Vdc Vdc - Neptronic

advertisement
ESC Steam Controller
Specification & Installation Instructions
Features:
ESC
Attractive modern look with large LCD and backlight
•
Icons driven information and 2 line of text information
•
Programmable parameters
•
Selectable Fahrenheit or Celsius scale
•
Multi level lockable access menu
•
Selectable internal or external control
•
Programmable proportional control band & dead band
ESC Series steam controller
Technical Data
ESC
Power supply
24 Vac
Power consumption
50 VA
Relay output
2 relay
Relay rating
125 Vac, resistive load 10 amps
Operating temperature
0ºC to 50ºC [32ºF to 122ºF]
Storage temperature
-30ºC to 50ºC [-22ºF to 122ºF]
Relative humidity
5 to 95 % non condensing
Weight
635 g. [1.4 lb]
Interface
Display Symbols
Alarm/Warning
Vdc
Vdc
Not used
Vdc
Dimensions
A
C
B
ESC rev1.2 / 110803
Dimension
A
B
C
Imperial (in)
6.3
5
2.25
Metric (mm)
160
126
57
1
ESC
Specification & Installation Instructions
4
3
DI2
DI1
2
High Limit (digital)
2
AM060-ESC
Common -1
DI3
COM
TB1
LEGEND
S = Separator
J = Jacket
NO = Normally Open
NC = Normally Close
NC
Interlock
PD Switch On/Off
1
Digital Input
Steam Control Valve
Actuator
DI4
Humidity Demand On/Off
NC
NO
On/Off
ESC
5
Terminal Description
NO
24 Vac -2
Jacket Heating Valve
Control Signal -3
Actuator
6
TO3
Not used -4
1
TS5
2
COM
3
TS6
Temperature Sensor Jacket 4
Common
Temperature Sensor Jacket 5
J5
4
3
2
1
3
1
3
2
Steam
Relay
TB3
2
TS4
NO
1
3
J4
NC
KCOM
Steam on Relay Status
Alarm Relay
4
2
COM
NO
24VAC
3
TS3
NC
2
TS2
1
J3
1- Common
COM
1
3
Temperature Sensor Jacket 3
2- Not used
COM
Alarm
Relay
TB4
COM
Temperature Sensor Inputs
TB12
TB13
2
Common
3- Control Signal
TO1
KCOM
Supply
1
TS1
Temperature Sensor Jacket 2
4- 24 Vac
TB5
AI4
TB11
COM
3
J2
Analog Inputs
TB10
2
Common
J1
TO2
COM
TB9
AI3
Temperature Sensor Separator
Temperature Sensor Jacket 1
Analog
Outputs
TB8
AI2
1
S1
COM
3
High Limit Humidity Sensor
AI1
2
2
AO2
1
Room Humidity Sensor
COM
3
External Demand/Setpoint
0 – 10
Volts
1
AO1
2
Common
1
Control Valve Signal
TB2
Not used -5
5
AT060-ESC
COM
24 Vac
Notes:
1
If the ESC control mode is set to “OFF” (external control) in step #14, Pin 1 of TB9 is used for the external control signal.
If the ESC control mode is set to “ON” (internal control) in step #14 and external setpoint is “ON” on step #18, Pin 1 of TB9 is used for the
external setpoint signal.
Step #14 = ON (internal control) &
Step #14 = OFF (external control)
Step #18 = ON (external setpoint)
TB9 – Pin 1 input signal
External demand
External Set point
2
The high limit sensor will be connected to TB1 or TB10 depending on the configuration done at step #24. See table below.
High Limit (Step #24)
Digital
Analog
Connect high limit sensor to
TB1 – Pin #4
TB10 – Pin #1
Temperature Sensor Jacket 1 -2-3-4-5 are optional depending on system configuration. They also need to be enable in the
Programming mode (step #7).
