A Comprehensive Protection Scheme for Generator Loss of Excitation Nitesh Kumar D R. Nagaraja H. P. Khincha Power Research & Development Consultants Pvt. Ltd Bangalore niteshostwal@gmail.com Power Research & Development Consultants Pvt. Ltd Bangalore nagaraja@prdcinfotech.com Advisor, Indian Institute of Science Bangalore hpk1598@gmail.com Abstract— Power system is constantly evolving with application of new technology to improve the reliability and security of the system. At the same time technology upgradation is being undertaken to reduce the cost of various power system components, which can have an impact on protection techniques. The paper evaluates the performance of loss of excitation protection scheme for increase in generator direct axis synchronous reactance. It is shown that for higher values of direct axis synchronous reactance, the coordination between loss of excitation protection, excitation control and capability limit is not adequate. This may restrict the generator reactive power absorption capability. The paper also reviews the conventional philosophy for setting the excitation limiters and discusses its impact on loss of excitation protection and system behavior. A conventional protection scheme is modified to allow for full utilization of machine capability and new power swing blocking criteria is developed to improve the reliability during stable power swings. Keywords—Loss of excitation protection; Increase in Xd; Under excitation limiter; Correlation function; Stable power swing; Power swing blocking I. INTRODUCTION The impact of loss of excitation (LOE) of a synchronous generator on the machine and the system stability [1], has led to considerable research in development of protection schemes which can detect loss of excitation at the earliest and also make the loss of excitation protection scheme immune to power swings and other external disturbances. The two variants of impedance measurement based protection schemes can provide highly reliable protection for loss of excitation occurring during any loading condition of the generator [2]-[4]. Reference [5] suggests the need for coordination of loss of excitation relay with generator capability curve (GCC), steady state stability limits (SSSL) and excitation controls in order to have an optimum protection scheme. The impedance based schemes are known to mal operate during certain external disturbances and either require intentional time delay or special logic to prevent their operation [6-7]. In recent times, certain generator parameters have undergone significant change due to change in the design aspects of machine. The loss of excitation protection settings mainly depends on the generator direct axis synchronous reactance (Xd) and generator direct axis transient reactance (Xd’) value. A significant change in these parameters can have 978-1-4799-5141-3/14/$31.00 ©2014 IEEE Fig. 1. Typical generator capability curve for different values of Xd an impact on performance of the protection scheme. The paper aims at studying the impact of change in machine parameter on the performance of loss of excitation protection scheme and its coordination with generator excitation control and capability limits. The paper suggests modifications to the existing protection scheme to allow full utilization of machine capability. To overcome the limitation of existing scheme during stable power swings, the paper discusses the use of correlation technique which can classify the disturbance as LOE or stable power swing and can accordingly block the relay from tripping. II. CONSIDERATIONS IN PROTECTION SCHEME WITH INCREASE IN XD A. Coordination of LOE with SSSL and GCC A survey of different generator data sheet of various ratings is carried out, which shows that there has been a change in the generator Xd and inertia values. It is observed that for the high rated machines of capacity around 300 to 600 MW, the Xd values is larger than the conventional value. This increase in Xd can have an impact on coordination of the LOE relay with SSSL and GCC. Fig 1 shows the generator capability curve (with impedance in pu on its own rating) for machines with different Xd rating. It can be observed that the capability curve does not follow a specific trend with change in Xd and mainly depends on the cooling techniques employed [8]. The capability curves for machine of different Xd value generally lie within a narrow band. The calculation of SSSL [9] considering different values of Xd shows the dependency between the SSSL and machine Xd value. Stability margin decreases with increase in Xd and when Fig. 2. Typical SSSL curve for different values of Xd and fixed system reactance Fig. 4. Coordination curve for Xd = 2.8pu • For