Test File No. TL1316 Moxa Managed & Unmanaged Ethernet Switches Plus Video Server Mariner Systems (UK) Ltd. 29 June 2009 Page 1 of 112 Test Report TL1316 Table of Contents Page 1 2 3 4 5 6 SCOPE OF WORK………………………………………………………………...3 EQUIPMENT UNDER TEST……………………………………………………..3 TEST LABORATORY………………………………………………………….....6 TEST PERIOD……………………………………………………………………..6 ATTENDING REPRESENTATIVES…………………………………………….6 TESTS……………………………………………………………………...……….6 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 APPENDCIES…………………………………………………………...…………19 STAMPED TIMETABLE………………………………………………………....20 DRY HEAT CHART ……………..…..…………………………………………...22 LOW TEMPERATURE CHART …………….………………………………….23 HIGH HUMIDITY CHART ……………..……………………………………….24 DWELL FREQUENCIES…………………………………………………………25 LOCATIONS OF ACCELEROMETERS………………………………………..26 VIBRATION CHARTS……………………………………………………………35 RADIATED EMISSIONS ………………………………...………………………77 CONDUCTED EMISSIONS…………………………...………………………….81 INSULATION RESISTANCE READINGS………………………..……………108 LIST OF EQUIPMENT TESTED..........................................................................109 Page 2 of 112 Test Report TL1316 1 SCOPE OF WORK Marine type-approval test requirements This file contains the results of tests car ried out to m eet the require ments of A BS, DNV, GL, LR and NKK, on behalf of Moxa networking Co. Ltd. All these test s meet or exc eed the require ments of th e guidelines laid out in IA CS Unified Require ment E10 and the relevant sections of IEC945 for equipm ent housed w ithin a protected environment. These consolidated requirements are detailed within Mariner Systems Test Requirements (Issue 9). 2 EQUIPMENT UNDER TEST The equipment being tested comprised the following units shown marked. These cover the rest of the units in the series as these units were chosen to have the most functionality of the series. (See Appendix for full list of equipment tested) Client: Moxa Inc. Fl. 4, No. 135, Lane 235, Pao-Chiao Rd., Shing Tien City, Taipei, Taiwan Contact: Mr John Yu Applications to the following Classification Societies: American Bureau of Shipping Det Norske Veritas Germanischer Lloyd Lloyd's Register of Shipping Nippon Kaiji Kyokai (ABS) (DNV) (GL) (LR) (NKK) Test Results The tests list ed and detail ed in the following pages we re completed succe ssfully with the equipm ent operating normally before and after all tests, and during those tests that require normal operation of the equipment whilst the test is being carried out. This test report may not be reproduced in whole or part without the prior written approval of the laboratory. Signed S. K. Lee Test Laboratory Manager 3 TEST LABORATORY The tests were carried out at the Environmental Test Laboratory of Mariner Systems (UK) Ltd, located in Spennymoor, Co Durham., UK Page 3 of 112 Test Report TL1316 Laboratory accreditation: Mariner Systems is recognized by Bureau Veritas as per note NR320. Ambient conditions in the laboratory PARAMETER Temperature °C Humidity % RH Barometric pressure mbar Required (IEC 60068-1) 15 - 35 25 - 75 860 - 1060 Actual 18.5 - 23.8 50 - 60 990 - 1009 4 TEST PERIOD The tests were carried out during 1-Dec-2008 to 26 -June-2009. 5 ATTENDING REPRESENTATIVES Karen Ryan – Det Norske Veritas Pawan Jha – Lloyds Register of Shipping Roger Partington - Lloyds Register of Shipping Bill Divine - Nippon Kaiji Kyokai Gavin Leader - American Bureau of Shipping 6 TESTS The tests detailed in this file are – TEST 01 Performance 02 Dry Heat 03 Cold/Low Temperature 04 Damp Heat/Humidity 05 High Voltage 06 Vibration 07 Power Supply Variation 08 Power Supply Failure 09 Conducted LF 10 Conducted RF 11 Electromagnetic Field 12 Radiated Emissions 13 Conducted Emissions 14 Electrostatic Discharge 15 Insulation Resistance 16 Bursts/Fast Transients 17 Surge Voltage 18 Inclination (Static) 19 Inclination (Dynamic) 20 Acoustic Noise 21 Compass Safe Distance 22 Shock Test IACS Unified Requirements E10 N/A IEC60068-2-2 IEC60068-2-1 IEC60068-2-30 Not Required IEC60068-2-6 IEC60092-504 IEC60092-504 IEC60533 IEC61000-4-6 IEC61000-4-3 IEC60533 CISRP 16-1 & 16-2 IEC60533 CISRP 16-1 & 16-2 IEC61000-4-2 IEC60092-504 IEC61000-4-4 IEC61000-4-5 IEC60092-504 IEC60092-504 Not Required Not Required Not Required Page 4 of 112 Test Report TL1316 IEC945 N/A Section 8.2.2.2 Section 8.4.2.3 Section 8.3 Not Required Section 8.7.2 Section 10.7.1 & 7.2 Section 10.8.2 Section 10.2.2 Section 10.3.2 Section 10.4.2 Section 9.3.2 Section 9.2.2 Section 10.9.2 Section 8.3 & 8.4 Section 10.5.2 Section 10.6.2 Not Required Not Required Section 11.1.2 Section 11.2.2 Not Required Environmental Test File No. TL1316.01 01/Dec/08 Equipment performance Specification The co nformance t o d rawings i s chec ked and a f unctional perf ormance t est i s demonstrated t o t hose C lassification Soci ety surveyors present. Test Procedure The units we attached to DIN rail to make it easier to move and also to connect together. The units were split into 2 systems as the EDS72810G is a backbone which the modules (see appendix for full list attached to EDS72810G) are mounted onto. One of the modules is a video server and had a test box which produced a constant test video stream so we put this module at the start of the 2 systems and then linked them all together using a combination of CAT5 and fibre optic (depending on what each module supported) with a laptop at the end of the line. The test box produced the video signal and the video server converted this to run over the network, this went through all of the modules and the test stream was displayed on the laptop. This ensured that there was always data flowing through the 2 systems all the time during the testing and if at any point the test stream was not displayed then we would know if we had a fault. Environmental Test File No. TL1316.02 02/Jun/09 Dry Heat (IEC945 Section 8.2.2.2, IEC60068-2-2) Specification The equipment is to be placed in a clima tic chamber and the temperature raised to 70°C ± 2°C for a period of not less than 16 hours. The equipment shall be operational during the test and no degradation of the equipment shall be seen. Test Procedure Test Equipment Calibration date Montford environmental test chamber RS Electronics Resistance box Signallogger PC & Thermistors Calibrated on use 05/04/10 Calibrated on use The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range. Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet thermistor are located in the plenum chamber. The plotted results for dry temperature are the a verage values of all five dry sensors. The equipment was then placed in the e nvironmental chamber and the te mperature was raised fro m a mbient to 7 0°C ±2 °C over two hours and held for a period of 16 hours. The relative humidity was monitored and during the heating process and did not exceed 50% at 35°C, the mesured value was 15%. Results A performance test was performed on the equipment during the last hour at the test temperture and after the test, the equipment continued to work with no degradation in performance. Refer to the Appendices for test result graphs Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1°C Page 5 of 112 Test Report TL1316 Environmental Test File No. TL1316.03 04/Jun/09 Low temperature (IEC945 Section 8.4.2.3, IEC60068-2-1) Specification The equipment shall be placed in a clim atic chamber and the temperature reduced to -25°C ± 2°C for a period of not less than 2 hours. No degradation of the equipment performance shall be observed. Test Procedure Test Equipment Calibration date Montford environmental test chamber Signallogger PC & thermistors RS Electronics Resistance box Calibrated on use Calibrated on use 05/04/10 The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range. Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet thermistor are located in the plenum chamber. The plotted results for dry temperature are the average values of all five dry The equipment was then plac ed in the ch amber and t he temperature was lowered from ambient to -25°C for a pe riod of 16 hours. An insulation resistance test was also performed. (ref TL1316.15) Results A performance test was performed on the equipment during the last hour at the test temperture and after the test, the equipment continued to work with no degradation in performance. Refer to the Appendices for test result graphs. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1°C Environmental Test File No. TL1316.04 08/Jun/09 Humidity Test 1 – Cyclic (IEC945 Section 8.3, IEC60068-2-30) Specification The equipment is to be placed in a test chamber and the te mperature raised to 55°C ± 2°C at a hum idity of 95% ± 5% for a period of 12 hours with the equipment operational. The temperature is then reduced to 20°C ± 5°C for not less than 6 hours. This cycle shall then be repeated but with the equipment non-operational. No degradation of the equipment performance shall be observed. Test Procedure Test Equipment Calibration date Montford environmental test chamber Signallogger PC & Thermistors RS Electronics Resistance box Calibrated on use Calibrated on use 05/04/10 The temperature recorder was calibrated using the resistance box in place of t he measuring thermistors to ch eck calib ration before use. The measuring thermistors have a rated accuracy of 0.2°C between 0 and 50°C, and ±1% outside of that range. Four thermistors are lo cated inside the test chamber measuring the internal temperature, and in addition one dry and one wet thermistor are located in the plenum chamber. The plotted results for dry temperature are the average values of all five dry Page 6 of 112 Test Report TL1316 The equipment was placed in the chamber and the temperature raised from ambient to 55°C ± 2°C with a hum idity of 95% ± 5% for a period of 12 hours. Th e operation of t he equip ment w as ch ecked du ring th e first t wo ho urs of t he test. Th e temperature was then lowered to a temperature of 20°C ± 5°C with the same humidity for a period of 6 hours. This cycle was repeated with the equipment being switched off for the second cycle and then a performance test was performed during the last two hours of the high temperature period and at the end of the second cool period after normal humidity was achi eved. An insulation resistance test was also performed. (ref TL1316.15) Results A performance t est was performed on t he eq uipment d uring t he first h our, a fter 50 hours, during l ast h our at t he t est temperture and humidity and after the test, the equipment continued to work with no degradation in performance. Refer to the Appendices for test result graphs. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1°C Environmental Test File No. TL1316.05 23/Jun/09 High voltage Specification The equipment shall be tested using a 596V 50Hz high voltage source between L1/L2 & Earth for 1 minute. There shall be no insulation b reakdown during t he t est and no degradation of t he e quipment perf ormance shal l be obseved a fter t he t est i s completed. Test Procedure Test Equipment Calibration date Fosters Transformers Ltd. High Voltage source 05/05/10 The L1/L2 were connected to the high voltage probes and the earth pin for a period of one minute. An insulation resistance test was also performed. (ref TL1316.15) Results No b reakdown i n i nsulation occurred during t he t est an d no de gradation of t he e quipment per formance was observed aft er these tests. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1% Environmental Test File No. TL1316.06 29/Jun/09 Vibration test 1 (IEC945 Section 8.7.2, IEC60068-2-6) Specification The equipment is to be mounted on a vibration table and tested in three mutually perpendicular axes. In each axis a sweep is to be carried out from 2-13.2Hz at ± 1mm and from 13.2-100Hz at ±0.7g. The equipment is then vibrated for a period of 2 hours at each resonant frequency with an amplification factor of 2 or above, and or 30Hz if no resonance is found. No degradation of the equipment performance shall be observed. Test Procedure Test Equipment Calibration date Dactron Vibration controller LDS CA4 Charge Amplifier 10/01/10 01/10/09 Page 7 of 112 Test Report TL1316 D.J DPA4 and DPA8 Amplifier Birchall Accelerometers D.J Birchall Accelerometers LDS Vertical and Horizontal vibration table Not required 01/10/09 01/10/09 Not required The fi rst rack of e quipment was b olted t o the vert ical vi bration t able. The f requency was t hen swe pt acro ss t he r equired frequencies at a sweep rate of less than 0.5 octave per minute. An endurance test was performed at any resonance found and at 30Hz for two hours with the performance being tested during the test with an acceleration of 0.7 for two hours. The equipment was th en mounted horizontally with the vibration acting side to side on the unit, and the frequency swept. An endurance test was performed at any resonance found and at 30Hz for two hours with the performance being tested during the test with an acceleration of 0.7 for two hours. The e quipment was t hen r otated t hrough 90° a nd t he sw eep t est repeat ed in the new axis. Agai n a n endura nce t est was performed at any re sonance f ound a nd at 3 0Hz for t wo h ours wi th t he pe rformance bei ng t ested during t he t est wi th an acceleration of 0.7 for two hours. The tests were repeated but for each of the units on the second rack Refer to the Appendices for the photos which show the locations of the accelerometers. The accelerometers were placed on each unit in turn wh ere we thought that it was the m ost represenative of the whole of the equipment under test. This was done in all three planes. Results A performance test was performed on t he equipment during the test and after the test, the equipment continued to work with no degradation in performance. Refer to the Appendices for test result graphs and table of the dwell frequencies tested. Note that the line marked “control(f)” is the acceleration on the vibration table (Black line) and t he line marked “input2(f)” (Blue line) is t he measured acceleration on the equipment under test. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 2.5% Environmental Test File No. TL1316.07 11/Jun/09 Power supply Variation (IEC945 Section 10.7.1 and 10.7.2, IEC60092-504) Specification The equ ipment will b e teste d with a voltage v ariation of +3 0% and -25 % of th e nominal su pply v oltage. Th e tests will b e repeated during, and after dry heat, high humidity and l ow temperature tests and no d egradation of equipment performance shall be observed. For IEC945 Section 7.2 Excessive conditions. The standard states, conditions exceed the extreme test conditions in which the EUT is required to operate, with or without performance degradation as indicated in the equipment standard. Excessive current is defined as greater than normal working current. At the start of the power supply variation test the equipment is operating at its standard voltage and current. When we reduce the voltage then the current flowing into the power supply increases so giving a current more than the normal working current. Excessive voltage is greater than that specified in IEC945 Section 7.1. When we do the power supply variation test we test +/-20% which