DNV Test Report

advertisement
Test File No. TL1316
Moxa Managed & Unmanaged
Ethernet Switches Plus Video Server
Mariner Systems (UK) Ltd.
29 June 2009
Page 1 of 112
Test Report TL1316
Table of Contents
Page
1
2
3
4
5
6
SCOPE OF WORK………………………………………………………………...3
EQUIPMENT UNDER TEST……………………………………………………..3
TEST LABORATORY………………………………………………………….....6
TEST PERIOD……………………………………………………………………..6
ATTENDING REPRESENTATIVES…………………………………………….6
TESTS……………………………………………………………………...……….6
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
APPENDCIES…………………………………………………………...…………19
STAMPED TIMETABLE………………………………………………………....20
DRY HEAT CHART ……………..…..…………………………………………...22
LOW TEMPERATURE CHART …………….………………………………….23
HIGH HUMIDITY CHART ……………..……………………………………….24
DWELL FREQUENCIES…………………………………………………………25
LOCATIONS OF ACCELEROMETERS………………………………………..26
VIBRATION CHARTS……………………………………………………………35
RADIATED EMISSIONS ………………………………...………………………77
CONDUCTED EMISSIONS…………………………...………………………….81
INSULATION RESISTANCE READINGS………………………..……………108
LIST OF EQUIPMENT TESTED..........................................................................109
Page 2 of 112
Test Report TL1316
1 SCOPE OF WORK
Marine type-approval test requirements
This file contains the results of tests car ried out to m eet the require ments of A BS, DNV, GL, LR and NKK, on
behalf of Moxa networking Co. Ltd.
All these test s meet or exc eed the require ments of th e guidelines laid out in IA CS Unified Require ment E10 and
the relevant sections of IEC945 for equipm ent housed w ithin a protected environment. These consolidated
requirements are detailed within Mariner Systems Test Requirements (Issue 9).
2 EQUIPMENT UNDER TEST
The equipment being tested comprised the following units shown marked. These cover the rest of the units in the
series as these units were chosen to have the most functionality of the series.
(See Appendix for full list of equipment tested)
Client:
Moxa Inc.
Fl. 4, No. 135, Lane 235,
Pao-Chiao Rd., Shing Tien City,
Taipei, Taiwan
Contact:
Mr John Yu
Applications to the following Classification Societies:
American Bureau of Shipping
Det Norske Veritas
Germanischer Lloyd
Lloyd's Register of Shipping
Nippon Kaiji Kyokai
(ABS)
(DNV)
(GL)
(LR)
(NKK)
Test Results
The tests list ed and detail ed in the following pages we re completed succe ssfully with the equipm ent operating
normally before and after all tests, and during those tests that require normal operation of the equipment whilst the
test is being carried out. This test report may not be reproduced in whole or part without the prior written approval
of the laboratory.
Signed
S. K. Lee
Test Laboratory Manager
3 TEST LABORATORY
The tests were carried out at the Environmental Test Laboratory of Mariner Systems (UK) Ltd, located in
Spennymoor, Co Durham., UK
Page 3 of 112
Test Report TL1316
Laboratory accreditation:
Mariner Systems is recognized by Bureau Veritas as per note NR320.
Ambient conditions in the laboratory
PARAMETER
Temperature °C
Humidity % RH
Barometric pressure mbar
Required (IEC 60068-1)
15 - 35
25 - 75
860 - 1060
Actual
18.5 - 23.8
50 - 60
990 - 1009
4 TEST PERIOD
The tests were carried out during 1-Dec-2008 to 26 -June-2009.
5 ATTENDING REPRESENTATIVES
Karen Ryan – Det Norske Veritas
Pawan Jha – Lloyds Register of Shipping
Roger Partington - Lloyds Register of Shipping
Bill Divine - Nippon Kaiji Kyokai
Gavin Leader - American Bureau of Shipping
6 TESTS
The tests detailed in this file are –
TEST
01 Performance
02 Dry Heat
03 Cold/Low Temperature
04 Damp Heat/Humidity
05 High Voltage
06 Vibration
07 Power Supply Variation
08 Power Supply Failure
09 Conducted LF
10 Conducted RF
11 Electromagnetic Field
12 Radiated Emissions
13 Conducted Emissions
14 Electrostatic Discharge
15 Insulation Resistance
16 Bursts/Fast Transients
17 Surge Voltage
18 Inclination (Static)
19 Inclination (Dynamic)
20 Acoustic Noise
21 Compass Safe Distance
22 Shock Test
IACS Unified Requirements E10
N/A
IEC60068-2-2
IEC60068-2-1
IEC60068-2-30
Not Required
IEC60068-2-6
IEC60092-504
IEC60092-504
IEC60533
IEC61000-4-6
IEC61000-4-3
IEC60533 CISRP 16-1 & 16-2
IEC60533 CISRP 16-1 & 16-2
IEC61000-4-2
IEC60092-504
IEC61000-4-4
IEC61000-4-5
IEC60092-504
IEC60092-504
Not Required
Not Required
Not Required
Page 4 of 112
Test Report TL1316
IEC945
N/A
Section 8.2.2.2
Section 8.4.2.3
Section 8.3
Not Required
Section 8.7.2
Section 10.7.1 & 7.2
Section 10.8.2
Section 10.2.2
Section 10.3.2
Section 10.4.2
Section 9.3.2
Section 9.2.2
Section 10.9.2
Section 8.3 & 8.4
Section 10.5.2
Section 10.6.2
Not Required
Not Required
Section 11.1.2
Section 11.2.2
Not Required
Environmental Test File No. TL1316.01
01/Dec/08
Equipment performance
Specification
The co nformance t o d rawings i s chec ked and a f unctional perf ormance t est i s demonstrated t o t hose C lassification Soci ety
surveyors present.
Test Procedure
The units we attached to DIN rail to make it easier to move and also to connect together. The units were split into 2 systems as
the EDS72810G is a backbone which the modules (see appendix for full list attached to EDS72810G) are mounted onto. One
of the modules is a video server and had a test box which produced a constant test video stream so we put this module at the
start of the 2 systems and then linked them all together using a combination of CAT5 and fibre optic (depending on what each
module supported) with a laptop at the end of the line. The test box produced the video signal and the video server converted
this to run over the network, this went through all of the modules and the test stream was displayed on the laptop. This ensured
that there was always data flowing through the 2 systems all the time during the testing and if at any point the test stream was
not displayed then we would know if we had a fault.
Environmental Test File No. TL1316.02
02/Jun/09
Dry Heat (IEC945 Section 8.2.2.2, IEC60068-2-2)
Specification
The equipment is to be placed in a clima tic chamber and the temperature raised to 70°C ± 2°C for a period of not less than 16
hours. The equipment shall be operational during the test and no degradation of the equipment shall be seen.
Test Procedure
Test Equipment
Calibration date
Montford environmental test chamber
RS Electronics Resistance box
Signallogger PC & Thermistors
Calibrated on use
05/04/10
Calibrated on use
The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration
before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range.
Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet
thermistor are located in the plenum chamber. The plotted results for dry temperature are the a verage values of all five dry
sensors.
The equipment was then placed in the e nvironmental chamber and the te mperature was raised fro m a mbient to 7 0°C ±2 °C
over two hours and held for a period of 16 hours.
The relative humidity was monitored and during the heating process and did not exceed 50% at 35°C, the mesured value was
15%.
Results
A performance test was performed on the equipment during the last hour at the test temperture and after the test, the equipment
continued to work with no degradation in performance.