Xd = 2.0 pu, the three characteristic curves now lie within a narrow band, with zone 2 of LOE and the GCC almost overlapping each other. However this may not have any significant impact. • For Xd>2.0 pu, it is observed that the zone 2 of LOE infringed into the GCC, thereby restricting the machine reactive power absorption capacity. • It is also observed that the variation of Xd has no impact on the coordination of LOE and SSSL. Fig. 3. Coordination curve for Xd = 1.6pu referred to impedance plane, the diameter of the SSSL circle increases with increase in Xd, as shown in Fig 2. Having shown that machine Xd has generally no direct impact on the GCC but affects the SSSL, we move to analyse the impact of this on the coordination of LOE characteristic, GCC and the SSSL. The conventional impedance based protection [3] is considered for analysing the change in loss of excitation characteristic due to change in Xd and system impedance (Xs). The value of Xd is varied from 1.6 pu to 2.8 pu and two values of Xs, i.e, 0.176 pu and 0 pu (infinite bus) are considered. The GCC (in pu) is considered same for all the cases and the under excitation limiter (UEL) is coordinated with GCC. For obtaining the loss of excitation and SSSL characteristics it is considered that a generator of synchronous reactance Xd is connected to a generator transformer having impedance Xtg, which is then connected to the system of impedance Xs, all impedance values referred to generator MVA rating as the base. The characteristic curves are obtained for different values of Xd and Xs by considering Xtg = 12.5%. The characteristic curves of conventional loss of excitation protection considering Xs equal to 0.176 pu for the case with Xd equal to 1.6 pu and 2.8 pu are given in Fig 3 and 4 respectively. The following observations can be drawn from the coordination curves. • For Xd less than 2.0 pu, it is observed that the LOE relay characteristic is adequately coordinated with GCC and SSSL. We note that for certain values of Xd and GCC, the relay characteristics can infringe into the normal operating region. Reference [10] suggests that when such a situation is encountered, the zone 2 reach be reduced by a margin such that it is coordinated with GCC. As discussed in [2], a zone reach equal to Xd is essential to detect LOE occurring at any initial loading condition of machine, the reduced reach will reduce the sensitivity of the scheme for LOE occurring during light loading conditions of the machine. B. Considerations for UEL setting References [5], [11] suggest that UEL is to be coordinated with the GCC, SSSL and loss of excitation relay whichever is most constraining. This indicates that for scenarios where the LOE characteristics infringe into the GCC, the UEL is to be coordinated with SSSL. With this coordination, a significant portion of the reactive power absorption capability of the generator is compromised. In case of salient pole machine having higher reactive power absorption capability than the non-salient pole machines, the compromise can be even severe. Two cases of UEL coordinated with GCC and UEL coordinated with SSSL are shown in Fig 5 for which the loss of reactive power absorption capability is clearly evident. Since SSSL limit is valid only for generator operating in manual excitation, it may not be idealistic to consider this in the modern day power system. Reference [12] discusses in detail the effect of coordination of UEL with SSSL, and suggests that the role of UEL be only limited to prevent stator end ring heating. It also shows that the stability margin of the system increases with use of AVR. Further in several cases in power system, redundancy is provided for AVR and in such case manual excitation operation may never occur. Fig. 5. Coordination of UEL with GCC and SSSL The UEL output is fed as an input to AVR which in turn controls the excitation voltage and hence limits the reactive power absorption. However this action will not be available during manual operation (for example AVR failure) and hence coordination of UEL with SSSL considering manual excitation has no significance and it unnecessarily limits the absorption capacity of the machine which can be of at most importance during severely disturbed system scenario [12]. Further, with use of modern computational tools it is possible to compute the dynamic stability limit with good accuracy and hence there is no justification for use of SSSL for use in protection study [11]. Another approach to this problem can be to coordinate the UEL with LOE zone 2 characteristics. Though this along with suitable time delay for zone 2 can be used as a possible relay scheme, it still restricts some portion of the reactive power absorption