exceeds the values specified in IEC945 Section 7.1. We also do a high voltage check at 596 V a.c on the power supply. To test Excessive Voltage we used the current limit on the variable power supplies and set them to 200mA. When the voltage was increased past the +30% the current limiter cut the voltage (same effect as a fuse). Once the voltage was returned to normal levels the units operated correctly. Power supply misconnections are also regarded as excessive conditions; where appropriate the EUT shall be subjected to and input from a power supply of reversed polarity. Page 8 of 112 Test Report TL1316 Test Procedure Test Equipment Calibration date Derritron Magnus SPS1000 power supply Iso Tech IDM 93 DMM Not Required 05/04/10 Results The s upply of the equipm ent was attach ed to t he power s upply w ith th e op eration of th e eq uipment b eing monitored continually. The units all have different power supply requirments and are classified as 12, 24 and 48 V DC and the test levels were calculated on this range for each module. The output of the power supply was checked with the IDM93 Multimeter. The following transient tests were then carried out for more than 15 minutes at each setting. 12 V Input Test Number 1 2 Voltage Deviation +30% -20% Test Voltage 15.6 9.6 Voltage Deviation +30% -20% Test Voltage 32 19.2 Voltage Deviation +30% -20% Test Voltage 62.5 38.4 24 V Input Test Number 1 2 48 V Input Test Number 1 2 The operation o f t he eq uipment w as ch ecked th roughout th e test. The tests w ere repeated during, and af ter dry h eat (r ef TL1316.02), high humidity (ref TL1316.04) and low temperature (Ref 1326.03) tests. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1% Environmental Test File No. TL1316.08 11/Jun/09 Power supply failure (IEC945 Section 10.8.2, IEC60092-504) Specification The equipment shall be expos ed to at least three interruptions to the power supp ly of at least 6 0 seconds within five minutes. Equipment swiched on and checked to be operational. Power turned off for 60 seconds. Equipment powered up and re-tested for 90 seconds to ensure that it is fully operational – this test shall be repeated two more times with no failures being detected at any time. Test Procedure Page 9 of 112 Test Report TL1316 The equipm ent was connect ed to t he su pply and t he s witched on. T he o peration was chec ked bef ore t he power t o t he equipment only was turned off for 60 seconds. The equipment was then powered up and re-tested for 90 seconds to ensure full operation after th e power failure. This test was th en repeated two more times with no failures being detected after the p ower was restored. Results A performance test was pe rformed on t he equipment after the test, the equipment continued to work with no degradation in performance. Environmental Test File No. TL1316.09 12/Jun/09 Immunity to conducted low frequency interference (IEC945 Section 10.2.2, IEC60533) Specification The e quipment shall be s ubjected to a si gnal s wept to t he 200th harmonic wi th t est voltage of 1 0% o f t he nominal s upply voltage to the 15th harmonic reducing to 1% at the 100 th an d maintained to th e 200th harmonic with a minimum 3 V (r.m.s) maximum 2 W. Test Procedure Test Equipment Calibration date Marconi Instruments 2123 Signal Generator Quad 405 Amplifier Iso Tech IDM 93 Frequency counter Fluke 87 RMS DMM Not required Not required 05/04/10 24/09/09 The input of the equipment was connected to the power supply via coupling clamp. The frequency generator was connected to the input of the amplifier and to the frequency counter. The output voltage was monitored using the Fluke 87 multimeter. The frequency was swept from 50Hz to 10KHz while maintaining the amplitude at the required levels. Results A performance test was performed on t he equipment during and after the test the test, the equipment continued to work with no degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : ± 1.5% Environmental Test File No. TL1316.10 12/Jun/09 Conducted RF (IEC945 Section 10.3.2, IEC61000-4-6) Specification The equipment shall be o perational and the test applied to both power and signal lines. The frequency shall be swe pt from 10kHz to 80MHz amplitude modulated at 1kHz ±10% and 400Hz ±10% to a modulated depth of 30% a nd 80%, amplitude maintained at 3V rms. The equipment shall also be subjected to the same series of tests at the following spot frequencies: 2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22 and 25MHz at 10V rms with 80% ±10% modulation at 400Hz ±10%. Test Procedure Test Equipment Calibration date Marconi 2017 RF signal generator ENI 325LA RF Amplifier Racal-Dana 9302 RF millivoltmeter 22/08/09 Not required 14/08/09 Page 10 of 112 Test Report TL1316 The in put of th e equ ipment was con nected to th e p ower supply v ia an i mpedance stab ilisation n etwork with th e am plifier output capacitively coupled to the supply. The fre quency generat or wa s connected to the input of the am plifier and the frequency swept from 10KHz to 80MHz modulated to 30% and 80% at 1KHz and at 400 Hz while maintaining the amplitude at 3V RMS as shown by the RF millivoltmeter. The equipment was also subjected to the same test at spot frequencies 2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22 and 25 MHz at 10 V rms. with modulation 80 % at 400 Hz in accordance with IEC945 for bridge and deck equipment. Results A performance test was performed on t he equipment during and after the test the test, the equipment continued to work with no degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : ±2.5dB Environmental Test File No. TL1316.11 12/Jun/09 Electromagnetic Field (IEC945 Section 10.4.2, IEC61000-4-3) Specification The equipment shall be operational. The equipment shall be exposed to an electric field of 10V/m swept from 30kHz-2GHz amplitude modulated at 1kHz ±10% and 400Hz ±10% to a modulation depth of 30% and 80% ±10% Test Procedure Fi Test Equipment Calibration date Schaffner GTEM Cell eld Probe HP Frequency Generator Amplifier Research 25W1000 25W RF Amplifier ENI 325LA RF Amplifier Amplifier Research 30W 4.2GHz RF Amplifier On Test 06/08/09 06/08/09 Not required Not required Not required Before any e quipment is placed insi de the GTEM cell it is re quired that the RF levels within the cell are verified across the frequency range. This is done under software control, a s weep is made across the frequency range using the probe to veryfy the correct level. This sweep pr oduces the calibration for th e cell at above 10 Volts/Meter. This calibration is th en used to perform the sweeps and a lev el check is mad e across the ran ge to ensure that the level never falls b elow 10 V/M. If th is is correct then the equipment can be put inside the cell and the sweeps done as below. The equipment was placed in the GTEM ce ll, the frequency generat or was set to sweep from 30KHz to 128M Hz amplitude modulated to a depth of 30% at 1KHz and the applied field was raised to 10V/m using the methods as mentioned above. The signal was th en swep t wh ilst th e field stren gth was m aintained at 10V/ m. The equipment was turned si de onto t he si gnal orientation and the test repeated to ensure that position did not affect the immunity of the unit. The equipment was then turned to ensure that the incide nt field was test ed in all three axes. The am plifier was ch anged from the ENI325LA amplifier to the Amplifier Research amplifier at 80MHz and swept to 1000MHz using the same method to calibrate the cell to ensure that the level inside the cell is correc t.. The equipment was again placed