GENERAC® TRANSFER SWITCHES RTS Automatic Transfer Switch 600 - 800 Amps, 1 and 3-phase DESCRIPTION STANDARD FEATURES Generac 600-800 amp RTS switches are compatible with the full 22-150kW line of liquid-cooled generators. The switches are open transition and are available in 120/240 1ø, 120/208 3ø, 120/240 3ø, and 277/480 3ø. 600-800 amp RTS transfer switches are housed in a rugged steel NEMA/UL Type 3R enclosure, with electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for years of service. The control at the generator handles all the timing, sensing and exercising functions. ® RTS 600-800 Amp Transfer Switch FUNCTIONS All Timing and sensing functions originate in the generator controller Utility voltage drop-out.......................................................................................................................................................................................................................<60% Timer to generator start....................................................................................................................................... 10 second factory set, adjustable between 10-30 seconds Engine warm up delay.................................................................................................................................................................................................................. 5 seconds Standby voltage sensor...................................................................................................................................................................................................60% for 5 seconds Utility voltage pickup..........................................................................................................................................................................................................................>80% Re-transfer time delay................................................................................................................................................................................................................ 15 seconds Engine cool-down timer............................................................................................................................................................................................................. 60 seconds Exerciser ............................................................................................................................................................................................................... 12 minutes every 7 days The transfer switch can be operated manually without power applied. SPECIFICATIONS Amps 600 800 Voltage 120/240, 1ø 120/208, 3ø 120/240, 3ø 277/480, 3ø 120/240, 1ø 120/208, 3ø 120/240, 3ø 277/480, 3ø Open Transition Open Transition NEMA 3R NEMA 3R 42,000 65,000 Load Transition Type (Automatic) Enclosure Type Withstand Rating (Amps) Lug Range 1/0 - 500 MCM Height External Dimensions 4/0 - 500 MCM Width H1 H2 W1 W2 120/240, 1ø 61.4 66 30 36 120/208, 3ø 61.4 66 30 120/240, 3ø 61.4 66 277/480, 3ø 61.4 66 Unit Weight (lbs.) Depth Height Width Depth H1 H2 W1 W2 21 61.4 66 30 36 21 36 21 61.4 66 30 36 21 30 36 21 61.4 66 30 36 21 30 36 21 61.4 66 30 36 21 439 469 W2 TRANSFER SWITCH FEATURES W1 • Electrically operated, mechanically-held contacts for fast, positive connections. • Rated for all classes of load, 100% equipment rated, both inductive and resistive. • 160 millisecond transfer time. • Dual coil design. • Main contacts are silver plated or silver alloy to resist welding and sticking. H2 H1 • NEMA 3R (indoor/outdoor rated) rugged steel enclosure is standard. • Limited Two Year Warranty. DEPTH ® Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com ©2011 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0190980SBY-B / Printed in U.S.A. 01/13/11