ACOUSTIC MEASUREMENTS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, T.R. Blackburn and Z. Liu School of Electrical Engineering and Telecommunications University of New South Wales, Australia Abstract: The acoustic pressure waves associated with partial discharges in HV power transformers can be detected with external piezoelectric sensors. The propagation time and the waveshape of the received signals are affected by factors such as the sensor position, internal barriers and sensor type. These are investigated in this paper. In particular, it is shown that the commonly-used resonant sensor gives a cleaner signal. On the other hand, the wideband sensor enables comparison between low and high frequency components. It was found that as the sensor is closer to the normal, the higher frequency components become more dominant. This can be utilised as a new diagnostic method for discharge location. The wavelet transform is used to show changes in the frequency distribution via the time-scale plot and also to de-noise the signal. 1. INTRODUCTION Electrical insulation plays an important role in the performance of high-voltage apparatus as it has to withstand high electrical stress during operation. Most power equipment failures are caused by breakdowns of the insulation. This in turn is often the consequence of gradually and cumulatively damaging effects of partial discharges (PD) on the insulation over the years. Partial discharges are indicative of some defects within the insulation. Hence, their early detection can facilitate appropriate repair and prevent costly breakdowns. In HV oil-filled power transformers, PDs generate high-frequency electrical pulses and ultrasonic pressure waves. The latter can propagate through the oil volume inside the transformer and eventually reach the tank wall. Such a pressure disturbance can be detected with external piezoelectric sensors. The relative difference in the propagation times of the signals from several sensor positions (or with respect to the electrical signal) can be used to determine the discharge location. This provides a simple and convenient on-line diagnostic method for locating the discharge site [1-2]. In practice, the location accuracy is often poor due to the complex nature of the acoustic signals which travel from the source to the sensor via various paths through the oil and the tank wall with different propagation velocities. Complications also arise due to the effects of signal attenuations, reflections, refractions, mechanical noise or reverberations, multiple discharge sources and the presence of internal solid barriers (transformer core, windings, pressboards). As such, correct location results are limited to situations where there is a single dominant discharge source occurring near the surface or outside the transformer windings. Extensive research has been carried out with the aim of improving the location accuracy, e.g. [3-7]. This paper provides further insight about some of the above-mentioned problems which influence the waveshapes of the detected acoustic signals and propagation time. Using a real transformer tank setup in the laboratory, measurements are carried out with different types of sensors and internal barriers. The sensor position in relation to the discharge is varied. The possibility of recognising different modes of signal propagation based on their Fourier spectrum characteristics is explored. The wavelet transform (WT), a new technique for analysing transient signals, is utilised to characterise the acoustic waveforms. The use of WT to denoise the signal is also investigated. 2. ULTRASONIC SIGNAL PROPAGATION There are two types of pressure waves: longitudinal and shear. For the longitudinal waves, the motion of the medium is purely in the direction of propagation. With the shear waves, the motion is transverse to the direction of propagation. Liquids only support the longitudinal waves. For transformer oil under normal operating conditions, the propagation velocity is v l ≅ 1400m / s . Transformer tanks are usually made of steel for which the longitudinal waves travel faster than the shear waves: v l ≅ 5900m / s and v s ≅ 3200m / s . A PD pulse creates a spherical pressure wave of a longitudinal nature in the oil which then excites a longitudinal wave and a shear wave in the transformer tank. Analogous to ray optics, this can be treated as equivalent to an infinite number of ‘beams’ originating from the discharge site and propagating equally in all directions, each arriving at the tank wall with a different incident angle θ. Thus, apart from the direct path (straight line between