in the GTEM cell, t he frequency generator was set to s weep from 80 MHz to 1000 MHz amplitude modulated to a depth of 30% at 1KHz and the applied field was raised to 10V/m using the methods as mentioned above. The equipment was turned side onto the signal orientation and the test repeated to ensure that position did not affect th e immunity of the unit. The equipment was then turned to ensure that the incident field was tested in all three axes. The amplifier was cha nged to the sec ond Amplifier Research amplifier at 9 00 MHz and swept to 2000MHz using the same method t o cal ibrate t he cell t o en sure t hat t he l evel i nside t he cel l i s cor rect. T he eq uipment was t hen pl aced i n t he cel l as before and the 3 axes tested. These t ests were repeat ed usi ng 80% am plitude m odulation t o com ply with al l requi rements and ag ain wi th a modulation frequency of 400 Hz. Results Page 11 of 112 Test Report TL1316 A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : ± 1.7dB Environmental Test File No. TL1316.12 16/Jun/09 Radiated Interference (IEC945 Section 9.3.2, IEC60533) Specification The equipment shall not radiate RF levels greater than. Test Procedure GTEM Limits (dBµV/m) 80 – 50 50 – 34 54 24 54 Frequency 10kHz - 300kHz 300kHz - 30MHz 30MHz - 156MHz 156MHz - 165MHz 165MHz - 2GHz Bandwidth 9KHz 9KHz 120KHz 9KHz 120KHz Test Equipment Calibration date Anritsu 2602 Spectrum Analyser Cell Calibrated on use Not required The equipment was placed in the GTEM Cell in 2 racks, rack 1 was the EDS72810G and its listed modules and rack 2 was the remaining stand alone modules which gave the worst case emissions. The equipment was t hen switched on and the levels taken over the full range a nd then over the reduced range with both the equipment being rotated through three axes. At no frequency or positions did the level of emitted radiation exceed those levels specified in the requirements. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : ± 2.1dB Environmental Test File No. TL1316.13 17/Jun/09 Conducted emissions (IEC945 Section 9.2.2, IEC60533) Specification The equipment shall not radiate conducted levels greater than Frequency 10kHz - 150kHz 150kHz - 350kHz 350kHz - 30MHz Limits (dBµV/m) 96 – 50 60 – 50 50 Bandwidth 200Hz 9KHz 9KHz Test Procedure Calibration date Test Equipment Page 12 of 112 Test Report TL1316 Anritsu 2602 Spectrum Analyser RayProof Faraday Room Calibrated on use Not required The equi pment was placed i n the Fa raday room with the coupling net work. A background level was the n take n with t he equipment switched off. The equipment was then switched on and the levels taken from each unit over the full range and then over the reduced range. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. At no frequency or positions did the level of conducted radiation exceed those levels specified in the requirements. Uncertainty of Measurement Total uncertainty of measurement for this test : ± 2.3dB Environmental Test File No. TL1316.14 17/Jun/09 Electrostatic discharge (IEC945 Section 10.9.2, IEC61000-4-2) Specification a) Air discharge: b) Contact discharge: The equipment shall be s ubjected to an electrostatic discharge of 8kV applied to any exposed part of the system which is accessible to the operator i n normal use. This will be repeated 10 times, in a number of different places, for both positive and negative polarity. The ab ove process will b e rep eated for co ntact d ischarge at a lev el o f 6kV, fo r both positive and negative polarity. At least 10 single contact discharges per polarity will be applied to positions on the ground plane at a distance away from the EUT. In addition at least 10 single discharges per polarity will be applied to a coupling plane of dimensions 0.5 x 0.5 m placed parallel to and at lease 0.1m away form the ETU, this will be done so that all axes are tested. Test Procedure Test Equipment Calibration date Schaffner Best EMC Compact test system 24/02/10 The equipment was placed on an ins ulator placed on an a luminium earth plane . The gun was set to 8KV and disc harged 10 times with one second between each discharge, the charge was applied to any exposed metal of the equipment in a number of different places positive and negative polarity for air and then repeated at 6 KV for contact discharge. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 1% Environmental Test File No. TL1316.15 23/Jun/09 Insulation resistance test. (IEC945 Section 8.3 & 8.4, IEC60092-504) Specification The equipment shall be tested before and after the humidity, high voltage and low temperature tests. The i nsulation between positive & negative to earth shall be tested for both polarities and shall not be less than 10 Mohms Page 13 of 112 Test Report TL1316 Test Procedure Test Equipment Calibration date Megger insulation tested 23/09/09 Before and after the low temperature, the high voltage and humidity tests the insulation resistance of the input of the unit was tested. Supply to earth was tested in both polarities. Results A performance test was pe rformed on t he equipment after the test, the equipment continued to work with no degradation in performance. At no time did the measured insulation resistance drop below 10 Megohms. See appendix for readings taken Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 0.05 + 1 Digit Environmental Test File No. TL1316.16 16/Jun/09 Burst/Fast Transients. (IEC945 Section 10.5.2, IEC61000-4-4) Specification With the equipment operational a fast transient pulse will be applied for a period of 10 minutes, as follows: Power supply line: Signal and control lines: Pulse rise time: Pulse width: 50 Application: 2kV Line/Earth at 2.5kHz & 5KHz 1kV common mode at 5kHz 5nS (10% and 90%) nS (50% value) 15mS burst every 300mS Test Procedure Test Equipment Calibration date Schaffner Best EMC Compact test system 24/02/10 The system was connected to the mainframe unit with the Schaffner Best EMC Compact test system. With the equipment operational a fast transient pulse was applied for a period of 10 minutes, as follows: Power supply line: Signal and control lines: Pulse rise time: Pulse width: 50 Application: 2kV Port/Earth at 2.5kHz & 5KHz 1kV common mode at 5kHz 5nS (10% and 90%) nS (50% value) 15mS burst every 300mS This level of interference was maintained for ten minutes on each polarity and conductor. The signal cables were also checked at 1KV at 5KHz. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Page 14 of 112 Test Report TL1316 Total uncertainty of measurement for this test : Frequency ± 1% Burst Duration & Period ± 1% Environmental Test File No. TL1316.17 16/Jun/09 Surge Immunity (IEC945 Section 10.6.2, IEC61000-4-5) Specification With t he eq uipment operat ional a 0. 5, 1 & 2k V com mon m ode pul se shal l be appl ied t o l ine/earth fo r a minimum of 10 minutes at a r ate of one p ulse/minute. With t he equi pment ope rational a 0.5 & 1 kV di fferential pul se shal l be appl ied t o line/line for a minimum of 10 minutes at a rate of one pulse/minute. These tests shall be repeated for both polarities. Pulse rise time: Pulse width: 50 1.2uS (10% and 90%) uS (50% value) Test Procedure Test Equipment Calibration date Schaffner Best EMC Compact test system 24/02/10 The System was connecte d to the Sc haffner Best EMC Co mpact test sy stem. The interference amplitude was set to 0 .5, 1 & 2KV and common mode pulses were applied to line/earth for 10 minutes at a rat e of one pulse/minute. With the equipment operational 0 .5 & 1kV d ifferential p ulse were app lied to line/line for 10 minutes at a rate o f one pu lse/minute. These tests were repeated for both polarities. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : Peak Voltage ± 1.4% Rise Time ± 1.5% Pulse Width ± 2.2% Environmental Test File No. TL1316.18 22/Jun/09 Static inclination test. (IEC60092-504) Specification The equipment shall be inclined at an angl e of at least 2 2.5° either side of horizontal at two mutually perpendicular axes for a period of at least 15 minutes. Test Procedure Test Equipment Calibration date Inclination test table Not required The equipment was bo lted to the inclination table and the operation checked before the test started. The equipment was then tilted to an ang le of 45° from h orizontal an d th e operation ch ecked over a period of fifteen m inutes du ring which tim e n o failures were detected. The table was then tilted to 45° on the other side of horizontal where it remained for fifteen minutes. The equipment was then rotated through 90 degrees and both of the tests repeated for fifteen minutes in this axis. Results Page 15 of 112 Test Report TL1316 A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 2° Environmental Test File No. TL1316.19 22/Jun/09 Dynamic inclination test. (IEC60092-504) Specification The equipment shall be rolled to an angle of at least 22.5° either side of horizontal with a period of 10 seconds for a period of at least fifteen minutes in two mutually perpendicular axes. Test Procedure Test Equipment Calibration date Inclination test table Not required The equipment was bolted to the inclination table and the operation checked before the test started. The table wa s then started to r oll t hrough 90 ° wi th a period o f ap proximately 10 sec onds a nd t he operation chec ked over a period of fifteen minutes during which time no failures were detected. The equipment was then rotated through 90 degrees and the tests repeated for fifteen minutes in this axis. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 2° Environmental Test File No. TL1316.20 22/Jun/09 Acoustic noise (IEC945 11.1.2) Specification The equipment shall not exceed a peak level of 60 dB (A) at a distance of 1 M from any part of the equipment Test Procedure Test Equipment Calibration date DAWE sound level meter DAWE acoustical calibrator Calibrated on use 12/04/09 The sound meter was calibrated using the acoustical calibrator. (Compliant with IEC651) The eq uipment was set up i n q uiet room with every thing swi tched of f and a back ground m eter readi ng was t aken. The equipment was then powered up and a reading taken 1M from the equipment. Another background reading was taken when the equipment was switched off. Results Page 16 of 112 Test Report TL1316 A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. The levels measured were well below the fail point. Before 32.0 dB (A) 32.5 dB (A) Reading Rack 1 Reading Rack 2 Equipment on 32.1 dB (A) 32.7 dB (A) After 32.0 dB (A) 32.4dB (A) Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 0.6dB Environmental Test File No. TL1316.21 22/Jun/09 Compass Safe Distance Test (IEC945 11.2.2) Specification The equipment shall be tested to determine the Compass Safe Distance. This test will be repeated with the equipment operational and non operational and rotated to find the worst case plane. The location of the lab is Latitude 54.42, longitude -1.36 which from the British Geological survey website (www.geomag.bgs.ac.uk) gives a horizontal component of magnetic flux of 17785nT for June 2009. From this we calculate 0.3 degrees for the standard compass and 1.0 degrees for the steering, standby and emergency compass. Frequency Un-powered, as received After Normalizing Powered (Energised) Worst case result 1 Degree Deflection 0.3 Degree Deflection A1mm A2mm B1mm C1 mm B2mm C2 mm Largest Value of A1, B1 or C1 Largest Value of A2, B2 or C2 Test Procedure Calibration date Test Equipment Fl uxgate magnetometer 02/ 04/09 The test equipment was set up and any background levels zeroed out. The equipment under test was then brought in to the area and tested in the position and attitude relative to the magnetometer that caused the most error to be seen. Results A performance t est was pe rformed on t he eq uipment d uring a nd aft er the t est, t he e quipment cont inued t o work wi th n o degradation in performance. The distances measured were as follows and is the worst case readings for all the module. Frequency Un-powered, as received After Normalizing Powered (Energised) Worst case result 1 Degree Deflection 0.3 Degree Deflection 500mm 600mm 500mm 600mm 600mm 700mm 600mm 700mm Page 17 of 112 Test Report TL1316 All the distances have been rounded up to the nearest 100mm in order to allow for the maximum deviation, which might be caused by the most magnetic sample of all units manufactured. Uncertainty of Measurement Total uncertainty of measurement for this test : < ± 10mm Environmental Test File No. TL1316.110 24/June/09 Shock Test Specification The equipment is to be mounted on a vibration table and tested in three mutually perpendicular axes with a shock test of 15g 11mS applied for 20 pulses. Test Procedure D.J Test Equipment Calibration date Dactron Vibration controller LDS CA4 Charge Amplifier DPA4 and DPA8 Amplifier Birchall Accelerometers D.J Birchall Accelerometers LDS Vertical and Horizontal vibration table 10/01/10 01/10/09 Not required 01/10/09 01/10/09 Not required The equipment was bolted to the vertical vibration table and a shock of 15g 11mS, 20 pulses were applied, test equipment was then checked and no degradation of the equipment performance was observed during these tests. The equipment was then mounted horizontally with the shock acting front-to-back on the unit. The shock of 15g 11mS, 20 pulses were applied, test equipment was then checked and no degradation of the equipment performance was observed during these tests. The equipment was then mounted horizontally with the shock acting side to side on the unit. The shock of 15g 11mS, 20 pulses were applied, test equipment was then checked. Results No degradation of the equipment performance was observed during these tests. Page 18 of 112 Test Report TL1316 APPENDICES Page 19 of 112 Test Report TL1316 Environmental Test Timetable Customer - Moxa - File No TL1316 ~~ a'K~~~~ r 41" I~) Equipment- Managed and Unmanaged Switches and Video Server I Test 01 Performance 02 Dry Heat (IEC945 section 8.2.2.2, IEC60068-2-2) 3 Low temperature (IEC945 section 8.4.2.3, IEC60068-2-1) V- Humidity Test I ­ Cyclic (IEC945 section 8.3,IEC60068-2-30) High voltage ,~ fl -"'-'..4. ~d \ Complete Iw. . Procedure Starts Equipment is tested The conformance to drawings is checked and a fuctional performance test is demonstrated to society surveyors present. -The equipment is to be installed in a climatic chamber and the temperature raised to 70°C ±2°C for a period of not less than 16 hours. The equipment will be operational during the test and no degradation of the equipment shall be seen. The equipment shall be placed in a climatic chamber and the temperature reduced to -25 °C ±2°C for a period of not less than 2 hours. 