Florham Park, New Jersey 07932 Published by Volume 6, Number 8 File Index: Automatic Transfer Switches Transfer Switching of Critical Computer Loads Automatic Switch Company Critical applications using computers and electronic equipment require the design and construction of elaborate power systems for continuity of service. These systems are designed to provide the highest quality power, without interruption, to these sensitive loads. Redundant power sources and distribution, with downstream transfer switches are typical of such systems. Such a system is shown in figure 1. Here the redundant power sources are UPSs. UTILITY UPS 1 UPS 2 PDU failure, or an upstream breaker trip caused by overcurrent, malfunction, fault, or operator error. Regardless of the cause, the unplanned transfer requires fast voltage sensing and switching. The resulting outage must be short enough for the sensitive equipment to remain unaffected. The single most critical element in the this type of application is the transfer switch. It must be reliable, and, it must be fast. A new switching technology, referred to here as the solid state hybrid transfer switch, was developed specifically for these critical applications. This new switch maintains the reliability and cool, efficient, operation of an electro-mechanical switch, while providing the fast operating speed required in most critical applications. The Information Technology Industry Council* recommends the voltage tolerance envelope for computer equipment (see figure 2). Accordingly, computer equipment must operate properly with a complete interruption of voltage for 20 milliseconds. PDU Transfer Switch Critical Load Figure 1. Redundant UPSs and a transfer switch provide reliable power to the critical load. The primary role of the transfer switch is to connect loads to an acceptable power source. This is accomplished by continually sensing the availability of both sources and providing instantaneous source selection. Transfer to the alternate source may be required for one of two reasons: 1. Planned Transfer System maintenance of the uninterruptible power supply (UPS) or other upstream equipment. In this instance the transfer is planned. Front panel controls are typically used to initiate a transfer between the two live sources. 2. Unplanned Transfer When the connected source fails, or is interrupted, the transfer switch must sense these conditions and automatically transfer the load to select the alternate (acceptable) source. The unplanned transfer may be the result of a UPS failure, utility Figure 2. CBEMA Curve Revised February 1996. This curve indicates that typical information technology equipment (ITE) is unaffected by voltage interruptions of up to 20 milliseconds, and voltage sags of 20% for 10 seconds and 30% for 0.5 seconds. See CBEMA curve application note for more complete information. Until now, the only transfer switch technology fast enough for these applications was static switch technology. This paper describes the performance of three transfer switching technologies: a) Electro-mechanical switches b) Static switches c) Hybrid solid state switches A comparison of features and functions of each technology follows: Electro-mechanical Switches: Electro-mechanical transfer switches employ double throw devices containing time-proven silver alloy contacts supported by electrically operated and mechanically held operators. The reliability of this approach is considered to be very high. The latest transfer controllers are microprocessor type and are usually designed for an MTBF of at least 300,000 to 500,000 hours. The life of the mechanical switch mechanism is a function of operational cycles rather than time, and is typically designed for a minimum of 12,000 transfers. In most applications* (two transfers per week) this amounts to 1,000,000 hours (115 years). Since the electro-mechanical switch is mechanically locked in either of two "on" positions (see figure 3), the control power supply or other control components can malfunction and still not affect the load. The switch contacts remain closed and continue to supply power from the connected source to the load. The controls must be functional when power outages occur and a transfer is required. Monitoring of the control panel indicators, or communications with the controls through the communication interface, can verify that the control is operational, and further enhance the reliability. WEIGHT STATIONARY CONTACT TO LOAD Figure 3. Example of ASCO electrically operated mechanically held transfer switch mechanism (one source and contact shown). This switch requires no control signals or electronics during the "idle" time between transfers in order to stay closed. When the switch is closed on a source (as shown) the moveable contact and yoke cannot exert an opening torque on the weight due to the geometry. The controls are only needed to sense and signal the solenoid to transfer upon an upstream failure. Volume 6, Number 8 A closed transition transfer switch (CTTS) is usually specified when planned transfers are frequent and the predominant concern. For planned transfers, this variation of the electromechanical transfer switch operates in a make before break mode. The controls inhibit transfer until the sources are in synchronism before initiating transfer. This results in zero power interruption to the load. The response to an outage (unplanned transfer) is open transition (break before make), however, and is much slower (typically in the order of 50 to 100 milliseconds or more). Static Switches: Static switches use SCRs (silicon controlled rectifiers) to conduct current from the sources to the load (figure 4). These devices turn on when gated, and turn off at the first current zero crossing following the removal of the gate signal. The major advantage of this type of switching is fast transfer without source interconnection. The response to an outage is, in the worst case, less than 8 milliseconds, provided the second source is available. The SCRs require the semiconductor junctions to be forward biased. This results in a voltage drop of approximately 1.5 volts per line (or 225 watts per phase in a 150 amp switch). This power loss generates considerable heat which must be dissipated by fans. The fans run continuously, and over-temperature sensors are usually required to set an alarm if there is a cooling malfunction. The switch may not be able to support the load under an over temperature condition and automatic bypassing may be required to protect the SCRs. MOVEABLE CONTACT TO SOURCE Mechanical switches exhibit very low heat dissipation. The silver alloy contacts in a 150 Amp switch would typically result in a 75 millivolt drop (approximately 11.25 watts per phase). Thus the power losses are low and the unit runs cool without the need for fans. This SCR technology should be considered when an 8 millisecond outage is the maximum that can be tolerated. It should be noted that most modern computing equipment can withstand a 20 millisecond outage as described in the February 1996 revision of the CBEMA curve (see figure 2). PIN YOKE There is an important difference between mechanical switches and static switches. A static switch control malfunction will likely result in loss of power to the load (even if the power sources are acceptable). Since the electro-mechanical transfer switch is "mechanically held", it will remain connected to the source, and not affect the load (provided the connected source is acceptable). In virtually all applications, the time that a transfer switch is idle (conducting from one source), is much greater than the time spent transferring from a failed source (typically by a ratio in excess of 108:1). During this "idle" time, when all else is in good working order, a transfer switch failure must not become the cause of a load outage. Page 2 Detection circuits are employed to prevent transfer if an SCR shorts (which would result in a source to source connection). If a shorted SCR on the connected source is detected, the opposite source breaker is shunt tripped (as protection against a source to source connection), and transfer to the opposite source is inhibited. Similarly, if circuitry detects open SCRs, load is transferred to the opposite source to restore power (providing the opposite source is available). Transfer back to the original source is then inhibited. Unlike the mechanical switch, the controller must be functioning, and providing continuous gate pulses to the SCRs to keep them on, or the static switch will, itself, cause the load to lose power. Source 1 Source 2 CB1 CB2 CB4 CB5 CB3 Output Figure 4. Typical one-line diagram of a static switch Hybrid Solid State Transfer Switches: This switching technology takes advantage of both static and mechanical switching elements. It utilizes the best of each technology and virtually eliminates the shortcomings. A standard electro-mechanical switch provides power to the load through mechanical contacts. The switch is electrically operated and mechanically held. The reliability, and cool operation, of mechanically locked contacts are maintained. SCRs are added to transfer to the opposite source with fast and precise timing (see figure 5). The result is a transfer switch that meets the total outage requirement of the February 1996 CBEMA curve (Computer Business Equipment Manufacturers Association, now known as Information Technology Industry Council). Source 2 Source 1 CN TS Planned transfers, with the ASCO hybrid solid state transfer switch result in less than a 3 millisecond disruption to the load. An unanticipated loss of the source supplying the load will result in an unplanned transfer in less than 20 milliseconds without source to source interconnection (break before make). The SCR conduction is limited to approximately 15 milliseconds during transfer, and the mechanically locked silver alloy contacts support the load at all other times. This results in an average voltage drop in the range of 75 millivolts, and cool operation