Model EM16-E-LP

advertisement
Project:
Type:
Catalog #:
Model EM16-E-LP
Two Headed Low Profile Emergency Light w/ MR16 Lamps
HOUSING
-- Sleek curved appearance
-- Injection molded, engineering-grade, UV-stable thermoplastic
-- UL94V-0 flame rating
-- Impact, scratch, fade and corrosion-resistant
-- Snap-fit housing and mounting plate
-- Universal mounting plate with quick-connect feature reduces
installation labor
-- White or black textured finish
ELECTRICAL
-- Dual voltage 120/277VAC
-- Rated for use in damp locations
-- Solid state charging and switching
-- Brownout protection
-- Battery low voltage disconnect (LVD)
-- Overload and short circuit protection
-- AC power indicator and test switch
LAMPS
-- Supplied with 12W MR16 Halogen lamps
-- Other lamping options available
BATTERY
-- Maintenance-free 6V or 12V sealed lead acid battery
-- Standard battery will operate fixture for a minimum of 90
minutes in the event of a power outage
-- Recharge time 24 hours
-- 20oC / 68oF - 30oC / 85oF
5.875"
5.5"
CODE COMPLIANCE
-- UL924 Listed for Damp Locations
-- NFPA 101 Life Safety Code compliant
-- NEC and OSHA compliant
12.125"
WARRANTY
-- 5 year warranty
ORDERING INFORMATION
MODEL
VOLTAGE
EM16-E-LP
6V
12V
MODEL
WATTAGE
VOLTAGE
-
OPTIONS
25
50
BLK - Black
SD - Self Diagnostics
25W - 25W Halogen Lamps MR-16 Lamps
WATTAGE
-
OPTIONS
-
Specifications and dimensions subject to change without notice.
EELP • 2577 Neshaminy Interplex Dr. - KOR A, Suite 102 - Trevose, PA 19053 • Phone: 800-490-4496 • Fax: 877-634-6887 • www.eelp.net
EM16-E-LP 072114
Self-Diagnostics (Option: SD)
The self diagnostic circuit continuously monitors the operating condition of the AC power, battery supply voltage,
emergency lamp continuity and charging circuit.
The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery
charger. If a failure is detected, visual status will occur immediately via the CHARGER LED and/or the BATTERY FAULT
LED. The LEDs will stay illuminated until the fault is corrected.
The self diagnostic circuit also monitors the transfer circuit as well as performing automatic code compliant testing. The
self diagnostic circuit will perform a 30 second discharge and self-test every 28-30 days. A 90 minute discharge and
self-test is performed every 6 months.
Damp Location Rated
Damp location rating ensures the fixture is designed to operate safely in outdoor locations that are protected from the
direct elements. Damp location rated fixtures may be installed indoors. Products with damp location ratings are not
designed to withstand constant or significant moisture or direct contact with water or steam.
12W MR16 lamping mounted at 7.5'
12W MR16 lamping mounted at 7.5'
40'
30'
6'
3'
25W MR16 lamping mounted at 7.5'
25W MR16 lamping mounted at 7.5'
50'
40'
3'
6'