mm No.4 screws and 25mm wall plugs as required, (a 5mm hole will be required for the wall plugs). Vertical Mount Angled Mount MOUNTING THE PIR MOVEMENT DETECTORS 90° angle Note: Do not over tighten or use larger headed screws when mounting the unit, as this may distort the casing. PIR Sensor (Do Not Touch) 2.2 metres 2 4 6 8 10 AntiTamper Switch 12 Distance (metres) Alarm LED PIR LED 2.2 metres N/C 24HR 123 8° Tilt 2 4 6 8 Distance (metres) PIR Detection Zone Patterns 10 10 12 Retaining Clip Connection Terminals Cover Retaining Screw Pulse Count Jumper Link PIR Movement Detector PCB Layout PA4 Alarm WIRING THE PIR MOVEMENT DETECTOR(S) 1. Thread the cable through the entry on the base, then strip back 5 mm of each core, twist the strand ends then fold over and wire into the appropriate terminals on the PIR Movement Detector. The terminals on the PIR and the wires in the cable are colour coded. The correct colour coding should be followed throughout the entire system. 7. When the wiring has been completed, connect the plug in Mains Adaptor. Wait 4 minutes for the detectors to stabilise. Only the ‘Mains’ LED should be ‘ON’ at the Control Panel. Note: If any Zone or 24 Hr LEDs are illuminated, refer to ‘Fault Finding’. TESTING THE PIR MOVEMENT DETECTORS AT THE CONTROL PANEL 1. Test the PIR Movement Detectors one at a time. Red +ve power supply to each PIR Movement Detector. Yellow/Blue Detector normally closed Alarm Contact Zone circuit. Green/White 24 Hr normally closed Tamper circuit. 2. Carefully refit the PCB into the casing taking care not to touch the PIR detector lens. 3. The PIR Detector incorporates an anti false alarm feature designed to compensate for situations where the detector may be affected by environmental changes, (e.g. insects, hot air thermals from radiators, etc). This feature is called ‘Pulse Count’ and may be selected for 1, 2 or 3 pulse detection. The factory default and recommended setting is for 2 Pulse detection. However, in cases of extreme environmental problems, or if unattributable false alarms are experienced, it may be necessary to set "Pulse Count" 3. Note: The higher the ‘Pulse Count’, the more movement will be necessary before the PIR detector will trigger the alarm. 1 Pulse 2 Pulses 3 Pulses 1 2 3 1 2 3 1 2 3 Important: When testing a PIR Movement Detector, ensure that no movement occurs in any other area protected by PIR Movement Detector. 2. Press AWAY . The ‘Clear’ LED will illuminate. Slowly walk across the PIR Movement Detector’s field of view. As you are detected, the LED on the PIR Movement detector will illuminate and the Control Panel will emit a number of beeps corresponding to the Zone number the detector is connected to and the relevant Zone LED will flash. 3. When clear of the detector, the beeps will cease and the Zone and PIR detector LEDs will extinguish. 4. Allow ten seconds for the detector to settle, then move again to confirm that the PIR detector gives the desired protection within the area required. 5. Repeat the above test sequence for each PIR Movement Detector fitted. 6. When all the PIR Movement Detectors have been tested successfully, press RESET to return to the Standby Mode. 7. Disconnect the Mains Adaptor before continuing with the installation. SIMPLE TROUBLE SHOOTING Pulse Count jumper link positions 4. Select the required ‘Pulse Count’. Refit the cover and tighten the retaining screw. The PIR Movement Detector is now ready to be connected at the Control Panel. 5. Bring the detector cable(s) though the cable entry slot in the rear of the Control Panel and strip back 5 mm on each core. 6. Ensure that the Mains Adaptor is disconnected from the Control Panel. Remove the appropriate wire links, then connect the wires to the terminals as shown in the diagrams on pages 13 - 15. PA4 Alarm If the PIR Movement Detector is not operating, ie. LED not illuminating, the following simple checks should be carried out; 1. Allow 4 minutes for the detector to stabilise then retest. 2. If the PIR Movement Detector LED does not illuminate, check the power supply to the PIR. Check for a damaged cable or poor termination. 3. If the PIR Movement Detector false alarms, the unit may be positioned incorrectly. Re-position the unit and adjust the ‘Pulse Count’ if necessary. 4. If the PIR Movement Detector LED is operating, but not activating an alarm, check that the relevant Zone wire link has been removed at the Control Panel. 