This Datasheet is for the IC693MDL931 Isolated Relay Output, N.C. and Form C, 8 Amp - 8 Point http://www.cimtecautomation.com/parts/p-14678-ic693mdl931.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-30 module. For further information, please contact Qualitrol Technical Support at 1-800-784-9385 support@qualitrol.com 7 Discrete Output Modules Isolated Relay Output, N.C. and Form C, 8 Amp - 8 Point IC693MDL931 This 8 Amp Isolated Relay Output module for the Series 90-30 Programmable Logic Controller provides 4 normally-closed and 4 Form C relay circuits for controlling output loads provided by the user. The output switching capacity of each circuit is 8 amps for the normally-closed contacts or the normally open contacts. Each output relay is isolated from the other relays, and each relay has a separate common power output terminal. The relay outputs can control a wide range of user-supplied load devices, such as: motor starters, solenoids, and indicators. The user must supply the AC or DC power to operate the field devices connected to this module. There are no fuses on this module. LED indicators which provide the ON/OFF status of each point are located at the top of the module. The LEDs are arranged in two horizontal rows with eight green LEDs in each row. This module uses the top row labeled A1 through 8 (points 1 through 8) for output status; the bottom row is not used and the fuse LED is not used. An insert goes between the inside and outside surface of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is color-coded red to indicate a high-voltage module. This module can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC system. Table 7-17. Specifications for IC693MDL931 Rated Voltage 24 volts DC, 120/240 volts AC, 50/60 Hz (nominal – see the following table for exceptions) Output Voltage Range 5 to 30 volts DC 5 to 250 volts AC, 50/60 Hz Outputs per Module 8 isolated outputs Isolation 1500 volts between field side and logic side 500 volts between groups Maximum Load 8 amps resistive maximum per output 20 amps maximum per module for UL installations Minimum Load 10 mA Inrush Current 8 amps maximum for one cycle On Response Time 15 ms maximum Off Response Time 15 ms maximum Output Leakage Current 1 mA maximum at 250 volts AC, (25C (77F)) Internal Power Consumption 45 mA (all outputs on) from 5 volt bus on backplane 100 mA (all outputs on) from relay 24V bus on backplane Maximum load current is dependent upon ambient temperature as shown in graph on following page. Refer to Appendix B for product standards and general specifications. GFK-0898F Chapter 7 – Discrete Output Modules 7-33 7 IC693MDL931 Output Module Field Wiring Information The following figure provides wiring information for connecting user supplied load devices and power source to the 8 amp Isolated Relay Output module. a47015 MODULE CIRCUITRY TERMINALS 1 FIELD WIRING A1 N.C. 2 LED 3 V A2 N.C. 4 5 V A3 N.C. 6 7 V A4 N.C. 8 RELAY N.C. V A5 N.C. 9 10 RELAY N.C. 11 LED V A5 N.O. 12 A6 N.C. 14 A6 N.O. 13 V 15 A7 N.C. 16 RELAY N.O. V A7 N.O. 17 18 A8 N.C. 20 A8 N.O. V 19 Figure 7-31. IC693MDL931 Output Module Field Wiring 4A PER POINT a45145 32 6A PER POINT 8A PER POINT TOTAL 24 MODULE LOAD CURRENT 16 (AMPS) 8 35°C 10°C 45°C 20°C 30°C 40°C 50°C 60°C AMBIENT TEMPERATURE (°C) Figure 7-32. Load Current vs. Temperature for IC693MDL931 7-34 Series 90-30 PLC I/O Module Specifications – July 2000 GFK-0898F Discrete Output Modules 7 Table 7-18. Load Current limitations for IC693MDL931 Operating Maximum Current for Load Type Voltage 5 to 120 VAC 240 VAC 24 VDC Resistive Lamp or Solenoid Typical Contact Life (number of operations) 8 amps 3 amps 200,000 6 amps 2.5 amps 300,000 4 amps 1.5 amps 400,000 1 amp 0.5 amps 1,100,000 8 amps 3 amps 100,000 6 amps 2.5 amps 150,000 4 amps 1.5 amps 200,000 1 amp 0.5 amps 800,000 8 amps 3 amps 100,000 6 amps 2.5 amps 150,000 4 amps 1.5 amps 200,000 1 amp 0.5 amps 800,000 48 VDC 1.5 amps - 100,000 100 VDC 0.5 amps - 100,000 125 VDC 0.38 amps 0.12 amps 100,000 150 VDC 0.30 amps 0.10 amps 100,000 For inductive loads Relay contact life, when switching inductive loads, will approach resistive load contact life if suppression circuits are used. The following figures are examples of typical suppression circuits for AC and DC loads. The 1A, 200V diode shown in the DC load typical suppression circuit is an industry standard 1N4935. The resistor and capacitor shown for AC load suppression are standard components, available from most electronics distributors. AC LOADS a45151A IC693MDL931 DC LOADS 1A, 200V Output Module 2 IC693MDL931 .022 100 Ω Output Module 600V 1/2W 2 Load Coil 3 3 DC SUPPLY a45152A Load Coil ~ AC SOURCE Figure 7-33. Load Suppression Examples for IC693MDL931 Output Module GFK-0898F Chapter 7 – Discrete Output Modules 7-35