2
ESC
Specification & Installation Instructions
System Overview
Single tube configuration
ISOLATING
VALVE
STRAINER
CONTROL VALVE
DISTRIBUTOR
TEMPERATURE SENSOR
FOR ISOLATING VALVE
SEPARATOR
FLOAT AND THERMOSTATIC
STEAM TRAP
Multi tube Single jacket configuration
STRAINER
ISOLATING
VALVE
DISTRIBUTORS
CONTROL VALVE
SEPARATOR
TEMPERATURE SENSOR
FOR SEPARATOR
TEMPERATURE SENSOR
FOR JACKET 1
FLOAT AND THERMOSTATIC
STEAM TRAP
3
ESC
Specification & Installation Instructions
Double jacket configuration
STRAINER
ISOLATING
VALVE
CONTROL VALVE
TEMPERATURE SENSOR
FOR JACKET 1
DISTRIBUTORS
SEPARATOR
TEMPERATURE SENSOR
FOR SEPARATOR
FLOAT AND THERMOSTATIC
STEAM TRAP
TEMPERATURE SENSOR
FOR JACKET 2
4
ESC
Specification & Installation Instructions
Programming Mode
Press on
to edit function, press on button
or
to change values and navigate the menus. The system will exit the menus
and return to normal function if you press
or if no button is pressed for 5 minutes, changed values will automatically be saved.
Step
Display
Description
Values
Controller language:
Display scrolls “enter passwrd”.
1
2
3
4
You have 1 minute to enter the password using the arrow buttons
and
increase
to move to the next digit and
or decrease the value, one digit at a time. Press
to exit the menu.
press
When the password is correct press on
. If you make a mistake, the controller
returns to normal operation mode. You will need to repeat this step.
Controller language:
Select either “FRA” for French or “ENG” for English.
Units:
Display scrolls “Metric display units”.
Default: ON
“ON” : Econo mode activated
“Off”: Econo mode deactivated
In Econo mode, the isolation valve will be closed when there is no demand.
Default: OFF
Metric: kg H2O/Hr
Range:0 to 6554
Default: 0
Imperial: lbs H2O/Hr
Range: 0 to 14448
Shows the system capacity.
Working capacity:
Display scrolls “working capacit in pct”.
You can adjust the maximum demand capacity in % of the full system capacity (of step
#4).
Note: Factory set. You should not change this value without consulting the
manufacturer.
Number of temperature switches:
Display scrolls “num of temper switch”.
Number of temperature sensors, depends on system configuration.
8
Separator temperature offset:
Display scrolls “separat temper offset”.
You can adjust the temperature reading by using the offset.
9
10
“ON” metric: ºC, kg H2O/Hr
“Off” imperial: ºF, lbs H2O/Hr
You can change the units used.
5
7
Default value: English
Econo mode:
Display scrolls “econo mode”.
System capacity:
Display scrolls “System capacit KG H2o per hr”.
6
Password: 637
Jacket temperature offset: Only available if “number of temperature switches” is greater than 1 at step #7.
Display scrolls “Jacket temper offset”.
You can adjust the temperature reading by using the offset.
Range: 10-100%
Increment: 5%
Default value: 100%
Range: 1 to 6
Default value: 1
Range: -10 to 10ºC [-18 to
18ºF]
Increment: 0.1ºC [0.1ºF]
Default value: 0
Range: -10 to 10ºC [-18 to
18ºF]
Increment: 0.1ºC [0.1ºF]
Default value: 0
Jacket2 temperature offset: Only available if “number of temperature switches” is greater than 2 at step #7. Range: -10 to 10ºC [-18 to
Display scrolls “Jacket2 temper offset”.
18ºF]
You can adjust the temperature reading by using the offset.
Increment: 0.1ºC [0.1ºF]
Default value: 0
11
Jacket temperature offset: Only available if “number of temperature switches” is greater than 3 at step #7.
Display scrolls “Jacket3 temper offset”.
You can adjust the temperature reading by using the offset.
Range: -10 to 10ºC [-18 to
18ºF]
Increment: 0.1ºC [0.1ºF]
Default value: 0
12
Jacket temperature offset: Only available if “number of temperature switches” is greater than 4 at step #7.
Display scrolls “Jacket4 temper offset”.
You can adjust the temperature reading by using the offset.
Range: -10 to 10ºC [-18 to
18ºF]
Increment: 0.1ºC [0.1ºF]
Default value: 0
13
Jacket temperature offset: Only available if “number of temperature switches” is greater than 5 at step #7.