Refer to the Appendices for test result graphs
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1°C
Page 5 of 112
Test Report TL1316
Environmental Test File No. TL1316.03
04/Jun/09
Low temperature (IEC945 Section 8.4.2.3, IEC60068-2-1)
Specification
The equipment shall be placed in a clim atic chamber and the temperature reduced to -25°C ± 2°C for a period of not less than
2 hours. No degradation of the equipment performance shall be observed.
Test Procedure
Test Equipment
Calibration date
Montford environmental test chamber
Signallogger PC & thermistors
RS Electronics Resistance box
Calibrated on use
Calibrated on use
05/04/10
The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration
before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range.
Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet
thermistor are located in the plenum chamber. The plotted results for dry temperature are the average values of all five dry
The equipment was then plac ed in the ch amber and t he temperature was lowered from ambient to -25°C for a pe riod of 16
hours. An insulation resistance test was also performed. (ref TL1316.15)
Results
A performance test was performed on the equipment during the last hour at the test temperture and after the test, the equipment
continued to work with no degradation in performance.
Refer to the Appendices for test result graphs.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1°C
Environmental Test File No. TL1316.04
08/Jun/09
Humidity Test 1 – Cyclic (IEC945 Section 8.3, IEC60068-2-30)
Specification
The equipment is to be placed in a test chamber and the te mperature raised to 55°C ± 2°C at a hum idity of 95% ± 5% for a
period of 12 hours with the equipment operational. The temperature is then reduced to 20°C ± 5°C for not less than 6 hours.
This cycle shall then be repeated but with the equipment non-operational. No degradation of the equipment performance shall
be observed.
Test Procedure
Test Equipment
Calibration date
Montford environmental test chamber
Signallogger PC & Thermistors
RS Electronics Resistance box
Calibrated on use
Calibrated on use
05/04/10
The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration
before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range.
Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet
thermistor are located in the plenum chamber. The plotted results for dry temperature are the average values of all five dry
Page 6 of 112
Test Report TL1316
The equipment was placed in the chamber and the temperature raised from ambient to 55°C ± 2°C with a hum idity of 95% ±
5% for a period of 12 hours. Th e operation of t he equip ment w as ch ecked du ring th e first t wo ho urs of t he test. Th e
temperature was then lowered to a temperature of 20°C ± 5°C with the same humidity for a period of 6 hours. This cycle was
repeated with the equipment being switched off for the second cycle and then a performance test was performed during the last
two hours of the high temperature period and at the end of the second cool period after normal humidity was achi eved. An
insulation resistance test was also performed. (ref TL1316.15)
Results
A performance t est was performed on t he eq uipment d uring t he first h our, a fter 50 hours, during l ast h our at t he t est
temperture and humidity and after the test, the equipment continued to work with no degradation in performance.
Refer to the Appendices for test result graphs.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1°C
Environmental Test File No. TL1316.05
23/Jun/09
High voltage
Specification
The equipment shall be tested using a 596V 50Hz high voltage source between L1/L2 & Earth for 1 minute. There shall be no
insulation b reakdown during t he t est and no degradation of t he e quipment perf ormance shal l be obseved a fter t he t est i s
completed.
Test Procedure
Test Equipment
Calibration date
Fosters Transformers Ltd. High Voltage source
05/05/10
The L1/L2 were connected to the high voltage probes and the earth pin for a period of one minute.
An insulation resistance test was also performed. (ref TL1316.15)
Results
No b reakdown i n i nsulation occurred during t he t est an d no de gradation of t he e quipment per formance was observed aft er
these tests.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1%
Environmental Test File No. TL1316.06
29/Jun/09
Vibration test 1 (IEC945 Section 8.7.2, IEC60068-2-6)
Specification
The equipment is to be mounted on a vibration table and tested in three mutually perpendicular axes. In each axis a sweep is to
be carried out from 2-13.2Hz at ± 1mm and from 13.2-100Hz at ±0.7g. The equipment is then vibrated for a period of 2 hours
at each resonant frequency with an amplification factor of 2 or above, and or 30Hz if no resonance is found. No degradation of
the equipment performance shall be observed.
Test Procedure
Test Equipment
Calibration date
Dactron Vibration controller
LDS CA4 Charge Amplifier
10/01/10
01/10/09
Page 7 of 112
Test Report TL1316
D.J
DPA4 and DPA8 Amplifier
Birchall Accelerometers
D.J Birchall Accelerometers
LDS Vertical and Horizontal vibration table
Not required
01/10/09
01/10/09
Not required
The fi rst rack of e quipment was b olted t o the vert ical vi bration t able. The f requency was t hen swe pt acro ss t he r equired
frequencies at a sweep rate of less than 0.5 octave per minute. An endurance test was performed at any resonance found and at
30Hz for two hours with the performance being tested during the test with an acceleration of 0.7 for two hours.
The equipment was th en mounted horizontally with the vibration acting side to side on the unit, and the frequency swept. An
endurance test was performed at any resonance found and at 30Hz for two hours with the performance being tested during the
test with an acceleration of 0.7 for two hours.
The e quipment was t hen r otated t hrough 90° a nd t he sw eep t est repeat ed in the new axis. Agai n a n endura nce t est was
performed at any re sonance f ound a nd at 3 0Hz for t wo h ours wi th t he pe rformance bei ng t ested during t he t est wi th an
acceleration of 0.7 for two hours.
The tests were repeated but for each of the units on the second rack
Refer to the Appendices for the photos which show the locations of the accelerometers. The accelerometers were placed on
each unit in turn wh ere we thought that it was the m ost represenative of the whole of the equipment under test. This was done
in all three planes.
Results
A performance test was performed on t he equipment during the test and after the test, the equipment continued to work with
no degradation in performance.
Refer to the Appendices for test result graphs and table of the dwell frequencies tested. Note that the line marked “control(f)”
is the acceleration on the vibration table (Black line) and t he line marked “input2(f)” (Blue line) is t he measured acceleration
on the equipment under test.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 2.5%
Environmental Test File No. TL1316.07
11/Jun/09
Power supply Variation (IEC945 Section 10.7.1 and 10.7.2, IEC60092-504)
Specification
The equ ipment will b e teste d with a voltage v ariation of +3 0% and -25 % of th e nominal su pply v oltage. Th e tests will b e
repeated during, and after dry heat, high humidity and l ow temperature tests and no d egradation of equipment performance
shall be observed.
For IEC945 Section 7.2 Excessive conditions. The standard states, conditions exceed the extreme test conditions in which the
EUT is required to operate, with or without performance degradation as indicated in the equipment standard. Excessive current
is defined as greater than normal working current.
At the start of the power supply variation test the equipment is operating at its standard voltage and current. When we reduce
the voltage then the current flowing into the power supply increases so giving a current more than the normal working current.
Excessive voltage is greater than that specified in IEC945 Section 7.1.
When we do the power supply variation test we test +/-20% which exceeds the values specified in IEC945 Section 7.1.
We also do a high voltage check at 596 V a.c on the power supply. To test Excessive Voltage we used the current limit on the
variable power supplies and set them to 200mA. When the voltage was increased past the +30% the current limiter cut the
voltage (same effect as a fuse). Once the voltage was returned to normal levels the units operated correctly.
Power supply misconnections are also regarded as excessive conditions; where appropriate the EUT shall be subjected to and
input from a power supply of reversed polarity.