11 INSTALLATION Black 0V power supply to each PIR Movement Detector. TYPICAL WIRING ARRANGEMENTS PIR MOVEMENT DETECTOR CONTROL PANEL 1 N/C + - 3 2 5 4 6 Z3 Z2 Z1 7 8 Z4 11 12 13- 14+ SPEAKER 24Hr 21- +22 AUX 17+ -18 D BELL B 24 Hr CONNECT TO REQUIRED ZONE GREEN WHITE BLACK RED YELLOW BLUE PIR MOVEMENT DETECTOR CONTROL PANEL 1 N/C + 2 Z1 - 3 5 4 6 7 Z3 Z2 11 12 13- 14+ SPEAKER 24Hr 8 Z4 21- +22 AUX 17+ -18 D BELL B 24 Hr CONNECT TO REQUIRED ZONE GREEN TWIST AND INSULATE WHITE BLACK BLUE BLUE YELLOW + RED TWIST AND INSULATE 24 Hr WHITE GREEN - BLACK PIR MOVEMENT DETECTOR RED YELLOW N/C INSTALLATION Wiring diagram for a Single PIR Detector on a zone Wiring diagram for two PIR Detectors to a single zone with all cables returning to the Control Panel PIR MOVEMENT DETECTOR CONTROL PANEL 1 N/C + - 2 Z1 3 4 Z2 5 6 Z3 7 8 Z4 11 12 13- 14+ SPEAKER 24Hr 17+ -18 D BELL B 21- +22 AUX 24 Hr GREEN WHITE BLACK BLACK RED RED YELLOW BLUE BLUE YELLOW Twist (or Solder) cable cores together and insulate MAGNETIC CONTACT WHITE GREEN Wiring diagram for PIR Detector and Magnetic Contact Detector on different zones with all cables returning to the Control Panel 12 PA4 Alarm CONTROL PANEL 1 3 2 4 5 6 7 Z3 Z2 Z1 11 12 13- 14+ SPEAKER 24Hr 8 Z4 PIR MOVEMENT DETECTOR 21- +22 AUX 17+ -18 D BELL B PIR MOVEMENT DETECTOR CONNECT TO REQUIRED ZONE BLUE YELLOW BLACK WHITE RED + N/C - 24 Hr + N/C - 24 Hr GREEN RED BLACK BLUE YELLOW WHITE GREEN Twist (or Solder) cable cores together and insulate PIR MOVEMENT DETECTOR N/C + - PIR MOVEMENT DETECTOR CONTROL PANEL 1 24 Hr 2 3 4 5 6 7 Z3 Z2 Z1 8 Z4 11 12 13- 14+ SPEAKER 24Hr 21- +22 AUX 17+ -18 D BELL B N/C GREEN WHITE WHITE GREEN BLACK BLACK RED RED YELLOW BLUE BLUE YELLOW + - 24 Hr Twist (or Solder) cable cores together and insulate GREEN WHITE WHITE GREEN YELLOW BLUE BLUE YELLOW Wiring diagram with zones 1-4 used with all cables returning to the Control Panel MAGNETIC CONTACT MAGNETIC CONTACT CONTROL PANEL Twist (or Solder) cable cores together and insulate 1 2 3 4 Z2 Z1 5 6 Z3 YELLOW YELLOW YELLOW 8 Z4 BLUE 11 12 13- 14+ SPEAKER 24Hr WHITE BLUE BLUE Zone Wiring from Detector 1 Zone Wiring from Detector 2 Zone Wiring from Detector 3 WHITE GREEN Zone Wiring from Detector 4 Series wiring of zone connections from multiple detectors on a single zone 21- +22 AUX 17+ -18 D BELL B Twist (or Solder) cable cores together and insulate GREEN YELLOW BLUE PA4 Alarm 7 "24-Hour" Wiring from Detector 1 WHITE GREEN "24-Hour" Wiring from Detector 2 WHITE GREEN "24-Hour" Wiring from Detector 3 WHITE GREEN "24-Hour" Wiring from Detector 4 "24-Hour" Wiring from Siren Tamper Connections Series wiring of 24-hour connections from multiple detectors 13 INSTALLATION Wiring diagram for multiple detectors (connected in series) on a single zone with one cable returning to the Control Panel INSTALLING THE MAGNETIC CONTACT DETECTORS Decide which doors and windows are to be protected by Magnetic Contact Detectors, usually the front and back doors will have Magnetic Contact Switches fitted. Additional contacts may be fitted where required to other vulnerable doors or windows, e.g. garage, patio and conservatory doors etc. INSTALLATION Note: It is not recommended to connect more than 4 Magnetic Contacts in any one zone, as this may cause difficulty in wiring and hinder any attempt to efficiently remedy any wiring faults and locate the device that initiated the alarm. 1. Having chosen a suitable position to locate the Magnetic Contact, run the required length of 6 core cable back to the Control Panel. Alternatively, Magnetic Contact(s) may be wired in series with each other and terminated appropriately. However, working space within the Magnetic Contact is limited and more than two or three termination's may prove difficult. Do not make any connections at this stage. 2. Fit the Magnet to the moving part of the window or door (on the opening edge opposite the hinge) and make sure that the parallel gap to where the Contact Switch is fitted on the frame is no more than 9mm. Magnet Magnet Contact Switch Contact Switch Connect the Yellow and Blue wires to the Contact Switch terminals as shown. YELLOW BLUE SINGLE CONTACT WHITE GREEN 3. Strip off 5 mm of the insulation from the Green and White wires and connect together using a spare terminal in the contact housing. Note: If the spare contact terminals are not present in the contact then the ends of the wires should be securely twisted (or soldered) together and insulated. If connecting multiple contacts the Tamper circuit wiring should be continued in a series loop in a similar way to the zone wiring. MULTIPLE CONTACTS Wired in series Note: If spare terminals are not present in the Contact Switch, ends of wires should be twisted (or soldered) together and insulated. GREEN WHITE BLUE Door Mounting Window Mounting Max Gap 9mm (door/window closed) Typical position of contact fitted to door WIRING THE MAGNETIC CONTACTS 1. Remove one of the cable entry cut-outs on the Contact Switch and thread the cable through the entry into the Contact Switch housing. 2. Carefully remove the outer sheath of the cable and then strip 5mm of insulation from the Yellow and Blue wires. 14 YELLOW The remaining wires should be trimmed back and insulated to prevent short circuits and then tucked away in the Contact Switch housing. 