CERRITOS COLLEGE 100% CONSTRUCTION DOCUMENTS 6/01/2015 B. Product Description: Single conductor, NEMA WC 8, ethylene propylene rubber (EPR) insulated cable with 133% insulation level. UL listed as Type MV-105 and sunlight resistant in accordance withUL 1072. C. Voltage: 5kV. D. Conductor: Single conductor, uncoated copper, compact stranded per ASTM B-496. E. Strand Screen: Extruded semiconducting EPR strand screen. Meet or exceed electrical and physical requirements of ICEA S-93-639/NEMA SC74 & S-97-682, AEIC CS8, and UL 1072. F. Insulation: EPR. Meet or exceed electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AIEC CS8, and UL 1072. G. Insulation Screen: Extruded semiconducting EPR insulation screen. Meet or exceed electrical and physical requirements of ICEA S-93-639/NEMA SC74 & S-97-682, AEIC CS8, and UL 1072. H. Shield: 5 mil bare copper tape helically applied. I. 2.2 Jacket: PVC, 80 mils minimum thickness. Meet or exceed electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, and UL 1072 for polyvinyl chloride jackets. SEPARABLE CONNECTORS A. Manufacturers: 1. Cooper Separable Connector System. 2. Thomas & Betts. 3. Substitutions: Not Permitted. B. Product Description: Complete separable connector system using loadbreak/deadbreak elbows with bolted connections and deadfront modular construction for splicing and connection of medium voltage feeders and equipment. C. Standards: Design, manufacture, and test all components to IEEE Standard 386 (Separable Insulated Connector Systems). Provide all components from same manufacturer. D. Materials: Use copper bus and connection components for all components of the separable connector system. E. Separable Connectors 1. Cooper Power Systems: Model 625 Series BOL-T type elbows. Sizes to match cable type and dimensions. 2. Accessories: Insulating plug with test point, test point on the T-body, compression lugs, cable adapters, connecting plug, shield adaptor, grounding kit, and jacket seals. 3. Current Ratings: 600 Amp Continuous; 25kA sym., 10 cycles; lOkA sym, 3 seconds. 4. Voltage Ratings: a. 15kV Class. b. 15.2kV Phase-to-Ground. c. 28kV Phase-to-Phase. CAMPUS ELECTRICAL & CHILLED WATER UPGRADE Bid No. 14P019 MEDIUM-VOLTAGE CABLES - 26 05 13 Page 3 of 6