Page 8 of 112
Test Report TL1316
Test Procedure
Test Equipment
Calibration date
Derritron Magnus SPS1000 power supply
Iso Tech IDM 93 DMM
Not Required
05/04/10
Results
The s upply of the equipm ent was attach ed to t he power s upply w ith th e op eration of th e eq uipment b eing monitored
continually. The units all have different power supply requirments and are classified as 12, 24 and 48 V DC and the test levels
were calculated on this range for each module. The output of the power supply was checked with the IDM93 Multimeter.
The following transient tests were then carried out for more than 15 minutes at each setting.
12 V Input
Test
Number
1
2
Voltage
Deviation
+30%
-20%
Test
Voltage
15.6
9.6
Voltage
Deviation
+30%
-20%
Test
Voltage
32
19.2
Voltage
Deviation
+30%
-20%
Test
Voltage
62.5
38.4
24 V Input
Test
Number
1
2
48 V Input
Test
Number
1
2
The operation o f t he eq uipment w as ch ecked th roughout th e test. The tests w ere repeated during, and af ter dry h eat (r ef
TL1316.02), high humidity (ref TL1316.04) and low temperature (Ref 1326.03) tests.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1%
Environmental Test File No. TL1316.08
11/Jun/09
Power supply failure (IEC945 Section 10.8.2, IEC60092-504)
Specification
The equipment shall be expos ed to at least three interruptions to the power supp ly of at least 6 0 seconds within five minutes.
Equipment swiched on and checked to be operational. Power turned off for 60 seconds. Equipment powered up and re-tested
for 90 seconds to ensure that it is fully operational – this test shall be repeated two more times with no failures being detected
at any time.
Test Procedure
Page 9 of 112
Test Report TL1316
The equipm ent was connect ed to t he su pply and t he s witched on. T he o peration was chec ked bef ore t he power t o t he
equipment only was turned off for 60 seconds. The equipment was then powered up and re-tested for 90 seconds to ensure full
operation after th e power failure. This test was th en repeated two more times with no failures being detected after the p ower
was restored.
Results
A performance test was pe rformed on t he equipment after the test, the equipment continued to work with no degradation in
performance.
Environmental Test File No. TL1316.09
12/Jun/09
Immunity to conducted low frequency interference (IEC945 Section 10.2.2, IEC60533)
Specification
The e quipment shall be s ubjected to a si gnal s wept to t he 200th harmonic wi th t est voltage of 1 0% o f t he nominal s upply
voltage to the 15th harmonic reducing to 1% at the 100 th an d maintained to th e 200th harmonic with a minimum 3 V (r.m.s)
maximum 2 W.
Test Procedure
Test Equipment
Calibration date
Marconi Instruments 2123 Signal Generator
Quad 405 Amplifier
Iso Tech IDM 93 Frequency counter
Fluke 87 RMS DMM
Not required
Not required
05/04/10
24/09/09
The input of the equipment was connected to the power supply via coupling clamp. The frequency generator was connected to
the input of the amplifier and to the frequency counter. The output voltage was monitored using the Fluke 87 multimeter. The
frequency was swept from 50Hz to 10KHz while maintaining the amplitude at the required levels.
Results
A performance test was performed on t he equipment during and after the test the test, the equipment continued to work with
no degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : ± 1.5%
Environmental Test File No. TL1316.10
12/Jun/09
Conducted RF (IEC945 Section 10.3.2, IEC61000-4-6)
Specification
The equipment shall be o perational and the test applied to both power and signal lines. The frequency shall be swe pt from
10kHz to 80MHz amplitude modulated at 1kHz ±10% and 400Hz ±10% to a modulated depth of 30% a nd 80%, amplitude
maintained at 3V rms.
The equipment shall also be subjected to the same series of tests at the following spot frequencies: 2, 3, 4, 6.2, 8.2, 12.6, 16.5,
18.8, 22 and 25MHz at 10V rms with 80% ±10% modulation at 400Hz ±10%.
Test Procedure
Test Equipment
Calibration date
Marconi 2017 RF signal generator
ENI 325LA RF Amplifier
Racal-Dana 9302 RF millivoltmeter
22/08/09
Not required
14/08/09
Page 10 of 112
Test Report TL1316
The in put of th e equ ipment was con nected to th e p ower supply v ia an i mpedance stab ilisation n etwork with th e am plifier
output capacitively coupled to the supply. The fre quency generat or wa s connected to the input of the am plifier and the
frequency swept from 10KHz to 80MHz modulated to 30% and 80% at 1KHz and at 400 Hz while maintaining the amplitude
at 3V RMS as shown by the RF millivoltmeter.
The equipment was also subjected to the same test at spot frequencies 2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22 and 25 MHz at 10 V
rms. with modulation 80 % at 400 Hz in accordance with IEC945 for bridge and deck equipment.
Results
A performance test was performed on t he equipment during and after the test the test, the equipment continued to work with
no degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : ±2.5dB
Environmental Test File No. TL1316.11
12/Jun/09
Electromagnetic Field (IEC945 Section 10.4.2, IEC61000-4-3)
Specification
The equipment shall be operational. The equipment shall be exposed to an electric field of 10V/m swept from 30kHz-2GHz
amplitude modulated at 1kHz ±10% and 400Hz ±10% to a modulation depth of 30% and 80% ±10%
Test Procedure
Fi
Test Equipment
Calibration date
Schaffner GTEM Cell
eld Probe
HP Frequency Generator
Amplifier Research 25W1000 25W RF Amplifier
ENI 325LA RF Amplifier
Amplifier Research 30W 4.2GHz RF Amplifier
On Test
06/08/09
06/08/09
Not required
Not required
Not required
Before any e quipment is placed insi de the GTEM cell it is re quired that the RF levels within the cell are verified across the
frequency range. This is done under software control, a s weep is made across the frequency range using the probe to veryfy
the correct level. This sweep pr oduces the calibration for th e cell at above 10 Volts/Meter. This calibration is th en used to
perform the sweeps and a lev el check is mad e across the ran ge to ensure that the level never falls b elow 10 V/M. If th is is
correct then the equipment can be put inside the cell and the sweeps done as below.
The equipment was placed in the GTEM ce ll, the frequency generat or was set to sweep from 30KHz to 128M Hz amplitude
modulated to a depth of 30% at 1KHz and the applied field was raised to 10V/m using the methods as mentioned above. The
signal was th en swep t wh ilst th e field stren gth was m aintained at 10V/ m. The equipment was turned si de onto t he si gnal
orientation and the test repeated to ensure that position did not affect the immunity of the unit. The equipment was then turned
to ensure that the incide nt field was test ed in all three axes. The am plifier was ch anged from the ENI325LA amplifier to the
Amplifier Research amplifier at 80MHz and swept to 1000MHz using the same method to calibrate the cell to ensure that the
level inside the cell is correc t.. The equipment was again placed in the GTEM cell, t he frequency generator was set to s weep
from 80 MHz to 1000 MHz amplitude modulated to a depth of 30% at 1KHz and the applied field was raised to 10V/m using
the methods as mentioned above. The equipment was turned side onto the signal orientation and the test repeated to ensure that
position did not affect th e immunity of the unit. The equipment was then turned to ensure that the incident field was tested in
all three axes.
The amplifier was cha nged to the sec ond Amplifier Research amplifier at 9 00 MHz and swept to 2000MHz using the same
method t o cal ibrate t he cell t o en sure t hat t he l evel i nside t he cel l i s cor rect. T he eq uipment was t hen pl aced i n t he cel l as
before and the 3 axes tested.