Display scrolls “Jacket5 temper offset”.
You can adjust the temperature reading by using the offset.
Range: -10 to 10ºC [-18 to
18ºF]
Increment: 0.1ºC [0.1ºF]
Default value: 0
Internal control mode:
Display scrolls “Interna Control Mode”.
14
If “ON”, the control is done by the ESC.
If “OFF”, the control is from an external signal.
Default value: OFF
If “ON” is selected go to step #16.
5
ESC
Step
Specification & Installation Instructions
Display
Description
External control demand signal (AI3):
Display scrolls “demand signal range”.
15
Select the relative humidity sensor signal: 0-10Vdc or 2-10Vdc.
Vdc
16
Go directly to step #24.
Relative humidity offset:
Display scrolls “room humidty offset in pct”.
You can adjust the room relative humidity reading by using the offset.
Humidity sensor signal range:
Display scrolls “Room humidty signal range”.
17
Values
Default value: 2-10Vdc
Range: -10 to 10 %RH
Increment: 0.1 %RH
Default value: 0 %RH
Default value: 2-10Vdc
Select the relative humidity sensor signal: 0-10Vdc or 2-10Vdc.
Vdc
External humidity setpoint (AI3):
Display scrolls “Externa Humidty Setpnt”.
18
Select “ON” to use an external setpoint for humidity.
Default value: OFF
If “OFF” is selected go to step #20.
Set point signal range:
Display scrolls “setpnt signal range”.
19
Select the relative humidity sensor signal: 0-10Vdc or 2-10Vdc.
Vdc
20
Go directly to step #21.
Internal RH setpoint:
Display scrolls “interna humidty setpnt in pct”.
Adjust the desired humidity setpoint in %RH.
Control dead band:
Display scrolls “control dead band in pct”.
21
Adjust the desired control dead band.
Control proportional ramp:
Display scrolls “control Prop ramp in pct”.
22
Adjust the desired control proportional ramp.
Control integral ramp:
Display scrolls “control integra ramp in pct”.
23
Adjust the desired control integral ramp.
High limit duct sensor:
Display scrolls “High limit sensor”.
24
Select the type of high limit sensor (analog or digital) if any.
If “Disable” or “Digital” is selected, go to step #29.
High limit setpoint:
Display scrolls “High limit setpnt in pct”.
25
Input the high limit relative humidity setpoint.
Internal control mode:
Display scrolls “High limit prop ramp in pct”.
26
Adjust the desired high limit proportional ramp.
High limit offset:
Display scrolls “High limit humidty offset in pct”.
27
You can adjust the room relative humidity reading by using the offset.
High limit signal range:
Display scrolls “High limit signal range”.
28
Default value: 2-10Vdc
Range: 10 to 90 %RH
Increment: 1 %RH
Default value: 40 %RH
Range: 0 to 5 %RH
Increment: 0.1 %RH
Default value: 2.0 %RH
Range: 1 to 10 %
Increment: 0.1 %
Default value: 5.0 %
Range: 1 to 10 %
Increment: 0.1 %
Default value: 5.0 %
- Disable
- Analog
- Digital (On/Off)
Default value: Disable
Range: 10 to 90 %RH
Increment: 1 %RH
Default value: 80 %RH
Range: 0 to 20 %
Increment: 0.1 %
Default value: 10.0 %
Range: -10 to 10 %RH
Increment: 0.1 %RH
Default value: 0 %RH
Default value: 2-10Vdc
Select the high limit sensor signal: 0-10Vdc or 2-10Vdc.
Vdc
29
High limit reading:
Display scrolls “High limit max demand in pct”.
Show the actual reading of the high limit sensor.
30
End of season: Not available if Econo mode is selected at step #3.
Display scrolls “end of season delay in hr”.
The isolation valve will be turned off after 100 hours (default) without any demand.
Range: 100 to 250 hours
Increment: 5 hours
Default value: 100 hours
6
ESC
Step
31
32
33
Specification & Installation Instructions
Display
Description
Service delay:
Display scrolls “service delay in hr”.
Number of hours running at 100% capacity before servicing.
Values
Press on button
&
simultaneously to reset the counter along with any associated
alarms.