4. Fix the Contact Switch to the fixed part of the door/ window frame immediately beside and parallel to the Magnet using two 25mm Counter-sunk fixing screws. Ensure that the parallel gap between the Magnet and Contact Switch positions is no greater than 9mm. 5. Bring the contact cable(s) through the cable entry slot in the rear of the Control Panel and strip back 5mm of each core and twist the strand ends. PA4 Alarm 7. When the wiring has been completed, re-connect the Mains Adaptor. 8. Wait 4 minutes for any PIR Movement Detectors to stabilise, and then clear all protected area(s). 9. No Zone or 24 Hr LEDs should be ‘ON’ at the Control Panel at this stage. TESTING MAGNETIC CONTACTS AT THE CONTROL PANEL 1. First, ensure that all doors and windows fitted with Magnetic Contacts are closed. 2. Press AWAY and the ‘Clear’ LED will illuminate Note: At this stage, if any Magnetic Contacts are open or PIR Movement Detectors are activated, the relevant Zone LED(s) will be illuminated and the panel will beep, The number of beeps will indicate which Zone is open. You should ensure that no movement occurs in areas fitted with PIR Movement Detectors, as this may cause confusion during the test sequence. If walking past a PIR Movement Detector is unavoidable, allow 10 seconds at the Control Panel for the PIR Movement Detector to settle. 3. Open the first contact, the Control Panel will emit a number of beeps corresponding to the Zone number the detector is connected to and the relevant Zone LED will flash. INSTALLING THE EXTERNAL SIREN The External Siren should be fitted to the outside of the building in a prominent position that is clearly visible and at a height that is relatively inaccessible to an intruder. Consideration should also be given to the cable route to the siren, with the cable preferably passing directly through the external wall into the back of the siren housing. FITTING THE EXTERNAL SIREN UNIT IMPORTANT: If ladders are required to reach the mounting position of the Siren they should be positioned on a firm stable surface at the correct angle and suitably secured before use. 1. Undo the two front cover retaining screws and remove the front cover by sliding up and away from the backplate. 2. Fix the siren mounting bracket to the backplate using the M3 screws, nuts and washers supplied. 3. Run the required length of cable from the Control Panel to the External Siren position. Drill a suitable hole through the wall so that the cable enters through the rear of the housing without showing on the outside of the property. BACK-PLATE Close the contact to silence the beeps and extinguish the LED. 4. Repeat the test sequence for all Magnetic Contacts fitted. SIREN BRACKET 5. When the Magnetic Contacts have been tested successfully, press RESET to return to the Standby Mode. SIREN 6. Now disconnect the Mains Adaptor before continuing with the installation. CABLE ENTRY HOLE SIREN COVER PA4 Alarm 15 INSTALLATION 6. Ensure the Mains Adaptor is disconnected at the Control Panel. Remove the appropriate Zone wire link and then connect the wires to the Control Panel terminals as shown in the diagrams on pages 13 - 15. 4. Hold the backplate in position so that the hole drilled for the cable is aligned with the cable entry aperture and Mark the positions of the four mounting holes. A spirit level placed on the casing will ensure a perfect level. 5. Mount the backplate using four 35mm No.10 screws and 30mm wall plugs supplied, (a 6mm hole will be required for the wall plugs). WIRING THE SIREN UNIT 1. Ensure the Mains Adaptor is disconnected at the Control Panel. INSTALLATION 2. Strip back 5mm of insulation from the Red, Black, Green and White wires. 3. Twist and double over the end of each wire, then connect to the terminal blocks in the Siren and Control Panel as shown below. External Siren Terminal Block Tamper Circuit Wiring to Other Detectors GREEN Twist (or Solder) cable cores together and insulate D BELL B 17 + – 18 External Siren Wiring Arrangement 12 BLACK 24Hr RED 11 WHITE 1. Connect the Mains Adaptor to the plug in connector in the Control Panel. 2. Plug the adaptor into a 13A socket and switch ON. The mains LED will illuminate when the Control Panel is powered from the mains. (It is normal for the Mains Adaptor to appear warm to the touch when in use). Note: Ensure that the adaptor will not be removed from the socket or accidently switched off, when the system is in use. Note: The Back-up Batteries are NOT recharged upon restoration of the mains supply and should be replaced after any mains failure. The batteries should also be changed every year to prevent leakage and possible damage to the Control Panel. WHITE GREEN CONNECTING THE CONTROL PANEL MAINS ADAPTOR AND OPTIONAL BACK-UP BATTERIES Optional Back-up Batteries The Control Panel has the facility to connect Optional Back-up Batteries which will power the system for up to 4 hours in the event of a mains failure. Fit 2 x 9 volt PP3 Alkaline Batteries (not supplied) to the battery connectors in the Control Panel housing. RED BLACK 4. Refit the External Siren cover. Terminals in Control Panel 3. The Control Panel fixing screws may now be finally tightened. Do not over tighten the screws as this may damage the casing. 