the PD source and the sensor), there are many other indirect paths that the ultrasonic signal can travel before reaching the sensor. Because of the higher propagation velocitity in steel, the direct path – althought the shortest - is not necessarily the quickest path. Discharge source Fig.2: Method of measuring the propagation time. ψ Y θ Tank wall x Sensor X Fig.1: Model for ultrasonic wave propagations. Consider Figure 1 where the sensor is at an angle ψ from the normal. The time it takes for the signal which follows the path shown in the figure to reach the sensor is: x2 +Y 2 X − x + (1) v oil v steel The quickest path can be found by setting dt / dx = 0 and solve for x. This corresponds to the case where θ is equal to the critical incidence angle: v α = sin −1 oil (2) v steel and the quickest propagation time is: Y X − Y tan α ts = + (3) v oil . cos α v steel Equation 3 is valid only if ψ > α . If ψ ≤ α , the direct path (i.e. θ = ψ ) is the quickest path. The propagation time for the direct path is: t= td = different paths. However, the signal from the quickest path is the most critical as it constitutes the wavefront of the composite signal. The start of this wavefront is used in the measurement of the propagation time. X 2 +Y 2 v oil (4) In the above equations, v oil and v steel are the longitudinal propagation velocities in oil and steel respectively. The resultant composite signal picked up by the sensor is an overlapping of signals travelling through many There are two main techniques for locating the discharge source. One common method is to simultaneously record the electrical and ultrasonic signals. Figure 2 is an example using a digital storage oscilloscope. By taking the electrical signal as the reference, the propagation time of the ultrasonic signal can be determined. This in turn can be used to calculate the distance between the discharge source and the sensor (assuming straight line propagation). Hence the locus of possible discharge locations would be part of the sphere lying inside the transformer tank boundary with the sensor as the centre. Measurements at other sensor positions would give additional loci and their intersections would provide the discharge location. The assumption of straight-line propagation would result in error in the measurement of the propagation time. The absolute error is: (5) ∆t = t s − t d For ease of demonstrating the magnitude of this error, assume that the PD source is close to the tank wall so that X >> Y . Substitute Eqs.3&4 into Eq.5: 1 1 . X (6) ∆t ≈ − v oil v steel The relative error is: ∆t v steel − v oil ≈ (7) td v steel Thus the absolute error tends to increase linearly with the distance between the sensor and the normal. On the other hand the relative error remains constant but is large (76%). 3. SETUP AND MEASUREMENT RESULTS The experiment was set up using an actual transformer tank but with the core and windings removed (Figure 3). The dimension of this tank, made from 10mm thick steel, is 900mm (H) x 1100mm (W) x 600mm (D). Tank wall barrier 35cm PD source O C sensor 30cm 50cm B sensor A sensor TOP VIEW Fig.5: Locations of the discharge source and sensors. Fig.3: Transformer tank. The test circuit is shown in Figure 4. A point-to-plane electrode system, suspended in the oil, was used as the discharge source. The discharge level, measured with a conventional PD detector, was about 1000pC at 20kV applied voltage. The position of the discharge source was fixed for all the measurements taken. The positions of the PD source and the sensors are shown in Figure 5. A number of different sensors were tested. The PAC (type R15I) are resonant sensors with built-in 40dB pre-amplifier. The typical operation range is from 100kHz to 450kHz and the resonant frequency is ~160kHz. The B&K (type 8312) are broad-band sensors operating over a wider frequency band. The response is flat within 10dB over the range 100kHz to 1MHz. The PAC (type D9241A) is a lowfrequency sensor. The typical operation range is from 30kHz to 70kHz. A high-frequency CT clipped onto the earth lead picks up the electrical PD signal. This is used as the time reference to determine the propagation time of the acoustic signals. 