Service runtime:
Display scrolls “service runtime in hr”.
Displays the running time at 100% capacity in hours since the last service.
Once in edit mode (by pressing
), press on button
the counter along with any associated alarms.
Service alarm:
Display scrolls “runs while service alarm”.
&
Range: 400 to 1500 hours
Increment: 100 hours
Default value: 1000 hours
simultaneously to reset
Default value: Inactive
To let the system run even when servicing is due (set in step #31), select “ACT” (active).
34
Total runtime:
Display scrolls “total runtime in hr”.
Displays the running time at 100% capacity in hours.
35
Control valve ouput:
Display scrolls “control output signal in mv”.
Displays the control valve output in mV.
36
Isolating valve state: Only available if “ON” is selected at step #4.
Display scrolls “isolat valve output state”.
Displays if the isolating valve is activated (open) or inactivated (closed).
37
Alarm relay state:
Display scrolls “alarm relay output state”.
Displays if the alarm relay is activated or inactivated.
38
Steam output relay state:
Display scrolls “steam on output relay output state”.
Displays if the steam output relay is activated or inactivated.
39
Separator temperature input:
Display scrolls “separat temper input signal in mv”.
Displays the separator temperature sensor reading in mV.
40
Jacket temperature input: Only available if “number of temperature switches” is greater than 1 at step #7.
Display scrolls “jacket temper input signal in mv”.
Displays the jacket temperature sensor reading in mV.
41
Jacket2 temperature input: Only available if “number of temperature switches” is greater than 2 at step #7.
Display scrolls “jacket2 temper input signal in mv”.
Displays the jacket temperature sensor reading in mV.
42
Jacket3 temperature input: Only available if “number of temperature switches” is greater than 3 at step #7.
Display scrolls “jacket3 temper input signal in mv”.
Displays the jacket temperature sensor reading in mV.
43
Jacket4 temperature input: Only available if “number of temperature switches” is greater than 4 at step #7.
Display scrolls “jacket4 temper input signal in mv”.
Displays the jacket temperature sensor reading in mV.
44
Jacket5 temperature input: Only available if “number of temperature switches” is greater than 5 at step #7.
Display scrolls “jacket5 temper input signal in mv”.
Displays the jacket temperature sensor reading in mV.
45
Demand input: Only available if “interna control mode”
Display scrolls “demand input signal in mv”.
is set to ”OFF” at step #14.
Displays the demand reading in mV.
46
Room relative humidity input: Only available if “interna control mode” is set to ”ON” at step #14.
Display scrolls “room humidity input signal in mv”.
Displays the room relative humidity reading in mV.
47
Setpoint input: Only available if “externa humidty setpnt” is set to ”ON” at step #18.
Display scrolls “setpnt input signal in mv”.
Displays the setpoint reading in mV.
7
ESC
Step
48
Specification & Installation Instructions
Display
Description
High limit sensor input: Only available if “high limit sensor” is set to ”ANALOG” at step #24.
Display scrolls “high limit input signal in mv”.
Values
Displays the high limit sensor reading in mV.
49
External demand state: Only available if “interna control mode” is set to ”OFF” at step #14.
Display scrolls “extern demand input state”.
Displays if the external demand is activated (open) or inactivated (closed).
50
Air flow switch state:
Display scrolls “air flow input state”.
Displays if the air flow switch is triggered (activated) or not (inactivated).
51
High limit switch state: Only available if “high limit sensor” is set to”DIGITAL” at step #24.
Display scrolls “high limit switch input state”.
Displays if the high limit switch is triggered (activated) or not (inactivated).
52
Interlock state:
Display scrolls “intrlck input state”.
Displays if the interlock is triggered (activated) or not (inactivated).
53
Microcontroller temperature:
Display scrolls “micro temper”.
Displays if the microcontroller temperature in ºC or ºF.
54
PCB temperature:
Display scrolls “PCB temper”.
Displays if the PCB temperature in ºC or ºF.
8
ESC
Specification & Installation Instructions
Alarms & Notifications
Step
A1
Display
Action
Description
Air flow:
Display scrolls “no air flow”.
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
Air flow sensor not detected.
A2
High limit cutout:
Display scrolls “high limit cutout”.