capacity of the machine. With UEL tuned to prevent mal operation of LOE relay, the dynamic performance of UEL becomes a very important consideration. The overshoot occurring during UEL control action can cause the impedance to lie in the operating region for considerable time which can issue a false tripping [11]. Thus for machine with higher values of Xd and UEL coordinated with SSSL or LOE relay, there exists a compromise in operational capability and at the same time does not provide full proof protection. III. PROPOSED SCHEME A. Modified Two Zone Scheme Fig 6 shows the impedance trajectory for LOE occurring at different initial loading conditions. It can be inferred that the impedance trajectory during LOE occurring at light loading conditions enters the relay operating zone from the bottom part of the characteristic and does not penetrate too deep. Fig. 7. Proposed modifications in LOE protection scheme For the extreme case where the machine is operating as a synchronous condenser, the impedance trajectory stops at the co-ordinates - [0,-Xd]. This indicates that by reducing the zone 2 diameter and introducing an additional zone such that it covers those impedance trajectories which will not enter the reduced zone 2, we can achieve an optimal LOE protection scheme which can detect LOE at all conditions and at the same time allow better utilization of machine capability. The proposed scheme is as shown in Fig 7. The mod zone 1 is offset by an amount of –Xd’/2 and the diameter is adjusted to coordinate with GCC. With a reduced mod zone 1 reach, the impedance trajectory entry time for the modified zone 1 is greater than entry time for original zone 2 reach. Therefore using a typical original zone 2 time delay of 1s may be inadequate to trip the machine before occurrence of loss of synchronism. In order to improve the performance of the scheme during stable power swings, a power swing blocking criteria is used to supervise the tripping. The proposed mod zone 2 is of quadrilateral characteristics with its reactive reach starting from the point –1.1*(Xd’/2). The resistive reach is defined as an angle with respect to Y-axis such that mod zone 2 characteristic overlaps the LOE impedance trajectory which just touches the modified zone 1 (just before losing synchronism) as shown in Fig 8. Typically this angle is less than 10° and the overlapping ensures that the scheme can detect LOE occurring at any loading conditions. The mod zone 2 can be used to initiate an alarm as soon as the impedance trajectory enters into it and can be configured to trip the machine with some time delay. Fig. 8. Overlapping of mod zone 1, mod zone 2 and LOE trajectory Fig. 6. LOE trajectory for different initial loading Fig. 9. Resistance variation during LOE Fig. 10. Resistance variation during stable power swing B. Power Swing Blocking Scheme The power swing blocking criteria takes advantage of the difference in resistance variation pattern during LOE and power swing. Fig 9 and 10 shows the variation of resistance during LOE and power swings respectively. For use of correlation function as criteria for detecting power swing conditions, one of the data set (x) is chosen as generator terminal resistance. The start point of the data set is at the time (t2) when mod zone 1 triggers and end point is at a time t2+toss, where toss = 1/foss. Thus the data set consists of data from t2 to t2+toss with a step time of Δt = 1/f, where f is the nominal system frequency. The initial variation of resistance during LOE is oscillatory in nature, following which the variation becomes almost linear with respect to time. This linear pattern can be observed till the machine goes out of step, beyond which the variation in resistance is erratic. By overlapping the impedance trajectory during LOE on the relay characteristic as shown in Fig 6, it is observed that for the time period when the trajectory is within the characteristic zone, the variation in resistance is always linear. The variation of resistance during power swing conditions is highly oscillatory and typically oscillates with a frequency (foss) of 1Hz. The oscillatory variation in resistance can be clearly observed even when the power swing locus infringes into LOE relay characteristics. The proposed scheme for power swing detection uses the correlation function to classify the resistance variation as linear or nonlinear, and tripping is permitted if the variation is linear. Correlation function – r is computed using (1). The second set of data can be any reference data set with linearly increasing data. The ideal reference data set can be time sequence which starts when mod zone 1 trigger, treating this time t2 as 0s. The end time of the reference data set