These t ests were repeat ed usi ng 80% am plitude m odulation t o com ply with al l requi rements and ag ain wi th a modulation
frequency of 400 Hz.
Results
Page 11 of 112
Test Report TL1316
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : ± 1.7dB
Environmental Test File No. TL1316.12
16/Jun/09
Radiated Interference (IEC945 Section 9.3.2, IEC60533)
Specification
The equipment shall not radiate RF levels greater than.
Test Procedure
GTEM
Limits (dBµV/m)
80 – 50
50 – 34
54
24
54
Frequency
10kHz - 300kHz
300kHz - 30MHz
30MHz - 156MHz
156MHz - 165MHz
165MHz - 2GHz
Bandwidth
9KHz
9KHz
120KHz
9KHz
120KHz
Test Equipment
Calibration date
Anritsu 2602 Spectrum Analyser
Cell
Calibrated on use
Not required
The equipment was placed in the GTEM Cell in 2 racks, rack 1 was the EDS72810G and its listed modules and rack 2 was the
remaining stand alone modules which gave the worst case emissions.
The equipment was t hen switched on and the levels taken over the full range a nd then over the reduced range with both the
equipment being rotated through three axes.
At no frequency or positions did the level of emitted radiation exceed those levels specified in the requirements.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : ± 2.1dB
Environmental Test File No. TL1316.13
17/Jun/09
Conducted emissions (IEC945 Section 9.2.2, IEC60533)
Specification
The equipment shall not radiate conducted levels greater than
Frequency
10kHz - 150kHz
150kHz - 350kHz
350kHz - 30MHz
Limits (dBµV/m)
96 – 50
60 – 50
50
Bandwidth
200Hz
9KHz
9KHz
Test Procedure
Calibration date
Test Equipment
Page 12 of 112
Test Report TL1316
Anritsu 2602 Spectrum Analyser
RayProof Faraday Room
Calibrated on use
Not required
The equi pment was placed i n the Fa raday room with the coupling net work. A background level was the n take n with t he
equipment switched off.
The equipment was then switched on and the levels taken from each unit over the full range and then over the reduced range.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
At no frequency or positions did the level of conducted radiation exceed those levels specified in the requirements.
Uncertainty of Measurement
Total uncertainty of measurement for this test : ± 2.3dB
Environmental Test File No. TL1316.14
17/Jun/09
Electrostatic discharge (IEC945 Section 10.9.2, IEC61000-4-2)
Specification
a) Air discharge:
b) Contact discharge:
The equipment shall be s ubjected to an electrostatic discharge of 8kV applied to any exposed part
of the system which is accessible to the operator i n normal use. This will be repeated 10 times, in a
number of different places, for both positive and negative polarity.
The ab ove process will b e rep eated for co ntact d ischarge at a lev el o f 6kV, fo r both positive and
negative polarity.
At least 10 single contact discharges per polarity will be applied to positions on the ground plane at
a distance away from the EUT. In addition at least 10 single discharges per polarity will be applied
to a coupling plane of dimensions 0.5 x 0.5 m placed parallel to and at lease 0.1m away form the
ETU, this will be done so that all axes are tested.
Test Procedure
Test Equipment
Calibration date
Schaffner Best EMC Compact test system
24/02/10
The equipment was placed on an ins ulator placed on an a luminium earth plane . The gun was set to 8KV and disc harged 10
times with one second between each discharge, the charge was applied to any exposed metal of the equipment in a number of
different places positive and negative polarity for air and then repeated at 6 KV for contact discharge.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 1%
Environmental Test File No. TL1316.15
23/Jun/09
Insulation resistance test. (IEC945 Section 8.3 & 8.4, IEC60092-504)
Specification
The equipment shall be tested before and after the humidity, high voltage and low temperature tests. The i nsulation between
positive & negative to earth shall be tested for both polarities and shall not be less than 10 Mohms
Page 13 of 112
Test Report TL1316
Test Procedure
Test Equipment
Calibration date
Megger insulation tested
23/09/09
Before and after the low temperature, the high voltage and humidity tests the insulation resistance of the input of the unit was
tested. Supply to earth was tested in both polarities.
Results
A performance test was pe rformed on t he equipment after the test, the equipment continued to work with no degradation in
performance.
At no time did the measured insulation resistance drop below 10 Megohms.
See appendix for readings taken
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 0.05 + 1 Digit
Environmental Test File No. TL1316.16
16/Jun/09
Burst/Fast Transients. (IEC945 Section 10.5.2, IEC61000-4-4)
Specification
With the equipment operational a fast transient pulse will be applied for a period of 10 minutes, as follows:
Power supply line:
Signal and control lines:
Pulse rise time:
Pulse width: 50
Application:
2kV Line/Earth at 2.5kHz & 5KHz
1kV common mode at 5kHz
5nS (10% and 90%)
nS (50% value)
15mS burst every 300mS
Test Procedure
Test Equipment
Calibration date
Schaffner Best EMC Compact test system
24/02/10
The system was connected to the mainframe unit with the Schaffner Best EMC Compact test system.
With the equipment operational a fast transient pulse was applied for a period of 10 minutes, as follows:
Power supply line:
Signal and control lines:
Pulse rise time:
Pulse width: 50
Application:
2kV Port/Earth at 2.5kHz & 5KHz
1kV common mode at 5kHz
5nS (10% and 90%)
nS (50% value)
15mS burst every 300mS
This level of interference was maintained for ten minutes on each polarity and conductor. The signal cables were also checked
at 1KV at 5KHz.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Page 14 of 112
Test Report TL1316
Total uncertainty of measurement for this test : Frequency ± 1%
Burst Duration & Period ± 1%
Environmental Test File No. TL1316.17
16/Jun/09
Surge Immunity (IEC945 Section 10.6.2, IEC61000-4-5)
Specification
With t he eq uipment operat ional a 0. 5, 1 & 2k V com mon m ode pul se shal l be appl ied t o l ine/earth fo r a minimum of 10
minutes at a r ate of one p ulse/minute. With t he equi pment ope rational a 0.5 & 1 kV di fferential pul se shal l be appl ied t o
line/line for a minimum of 10 minutes at a rate of one pulse/minute. These tests shall be repeated for both polarities.
Pulse rise time:
Pulse width: 50
1.2uS (10% and 90%)
uS (50% value)
Test Procedure
Test Equipment
Calibration date
Schaffner Best EMC Compact test system
24/02/10
The System was connecte d to the Sc haffner Best EMC Co mpact test sy stem. The interference amplitude was set to 0 .5, 1 &
2KV and common mode pulses were applied to line/earth for 10 minutes at a rat e of one pulse/minute. With the equipment
operational 0 .5 & 1kV d ifferential p ulse were app lied to line/line for 10 minutes at a rate o f one pu lse/minute. These tests
were repeated for both polarities.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : Peak Voltage ± 1.4%
Rise Time ± 1.5%
Pulse Width ± 2.2%
Environmental Test File No. TL1316.18
22/Jun/09
Static inclination test. (IEC60092-504)
Specification
The equipment shall be inclined at an angl e of at least 2 2.5° either side of horizontal at two mutually perpendicular axes for a
period of at least 15 minutes.
