ED2-UT-Ex2 Universal Temperature Converter Connection

advertisement
Universal Temperature Converter
ED2-UT-Ex2
Assembly
Features
•
•
•
•
•
•
•
2-channel isolated barrier
24 V DC supply
Thermocouple or RTD input
Current output 0/4 mA ... 20 mA
Configurable by PACTware
Line fault (LFD) and sensor burnout detection
Internal cold junction compensation
Front view
ED2-UTEx2
LED red:
Fault signal
channel 1
CH. 1
FAULT
CH. 2
LED red:
Fault signal
channel 2
Function
This isolated barrier is used for intrinsic safety applications.
LED green:
Power supply
PWR
The device converts RTD input signals or thermocouple input
signals in the hazardous area to 0/4 mA ... 20mA signals in the
safe area.
Programming jack
For temperature measurements with thermocouples the cold
junction module E-CJC is used to enable cold junction
compensation.
PRGRM.
If required the device can be used as a dual output single
channel unit, using channel 1 input.
The cold-junction temperature is measured by channel 1, so if
only one channel is to be used with a thermocouple, it must be
channel 1.
A fault is indicated by LEDs acc. to NAMUR NE44 and by
user-configured fault indication outputs.
The device is easily configured by the use of the PACTware
configuration software.
Release date 2012-05-22 12:20
Date of issue 2014-04-29
118828_eng.xml
Connection
ED2-UT-Ex2
1
E-CJC
-
d2
+
T
T
2
+ d30
- z30
d4
T
1
2
T
d8
+
-
d6
-
d32
z32
z2
+
z4
T
T
T
z8
z6
z14d14+
24 V DC
Zone 0, 1, 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1
Technical data
ED2-UT-Ex2
General specifications
Signal type
Analog input
Supply
Connection
d14+, z14-
Rated voltage
20 ... 30 V DC
Ripple
within the supply tolerance
Power consumption
≤3W
Input
Connection
channel 1: d2, d4, d6, d8
channel 2: z2, z4, z6, z8
RTD
type Pt100 (EN 60751: 1995)
type Ni100 (DIN 43760)
Measuring current
approx. 400 µA with RTD
Types of measuring
2-, 3-, 4-wire connection
Lead resistance
≤ 50 Ω per lead
Measuring circuit monitoring
line fault
Thermocouples
type B, E, J, K, N, R, S, T (IEC 584-1: 1995), type L (IEC 584-1: 1989)
Cold junction compensation
external and internal , see connection diagram
Measuring circuit monitoring
sensor breakage
Resistor
Measurement range
0 ... 400 Ω
Voltage
Measurement range
-240 ... 240 mV
Output
Connection
channel 1: d30+, z30channel 2: d32+, z32-
Current range
0/4 ... 20 mA
Load
≤ 500 Ω
Output
Analog current output
Fault signal
in case of input signal overrange 20.5 mA
Line fault detection
downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Deviation
After calibration
Pt100: ± (0.01 % of measurement value in K + 0.05 % of span + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 0.05 % of span + 1 K (1.2 K for types R and S))
this includes ± 0.8 K error of the cold junction compensation
mV: ± (50 µV + 0.1 % of span)
potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes errors due to lead resistance))
Influence of ambient temperature
deviation of CJC included:
Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ∆Tamb*)
thermocouple: ± (0.02 K + 0.004 % of measurement value in °C + 0.006 % of span)/K ∆Tamb*)
*) ∆T
amb = ambient temperature change referenced to 23 °C (296 K)
Influence of supply voltage
Influence of load
< 0.01 % of span
≤ 0.001 % of output value per 100 Ω
Electrical isolation
Output/power supply
Output/Output
Release date 2012-05-22 12:20
Date of issue 2014-04-29
118828_eng.xml
Directive conformity
functional insulation, rated insulation voltage 50 Veff
functional insulation, rated insulation voltage 50 Veff
Electromagnetic compatibility
Directive 2004/108/EC
The device has been used for the same applications for several years. It therefore features an appropriate
electromagnetic field immunity. The device must not be used in new plants.
Conformity
Insulation coordination
EN 50178
Electromagnetic compatibility
NE 21:2006
Degree of protection
IEC 60529
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection
IP20
Connection
48-pin plug connector acc. to DIN 41612 , series 2 , type F , z, b and d provided
Mass
approx. 200 g
Dimensions
20 x 128 x 193 mm (0.8 x 5 x 7.6 in)
Construction type
Eurocard 100 x 160 mm (3.9 x 6.3 in) acc. to DIN 41494, front panel 4TE
Mounting
in 19" rack
Coding
a15/a27
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
2
Technical data
ED2-UT-Ex2
Data for application in connection
with Ex-areas
EC-Type Examination Certificate
BAS 00 ATEX 7044 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
Input
Voltage
Current
Power
Supply
Maximum safe voltage
Output
Maximum safe voltage
Electrical isolation
Input/Other circuits
¬ II (1)GD [Ex ia] IIC, [Ex iaD] (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Ex ia IIC
Uo
11 V
Io
33 mA
Po
90 mW (linear characteristic)
Um
250 V (Attention! The rated voltage is lower.)
Um
250 V (Attention! The rated voltage is lower.)
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC
EN 60079-0:2006, EN 60079-11:2007, EN 61241-0:2006, EN 61241-11:2005
General information
Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperlfuchs.com.
Accessories
optional accessories:
- cold junction module E-CJC
- programming adapter K-ADP-USB
- configuration software PACTwareTM
Release date 2012-05-22 12:20
Date of issue 2014-04-29
118828_eng.xml
Designation
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
3
Download