is toss, with a step size of Δt. Thus the second set of data will consist of data y = [0 Δt 2Δt 3Δt ………….toss]. Considering the inherent non linearity in measurement and taking additional margin, the power swing blocking criteria can be defined as: Trip: -1 < r < -r1 Block: otherwise r1 is a set threshold. r = -1 indicates negative correlation. i.e. for linearly increasing y, x decreases linearly. For LOE occurring during very low initial loading (typically less than 5% of machine rating), it is observed that rate of change of resistance is very slow and hence the resistance value appears as a constant within the time frame considered for power swing blocking criteria. Therefore the power swing blocking criteria fails to detect LOE occurring at extremely low initial loadings. As discussed earlier, the proposed mod zone 2 is used to detect LOE occurring at very low initial loadings and hence the power swing blocking scheme is not applied for those impedance trajectories which first enter the mod zone 2 characteristics. However the probability of power swing entering the relay characteristic through this small region is very remote and any impedance trajectory entering through this region can be considered as LOE. r = 0 indicates no correlation. No linearity relation exist between x and y. The trip logic for LOE detection and power swing blocking criteria is shown in Fig 11. r = 1 indicates positive correlation. i.e for linearly increasing y, x increases linearly. Other values of r define the degree of linearity between the two data sets. function (r). With this, the proposed scheme has an internal delay of 0.5s to classify the event and issue a trip signal. Fig. 13. System considered for study Fig. 11. Trip logic for proposed relay scheme C. Additional Application of Proposed Scheme The proposed scheme can also be used for cases where the conventional LOE relay is well coordinated with GCC and SSSL. The application of power swing blocking criteria will help to improve the speed of relay operation and also improve relay performance during stable power swing. The relay characteristic for this application is shown in Fig 12. The mod zone 2 characteristic is marginally extended beyond the –(Xd+Xd’/2) point. This is done so that during very low loading conditions, the impedance trajectory first enters the mod zone 2 which blocks the use of power swing blocking criteria. LOE is simulated by reducing the field voltage of generator 1 to zero at t =1s. Case studies are performed considering seven different initial loading conditions such that all possible operating scenarios are covered. The results are presented in table 1, case 1 to case 7. The time values given in table are after applying the disturbance. It is evident that the proposed scheme can successfully detect and classify LOE during all operating scenarios and is capable of issuing trip signal before loss of synchronism occurs. For case 5 to case 7, the mod zone 2 triggers first and hence power swing blocking criteria is disabled. The tripping signal provided after a preset delay (D2) after the trajectory enters mod zone 2 characteristic. Power system disturbance like three phase to ground fault and generator outage are simulated such that the machine does not lose synchronism after the disturbance. Three phase to ground fault is simulated considering two initial operating conditions. The fault is created at t =1s on HV side of the generator transformer with duration equal to its critical clearing time. For the two cases of fault simulation, generator 2 is considered to be out of service. The results are presented in table 1, case 8 to case 10. The proposed power swing blocking criteria can effectively classify stable power swings entering the characteristic zone. The scheme blocks the relay from tripping during all the above cases. Fig. 12. Characteristic of proposed relay for scenario where conventional LOE scheme is adequtely coordinated with GCC IV. CASE STUDY AND RESULTS In order to demonstrate the effectiveness of proposed scheme in allowing full utilization of machine capability, and to differentiate between LOE and stable power swings, the scheme is applied to a test system. The system considered for study is shown in Fig 13 and the system data is provided in appendix. For the considered system the conventional LOE scheme will result in zone 2 infringing the GCC and hence the proposed scheme is used. The test system is subjected to disturbance like full LOE, three phase fault and generator outage, simulation studies are conducted using MiPower software. For the system considered, the fundamental oscillation frequency (foss) at the generator terminal is around 2 Hz. Hence the time period for use in power