Duct humidity has exceeded high limit level.
A3
Service warning:
Display scrolls “service warning”.
Servicing is due in less than 100 hours.
Service the unit and reset the service
pushing simultaneously the arrow
buttons
and
for 3 seconds
Service alarm:
Display scrolls “service unit”.
If step #33 “runs while service alarm” is
set to “inact”:
A4
Service is due.
A5
Interlock alarm:
Display scrolls “inter lock”.
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
-
Control valve will be closed
-
Control valve will be closed
-
Control valve will be closed
-
Control valve will be closed
-
Control valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
Interlock is activated.
A6
Flooded separator steam trap:
Display scrolls “flooded separat steam trap”.
The separator steam trap is flooded or temperature is too low.
A7
Flooded Jacket steam trap:
Display scrolls “flooded jacket steam trap”.
The jacket steam trap is flooded or temperature is too low.
A8
Flooded Jacket2 steam trap:
Display scrolls “flooded jacket2 steam trap”.
The jacket2 steam trap is flooded or temperature is too low.
A9
Flooded Jacket3 steam trap:
Display scrolls “flooded jacket3 steam trap”.
The jacket3 steam trap is flooded or temperature is too low.
A10
Flooded Jacket4 steam trap:
Display scrolls “flooded jacket4 steam trap”.
The jacket4 steam trap is flooded or temperature is too low.
A11
Flooded Jacket5 steam trap:
Display scrolls “flooded jacket5 steam trap”.
The jacket5 steam trap is flooded or temperature is too low.
A12
Separator temperature sensor:
Display scrolls “separat temper sensor”.
The separator sensor is defective.
A13
Jacket temperature sensor:
Display scrolls “Jacket temper sensor”.
The jacket sensor is defective.
A14
Jacket2 temperature sensor:
Display scrolls “Jacket2 temper sensor”.
The second jacket sensor is defective.
A15
Jacket3 temperature sensor:
Display scrolls “Jacket3 temper sensor”.
The third jacket sensor is defective.
A16
Jacket4 temperature sensor:
Display scrolls “Jacket4 temper sensor”.
The fourth jacket sensor is defective.
A17
Jacket5 temperature sensor:
Display scrolls “Jacket5 temper sensor”.
The fifth jacket sensor is defective.
9
ESC
Step
A18
Specification & Installation Instructions
Display
Description
Room humidity sensor:
Display scrolls “room humidty sensor”.
Action
-
Control valve will be closed
Isolating valve will be closed
-
Control valve will be closed
Isolating valve will be closed
Room humidity sensor failure detected.
A19
High limit humidity sensor:
Display scrolls “high limit humidty sensor”.
High limit humidity sensor failure detected.
10
ESC
Specification & Installation Instructions
Operation Mode
Step
A
Description
At powering up, thermostat will light display and activate all LCD segments
during 2 seconds.
The serial number, model and revision will then be displayed.
In normal operation mode various information is displayed one after the other. You can use the
B
C
D
Display
or
to scroll quicker.
The following humidity levels will be displayed (if applicable):
•
Humidty setpnt in pct – Humidity setpoint in %RH
•
Room humidty in pct – Room humidity reading in %RH
•
High limit humidty in pct – Duct sensor reading in %RH
The following control parameters will be displayed:
•
Control demand in pct – Current demand in % of the total system capacity
•
Control output in pct – Current output in % of the total system capacity
•
Control demand – Current demand in kg/hr or Lbs/hr
•
Control output – Current output in kg/hr or Lbs/hr
The following Temperature levels will be displayed (if applicable):
•
Separat temper – Separator temperature in ºC or ºF
•
Jacket temper – Jacket #1 temperature in ºC or ºF
•
Jacket2 temper – Jacket #2 temperature in ºC or ºF
•
Jacket3 temper – Jacket #3 temperature in ºC or ºF
•
Jacket4 temper – Jacket #4 temperature in ºC or ºF
•
Jacket5 temper – Jacket #5 temperature in ºC or ºF
11
ESC
Specification & Installation Instructions
Notes:
Recycling at end of life
®
At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic
authorized distributor, please consult www.neptronic.com.
®
12
Download