55kV Transformer 30kΩ Voltmeter DSO Bushing ch2 Oil level 0.5m deep Point-plane PD source ch1 Fig.6: Resonant sensor at point A. Pressure wave Ultrasonic sensor HF CT Fig.4: Test circuit arrangement. The ultrasonic pressure waves created by the discharge are detected by the piezoelectric sensors. These sensors were clamped onto the outer walls of the transformer tank using magnets. To enable better coupling of the pressure waves, a thick layer of grease was applied to the surface of the sensors before they are attached to the tank wall. The PD source and the sensors are placed on the same horizontal plane which is 35cm above the bottom of the tank. Fig.7: Resonant sensor at point B. Fig.6 shows the time-domain waveform of the acoustic signal using the resonant sensor at point A. As the sensor is at the normal, the direct path is the quickest. The predicted propagation time is 214µs as compared to the measured value of 216µs. Note that in this case, the acoustic signal has a sharp wavefront with the magnitude reaching its maximum almost at the beginning. Fig.8: Resonant sensor at point C. Fig.9: Resonant sensor at point C, metal barrier. Fig.10: Resonant sensor at C, cylinder barrier. Fig.7 corresponds to the resonant sensor at point B. From Eq.2, the critical incidence angle is 13.73o. This translates to a distance of 7.33cm from point A. Hence point B is well outside the critical angle. Compared to the previous case (Fig.6), there is a marked difference in the wavefront. The signal is relatively small for some time before its magnitude changes suddenly. The latter corresponds to the arrival of the direct path signal. Using Eq.3, the propagation time for the quickest path is 293µs. This agrees well with the measured value of 300µs. The calculated propagation time for the direct path is 417µs. The time difference is significant. Thus for discharge location, it is important to distinguish between direct and indirect path propagation. As demonstrated in Figs.6 and 7, this can be achieved by carefully examining the time-domain waveforms of the received signals. For Fig.7, the arrival of the direct path signal can be located by ignoring the smaller oscillations in the wavefront. This gives a value of 380µs as compared to the expected value of 417µs. If the measurement is based on the largest oscillation, the result is 450µs. Internal barriers increase the complexity of the received signals. Fig.8 shows the results for the resonant sensor on the normal at point C without the barrier (a flat 10mm thick steel plate). The predicted propagation time is 250µs which agrees with the measured value. As expected, the waveform is similar to that of Fig.6 with a sharp and large wavefront. With the barrier present, the result is shown in Fig.9. Although there is no noticeable time shift, the relative magnitude of the wavefront is reduced. The waveform is somewhat similar to Fig.7. Thus, although the sensor is on the normal, its time-domain waveform tends to indicate otherwise. Instead of the metal plate barrier, the discharge source was put inside a cylindrical metal barrier (30cm diameter). The waveform, shown in Fig.10, is still somewhat similar to Fig.9. However, there is a noticeable increase in the propagation time, 275µs as compared to the expected value of 250µs. Although the cylindrical barrier has an open top, it can be seen that it is more effective in blocking the propagation of the pressure waves. For comparison with Figs.6 and 7, the results using the wideband sensor are shown in Figs.11 and 12. The waveforms are much noisier due to the wider bandwidth. Also shown are the corresponding frequency spectra. The higher frequency components in the 400-500kHz range are clearly dominant in Fig.11 but become negligible in Fig.12. This suggests a new discharge location technique. By using a wideband sensor, one can vary the sensor location until the higher frequency components in the detected signal are maximised. This would correspond to the sensor at the normal. Note that the commonly used resonant sensor is not suitable as the frequency of interest is outside its range. transformation of the signal from the time domain to the frequency domain causes its time information to be lost. This is undesirable, particularly when the signal is non-stationary and its transitory characteristics are important. The Wavelet Transform produces a timescale view of the signal. In essence, the technique decomposes a signal into shifted and scaled versions of an original wavelet. The mathematical details of wavelet analysis can be found in numerous textbooks, e.g. [8]. The computations in this paper made use of the Wavelet Toolbox [9] which is a collections of functions run under the MatLab environment. Absolute Values of Ca,b Coefficients for a = 2 4 6 8 10 ... 122 114 106 98 90 scales a 82 74 66 58 50 42 34 26 18 Fig.11: Wideband sensor at point A. 10 2 0.5 1 1.5 time (or space) b 2 2.5 4 x 10 (a) Absolute Values of Ca,b Coefficients for a = 2 4 6 8 10 ... 