swing blocking criteria is 0.5s. With each phasor extracted at 0.02s, a data set of 25 samples is to be used for calculating the correlation The locus of power swing during disturbance depends on the electrical center. The change in electrical center will alter the way in which the power swing enters the LOE characteristic region. The power swing disturbances given in case 8 to case 10 are simulated with line length reduced to 25km. The results are presented in table 1, case 11 to case 13. The results demonstrate the capability of the power swing blocking criteria for different electrical centers. V. CONCLUSION An improved LOE protection scheme is presented in this paper which allows the full utilization of machine reactive power absorption capability and at the same time can detect LOE before machine loses synchronism. A power swing blocking criteria is developed which uses correlation function to classify LOE and stable power swings, which enhances the detection of LOE. The effectiveness of the proposed scheme is demonstrated through extensive case studies. Table I. CASE STUDY RESULTS Case No 1 2 3 4 5 6 7 8 9 10 11 12 13 Disturbance Initial Loading (pu, pf) Mod Zone 1 Entry (s) LOE LOE LOE LOE LOE LOE LOE 3P 3P Gen Out 3P 3P Gen Out 0.85, 0.98 0.85, -0.98 0.35, 0.95 0.35, -0.86 0.06, -0.4 0.03, 0.23 0.03, -0.22 0.7 -0.83 0.5 -0.71 0.85 -0.95 0.7 -0.83 0.5 -0.71 0.85 -0.95 2.84 1.20 8.70 6.92 86.08 NE NE 0.14 0.18 1.82 0.16 0.20 NE Mod Zone 1 Exit (s) NL NL NL NL NL NL NL 0.78 0.92 2.76 0.92 0.92 NL r -0.998 -1.000 -1.000 -1.000 NV NV NV 0.716 0.819 0.485 0.029 0.789 NV Mod Zone 1 Trip (s) 3.34 1.70 9.20 7.42 87.08 No No PS Block PS Block PS Block PS Block PS Block No Mod Zone 2 Entry (s) NE NE NE NE 82.64 16.08 14.14 0.74 0.70 0.74 0.96 0.90 NE Mod Zone 2 Exit (s) NL NL NL NL NL NL NL 0.76 0.72 0.76 0.98 0.92 NL No No No No 83.64 17.08 15.14 No No No No No No 3.70 2.98 12.12 10.76 89.72 178.58 182.78 Stable Stable Stable Stable Stable Stable Mod Zone 2 Trip (s) Loss of Synchronism (s) Pf: Power factor, Negative pf indicates leading power factor, 3P: Three phase to ground fault, Gen out: Generator outage, NE: Not entered, NL: Not left, NV: Not valid, PS Block: Blocking signal from power swing blocking criteria. REFERENCES [1] Donald Reimert, “Protective Relaying for Power Generation Systems” CRC press. [2] C.R. Mason, “A New Loss of Excitation Relay for Synchronous Generators”, AIEE transactions vol 68, Issue 2, July 1949, pp 12401245. [3] John Berdy, “LOE Protection for Modern Synchronous Generators’, IEEE Transactions on Power Apparatus and Systems, vol. PAS-94, no. 5, September/October 1975 pp 1457-1463. [4] R. L Tremaine, J. L. Blackburn, “Loss of Field Protection for Synchronous Generators”, Electrical Engineering, vol: 73, issue: 11, Nov 1954. [5] C. J. Mozina, “Coordination of Generator Protection with Generator Excitation Control and Generator Capability”, Working Group J-5 of rotating machinery subcommittee, IEEE PES, 2007 [6] S. R. Thambay, Y. G. Paithankar, “A New Adaptive Loss of Excitation Relay Augmented by Rate of Change of Reactance”, IEEE Power Engineering Society General Meeting, Vol 2, June 2005, pp 1831-1835 [7] Z. P. Shi, J. P. Wang, “The Comparison and Analysis for Loss of Excitation Protection Schemes in Generator Protection”, 11th International conference on Developments in Power System Protection, April 2012. [8] P. Kundur, “Power System Stability and Control”, McGraw-Hill inc. [9] G Benmouyal, “The impact of synchronous generator excitation supply on protection and relays”, Schweitzer Engineering Laboratories, Inc. [10] M. Elsamahy, S. O. Faried, T. Sidhu, “Impact of Midpoint STATCOM on Generator Loss of Excitation Protection”, IEEE Transactions on power delivery, vol. 29, no. 2, April 2014. [11] G. R. Bérubé, L. M. Hajagos, “Coordination of Under Excitation Limiters and Loss of Excitation Relays with Generator Capability”, IEEE Power and Energy Society General Meeting, July 2009, Calgary [12] J.R. Riberio, “Minimum Excitation Limiter Effects on Generator Response to System Disturbances”, IEEE Transactions on Energy Conversion, Vol. 6, No. 1, March 1991, pp 29 – 38. APPENDIX AVR Model Generator Data Rated MVA: 705.88 MVA Tr: 0.01 s AVR Data Terminal Voltage: 20 kV Tc2: 0.8 s, Tb: 2.6 s Inertia constant: 2.5 MJ/MVA Tc1: 0.01 s, Tb1: 0.08 s Xd: 2.4 pu, Xq: 2.33 pu Kr: 300 pu, Ts: 0.04 s X′d: 0.2828 pu, X′q: 0.408 pu Up+: 7.3, Up-: -7.3 X″d: 0.21 pu, X″q: 0.21 pu Utility Data Tdo′: 8.724 s, Tqo′: 0.969 s 3ph MVA: 15000 MVA Tdo″: 0.046 s, Tqo″: 0.068 s SLG MVA: 15000 MVA Transmission Line Data Voltage Level: 400 kV Transformer Data MVA: 705.88 MVA Z: 0.015664+j 0.26816 ohm/km Voltage Rating: 20/400 kV B/2: j2.18437e-006 mho/km Z: j0.125 pu