with no requirement for fans or over-temperature alarms. The unit has two control power supplies, one on the normal source and one on the alternate source. The control can completely function on either power supply and for 6 seconds after loss of both power supplies. A third and fourth supply can be added for additional redundancy. This is not recommended since the switch, like an electro-mechanical transfer switch, only relies on the control circuit for transfer. A lost power supply will not result in a lost load (assuming the connected source is acceptable). Even if both power supplies fail, the switch will not disconnect the load. Static switches require power supply redundancy to reduce the likelihood of a control failure resulting in a transfer switch induced outage. The ASCO hybrid switch operates as follows: Planned transfers are manually initiated from the front panel. The controller will check for synchronism (voltage, frequency, and phase angle), signal the mechanical switch to operate, and fire the SCRs 3 milliseconds after the mechanical contacts part. This will immediately extinguish any arc (the sources are in synchronism which forces zero arc voltage), and connect the load to the opposite source until the mechanical contacts complete their transfer. The result is a 3 millisecond load disruption with no current between sources(see figure 6). The SCRs are then gated off. The extremely short on-time results in almost no heat burden. In an unplanned transfer the switch will sense the outage in 3 milliseconds, signal the mechanical transfer switch to operate, wait until the contacts just disconnect (from the unacceptable source), wait 9 more milliseconds to insure arc extinction, and then fire the solid state devices to the opposite source to power the load. The transfer switch will complete it's mechanical transfer to the good source, parallel the SCRs, and support the load until the next transfer. The SCR's are then turned off. The result is open (break before make) transition, and an outage of less than 20 milliseconds(see figure 7). Shorted and open SCR detection and open fuse detection are incorporated to prevent cross connection. It should be noted that, even if the SCRs short (or open), the switch can still respond automatically to an outage and transfer mechanically in approximately 32 milliseconds. Figure 5. The Hybrid Solid State Transfer Switch maintains the reliability and cool operation of a mechanical switch. The SCRs are used for fast transfer to the opposite source. This approach meets the requirements of the Supply Voltage Tolerance Envelope for Information Technology Equipment (Feb. 1996). Volume 6, Number 8 Page 3 Figure 6. The top trace above represents the solenoid current. The other traces represent the three, phase to neutral, load voltages during a manually initiated test transfer between two live sources. Note the maximum load interruption is approximately 3 msec. Figure 7. The top trace above represents the solenoid current. The other traces represent the three, phase to neutral, load voltages during an unplanned transfer. The transfer resulted when the connected source breaker tripped. The total load interruption in this case is less than 20 msec. A performance and feature summary of these three types of switches is shown below: Static Switch (typical) ElectroMechanical Switch (CTTS) Hybrid Solid State Switch Ampacity (amps) 30 to 2000 30 to 4000 Up to 150 Line Voltage (VAC) 208-480 208-600 208 Worst case response to a power outage without source to source connection (synchronism not required) 8 msec 50-500 msec 20 msec Load interruption during planned transfer (no source to source connection) <1 msec 0 msec (source to source connection) 3 msec Relative Enclosure Size Large Compact Compact Overlapping Neutral No Yes Yes Voltage Drop in 3 phase wye 1.5 volts per phase 75 millivolts 75 millivolts Power Loss @ 150 amps 700 watts 35 watts 35 watts Cooling Fans Required 2 None required None required Over-temperature alarm 1 None required None required SCR Failure Detection Open and shorted None required Open and shorted Can device automatically transfer if SCRs fail? No N/A Yes No Yes Yes Will transfer switch maintain load if the controller or SCRs malfunction when connected upstream source is acceptable Volume 6, Number 8 Page 4 The selection of transfer switches, for critical applications, is difficult. The tradeoffs between characteristics such as mechanically held contacts, high speed operation, power losses, heat, fans, and the reliability under different conditions must be considered. If the loads can handle interruptions as defined in the CBEMA curve, both the solid state hybrid switch, and the static switch, should be given serious consideration. The ASCO hybrid technology meets the latest standards of performance in speed without sacrificing the cool operation and reliability of mechanical transfer switches. CBEMA Curve Application Note* The CBEMA Curve and this Application Note are published by Environment & Safety Committee #3 (ESC-3) of the Information Technology Industry Council (ITI), formerly known as the Computer & Business Equipment Manufacturer's Association (CBEMA). 