122 114 106 98 90 scales a 82 74 66 58 50 42 34 26 18 10 2 0.5 1 1.5 2 2.5 3 time (or space) b 3.5 4 4.5 5 4 x 10 (b) Fig.13: Wavelet transforms. Fig.12: Wideband sensor at point B. 4. ANALYSIS USING WAVELET TRANSFORM The well-known Fourier transform decomposes a signal into consituent sinusoids of different frequencies (fundamental and harmonics). Such a The time-scale plots of the wavelet coefficients for the wideband signals (Figs.11 and 12) are shown in Fig.13. The x-axis represents position along the signal (time) and the y-axis represents scale. The colour at each point on the plot represents the magnitude of the wavelet coefficient. The darker shades correspond to smaller coefficients. Note the large coefficients occurring at the wavefront in Fig.13(a). The received signal such as that in Fig.11 is noisy and hence it is difficult to recognise the wavefront associated with the quickest path. Wavelet decomposition can be used to remove the highfrequency noise from the signal. Successive approximations become less noisy as more high frequency information is filtered out. Thus this provides a simple method to de-noise the signal. The signal of Fig.11 was de-noised using level-5 approximation and Daubechies db3 wavelet. It was found that in comparison to the original, the de-noised signal is much cleaner but the fast changing features of the original signal is lost. In particular, the smoothing effect on the wavefront would reduce the accuracy of the measurement of the propagation time. 60 give a low noise signal. For propagation time measurements, this is advantageous. Although the wideband sensors give a noisier signal, the sensor position in relation to the discharge source can be determined by analysing the higher frequency components of the spectra. This can be utilised as a new method for discharge location. To a certain extent, it is possible to distinguish between direct and indirect path propagations by examining the time-domain waveforms. However, it was shown that the presence of internal barriers could alter not only the received waveforms but also the propagation time. 40 The time-scale plot of the wavelet transform is an interesting and informative way to view the signals. The technique can also be utilised to de-noise the signals and thus enhance the detection sensitivity. 20 0 -20 -40 6. REFERENCES -60 -80 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 (a) 60 40 20 0 -20 -40 -60 -80 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 (b) Fig.14: Original and de-noised signals. An alternative to overcome such a problem is the technique called thresholding whereby the details are discarded only if the magnitudes exceed a certain limit. The procedure is to examine the details vectors of the wavelet decomposition, select the appropriate threshold coefficients and reconstruct the new details signals. The Matlab toolbox provides two calling functions: one to calculate the default threshold parameters and the other to perform the actual denoising. Applying these functions, the result is shown in Fig.14(b) which clearly reveals the smaller oscillations at the wavefront. 5. CONCLUSIONS In this paper, the acoustic signals produced by partial discharges in oil-filled transformers were studied. It was shown that the commonly used resonant sensors [1] E. Howells and E.T. Norton, “Detection of partial discharges in transformers using acoustic emission techniques”, IEEE Trans., Vol. PAS-97, No.5, 1978, pp.1538-1549. [2] R.T. Harold, “Acoustical techniques for detecting and locating electrical discharges”, Engineering Dielectrics, Vol.1, Chapt. 10, ASTM Publications, STP 669, 1979 [3] B.T. Phung, R.E. James, T.R. Blackburn and Q. Su, "Partial discharge ultrasonic wave propagation in steel transformer tanks", Paper 74.04, 7th Int. Symp. On High Voltage Engineering, Dresden, Germany, Aug. 1991, pp.131-134. [4] L. E. Lundgaard, "Partial Discharge- Part XIV: Acoustic Partial Discharge Detection- Practical Application", IEEE Electrical Insulation Magazine, Vol. 8, No. 5, Sept/Oct 1992. [5] P. M. Eleftherion, "Partial Discharge XXI: Acoustic Emission- Based PD Source Location In Transformers", IEEE Elec. Insulation Magazine, Vol. 11, No. 6, Nov/Dec 1995. [6] T. Bengtsson and H. Kols, "Transformer PD Diagnosis using Acoustic Emission Technique", 10th Int. Symp. on HV Engineering, Montreal, Quebec, Canada, August 25-29, 1997. [7] S.B. Tok, “Acoustic detection of partial discharge – Effect of PD waveforms”, B.E. Thesis, June 2000, University of NSW. [8] C.K. Chui, An Introduction to Wavelets, Academic Press, 1992. [9] M. Misiti,, Y. Misiti, G. Oppenheim and J. Poggi, Wavelet Toolbox for Use with MatLab, The Math Works Inc., 1996.