Test Procedure
Test Equipment
Calibration date
Inclination test table
Not required
The equipment was bo lted to the inclination table and the operation checked before the test started. The equipment was then
tilted to an ang le of 45° from h orizontal an d th e operation ch ecked over a period of fifteen m inutes du ring which tim e n o
failures were detected. The table was then tilted to 45° on the other side of horizontal where it remained for fifteen minutes.
The equipment was then rotated through 90 degrees and both of the tests repeated for fifteen minutes in this axis.
Results
Page 15 of 112
Test Report TL1316
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 2°
Environmental Test File No. TL1316.19
22/Jun/09
Dynamic inclination test. (IEC60092-504)
Specification
The equipment shall be rolled to an angle of at least 22.5° either side of horizontal with a period of 10 seconds for a period of
at least fifteen minutes in two mutually perpendicular axes.
Test Procedure
Test Equipment
Calibration date
Inclination test table
Not required
The equipment was bolted to the inclination table and the operation checked before the test started. The table wa s then started
to r oll t hrough 90 ° wi th a period o f ap proximately 10 sec onds a nd t he operation chec ked over a period of fifteen minutes
during which time no failures were detected.
The equipment was then rotated through 90 degrees and the tests repeated for fifteen minutes in this axis.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 2°
Environmental Test File No. TL1316.20
22/Jun/09
Acoustic noise (IEC945 11.1.2)
Specification
The equipment shall not exceed a peak level of 60 dB (A) at a distance of 1 M from any part of the equipment
Test Procedure
Test Equipment
Calibration date
DAWE sound level meter
DAWE acoustical calibrator
Calibrated on use
12/04/09
The sound meter was calibrated using the acoustical calibrator. (Compliant with IEC651)
The eq uipment was set up i n q uiet room with every thing swi tched of f and a back ground m eter readi ng was t aken. The
equipment was then powered up and a reading taken 1M from the equipment. Another background reading was taken when the
equipment was switched off.
Results
Page 16 of 112
Test Report TL1316
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
The levels measured were well below the fail point.
Before
32.0 dB (A)
32.5 dB (A)
Reading Rack 1
Reading Rack 2
Equipment on
32.1 dB (A)
32.7 dB (A)
After
32.0 dB (A)
32.4dB (A)
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 0.6dB
Environmental Test File No. TL1316.21
22/Jun/09
Compass Safe Distance Test (IEC945 11.2.2)
Specification
The equipment shall be tested to determine the Compass Safe Distance. This test will be repeated with the equipment
operational and non operational and rotated to find the worst case plane.
The location of the lab is Latitude 54.42, longitude -1.36 which from the British Geological survey website
(www.geomag.bgs.ac.uk) gives a horizontal component of magnetic flux of 17785nT for June 2009.
From this we calculate 0.3 degrees for the standard compass and 1.0 degrees for the steering, standby and emergency compass.
Frequency
Un-powered, as
received
After Normalizing
Powered (Energised)
Worst case result
1 Degree Deflection
0.3 Degree Deflection
A1mm
A2mm
B1mm
C1 mm
B2mm
C2 mm
Largest Value of A1, B1
or C1
Largest Value of A2,
B2 or C2
Test Procedure
Calibration date
Test Equipment
Fl
uxgate magnetometer
02/
04/09
The test equipment was set up and any background levels zeroed out. The equipment under test was then brought in to the area
and tested in the position and attitude relative to the magnetometer that caused the most error to be seen.
Results
A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o
degradation in performance.
The distances measured were as follows and is the worst case readings for all the module.
Frequency
Un-powered, as
received
After Normalizing
Powered (Energised)
Worst case result
1 Degree Deflection
0.3 Degree Deflection
500mm
600mm
500mm
600mm
600mm
700mm
600mm
700mm
Page 17 of 112
Test Report TL1316
All the distances have been rounded up to the nearest 100mm in order to allow for the maximum deviation, which might be
caused by the most magnetic sample of all units manufactured.
Uncertainty of Measurement
Total uncertainty of measurement for this test : < ± 10mm
Environmental Test File No. TL1316.110
24/June/09
Shock Test
Specification
The equipment is to be mounted on a vibration table and tested in three mutually perpendicular axes with a shock test of 15g
11mS applied for 20 pulses.
Test Procedure
D.J
Test Equipment
Calibration date
Dactron Vibration controller
LDS CA4 Charge Amplifier
DPA4 and DPA8 Amplifier
Birchall Accelerometers
D.J Birchall Accelerometers
LDS Vertical and Horizontal vibration table
10/01/10
01/10/09
Not required
01/10/09
01/10/09
Not required
The equipment was bolted to the vertical vibration table and a shock of 15g 11mS, 20 pulses were applied, test equipment was
then checked and no degradation of the equipment performance was observed during these tests.
The equipment was then mounted horizontally with the shock acting front-to-back on the unit. The shock of 15g 11mS, 20
pulses were applied, test equipment was then checked and no degradation of the equipment performance was observed during
these tests.
The equipment was then mounted horizontally with the shock acting side to side on the unit. The shock of 15g 11mS, 20
pulses were applied, test equipment was then checked.
Results
No degradation of the equipment performance was observed during these tests.
Page 18 of 112
Test Report TL1316
APPENDICES
Page 19 of 112
Test Report TL1316
Environmental Test Timetable
Customer -
Moxa
-
File No TL1316
~~
a'K~~~~
r 41" I~)
Equipment- Managed and Unmanaged Switches and Video Server
I
Test
01
Performance
02
Dry Heat (IEC945
section 8.2.2.2,
IEC60068-2-2)
3
Low temperature
(IEC945 section 8.4.2.3,
IEC60068-2-1)
V-
Humidity Test I ­
Cyclic (IEC945 section
8.3,IEC60068-2-30)
High voltage
,~ fl -"'-'..4. ~d \
Complete
Iw. .
Procedure
Starts
Equipment is tested The conformance to drawings is checked
and a fuctional performance test is demonstrated to society
surveyors present.
-The equipment is to be installed in a climatic chamber and
the temperature raised to 70°C ±2°C for a period of not less
than 16 hours. The equipment will be operational during the
test and no degradation of the equipment shall be seen.
The equipment shall be placed in a climatic chamber and the
temperature reduced to -25 °C ±2°C for a period of not less
than 2 hours.
02/06/09
Q/;~/., I ~ :"
02/06/09
U!Oq •ol.. oz.
03/06/09
if/bid,
Two cycles of 55°C for 12 hours & 6 hours at 20°C at 95% ±
5%RH
04/06/09
£~-
fI
5
6
6
Vibration test J
(IEC945 section 8.7.2,
IEC60068-2-6)
- Side to side
6
- Front to back
7
Power supply Variation
(IEC945 section 7.1 &
7.2,IEC60092-504)
-­
8
Power supply failure
(IEC945 section 10.8.2,
IEC60092-504 )
9
Immunity to conducted
low frequency
interference (IEC945
section 10.2.2,
IEC60533)
Conducted RF (IEC945
section 10.3.2,
IEC61 000-4-6)
10
-(jD~
'h"
~
.pl\:
1
'b"""
The equipment shall be tested using a 1500V 50Hz high
voltage source between LivelNuetral & Earth for I minute.
There should be no insulation breakdown during the test and
no degradation of the equipment performance after the test is
completed.
The equipment is to be mounted on a vibration table and
""ed
in there morn,lIy p'"P~di,"I" "'~ In I~
sweep is to be carried out from 2-13.2Hz at ±lmm an
13.2-100Hz at ±0.7g. The units then vibrated for a p
0
hours at each resonant frequency with an amplificatio
ct4
of 2 or above, or 30Hz if no resonance is foun
dezradation of the equipment performance shall be seen.