4. Remove the temporary Anti-Tamper wire link from terminals 11 and 21. In doing so, the internal speaker will sound. Refit the cover and secure the cover retaining screws, then enter 1 2 3 4 or Current User Access Code to silence the alarm. Press Note: The Green and White Tamper circuit wires should be wired in series with the Green and White tamper circuit wires from the detectors at the Control Panel terminal block. 16 RESET to return to Standby Mode. Note: Although optional, it is strongly recommended that backup batteries are fitted. PA4 Alarm PROGRAMMING Once programming is complete press to Standby Mode. GENERAL Note: When selecting options, the system will allow 30 seconds to make a selection. If this time is exceeded, the Control Panel will exit the function and revert to Installer Programming Mode and the option button will have to be pressed again. Once a selection is made the system will allow 10 seconds for a valid key to be pressed. If this time is exceeded the system will return to the top level of the installer mode and the selection will have to be made again. Programming of the Control Panel options is divided into two distinct categories, User Programming and Installer Programming. User programming is used when the system is fully operational, whilst Installer Programming is only carried out when the system is new or when subsequent changes are required. Access to either programming mode requires a valid User or Installer Access Code to be entered. The more complex and infrequently required programmable options are available in Installer Programming Mode only. This prevents the major system functions from being accidentally changed by a general User. The Control Panel has most of the options factory pre-set at the most common settings, please consider whether you really need to change them before re-programming. a) b) c) d) e) f) g) h) accessed via Installer Selecting Walk Through Zone(s) Entry Time Adjustment Exit Time Adjustment Selecting ‘Home’ Zones (Part Setting) Alarm Duration Select User Access Code arming Change Installer Access Code Reset System Defaults to return Before starting programming any feature read all the steps first. CHANGING THE INSTALLER ACCESS CODE Factory default Setting: 9 9 9 9 To maintain the security of your system the Installer Access code should be changed from the factory default to your own unique 4-digit code. The Installer Access code must not be the same as the User Access code. Make a note of the new Installer Access Code in the Alarm Record section. To change the setting proceed as follows: With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), Press 1 . The 4 Zone LEDs will illuminate. Programmable options Programming Mode are; accessed via User Change User Access Code Note: The User Access code can only be changed if the "Code Arming" feature is disabled. INSTALLER PROGRAMMING MODE Before changing any installer programmable options, the Control Panel must be set to Installer Programming Mode. This is shown by the ‘Clear’ LED flashing. Enter the default or current Installer Acess Code. 9 9 9 9 or Current Installer Access Code The ‘Clear’ LED will flash to indicate that the system is now in the Installer Programming Mode. PA4 Alarm Enter the new 4-digit Installer Access code ? ? ? ? As each digit is entered, a Zone LED will extinguish in sequence. Press ARM to save the new setting or Press RESET to exit without saving. The system will return to the top level Installer Programming Mode with only the Clear LED flashing. EXIT DELAY TIME ADJUSTMENT Factory default Setting: 30 seconds To change the setting proceed as follows: With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), 17 PROGRAMMING Programmable options Programming Mode are; RESET Press 2 . Zone 1 and 2 LEDs will illuminate. Enter the required Exit Delay time (1-99), e.g. enter “01” for a 1s delay, enter “99” for a 99s delay. Press ARM to save the new setting or Press RESET to exit without saving. The system will return to the top level Installer Programming Mode with only the Clear LED flashing. ENTRY DELAY TIME ADJUSTMENT Factory default Setting: 30 seconds SELECTING “HOME” FEATURE ZONES The HOME button can be used to part-arm the system omitting a selection of pre-selected Zones. This feature is useful if you have a regular requirement to arm the system with a permanent selection Zone(s) omitted. For example at night when you may wish to have the detectors on the ground floor armed, whilst the detectors on the first floor are disarmed. Note: The Entry/Exit Zone (Zone 1) and any zones configured as ‘Walk Through’ cannot be omitted from "Home" Arm. To select the Zones to be omitted when using the ‘HOME’ feature proceed as