02/06/09 Q/;~/., I ~ :" 02/06/09 U!Oq •ol.. oz. 03/06/09 if/bid, Two cycles of 55°C for 12 hours & 6 hours at 20°C at 95% ± 5%RH 04/06/09 £~- fI 5 6 6 Vibration test J (IEC945 section 8.7.2, IEC60068-2-6) - Side to side 6 - Front to back 7 Power supply Variation (IEC945 section 7.1 & 7.2,IEC60092-504) -­ 8 Power supply failure (IEC945 section 10.8.2, IEC60092-504 ) 9 Immunity to conducted low frequency interference (IEC945 section 10.2.2, IEC60533) Conducted RF (IEC945 section 10.3.2, IEC61 000-4-6) 10 -(jD~ 'h" ~ .pl\: 1 'b""" The equipment shall be tested using a 1500V 50Hz high voltage source between LivelNuetral & Earth for I minute. There should be no insulation breakdown during the test and no degradation of the equipment performance after the test is completed. The equipment is to be mounted on a vibration table and ""ed in there morn,lIy p'"P~di,"I" "'~ In I~ sweep is to be carried out from 2-13.2Hz at ±lmm an 13.2-100Hz at ±0.7g. The units then vibrated for a p 0 hours at each resonant frequency with an amplificatio ct4 of 2 or above, or 30Hz if no resonance is foun dezradation of the equipment performance shall be seen. Equipment shall be tested as the vertical vibration test. 18/06/09 - haa ~1 08/06/09 t~ !l~ ~dof ~ A L~ 7.l~ v'Wlt.iJj~" /0 II Test voltage (r.m.s.): 10% of supply to 15th harmonic reducing to I % at I OOth harmonic and maintain this level to the 200th harmonic, minimum 3 V (r.m.s.), maximum 2 W 11 /06/09 II/ G The equipment shall be operational and the test applied to both power and signal lines. The frequency shall be swept from 10kHz to 80MHz amplitude modulated at 1kHz +/-10% and 400Hz +/-10% to a modulated depth of30% and 80%, amplitude maintained at 3V nns. The equipment shall also be subjected to the same series of tests at the following spot frequencies: 2,3,4, 6 .2, 8.2, 12.6, 16.5, 18.8,22 and 25MHz at 10V rms with 80% +/-10% modulation at 400Hz +/-10% . 11/06/09 'zlb ~~~ ~~ ~ ., ­' :~J .AL l! y~ f ;1&d1~ r:-b/ (:./' ,4 1/6 ~ .~/~ < J:P'J 11" ",.i ,~~ /?J. 11 /06/09 Page 20 of 112 Test Report TL1316 (fli9~f) IBUREAUOF~ 09/06/09\ Equipment shall be tested as the vertical vibration test. 10106/09 The unit will be tested with a voltage variation of + I 0% and - 11/06/09 15% of the nominal supply voltage, and a frequency variation of ±5%. Transient conditions of ±20% voltage and ±15% frequency shall also be tested. Equipment will be tested a 230 & 110 Volts if selectable. Tests will be performed before, during and after dry heat and low temperature tests with no degradation of perform ace seen The unit is to be exposed to at least three interruptions to the supply of at least 60 seconds within five minutes. Unit swiched on and checked to be operational. Power turned off for 60 seconds. System powered up and retested for 90 seconds to ensure that it is full y operational - this test repeated two more times with no failures being detected 2'>/{' ~ ,,~ ~'~ -.......:.::. II Electromagnetic Field (IEC945 section 10.4.2, IEC61 000-4-3) The equipment shall be operational. The equipment shall be exposed to an electric field of IOV/m swept from 30kHz­ 2GHz amplitude modulated at 1kHz +/-10% and 400Hz +/­ 10% to a modulation depth of 30% and SO% +/-10% 12/06/09 12 Ie 12 Radiated Interference (IEC945 section 9.3.2, IEC60533) The equipment shall not radiate RF levels greater than Frequency Range Limits 10KHz- 300 KHz SO-50dB uV/m 300KHz-30MHz 52-34dB uV/m 30MHz-156MHz 54dB uV/m 156MHz-165Mhz 24dB uV/m 165MHz-2GHz 54dB uV/m The equipment shall not radiate conducted levels greater than 96-50 dB uV in the range 10 kHz-ISO kHz 60-50 dB uV in the range ISO kHz-350 kHz or 50 dB uV in the range 350 kHz-30MhZ 15/06/09 I ~/' a) Air discharge: The equipment shall be subjected to an electrostatic discharge of SkV applied to any exposed metal part of the system. This will be repeated 10 times, in a number of different places, for both positive and negative polarity. b) Contact discharge: The above process will be repeated for contact discharge at a level of 6kV, for both positive and negative polarity. The equipment shall be tested before and after the humidity and low temperature tests. The insulation between live & neutral to earth shall be tested for both polarities and shall not be less than 100Mohms With the equipment operational a fast transient pulse will be applied for a period of 10 minutes, as follows: Power supply line 2kV differential at 2.5kHz Signal and control lines: IkV common mode at 5kHz Pulse rise time: 5nS (10% and 90%) Pulse width: SOnS (50% value) Application: ISmS burst every 300mS With the equipment operational a 0.5, 1.0 & 2kV common mode pulse shall be applied to line/earth for a minimum of 10 minutes at a rate of one pulse/minute. With the equipment operational a 0.5 & 1kV differential pulse shall be applied to line/line for a minimum of 10 minutes at a rate of one pulse/minute. These tests shall be repeated for both polarities. The equipment shall be inclined at an angle of at least 22.5° either side of horizontal at two mutually perpendicular axes for a period of at least 15 minutes. 16/06/09 13 14 ,.... 15 16 Conducted emissions (IEC945 section 9.2.2, IEC60533) Electrostatic Discharge Electrostatic discharge (IEC945 section 10.9.2, IEC61 000-4-2) Insulation resistance test. (IEC945 section S.3 & S.4, IEC60092­ 504) BurstlFast Transients. (IEC945 section 10.5.2, IEC61 000-4-4 ) 17 Surge Immunity (IEC945 section 10.6.2, IEC61000-4-5) IS Static inclination test. (IEC60092-504) 19 Dynamic inclination test. (IEC60092-504) 20 21 - 151061°1~ ......./1 I ~/V" ~,;i(./ " ." ,.,u, ~ O'7-I,7.-/o'Y 17/ (/oq 02/06/09 '2 /{, 1-')/6 ~' \~ ~Ci:::::S"'" '1...)' )/.11 »9 I(./e 22/& The equipment shall be rolled to an angle of at least 22.5° either side of horizontal with a period of 10 seconds for a period of at least fifteen minutes in two mutually perpendicular axes. 17/06/09 2l !~ Acoustic noise (IEC945 11.1.2) The equipment shall not exceed a peak level of 60 dB (A) at a distance of I M from any part of the equipment 18/06/09 ZZ I( Compass safe Distance IEC60945 section 11.2.2 The equipment shall be tested to determine the compass safe distance. This will be repeated with the equipment operational and non-operational 18/06/09 21./(, I~ ~ /1 <>.". '-' Claas~ - tl I~ \~ !, ~!. c,~~ 17/06/09 ~ h~€' ~W KA 16/06/09 1(./(" Page 21 of 112 Test Report TL1316 : :-.ltJK~": _J,o . 16/06/09 I ,,-v.'J~ ~. ~---A~ ~ wI~ ~ Dry Heat 80 60 70 50 60 40 40 30 30 20 20 10 10 0 0 0 2 4 6 8 10 12 Time in Hours Page 22 of 112 Test Report TL1316 14 16 18 %RH Temperature C 50 Temperature Humidity Low Temperature 30 20 0 -10 -20 -30 Time in hours Page 23 of 112 Test Report TL1316 20 19 19 18 18 17 16 16 15 15 14 13 13 12 12 11 10 10 9 9 8 7 7 6 6 5 4 4 3 3 2 1 1 0 Temperature 0 Temperature C 10 Humidity 60 100 95 90 85 50 80 75 70 65 60 55 30 50 45 40 35 20 30 25 20 10 15 10 5 0 0 0 2 4 6 8 11 13 15 17 19 22 24 26 28 Time in Hours Page 24 of 112 Test Report TL1316 30 33 35 37 39 41 %RH Temperature C 40 Temperature Humidity Vertical 1 Side to Side Front to Back EDS-72810G IM-4TX IM-4MSC IM-4SSC IM-2MSC/2TX IM-2MST/2TX IM-2SSC/2TX 30 30, 33, 37 30, 40, 49 IM-2GTX IM-2GSFP SFP-1GLXLC SFP-1G10ALC SFP-1G10BLC 2 EDS-G509 12, 14, 16, 30 28, 30 30, 96 3 EDS-408A-3M-SC 13, 30 30, 38 20, 27, 30 4 EDS-408A-2M1S-SC 18, 30 30, 39, 55 27, 30 5 EDS-P510 19, 30 30, 31, 33, 40 23, 28, 30, 96 6 EDS-305-M12 30 30 30 7 8 EDS-208A-MM-SC EDS-205A 19, 30 30, 36 30, 38 22, 27, 30 28, 30, 54, 82 30, 51 9 EDS-P308-MM-SC 14, 30 28, 30, 53, 82 28, 30, 57 10 SPL-24 30, 44 30 30 11 12 EDS-G308 EDS-G308-2SFP 13, 30 18, 30 30, 41, 56 30, 39, 56 23, 28, 30 28, 30, 52 13 EDS-G205 21, 30, 22, 30 22, 30 14 VPort 351-M-SC 17, 30 30, 40, 55 22, 28, 30, 56 Page 25 of 112 Test Report TL1316 Locations of Accelerometers Vertical EDS-305-M12 Vertical EDS- 205A Vertical 408A-3M-SC Vertical Vport 351-M-SC Vertical EDS-208A-MM-SC Vertical EDS-G308-2SFP Page 26 of 112 Test Report TL1316 Vertical EDS-P510 Vertical EDS-G509 Vertical EDS-G308 Vertical EDS-P308-MM-SC Vertical EDS-408A-2M1S-SC Vertical 728 Page 27 of 112 Test Report TL1316 Vertical EDS-G205 