Rental Accessories
Power Distribution Packs
TM
D Kohler Rental Power provides one-source
responsibility for the generating system and
accessories.
D Select from a wide variety of power distribution
configurations to meet your application needs.
D Nine models are available with UL NEMA 3R listing.
D The rubber enclosure power distribution pack
typically has individual circuit breaker protection and
quick setup with color-coded, cam-type electrical
connections or a twist-lock connector.
30 Amp Quad Box
Model Number
DB200NT-ALL-S3
Agency Approval
UL NEMA 3R
Rating
150 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Five L21-30, 30 A,
120/208 V, 3-phase,
weatherproof receptacles
Breaker
Configuration
Five 30 A, 3-pole, branch
circuit-rated breakers
Overall Dimensions, 279 x 279 x 356
L x W x H, mm (in.) (11 x 11 x 14)
Weight, kg (lb.)
15.9 (35)
Model Number
7506G
Agency Approval
UL NEMA 3R
Rating
150 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Four male panel mount minicam connectors,
100 A/220 V
Output
Four 30A, TT--30R, 125 V, 1-phase straight blade
receptacle, see View A
Four 20 A, duplex 5-20R, 125 V, 1-phase
non-GFI receptacle, see View B
DB200NT-ALL-S3
30 Amp RV Distribution Box
G
G
7506G
View A
Breaker
Configuration
G32-4 11/04d Page 1
View B
Four 30 A, 1-pole branch circuit-rated breakers
Four 20 A, 1-pole branch circuit-rated breakers
Overall Dimensions, 533 x 381 x 279
L x W x H, mm (in.) (21 x 15 x 11)
Weight, kg (lb.)
W
13.2 (29)
50 Amp RV to 6-5/20 NEMA
Model Number
DB50A-SPZ620FT
Agency Approval
UL NEMA 1
Rating
50 A, 120/240 V, 1-phase, 60 Hz, 3-wire
Input
One CS63-65, 50 A plug, one feed through
CS63-69, 50 A, single locking receptacle
Output
Six 20 A duplex receptacles,
5-20R 125 V, non GFI
G
W
Breaker
Configuration
Six 20 A, 1-pole, branch
circuit-rated breakers
Overall Dimensions, 358.3 x 368.3 x 317.5
L x W x H, mm (in.) (14.5 x 14.5 x 12.5)
DB50A-SPZ620FT
Weight, kg (lb.)
12.2 (27)
Model Number
DB100A-SPZ1000
Agency Approval
UL NEMA 3R
Rating
100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Five L21-20, 20 A,
120/208 V, 3-phase,
weatherproof receptacles
Breaker
Configuration
Five 20 A, 3-pole, branch
circuit-rated breakers
100 Amp Quad Box
DB100A-SPZ1000
Overall Dimensions, 317.5 x 317.5 x 317.5
L x W x H, mm (in.) (12.5 x 12.5 x 12.5)
Weight, kg (lb.)
12 (26.5)
Model Number
DB100A-SPZ6369
Agency Approval
UL NEMA 3R
Rating
100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Four CS-63-69, 50 A,
125/250 V, 1-phase,
4-wire, weatherproof
locking receptacles
100 Amp RV Distribution Box
Y
X
W
G
Breaker
Configuration
Four 50 A, 2-pole, branch circuit-rated breakers
Overall Dimensions, 317.5 x 317.5 x 317.5
L x W x H, mm (in.) (12.5 x 12.5 x 12.5)
Weight, kg (lb.)
DB100A-SPZ6369
G32-4 11/04d Page 2
12.2 (27)
100 Amp Minicam Distribution Box
Model Number
DBSPZ-100A-MC
Agency Approval
UL NEMA 3R
Rating
100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Two rows 60 A, 220 V, 1-phase, panel mount
minicams
Two rows 100 A, 220 V, 1-phase, panel mount
minicams
Breaker
Configuration
Two 60 A, 2-pole, branch circuit-rated breakers
Two 100 A, 2-pole, branch circuit-rated breakers
Overall Dimensions, 317.5 x 317.5 x 317.5
L x W x H, mm (in.) (12.5 x 12.5 x 12.5)
Weight, kg (lb.)
14.5 (32)
DBSPZ-100A-MC
100 Amp 3-Phase to Multiple 30 Amp and 20 Amp, 1-Phase Outputs
Model Number
DBC100DP-A4T3
Agency Approval
UL NEMA 3R
Rating
100 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five male panel mount cams, 16 series
Output
Two 30 A, TT-30R, 125 V, 1-phase, straight blade
receptacles, see View A
Two 30 A, L5-30R, 125 V, 1-phase, locking
receptacles, see View B
Two 30 A, L6-30R, 250 V, 1-phase, locking
receptacles, see View C
One 30 A, L14-30R, 125/250 V, 1-phase, locking
receptacle, see View D
One 20 A, L6-20R, 250 V, 1-phase, locking
receptacle, see View E
G
DBC100DP-A4T3
View A
View D
Breaker
Configuration
View B
View E
Four 30 A, 1-pole branch circuit-rated breakers
Three 30 A, 2-pole branch circuit-rated breakers
One 20 A, 2-pole branch circuit-rated breaker
Overall Dimensions, 279.4 x 279.4 x 330.2
L x W x H, mm (in.) (11 x 11 x 13)
Weight, kg (lb.)