follows: To change the setting proceed as follows: With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), Press Press 3 Zone 1 and 2 LEDs will illuminate. Enter the required Entry Delay time (1-99), e.g. enter “01” for a 1s delay, enter “99” for a 99s delay. PROGRAMMING 6 . . Press ARM to save the new setting or Press RESET to exit without saving. The system will return to the top level Installer Programming Mode with only the Clear LED flashing. The zone LEDs corresponding to the Zones currently selected to be omitted during "Home" operation will be illuminated. LED ON LED OFF Zone omitted during "Home" arm Zone active during "Home" arm. To change the setting of a zone press the button corresponding to the zone number. The zone will toggle between omitted and active each time the button is pressed. Remember, Zone 1 and any "Walk Through" zones cannot be omitted. ALARM DURATION ADJUSTMENT Press ARM to save the new setting or Factory default Setting: 20 minutes Press RESET to exit without saving. To change the setting proceed as follows: The system will return to the top level Installer Programming Mode with only the Clear LED flashing. With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), Press 4 SELECTING WALK THROUGH ZONES . Zone 1 and 2 LEDs will illuminate. Zones which are located between the Entry/Exit door and Control Panel should be configured as "Walk Through" zones. Enter the required Alarm Period (1-20), e.g. enter “01” for a 1 minute duration, enter “15” for a 15 minutes duration. Zone 1 cannot be configured as a ‘Walk Through’ zone. Press ARM to save the new setting or Press RESET to exit without saving. The system will return to the top level Installer Programming Mode with only the Clear LED flashing. 18 Zone 2 is factory set as a ‘Walk Through’ zone. It is advisable to change Zone 2 to an ‘Instant’ Zone if this facility is not required. To select the Zones to be configured as "Walk Through" zones proceed as follows: PA4 Alarm Press 7 . The zone LEDs corresponding to the Zones currently set as "Walk Through" zones will be illuminated. LED ON Walk Through ON LED OFF Walk Through OFF (i.e. Instant). RESET SYSTEM DEFAULTS If the User Access Code has been lost or forgotten, or the installer is unsure of the options programmed, the system may be returned to the factory settings by the following method; With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), Press 0 . To change the setting of a zone press the button corresponding to the zone number. The zone will toggle between "Walk Through" and "Instant "each time the button is pressed. Remember, Zone 1 cannot be set as "Walk Through". Zone 1 led will flash briefly to indicate that all system default settings have been restored. Press ARM to save the new setting or Press RESET to exit without saving. 1. Switch off mains power and remove the Control Panel front cover. The alarm will sound on tamper if backup batteries are fitted. The system will return to the top level Installer Programming Mode with only the Clear LED flashing. SELECTING ‘CODE ARMING’ For convenience the Control Panel is factory set to be able to be armed without first entering the User Access Code. To avoid accidental arming, or if there is a concern regarding children arming the system, it is possible to program the Control Panel to require the User Access Code to be entered before allowing the system to be armed. Important: The User Access Code should be changed from the factory default before activating this functionality. LOST OR FORGOTTEN INSTALLER ACCESS CODE 2. If fitted disconnect the Control Panel Back-up Batteries. Important: The mains and battery power supply must be removed before continuing. 3. Place the Jumper Link across both of the NVM RESET pins positioned on the Control Panel PCB. 4. Wait for 30 seconds and then switch on the mains supply adaptor. The Clear and 24Hr LEDs will flash and after approximately 5 s the alarm will sound on tamper, Enter 1 To activate or de-activate the code arming feature proceed as follows: With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), Press 8 . Zone LED 2 will indicate the current status of the code arming feature. Zone 2 LED ON Code Arming Enabled Zone 2 LED OFF Code Arming Disabled To change the setting press 2 to toggle code arming ON and OFF each time the button is pressed. Press ARM to save the new setting or Press RESET to exit without saving. PA4 Alarm the 2 3 default User Access 4 , to cancel the alarm. code, 5. Remove the Jumper Link (store on one Pin) replace the front cover and reconnect the mains. The Control Panel has been returned to factory settings and will require programming to your requirements. USER PROGRAMMING MODE CHANGING THE USER ACCESS CODE Note: The User Access code can only be changed if the "Code Arming" feature is disabled. Factory default Setting: 1 2 3 4 19 PROGRAMMING With the Control Panel already in the Installer