Equipment shall be tested as the vertical vibration test.
18/06/09
-
haa ~1
08/06/09
t~ !l~ ~dof
~
A
L~
7.l~
v'Wlt.iJj~"
/0
II
Test voltage (r.m.s.): 10% of supply to 15th harmonic
reducing to I % at I OOth harmonic and maintain this level to
the 200th harmonic, minimum 3 V (r.m.s.), maximum 2 W
11 /06/09
II/ G
The equipment shall be operational and the test applied
to both power and signal lines. The frequency shall be
swept from 10kHz to 80MHz amplitude modulated at
1kHz +/-10% and 400Hz +/-10% to a modulated depth
of30% and 80%, amplitude maintained at 3V nns.
The equipment shall also be subjected to the same
series of tests at the following spot frequencies: 2,3,4,
6 .2, 8.2, 12.6, 16.5, 18.8,22 and 25MHz at 10V rms
with 80% +/-10% modulation at 400Hz +/-10% .
11/06/09
'zlb
~~~
~~ ~
., ­' :~J
.AL l!
y~
f ;1&d1~
r:-b/ (:./' ,4
1/6
~
.~/~ < J:P'J
11" ",.i ,~~
/?J.
11 /06/09
Page 20 of 112
Test Report TL1316
(fli9~f)
IBUREAUOF~
09/06/09\
Equipment shall be tested as the vertical vibration test.
10106/09
The unit will be tested with a voltage variation of + I 0% and - 11/06/09
15% of the nominal supply voltage, and a frequency variation
of ±5%. Transient conditions of ±20% voltage and ±15%
frequency shall also be tested. Equipment will be tested a 230
& 110 Volts if selectable. Tests will be performed before,
during and after dry heat and low temperature tests with no
degradation of perform ace seen
The unit is to be exposed to at least three interruptions to the
supply of at least 60 seconds within five minutes. Unit
swiched on and checked to be operational. Power turned off
for 60 seconds. System powered up and retested for 90
seconds to ensure that it is full y operational - this test
repeated two more times with no failures being detected
2'>/{'
~
,,~ ~'~
-.......:.::.
II
Electromagnetic Field
(IEC945 section 10.4.2,
IEC61 000-4-3)
The equipment shall be operational. The equipment shall be
exposed to an electric field of IOV/m swept from 30kHz­
2GHz amplitude modulated at 1kHz +/-10% and 400Hz +/­
10% to a modulation depth of 30% and SO% +/-10%
12/06/09
12 Ie
12
Radiated Interference
(IEC945 section 9.3.2,
IEC60533)
The equipment shall not radiate RF levels greater than
Frequency Range
Limits
10KHz- 300 KHz
SO-50dB uV/m
300KHz-30MHz
52-34dB uV/m
30MHz-156MHz
54dB uV/m
156MHz-165Mhz
24dB uV/m
165MHz-2GHz
54dB uV/m
The equipment shall not radiate conducted levels greater than
96-50 dB uV in the range 10 kHz-ISO kHz 60-50 dB uV in
the range ISO kHz-350 kHz or 50 dB uV in the range 350
kHz-30MhZ
15/06/09
I ~/'
a) Air discharge: The equipment shall be subjected to an
electrostatic discharge of SkV applied to any exposed metal
part of the system. This will be repeated 10 times, in a
number of different places, for both positive and negative
polarity.
b) Contact discharge: The above process will be repeated for
contact discharge at a level of 6kV, for both positive and
negative polarity.
The equipment shall be tested before and after the humidity
and low temperature tests. The insulation between live &
neutral to earth shall be tested for both polarities and shall not
be less than 100Mohms
With the equipment operational a fast transient pulse will be
applied for a period of 10 minutes, as follows:
Power supply line 2kV differential at 2.5kHz
Signal and control lines: IkV common mode at 5kHz
Pulse rise time: 5nS (10% and 90%)
Pulse width: SOnS (50% value)
Application: ISmS burst every 300mS
With the equipment operational a 0.5, 1.0 & 2kV common
mode pulse shall be applied to line/earth for a minimum of 10
minutes at a rate of one pulse/minute. With the equipment
operational a 0.5 & 1kV differential pulse shall be applied to
line/line for a minimum of 10 minutes at a rate of one
pulse/minute.
These tests shall be repeated for both
polarities.
The equipment shall be inclined at an angle of at least 22.5°
either side of horizontal at two mutually perpendicular axes
for a period of at least 15 minutes.
16/06/09
13
14
,....
15
16
Conducted emissions
(IEC945 section 9.2.2,
IEC60533)
Electrostatic Discharge
Electrostatic discharge
(IEC945 section 10.9.2,
IEC61 000-4-2)
Insulation resistance
test. (IEC945 section
S.3 & S.4, IEC60092­
504)
BurstlFast Transients.
(IEC945 section 10.5.2,
IEC61 000-4-4 )
17
Surge Immunity
(IEC945 section 10.6.2,
IEC61000-4-5)
IS
Static inclination test.
(IEC60092-504)
19
Dynamic inclination
test. (IEC60092-504)
20
21
-
151061°1~
......./1
I ~/V"
~,;i(./
" ." ,.,u, ~
O'7-I,7.-/o'Y
17/ (/oq
02/06/09
'2 /{,
1-')/6
~' \~
~Ci:::::S"'"
'1...)' )/.11 »9
I(./e
22/&
The equipment shall be rolled to an angle of at least 22.5°
either side of horizontal with a period of 10 seconds for a
period of at least fifteen minutes in two mutually
perpendicular axes.
17/06/09
2l !~
Acoustic noise (IEC945
11.1.2)
The equipment shall not exceed a peak level of 60 dB (A) at
a distance of I M from any part of the equipment
18/06/09
ZZ I(
Compass safe Distance
IEC60945 section
11.2.2
The equipment shall be tested to determine the compass safe
distance. This will be repeated with the equipment
operational and non-operational
18/06/09
21./(,
I~
~
/1
<>.".
'-'
Claas~
-
tl
I~ \~
!,
~!.
c,~~
17/06/09
~
h~€'
~W
KA
16/06/09
1(./("
Page 21 of 112
Test Report TL1316
: :-.ltJK~":
_J,o .
16/06/09
I
,,-v.'J~
~.