2) APPLICABILITY The CBEMA Curve and this Application Note are applicable to 120V nominal voltages obtained from 120V, 208Y/120V, and 120/240V 60Hz systems. Other nominal voltages and frequencies are not specifically considered and it is the responsibility of the user to determine the applicability of these documents for such conditions. 3) DISCUSSION This section provides a brief description of the individual conditions which are considered in the CBEMA Curve. For all conditions, the term "nominal voltage" implies an ideal condition of 120V RMS, 60Hz. Seven types of events are described in this composite curve. Each event is briefly described in the following sections, with two similar line voltage sags being described under a single heading. Two regions outside the shaded portion of the curve are also noted. All conditions are assumed to be mutually exclusive at any point in time, and with the exception of steadystate tolerances, are assumed to commence from the nominal voltage. 3.1) Steady-State Tolerances The steady-state range describes an RMS voltage which is either very slowly varying or is constant. The subject range is +/-10% from the nominal voltage. Any voltages in this range may be present for an indefinite period, and are a function of normal loadings and losses in the distribution system. 3.2) Figure 8. Supply voltage tolerance envelope provided by Information Technology Industry Council. This region describes a voltage swell having an RMS amplitude of up to 120% of the RMS nominal voltage, with a duration of up to 0.5 seconds. This transient may occur when large loads are removed from the system or when voltage is supplied from sources other than the electric utility. 3.3) 1) SCOPE The CBEMA Curve and this Application Note describe an AC input voltage boundary which typically can be tolerated (no interruption in function) by most Information Technology Equipment (ITE). The CBEMA Curve and this Application Note comprise a single document and are not to be considered separately from each other. The CBEMA Curve and this Application Note are not intended to serve as a design specification for products or AC distribution systems. The CBEMA Curve and this Application Note describe both steady-state and transitory conditions Volume 6, Number 8 Line Voltage Swell Low-Frequency Decaying Ringwave This region describes a decaying ringwave transient which typically results from the connection of power-factor-correction capacitors to an AC distribution system. The frequency of this transient may range from 200Hz to 5KHz, depending upon the resonant frequency of the AC distribution system. The magnitude of the transient is expressed as a percentage of the peak 60Hz nominal voltage (not the RMS value). The transient is assumed to be completely decayed by the end of the half-cycle in which it occurs. The transient is assumed to occur near the peak of the nominal voltage waveform The amplitude of the transient varies from 40% for 200Hz ringwaves to 200% for 5KHz ringwaves, with a linear increase in amplitude with increasing frequency. Page 5 3.4) High-Frequency Impulse and Ringwave 3.6) Dropout This region describes the transients which typically occur as a result of lightning strikes. Wave shapes applicable to this transient and general test conditions are described in ANSI/IEEE C62.41-1996. This region of the curve deals with both amplitude and duration (energy), rather than RMS amplitude. The intent is to provide a 40 Joule minimum transient immunity. A voltage dropout includes both severe RMS voltage sags and complete interruptions of the applied voltage, followed by immediate re-application of the nominal voltage. The interruption may last up to 20 milliseconds. This transient typically results from the occurrence and subsequent clearing of faults in the AC distribution system. 3.5) Voltage Sags 3.7) No-Damage Region Two different RMS voltage sags are described. Generally, these transients result from application of heavy loads, as well as fault conditions, at various points in the AC distribution system. Sags to 80% of nominal (maximum deviation of 20%) are assumed to have a typical duration of up to 10 seconds, and sags to 70% of nominal (maximum deviation of 30%) are assumed to have a duration of up to 0.5 seconds. Events in this region include sags and dropouts which are more severe than those specified in the preceding paragraphs, and continuously applied voltages which are less than the lower limit of the steady-state tolerance range. The normal functional state of the ITE is not typically expected during these conditions, but no damage to the ITE should result. 3.8) Prohibited Region This region includes any surge or swell which exceeds the upper limit of the boundary. If ITE is subjected to such conditions, damage to the ITE may result. Volume 6, Number 8 Page 6