programming Mode (‘Clear’ LED flashing), To maintain the security of your system the User Access code should be changed from the factory default to your own unique 4-digit code. The User Access code must not be the same as the Installer Access code. Make a note of the new Installer Access Code in the Alarm Record section. Note: If no key is pressed for a period of 10s while within the function the system will return to Standby mode without any changes being made. To change the User Access Code proceed as follows: With the Control Panel in Standby Mode (Mains LED only On), Enter the default or current User Access Code code 2 1 3 4 Enter the new 4-digit User Access code ? Press ARM to save the new setting or Press RESET to exit without saving. The system will return to Standby Mode. TESTING THE SYSTEM To test the system 1. ‘Arm’ the system, by pressing AWAY then ARM , the Exit Timer will start, press ARM again to quick set the system. OPERATION Before arming the system, ensure all detectors are unobstructed and that all doors and windows are closed and secure. ? As each digit is entered, a Zone LED will extinguish in sequence. 2. Walk in front of a PIR Movement Detector or open a door or window fitted with a Magnetic Contact Detector. The Control Panel Sounder & External Siren will activate. (You can open a contact in the Entry/Exit route, however you will have to wait for the selected Entry Time to end before the system will activate). 3. Return to the Control Panel and enter the User Access Code ? ? ? ? . Current User Access Code The alarm will cease and the relevant Zone LED will be illuminated. 20 The following procedures for Arming and Disarming the system are based upon having the "Code Arming" feature disabled. If "Code Arming" has been enabled during installation programming the User Access Code will have to be correctly entered at the keypad before the following procedures will have any effect. ‘AWAY’ ARMING ALL ZONES All zone LEDs will illuminate and the Clear LED will flash. ? OPERATING INSTRUCTIONS . or Current User Access Code ? You may test your system at any time, however, it is recommended that the system is tested at regular intervals not exceeding three months. Test a different PIR /Magnetic Contact on each test occasion. Note: If Code Arming has been enabled, the User Access Code must be entered before proceding with the following sequnce. Press AWAY . If any Zone LED are ‘ON’, this indicates that a door/window contact is open or movement is being detected by a PIR on a zone being armed. Check that all doors/windows are closed and that PIR protected areas are clear of movement so that only the clear LED is illuminated before continuing the arming sequence. When the ‘Clear’ LED only is ‘ON’, press ARM . The Exit tone will start. During the last ten seconds of the Exit Delay, the tone will change pitch. You must leave the property via the Entry/Exit route before the Exit Delay expires, when the tone will stop and the system will be armed. Note: If a detector on Exit zone (zone 1) is triggered (e.g. the exit door is opened) during the exit delay an interrupted exit tone will be heard. When the zone is closed again the normal exit tone will be heard. If any detector on Zones 2, 3, or 4 is triggered during the exit delay and warning tone will be heard and the exit delay period will be PA4 Alarm suspended until the zone is cleared when the exit delay will continue. All zones must be closed when the exit delay expires or an alarm will occur. ‘HOME’ ARMING PRE-SELECTED ZONES When the ‘Clear’ LED only is ‘ON’, press The ‘Home’ facility can be used to arm the system with regularly used pre-selected Zones programmed to be omitted. Before arming the system, ensure all detectors are unobstructed and that all doors and windows are closed and secure. Note: If Code Arming has been enabled, the User Access Code must be entered before proceding with the following sequnce. Press HOME . If any Zone LEDs are ‘ON’, this indicates that a door/window contact is open or movement is being detected by a PIR on a zone being armed. Check that all doors/windows are closed and that PIR protected areas are clear of movement so that only the clear LED is illuminated before continuing the arming sequence. When the ‘Clear’ LED only is ‘ON’, press ARM being detected by a PIR on a zone being armed. Check that all doors/windows are closed and that PIR protected areas are clear of movement so that only the clear LED is illuminated before continuing the arming sequence. . The Exit tone will start. During the last ten seconds of the Exit Delay, the tone will change pitch. OMIT . The 24Hr LED will flash. Press buttons 2 , 3 or 4 to select the Zone(s) you wish to omit. The zone LEDs will illuminate to indicate if the zone is omitted. Note: The Entry/Exit Zone (Zone 1) cannot be omitted. When the zones required to be omitted have been selected press ARM . The Exit tone will