Vertical SPL-24 Page 28 of 112 Test Report TL1316 Locations of Accelerometers Front to Back EDS 208-MM-SC Front to Back EDS 308-2SFP Front to Back EDS-205A Front to Back EDS 408A-2M1S-SC Front to Back EDS-P510 Front to Back Vport 351-M-SC Page 29 of 112 Test Report TL1316 Front to Back EDS-305-M12 Front to Back SPL-24 Front to Back EDS-P308-MM-SC Front to Back EDS 728 (with extra Modules) Front To Back EDS-G205 Front to Back EDS-408A-3M-SC Page 30 of 112 Test Report TL1316 Front to Back EDS-G308 Front to Back EDS-G509 Page 31 of 112 Test Report TL1316 Locations of Accelerometers Side to Side EDS-G408-A2M1S-SC Side to Side EDS-408A-3M-SC Side to Side EDS-208AMM-SC Side to Side EDS-G308 Side to Side G308-2SFP Side to Side EDS-205A Page 32 of 112 Test Report TL1316 Side To Side VPort-M-SC Side To Side G509 Side to Side 728 Side To Side P510 Side To Side 305-M12 Side to Side SPL-24 Page 33 of 112 Test Report TL1316 Side to Side EDS-G205 Side to Side EDS-P308-MM-SC Page 34 of 112 Test Report TL1316 Front to Back Vibration – MOXA EDS-205A Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702012 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 35 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-408A-2M1S-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.701918 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 36 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-408A-3M-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702102 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 37 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-728 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.701190 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 38 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-305-M12 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.972771 Hz Control Peak: Demand Peak: 0.702959 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 08:06:32 AM, Tuesday, June 30, 2009 8230 00:00:00 Sweep Type: Sweep Rate: Report created at 08:06:33 AM, Tuesday, June 30, 2009 Page 39 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-G308 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.948158 Hz Control Peak: Demand Peak: 0.700922 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 03:18:08 PM, Monday, June 29, 2009 8228 00:00:00 Sweep Type: Sweep Rate: Report created at 03:18:09 PM, Monday, June 29, 2009 Page 40 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-G509 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.703247 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 41 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA P510 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.700768 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 42 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA VPORT-351-M-SC Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.935852 Hz Control Peak: Demand Peak: 0.701236 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 43 of 112 Test Report TL1316 8227 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA – EDS-G308-2SFP Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.700341 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 02:56:56 PM, Monday, June 29, 2009 8231 00:00:00 Sweep Type: Sweep Rate: Report created at 02:56:57 PM, Monday, June 29, 2009 Page 44 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA – EDS-P308-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.960464 Hz Control Peak: Demand Peak: 0.702224 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 45 of 112 Test Report TL1316 8229 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-208A-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702794 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 46 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front To Back Moxa EDS-G205 17-07-14 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.701001 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 47 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Moxa SPL-24 08-05-31 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.701331 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 48 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-205A Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702012 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 49 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-408A-2M1S-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.701918 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 50 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-408A-3M-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702102 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 51 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-728 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.701190 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 52 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-305-M12 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.972771 Hz Control Peak: Demand Peak: 0.702959 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 08:06:32 AM, Tuesday, June 30, 2009 8230 00:00:00 Sweep Type: Sweep Rate: Report created at 08:06:33 AM, Tuesday, June 30, 2009 Page 53 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-G308 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.948158 Hz Control Peak: Demand Peak: 0.700922 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 03:18:08 PM, Monday, June 29, 2009 8228 00:00:00 Sweep Type: Sweep Rate: Report created at 03:18:09 PM, Monday, June 29, 2009 Page 54 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-G509 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.703247 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 55 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA P510 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.700768 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 56 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA VPORT-351-M-SC Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.935852 Hz Control Peak: Demand Peak: 0.701236 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 57 of 112 Test Report TL1316 8227 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA – EDS-G308-2SFP Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.700341 gn 0.700000 gn Full Level Cycles: Time Remaining: Data saved at 02:56:56 PM, Monday, June 29, 2009 8231 00:00:00 Sweep Type: Sweep Rate: Report created at 02:56:57 PM, Monday, June 29, 2009 Page 58 of 112 Test Report TL1316 Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA – EDS-P308-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.960464 Hz Control Peak: Demand Peak: 0.702224 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 59 of 112 Test Report TL1316 8229 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Vibration – MOXA EDS-208A-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702794 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 60 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front To Back Moxa EDS-G205 17-07-14 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.701001 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 61 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Front to Back Moxa SPL-24 08-05-31 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.898956 Hz Control Peak: Demand Peak: 0.701331 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 62 of 112 Test Report TL1316 8223 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-305-M12 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.705184 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 