~---A~ ~
wI~
~
Dry Heat
80
60
70
50
60
40
40
30
30
20
20
10
10
0
0
0
2
4
6
8
10
12
Time in Hours
Page 22 of 112
Test Report TL1316
14
16
18
%RH
Temperature C
50
Temperature
Humidity
Low Temperature
30
20
0
-10
-20
-30
Time in hours
Page 23 of 112
Test Report TL1316
20
19
19
18
18
17
16
16
15
15
14
13
13
12
12
11
10
10
9
9
8
7
7
6
6
5
4
4
3
3
2
1
1
0
Temperature
0
Temperature C
10
Humidity
60
100
95
90
85
50
80
75
70
65
60
55
30
50
45
40
35
20
30
25
20
10
15
10
5
0
0
0
2
4
6
8
11
13
15
17
19
22
24
26
28
Time in Hours
Page 24 of 112
Test Report TL1316
30
33
35
37
39
41
%RH
Temperature C
40
Temperature
Humidity
Vertical
1
Side to Side
Front to Back
EDS-72810G
IM-4TX
IM-4MSC
IM-4SSC
IM-2MSC/2TX
IM-2MST/2TX
IM-2SSC/2TX
30
30, 33, 37
30, 40, 49
IM-2GTX
IM-2GSFP
SFP-1GLXLC
SFP-1G10ALC
SFP-1G10BLC
2
EDS-G509
12, 14, 16, 30
28, 30
30, 96
3
EDS-408A-3M-SC
13, 30
30, 38
20, 27, 30
4
EDS-408A-2M1S-SC
18, 30
30, 39, 55
27, 30
5
EDS-P510
19, 30
30, 31, 33, 40
23, 28, 30, 96
6
EDS-305-M12
30
30
30
7
8
EDS-208A-MM-SC
EDS-205A
19, 30
30, 36
30, 38
22, 27, 30
28, 30, 54, 82
30, 51
9
EDS-P308-MM-SC
14, 30
28, 30, 53, 82
28, 30, 57
10
SPL-24
30, 44
30
30
11
12
EDS-G308
EDS-G308-2SFP
13, 30
18, 30
30, 41, 56
30, 39, 56
23, 28, 30
28, 30, 52
13
EDS-G205
21, 30,
22, 30
22, 30
14
VPort 351-M-SC
17, 30
30, 40, 55
22, 28, 30, 56
Page 25 of 112
Test Report TL1316
Locations of Accelerometers
Vertical EDS-305-M12
Vertical EDS- 205A
Vertical 408A-3M-SC
Vertical Vport 351-M-SC
Vertical
EDS-208A-MM-SC
Vertical EDS-G308-2SFP
Page 26 of 112
Test Report TL1316
Vertical EDS-P510
Vertical
EDS-G509
Vertical EDS-G308
Vertical
EDS-P308-MM-SC
Vertical EDS-408A-2M1S-SC
Vertical 728
Page 27 of 112
Test Report TL1316
Vertical EDS-G205
Vertical
SPL-24
Page 28 of 112
Test Report TL1316
Locations of Accelerometers
Front to Back EDS 208-MM-SC
Front to Back EDS 308-2SFP
Front to Back EDS-205A
Front to Back EDS 408A-2M1S-SC
Front to Back EDS-P510
Front to Back Vport 351-M-SC
Page 29 of 112
Test Report TL1316
Front to Back EDS-305-M12
Front to Back SPL-24
Front to Back EDS-P308-MM-SC
Front to Back EDS 728 (with extra Modules)
Front To Back EDS-G205
Front to Back EDS-408A-3M-SC
Page 30 of 112
Test Report TL1316
Front to Back EDS-G308
Front to Back EDS-G509
Page 31 of 112
Test Report TL1316
Locations of Accelerometers
Side to Side EDS-G408-A2M1S-SC
Side to Side EDS-408A-3M-SC
Side to Side EDS-208AMM-SC
Side to Side EDS-G308
Side to Side G308-2SFP
Side to Side EDS-205A
Page 32 of 112
Test Report TL1316
Side To Side VPort-M-SC
Side To Side G509
Side to Side 728
Side To Side P510
Side To Side 305-M12
Side to Side SPL-24
Page 33 of 112
Test Report TL1316
Side to Side EDS-G205
Side to Side EDS-P308-MM-SC
Page 34 of 112
Test Report TL1316
Front to Back Vibration – MOXA EDS-205A
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702012 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 35 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-408A-2M1S-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.701918 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 36 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-408A-3M-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702102 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 37 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-728
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.701190 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 38 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-305-M12
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.972771 Hz
Control Peak:
Demand Peak:
0.702959 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 08:06:32 AM, Tuesday, June 30, 2009
8230
00:00:00
Sweep Type:
Sweep Rate:
Report created at 08:06:33 AM, Tuesday, June 30, 2009
Page 39 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-G308
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.948158 Hz
Control Peak:
Demand Peak:
0.700922 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 03:18:08 PM, Monday, June 29, 2009
8228
00:00:00
Sweep Type:
Sweep Rate:
Report created at 03:18:09 PM, Monday, June 29, 2009
Page 40 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-G509
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.703247 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 41 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA P510
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.700768 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 42 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA VPORT-351-M-SC
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.935852 Hz
Control Peak:
Demand Peak:
0.701236 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 43 of 112
Test Report TL1316
8227
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA – EDS-G308-2SFP
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.700341 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 02:56:56 PM, Monday, June 29, 2009
8231
00:00:00
Sweep Type:
Sweep Rate:
Report created at 02:56:57 PM, Monday, June 29, 2009
Page 44 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA – EDS-P308-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.960464 Hz
Control Peak:
Demand Peak:
0.702224 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 45 of 112
Test Report TL1316
8229
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-208A-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702794 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 46 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front To Back Moxa EDS-G205 17-07-14
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.701001 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 47 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Moxa SPL-24 08-05-31
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.701331 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 48 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-205A
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702012 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 49 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-408A-2M1S-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.701918 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 50 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-408A-3M-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702102 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 51 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-728
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.701190 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 52 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-305-M12
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.972771 Hz
Control Peak:
Demand Peak:
0.702959 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 08:06:32 AM, Tuesday, June 30, 2009
8230
00:00:00
Sweep Type:
Sweep Rate:
Report created at 08:06:33 AM, Tuesday, June 30, 2009
Page 53 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-G308
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.948158 Hz
Control Peak:
Demand Peak:
0.700922 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 03:18:08 PM, Monday, June 29, 2009
8228
00:00:00
Sweep Type:
Sweep Rate:
Report created at 03:18:09 PM, Monday, June 29, 2009
Page 54 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-G509
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.703247 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 55 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA P510
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.700768 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 56 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA VPORT-351-M-SC
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.935852 Hz
Control Peak:
Demand Peak:
0.701236 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 57 of 112
Test Report TL1316
8227
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA – EDS-G308-2SFP
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.700341 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Data saved at 02:56:56 PM, Monday, June 29, 2009
8231
00:00:00
Sweep Type:
Sweep Rate:
Report created at 02:56:57 PM, Monday, June 29, 2009
Page 58 of 112
Test Report TL1316
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA – EDS-P308-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.960464 Hz
Control Peak:
Demand Peak:
0.702224 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 59 of 112