start. During the last ten seconds of the Exit Delay, the tone will change pitch. When the tone stops and the system will be armed. QUICK ARM After arming the system in either "Home" or "Away" modes using the procedures described above the "Quick Arm" feature may be used to cancel any remaining exit delay period and Arm the system within 5s. This is useful for setting the system at night to silence the exit tone after just a few seconds. Press ARM again while the exit tone is running to Quick Arm the system after a few seconds. When the tone stops and the system will be armed. DISARMING THE SYSTEM If a system needs to be armed with a Zone combination different to that configured for the ‘HOME’ arm setting, it is possible to select a Zone(s) to be omitted on a temporary (one time) basis. Before arming the system, ensure all detectors are unobstructed and that all doors and windows are closed and secure. Note: If Code Arming has been enabled, the User Access Code must be entered before proceding with the following sequnce. Press AWAY . If any Zone LEDs are ‘ON’, this indicates that a door/window contact is open or movement is PA4 Alarm Enter the premises via the designated Entry route. The Entry tone will start. During the last ten seconds of the Entry Delay, the tone will change pitch. Proceed directly to the Control Panel and Disarm the system by entering the User Access Code ? ? ? ? . The system will disarm and the Entry tone will stop. Note 1: To Disarm the system during Home Arming proceed directly to the Control Panel and enter the User Access code. If an alarm has occurred while the system was Armed the zone LED(s) of the zone(s)that triggered the alarm will be illuminated, take note of Zones. To clear any illuminated zone LEDs press RESET . 21 OPERATION ARMING WITH OCCASIONAL ZONES OMITTED MAINTENANCE EVENT LOG If an alarm has occurred, the Event Log will enable the user to recall the Zone(s) that have triggered the alarm. The Event Log will record the last 4 alarm events. Press ER . The zone that triggered the most recent alarm will be illuminated. The zone that triggered the most recent alarm will be illuminated. Press ER again up to 3 times to recall the previous 3 alarm events in sequence. Press alarm. RESET Your PA4 Intruder Alarm system requires very little maintenance. However, a few simple tasks will ensure its continued reliability and operation. to return to show the most recent Press RESET again to return the system to ‘Standby’ mode. CONTROL PANEL AND DETECTORS The Control Panel and detectors require no maintenance. If cleaning is required, wipe the outside of the casings with a soft damp cloth. Do not use aerosols or sprays or proprietary cleaners. Do not attempt to clean inside the units or allow water to enter the units. BACK-UP BATTERIES The Optional Back-up Batteries in the Control Panel should be replaced every 12 months or after a prolonged power failure. PA4 ALARM RECORD Complete the following information during installation for future reference when adding to your system and to assist Trouble Shooting. Settings Zone Detector Type(s) 1 Location(s) Instant/ Delay Walk Through Home Zone Omit Delay N/A N/A N/A N/A N/A 2 3 4 OPERATION 24Hr Tamper You may make a note of your User Access Code and Installer Access Code below. User Access Code Installer Access Code Purchase Date/Installation Date Control Panel Serial Number This information is highly confidential and should be kept in a very safe location. 22 PA4 Alarm TROUBLE SHOOTING Symptom / Recommendation 24 hour fault (Internal Sounder or full alarm if system is armed). 1. PIR Detector Anti-Tamper Switch not closed fully check/refit detector cover. 2. External Siren cable connections loose or a cable damaged. 3. 24 hour Zone wiring open eg. damaged or incorrect wiring or poor terminations. Passive Infra Red Movement Detector not detecting a person’s movement 1. Allow up to 4 minutes for the detector to settle down and retest. 2. ‘Pulse Count’ set too high - reset to one or two ‘Pulse Count’ detection. 3. Ensure that detector is mounted the correct way up (with the cover fixing screw at the bottom). 4. Ensure that the detector is mounted at the correct height 2.2 metres from floor. 5. Check that the detector is correctly wired. Passive Infra Red Movement Detector false alarming 1. Ensure that the detector is not pointing at a source of heat or a moving object. 2. Ensure that the detector is not mounted above a radiator or heater. 3. Ensure that the detector is not facing a window or in direct sunlight. 4. Check Zone wiring to detector alarm contacts. Magnetic Contacts false alarming 1. Check that door/window closes firmly and that movement cannot trigger the contacts. HELPLINE If you have a problem with your alarm, please call the helpline on: PA4 Alarm Symptom / Recommendation Magnetic Contacts not operating 1. Check that gap between Magnet and Switch Contact blocks is less than 9 mm. 2. Check Zone wiring to contacts. (All contacts on a Zone must be wired in ‘Series’). External Siren Sounding continuously (24 hour LED NOT illuminated) 1. Check for incorrect wiring to External Siren. 