63 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-728 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 5.0000 profile(f) high-abort(f) low-abort(f) 1.0000 high-alarm(f) low-alarm(f) input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.972771 Hz Control Peak: Demand Peak: 0.698466 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 64 of 112 Test Report TL1316 8230 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-205A Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.703045 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 65 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-208A-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.985077 Hz Control Peak: Demand Peak: 0.701971 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 66 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-P308-MM-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702794 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 67 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-G308-2SFP Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.702398 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 68 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-G308 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.948158 Hz Control Peak: Demand Peak: 0.702379 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 69 of 112 Test Report TL1316 8228 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-408A-2M1S-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.935852 Hz Control Peak: Demand Peak: 0.702776 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 70 of 112 Test Report TL1316 8227 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-408A-3M-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.948158 Hz Control Peak: Demand Peak: 0.702521 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 71 of 112 Test Report TL1316 8228 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-G509 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702045 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 72 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA EDS-P510 Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.702897 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 73 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration – MOXA VPORT-351-M-SC Project File Name: mstest07g.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 23.000 profile(f) 10.000 high-abort(f) low-abort(f) high-alarm(f) low-alarm(f) 1.0000 input2(f) control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.985077 Hz Control Peak: Demand Peak: 0.702296 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 74 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration Moxa SPL-24 07-59-57 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.923553 Hz Control Peak: Demand Peak: 0.703032 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 75 of 112 Test Report TL1316 8226 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Side to Side Vibration Moxa G205 16-57-17 Project File Name: marine test.prj Profile Name: General Vibration Strain, Class A Test Type: Swept Sine Run Folder: .\RunDefault gn 45.000 profile(f) high-abort(f) 10.000 low-abort(f) high-alarm(f) low-alarm(f) input2(f) 1.0000 control(f) 0.1000 0.0100 0.0070 0.4000 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.00 Frequency (Hz) Level: Frequency: 0 dB 99.997383 Hz Control Peak: Demand Peak: 0.700833 gn 0.700000 gn Full Level Cycles: Time Remaining: Page 76 of 112 Test Report TL1316 8231 00:00:00 Sweep Type: Sweep Rate: Logarithmic 0.5 Oct/Min Page 77 of 112 Test Report TL1316 Page 78 of 112 Test Report TL1316 Page 79 of 112 Test Report TL1316 Page 80 of 112 Test Report TL1316 Page 81 of 112 Test Report TL1316 Page 82 of 112 Test Report TL1316 Page 83 of 112 Test Report TL1316 Page 84 of 112 Test Report TL1316 Page 85 of 112 Test Report TL1316 Page 86 of 112 Test Report TL1316 Page 87 of 112 Test Report TL1316 Page 88 of 112 Test Report TL1316 Page 89 of 112 Test Report TL1316 Page 90 of 112 Test Report TL1316 Page 91 of 112 Test Report TL1316 Page 92 of 112 Test Report TL1316 Page 93 of 112 Test Report TL1316 Page 94 of 112 Test Report TL1316 Page 95 of 112 Test Report TL1316 Page 96 of 112 Test Report TL1316 Page 97 of 112 Test Report TL1316 Page 98 of 112 Test Report TL1316 Page 99 of 112 Test Report TL1316 Page 100 of 112 Test Report TL1316 Page 101 of 112 Test Report TL1316 Page 102 of 112 Test Report TL1316 Page 103 of 112 Test Report TL1316 Page 104 of 112 Test Report TL1316 Page 105 of 112 Test Report TL1316 Page 106 of 112 Test Report TL1316 Page 107 of 112 Test Report TL1316 Page 108 of 112 Test Report TL1316 Start of testing 1 After Low Temp After High Voltage After High Humidity End of testing EDS-72810G IM-4TX IM-4MSC IM-4SSC IM-2MSC/2TX IM-2MST/2TX IM-2SSC/2TX >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ IM-2GTX IM-2GSFP SFP-1GLXLC SFP-1G10ALC SFP-1G10BLC 2 EDS-G509 >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 3 EDS-408A-3M-SC >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 4 EDS-408A-2M1S-SC >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 5 EDS-P510 >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 6 EDS-305-M12 >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 7 8 EDS-208A-MM-SC EDS-205A >200MΩ >200MΩ >200MΩ >200MΩ >200MΩ >200MΩ >100MΩ >100MΩ >200MΩ >200MΩ 9 EDS-P308-MM-SC >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 10 SPL-24 >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 11 12 EDS-G308 EDS-G308-2SFP >200MΩ >200MΩ >200MΩ >200MΩ >200MΩ >200MΩ >100MΩ >100MΩ >200MΩ >200MΩ 13 EDS-G205 >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ 14 VPort 351-M-SC >200MΩ >200MΩ >200MΩ >100MΩ >200MΩ Page 109 of 112 Test Report TL1316 Color Scheme models tested Managed switch EDS-828/728 series EDS-G509 series EDS-408A EDS-82810G EDS-G509 EDS-408A-3M-SC EDS-P510 EDS-72810G EDS-G509-T EDS-408A-3M-ST EDS-P510-T IM-4TX EDS-408A-2M1S-SC IM-4MSC EDS-408A-2M1S-ST IM-4MST EDS-408A-3S-SC IM-4SSC EDS-408A-3S-ST IM-2MSC/2TX EDS-408A-1M2S-SC IM-2MST/2TX EDS-408A-1M2S-ST IM-2SSC/2TX EDS-408A-3M-SC-T IM-1LSC/3TX EDS-408A-3M-ST-T IM-2GTX EDS-408A-2M1S-SC-T IM-2GSFP EDS-408A-2M1S-ST-T EDS-P510- Series EDS-408A-3S-SC-T EDS-518A series Optional Accessary EDS-408A-3S-ST-T SFP-1G series EDS-408A-1M2S-SC-T SFP-1GSXLC EDS-408A-1M2S-ST-T SFP-1GLSXLC SFP-1GLXLC SFP-1GLHXLC SFP-1GZXLC SFP-1GEZXLC SFP-1GSXLC-T SFP-1GLSXLC-T SFP-1GLXLC-T SFP-1GLHXLC-T SFP-1GZXLC-T SFP-1G10ALC SFP-1G10BLC SFP-1G20ALC SFP-1G20BLC SFP-1G40ALC SFP-1G40BLC SFP-1G10ALC-T SFP-1G10BLC-T SFP-1G20ALC-T SFP-1G20BLC-T SFP-1G40ALC-T SFP-1G40BLC-T Page 110 of 112 Test Report TL1316 Color Scheme models tested Unmanaged Switch EDS-305 series EDS-200A series EDS-P308 Series EDS-G308 series EDS-G205 series EDS-305-M12 EDS-208A EDS-P308 EDS-G308 EDS-G205 EDS-305-M12-T EDS-208A-M-SC EDS-P308 EDS-G308-2SFP EDS-G205-T EDS-208A-M-ST EDS-P308-M-SC EDS-G308-T EDS-208A-S-SC EDS-P308-S-SC EDS-G308-2SFP-T EDS-208A-MM-SC EDS-P308-MM-SC EDS-208A-MM-ST EDS-P308-SS-SC Optional Accessary EDS-208A-SS-SC EDS-P308-T SFP-1FE series EDS-205A EDS-P308-M-SC-T SFP-1FEMLC-T EDS-208A-T EDS-P308-S-SC-T SFP-1FESLC-T EDS-208A-M-SC-T EDS-P308-MM-SC-T SFP-1FELLC-T EDS-208A-M-ST-T EDS-P308-SS-SC-T EDS-208A-S-SC-T SPL-24 Series EDS-208A-MM-SC-T SPL-24 EDS-208A-MM-ST-T SPL-24-T EDS-208A-SS-SC-T EDS-205A-T Page 111 of 112 Test Report TL1316 Color Scheme models tested Video Server VPort 351 series VPort 351 VPort 351-M-SC VPort 351-S-SC VPort 351-T VPort 351-M-SC-T VPort 351-S-SC-T Page 112 of 112 Test Report TL1316