Test Report TL1316
8229
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Vibration – MOXA EDS-208A-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702794 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 60 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front To Back Moxa EDS-G205 17-07-14
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.701001 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 61 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Front to Back Moxa SPL-24 08-05-31
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.898956 Hz
Control Peak:
Demand Peak:
0.701331 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 62 of 112
Test Report TL1316
8223
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-305-M12
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.705184 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 63 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-728
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
5.0000
profile(f)
high-abort(f)
low-abort(f)
1.0000
high-alarm(f)
low-alarm(f)
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.972771 Hz
Control Peak:
Demand Peak:
0.698466 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 64 of 112
Test Report TL1316
8230
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-205A
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.703045 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 65 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-208A-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.985077 Hz
Control Peak:
Demand Peak:
0.701971 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 66 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-P308-MM-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702794 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 67 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-G308-2SFP
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.702398 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 68 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-G308
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.948158 Hz
Control Peak:
Demand Peak:
0.702379 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 69 of 112
Test Report TL1316
8228
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-408A-2M1S-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.935852 Hz
Control Peak:
Demand Peak:
0.702776 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 70 of 112
Test Report TL1316
8227
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-408A-3M-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.948158 Hz
Control Peak:
Demand Peak:
0.702521 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 71 of 112
Test Report TL1316
8228
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-G509
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702045 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 72 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA EDS-P510
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.702897 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 73 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration – MOXA VPORT-351-M-SC
Project File Name:
mstest07g.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
23.000
profile(f)
10.000
high-abort(f)
low-abort(f)
high-alarm(f)
low-alarm(f)
1.0000
input2(f)
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.985077 Hz
Control Peak:
Demand Peak:
0.702296 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 74 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration Moxa SPL-24 07-59-57
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.923553 Hz
Control Peak:
Demand Peak:
0.703032 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 75 of 112
Test Report TL1316
8226
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Side to Side Vibration Moxa G205 16-57-17
Project File Name:
marine test.prj
Profile Name:
General Vibration Strain, Class A
Test Type:
Swept Sine
Run Folder:
.\RunDefault
gn
45.000
profile(f)
high-abort(f)
10.000
low-abort(f)
high-alarm(f)
low-alarm(f)
input2(f)
1.0000
control(f)
0.1000
0.0100
0.0070
0.4000
10.000
20.000
30.000
40.000
50.000
60.000
70.000
80.000
90.000
100.00
Frequency (Hz)
Level:
Frequency:
0 dB
99.997383 Hz
Control Peak:
Demand Peak:
0.700833 gn
0.700000 gn
Full Level Cycles:
Time Remaining:
Page 76 of 112
Test Report TL1316
8231
00:00:00
Sweep Type:
Sweep Rate:
Logarithmic
0.5 Oct/Min
Page 77 of 112
Test Report TL1316
Page 78 of 112
Test Report TL1316
Page 79 of 112
Test Report TL1316
Page 80 of 112
Test Report TL1316
Page 81 of 112
Test Report TL1316
Page 82 of 112
Test Report TL1316
Page 83 of 112
Test Report TL1316
Page 84 of 112
Test Report TL1316
Page 85 of 112
Test Report TL1316
Page 86 of 112
Test Report TL1316
Page 87 of 112
Test Report TL1316
Page 88 of 112
Test Report TL1316
Page 89 of 112
Test Report TL1316
Page 90 of 112
Test Report TL1316
Page 91 of 112
Test Report TL1316
Page 92 of 112
Test Report TL1316
Page 93 of 112
Test Report TL1316
Page 94 of 112
Test Report TL1316
Page 95 of 112
Test Report TL1316
Page 96 of 112
Test Report TL1316
Page 97 of 112
Test Report TL1316
Page 98 of 112
Test Report TL1316
Page 99 of 112
Test Report TL1316
Page 100 of 112
Test Report TL1316
Page 101 of 112
Test Report TL1316
Page 102 of 112
Test Report TL1316
Page 103 of 112
Test Report TL1316
Page 104 of 112
Test Report TL1316
Page 105 of 112
Test Report TL1316
Page 106 of 112
Test Report TL1316
Page 107 of 112
Test Report TL1316
Page 108 of 112
Test Report TL1316
Start of testing
1
After Low Temp
After High Voltage After High Humidity
End of testing
EDS-72810G
IM-4TX
IM-4MSC
IM-4SSC
IM-2MSC/2TX
IM-2MST/2TX
IM-2SSC/2TX
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
IM-2GTX
IM-2GSFP
SFP-1GLXLC
SFP-1G10ALC
SFP-1G10BLC
2
EDS-G509
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
3
EDS-408A-3M-SC
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
4
EDS-408A-2M1S-SC
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
5
EDS-P510
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
6
EDS-305-M12
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
7
8
EDS-208A-MM-SC
EDS-205A
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>100MΩ
>200MΩ
>200MΩ
9
EDS-P308-MM-SC
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
10
SPL-24
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
11
12
EDS-G308
EDS-G308-2SFP
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>100MΩ
>200MΩ
>200MΩ
13
EDS-G205
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
14
VPort 351-M-SC
>200MΩ
>200MΩ
>200MΩ
>100MΩ
>200MΩ
Page 109 of 112
Test Report TL1316
Color Scheme
models tested
Managed switch
EDS-828/728 series
EDS-G509 series
EDS-408A
EDS-82810G
EDS-G509
EDS-408A-3M-SC
EDS-P510
EDS-72810G
EDS-G509-T
EDS-408A-3M-ST
EDS-P510-T
IM-4TX
EDS-408A-2M1S-SC
IM-4MSC
EDS-408A-2M1S-ST
IM-4MST
EDS-408A-3S-SC
IM-4SSC
EDS-408A-3S-ST
IM-2MSC/2TX
EDS-408A-1M2S-SC
IM-2MST/2TX
EDS-408A-1M2S-ST
IM-2SSC/2TX
EDS-408A-3M-SC-T
IM-1LSC/3TX
EDS-408A-3M-ST-T
IM-2GTX
EDS-408A-2M1S-SC-T
IM-2GSFP
EDS-408A-2M1S-ST-T
EDS-P510- Series
EDS-408A-3S-SC-T
EDS-518A series
Optional Accessary
EDS-408A-3S-ST-T
SFP-1G series
EDS-408A-1M2S-SC-T
SFP-1GSXLC
EDS-408A-1M2S-ST-T
SFP-1GLSXLC
SFP-1GLXLC
SFP-1GLHXLC
SFP-1GZXLC
SFP-1GEZXLC
SFP-1GSXLC-T
SFP-1GLSXLC-T
SFP-1GLXLC-T
SFP-1GLHXLC-T
SFP-1GZXLC-T
SFP-1G10ALC
SFP-1G10BLC
SFP-1G20ALC
SFP-1G20BLC
SFP-1G40ALC
SFP-1G40BLC
SFP-1G10ALC-T
SFP-1G10BLC-T
SFP-1G20ALC-T
SFP-1G20BLC-T
SFP-1G40ALC-T
SFP-1G40BLC-T
Page 110 of 112
Test Report TL1316
Color Scheme
models tested
Unmanaged Switch
EDS-305 series
EDS-200A series
EDS-P308 Series
EDS-G308 series
EDS-G205 series
EDS-305-M12
EDS-208A
EDS-P308
EDS-G308
EDS-G205
EDS-305-M12-T
EDS-208A-M-SC
EDS-P308
EDS-G308-2SFP
EDS-G205-T
EDS-208A-M-ST
EDS-P308-M-SC
EDS-G308-T
EDS-208A-S-SC
EDS-P308-S-SC
EDS-G308-2SFP-T
EDS-208A-MM-SC
EDS-P308-MM-SC
EDS-208A-MM-ST
EDS-P308-SS-SC
Optional Accessary
EDS-208A-SS-SC
EDS-P308-T
SFP-1FE series
EDS-205A
EDS-P308-M-SC-T
SFP-1FEMLC-T
EDS-208A-T
EDS-P308-S-SC-T
SFP-1FESLC-T
EDS-208A-M-SC-T
EDS-P308-MM-SC-T
SFP-1FELLC-T
EDS-208A-M-ST-T
EDS-P308-SS-SC-T
EDS-208A-S-SC-T
SPL-24 Series
EDS-208A-MM-SC-T
SPL-24
EDS-208A-MM-ST-T
SPL-24-T
EDS-208A-SS-SC-T
EDS-205A-T
Page 111 of 112
Test Report TL1316
Color Scheme
models tested
Video Server
VPort 351 series
VPort 351
VPort 351-M-SC
VPort 351-S-SC
VPort 351-T
VPort 351-M-SC-T
VPort 351-S-SC-T
Page 112 of 112
Test Report TL1316
Download