G32-4 11/04d Page 3
View C
14.5 (32)
200 Amp Quad Box
Model Number
DB200A-F201000
Agency Approval
UL NEMA 3R
Rating
200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five male panel mount cams, 16 series
Output
Ten L21-20, 20 A,
120/208 V, 3-phase,
weatherproof receptacles
Breaker
Configuration
Ten 20 A, 3-pole, branch circuit-rated breakers
Overall Dimensions, 381 x 444.5 x 558.8
L x W x H, mm (in.) (15 x 17.5 x 22)
Weight, kg (lb.)
28.6 (63)
Model Number
DB200A-XO16369
Agency Approval
UL NEMA 3R
Rating
200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Eight CS-63-69, 50 A,
125/250 V, 1-phase,
4-wire, weatherproof
locking receptacles
DB200A-F201000
200 Amp RV Distribution Box
Y
X
W
G
Breaker
Configuration
Eight 50 A, 2-pole, branch
circuit-rated breakers
Overall Dimensions, 508 x 508 x 355.6
L x W x H, mm (in.) (20 x 20 x 14)
Weight, kg (lb.)
24 (53)
Model Number
DBXO1/6CAM
Agency Approval
UL NEMA 3R
Rating
200 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five inline male cam connectors, 16 series tails
Output
Six rows 100 A, 220 V, 1-phase, panel mount
minicams
DB200AXO16369
200 Amp Minicam Distribution Box
Breaker
Configuration
Six 100 A, 2-pole, branch circuit-rated breakers
Overall Dimensions, 508 x 508 x 355.6
L x W x H, mm (in.) (20 x 20 x 14)
Weight, kg (lb.)
DBXO1/6CAM
G32-4 11/04d Page 4
24.9 (55)
400 Amp Multibox
Model Number
DBF20-MULTI
Agency Approval
UL NEMA 3R
Rating
400 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five male panel mount cams, 16 series
Output
Two rows 100 A, 220 V, 3-phase, panel mount
minicams; two L21-20, 20 A, 120/208 V, 3-phase,
weatherproof receptacles; see View A
Three CS63-69, 50 A, 125/250 V, 1-phase, 4-wire,
weatherproof locking receptacles; see View B
Four 20 A, 125 V duplex receptacles; see View C
Y
G
X
W
W
View A
DBF20-MULTI
Breaker
Configuration
View B
G
View C
Two 100 A, 3-pole, branch circuit-rated breakers
Two 20 A, 3-pole, branch circuit-rated breakers
Three 50 A, 2-pole, branch circuit-rated breaker
Four 20 A, 1-pole, branch circuit-rated breakers
Overall Dimensions, 381 x 444.5 x 558.8
L x W x H, mm (in.) (15 x 17.5 x 22)
Weight, kg (lb.)
31.8 (70)
Model Number
DB400A-F202000
Agency Approval
UL NEMA 3R
Rating
400 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Five male panel mount cams, 16 series
Output
Four rows 100 A, 208 V, 3-phase, female panel
mount cams, 16 series
Breaker Config.
Four 100 A, 3-pole, branch circuit-rated breakers
400 Amp Cam-Type Breakout Box
Overall Dimensions, 381 x 444.5 x 558.8
L x W x H, mm (in.) (15 x 17.5 x 22)
Weight, kg (lb.)
34 (75)
Model Number
DB800-5704200
Agency Approval
UL NEMA 3R
Rating
600 A, 208Y/120 V, 3-phase, 60 Hz, 4-wire
Input
Two male panel mount cams, 3-phase, 16 series
Two rows of five for parallel input cables
Output
Three rows 200 A, 3-phase, female panel mount
cams, 16 series
Breaker Config.
Three 200 A, 3-pole, branch circuit-rated
DB400A-F202000
600 Amp Cam-Type Breakout Box
Overall Dimensions, 622.3 x 530.7 x 383.7 (24.5 x 20.5 x 15.5)
L x W x H, mm (in.) with 88.9 (3.5) skids
Weight, kg (lb.)
DB800-5704200
G32-4 11/04d Page 5
47.2 (104)
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-459-1634; Fax 920-459-1846
For the nearest sales and service outlet in the USA and
Canada, call 1-888-769-3794 or kohlerrentalpower.com
TM
DISTRIBUTED BY:
Availability is subject to change without notice. Kohler Co. reserves the right
to change the design or specifications without notice and without any
obligation or liability whatsoever. Contact your local Kohlert Rental Power
regional office for availability.
 2001, 2002, 2004 by Kohler Co. All rights reserved.