(EPR) insulated cable with 133% insulation level.

advertisement
CERRITOS COLLEGE
100% CONSTRUCTION DOCUMENTS 6/01/2015
B. Product Description: Single conductor, NEMA WC 8, ethylene propylene rubber (EPR) insulated
cable with 133% insulation level. UL listed as Type MV-105 and sunlight resistant in accordance
withUL 1072.
C.
Voltage: 5kV.
D. Conductor: Single conductor, uncoated copper, compact stranded per ASTM B-496.
E.
Strand Screen: Extruded semiconducting EPR strand screen. Meet or exceed electrical and
physical requirements of ICEA S-93-639/NEMA SC74 & S-97-682, AEIC CS8, and UL 1072.
F.
Insulation: EPR. Meet or exceed electrical and physical requirements of ICEA S-93-639/NEMA
WC74 & S-97-682, AIEC CS8, and UL 1072.
G. Insulation Screen: Extruded semiconducting EPR insulation screen. Meet or exceed electrical and
physical requirements of ICEA S-93-639/NEMA SC74 & S-97-682, AEIC CS8, and UL 1072.
H. Shield: 5 mil bare copper tape helically applied.
I.
2.2
Jacket: PVC, 80 mils minimum thickness. Meet or exceed electrical and physical requirements of
ICEA S-93-639/NEMA WC74 & S-97-682, and UL 1072 for polyvinyl chloride jackets.
SEPARABLE CONNECTORS
A. Manufacturers:
1. Cooper Separable Connector System.
2. Thomas & Betts.
3. Substitutions: Not Permitted.
B. Product Description: Complete separable connector system using loadbreak/deadbreak elbows
with bolted connections and deadfront modular construction for splicing and connection of
medium voltage feeders and equipment.
C. Standards: Design, manufacture, and test all components to IEEE Standard 386 (Separable
Insulated Connector Systems). Provide all components from same manufacturer.
D. Materials: Use copper bus and connection components for all components of the separable
connector system.
E.
Separable Connectors
1. Cooper Power Systems: Model 625 Series BOL-T type elbows. Sizes to match cable type
and dimensions.
2. Accessories: Insulating plug with test point, test point on the T-body, compression lugs,
cable adapters, connecting plug, shield adaptor, grounding kit, and jacket seals.
3. Current Ratings: 600 Amp Continuous; 25kA sym., 10 cycles; lOkA sym, 3 seconds.
4. Voltage Ratings:
a.
15kV Class.
b. 15.2kV Phase-to-Ground.
c. 28kV Phase-to-Phase.
CAMPUS ELECTRICAL & CHILLED WATER UPGRADE
Bid No. 14P019
MEDIUM-VOLTAGE CABLES - 26 05 13
Page 3 of 6