2. Check for short-circuits in cable to siren, causing siren to be permanently energised. False Alarms when the system is Armed 1. Carefully note the Zone which activated the alarm before pressing ‘Reset’. Only the detector(s) and wiring on that Zone will need to be checked. 2. Check all Zone wiring and connectors for security. 3. For PIR false alarms, consider increasing ‘Pulse Count’ settings on suspect detector. Mains LED is not illuminated 1. Check mains power supply. 2. Check Mains Adaptor cable and connection onto PCB. 3. Mains power failure - check if other electrical circuits are operable. Detection Zone has been triggered but no alarm is sounding 1. Entry Delay Zone(s) triggered - alarm will sound when the Entry Delay Time expires. 2. Zone omitted on ‘Home’ setting. 3. Zone temporarily omitted before arming. 01268 563273 (Lines open 9.00am to 5.00pm, Monday to Friday) 23 EXTENDING YOUR PA4 WIRED INTRUDER ALARM SYSTEM Your system may be expanded to give additional protection by adding additional PIR Movement Detectors and Magnetic Contact Sets. ACCESSORIES ACCESSORY PACK - PU1 The PU1 Accessory Pack comprises 2 PIR Movement Detectors, 2 Magnetic Contact Sets and approx. 25 metres of 6 Core Cable. PU1 PASSIVE INFRA RED MOVEMENT DETECTORS (TWIN PACK) - PU2 2 additional PIR Movement Detectors. PU2 DUMMY SIREN - PU3 Siren box for added visual deterant. PU3 24 PA4 Alarm If you have a problem with your Alarm, please call the Helpline on: 01268 563273 (Lines open 9.00am to 5.00pm, Monday to Friday). GUARANTEE Novar ED&S undertakes to replace or repair at its discretion goods (excluding non rechargeable batteries) should they become defective within 1 year solely as a result of faulty materials and workmanship. Understandably if the product has not been installed, operated or maintained in accordance with the instructions, has not been used appropriately or if any attempt has been made to rectify, dismantle or alter the product in any way the guarantee will be invalidated. The guarantee states Novar ED&S entire liability. It does not extend to cover consequential loss or damage or installation costs arising from the defective product. This guarantee does not in any way affect the statutory or other rights of a consumer and applies to products installed within the UK and Eire only If If an item develops a fault, the product must be returned to the point of sale with: 1. Proof of purchase. 2. A full description of the fault. 3. All relevant batteries (disconnected). Friedland is a trade mark of Novar ED&S. Friedland, Novar Electrical Devices and Systems The Arnold Centre, Paycocke Road Basildon, Essex SS14 3EA PA4 Wired Intruder Alarm System Friedland COMPONENT SPECIFICATION Control Panel Novar Electrical Devices and Systems are Quality Assurance Registered to BS EN ISO9001:2000, by Asta MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 1 2 3 ARM 4 5 6 OMIT 7 8 9 RESET AWAY 0 ER HOME Magnetic Contact Detectors Zone 4 150 mm EXIT 1. Check all windows and doors are closed. 2. a) Fullguard - Press 'Away' then 'Arm'. or b) Partguard - Press 'Home' then 'Arm'. 3. Leave premises by entry/exit route. ENTRY 1. Enter premises by entry/exit route. 2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode. 67 mm 50 mm 260 mm ● Four Detection Zones ● Tamper Zone ● Front Cover Anti-Tamper 14 ● Zone(s) programmable for 12 mm - Entry Delay - Walk Through - Zone Omit mm ● Magnetic Reed Switch operation ● Operating gap up to 9mm ● Temporary Zone Omit facility ● Door or window mounted ● Entry Delay variable 01 - 99 seconds ● Surface mounting, white plastic finish ● Exit Delay variable 01 - 99 seconds ● Non volatile memory ● Quick arm facility ● Code arm facility selectable ON/OFF ● Individual Zone alarm activation LEDs PIR Movement Detectors ● Back-up Battery facilities ● Hard wired siren facility ● 4-Digit User Access Code 58 ● 4-Digit Installer Access Code mm ● Plug in Mains Adaptor RESEARCH & DEVELOPMENT Our R & D Department is constantly developing new products. 44 68 mm mm External Siren ● Detection range up to 12 metres at 90° ● Integral Detection LED We practice a policy of continued improvement and reserve the right to change specifications without prior notice. ● 1, 2, 3 ‘Pulse Count’ facility ● Anti-Tamper ● Corner or surface mount, with tilt facility ● 12 Volt dc operated, powered from the 350 mm If you have a problem with your Alarm, please call the Helpline on: 200 mm Control Panel. 75 mm ● Case material white plastic ● Piezo sounder 01268 563273 ● Blue Lens (Lines open 9.00am to 5.00pm, Monday to Friday). Friedland, Novar Electrical Devices and Systems. The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA. UK. © Novar ED&S, 2004 45165PL Ed.3