Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History –Early 1970’s Small Substation Transformers <5,000 kVA Single Phase Reclosers – Mostly H type Limited Three Phase Reclosers – McGraw Type 3 Current Limit Fuses for UG Protection High-Side Fuses Electromechanical Relays 40 Ohm Minimum Fault Resistance Phase/Ground Trip Plugs No Sequential Coordination No Automation Smaller Reclosers and Fuses Use Smallest Recloser which will Carry Load History - Present Larger Substation Transformers >5,000 kVA Single Phase Reclosers – 4H & L Three Phase Reclosers w/ Single Phase Trip Switchgear w/ E fuses for UG Protection Three Phase Circuit Switcher/Transducer High-Side Protection Solid-State Relays w/ many Options 30 Ohm Minimum Fault resistance Select Settings on Panel Sequential Coordination Standard Automation Multiple Options Larger Single Phase Reclosers Use Largest Recloser Possible Sectionalizing Publications REA/RUS Bulletin 61-2 – Guide for Making Sectionalizing Study on Rural Electric Systems – 1978 (Rescinded) Cooper/McGraw – Distribution System Protection Manual Westinghouse – Applied Protective Relaying CRN Bulletin 96-5 Ground Fault Impedance Values for System Protection Manufacturer’s Literature Recloser Interruption & Control Hydraulic Interruption & Control Least Expensive ($1,200-2,300) Maintain @ 5 Year or Less Intervals Subject to Miscoordination in Winter Recloser Interruption & Control Hydraulic Control & Vacuum Interruption $100 More Expensive per Unit Maintain @ 10+ Year Intervals Same Miscoordination as Above Higher Interruption Ratings Recloser Interruption & Control Vacuum Interruption & Solid-State Control Limited Maintenance Most Expensive (1-ph: $5,700 & 3-ph: $17,000) Coordination Not Affected by Temperature Most Options High Interruption Ratings Solid – Type Insulations (e. g. Epoxy) Recloser Selection Interrupting Rating Load Minimum Fault Coordination Simultaneous Trip Recloser Ratings Coil Size 15 25 35 50 70 100 140 200 Min. Trip 30 50 70 100 140 200 280 400 H 375 625 875 1250 ------------- 4H 600 1000 1400 2000 2000 2000 ------- L ---1500 2100 3000 4000 4000 4000 4000 WE ---------------6000 8400 10K E 900 1500 2100 2500 2500 2500 ------- 4E ----------3000 4000 4000 4000 4000 Recloser TCC 1,000 100 TimeInSeconds 10 70,L (B) 1 70,L (A) 70,L (C) .1 10,000 1,000 100 10 70,L (D) Recloser-Recloser Coordination 10 50,L (B) 70,L (B) Time In Seconds 1 50,H (B) 50,L (A) 70,L (A) 50,4H (B) C ti A 10,000 1,000 100 10 .1 Simultaneous Trip 1,000 1,000 100 100 400 400 600 600 50,L (B) 50,L (B) 70,L (B ) 70,L (B) 1 1 50,L 50,L (A) (A) 70,L 70,L (A) (A) 10,000 10,000 1,000 1,000 100 100 10 .1.1 10 Time In Seconds Time In Seconds 10 10 Simultaneous Trip 100 10 650 800 Time In Seconds 70,L (B) 35,L (B) 1 35,L (A) 70,L (A) i 10,000 1,000 100 10 .1 Recloser-Recloser Coordination Summary One Size Smaller Recloser will Coordinate Skipping one Size will Reduce Simultaneous Trip May Run Out of Sizes Recloser–Fuse Coordination Type T 1,000 100 25,T (TC) TimeInSeconds 10 15,T (MM) 1 12,T (MM) 70,L (A) 70,L (B) Current in Amperes 10,000 1,000 100 10 .1 Recloser-Fuse Coordination Type 200 1,000 1,000 20,N (MM) 20,N (MM) 15,N (MM) 15,N (MM) 30,N (TC) 100 30,N (TC) 100 10 Time In Seconds 1 1 70,L (B) CurrentCurrent in Amperes in Amperes 70,L (B) 10,000 10,000 70,L (A) 1,000 100 100 70,L (A) 1,000 .1 10 .1 10 Time In Seconds 10 Recloser-Fuse Coordination Type E 1,000 15<E (MM) 20,E (MM) 30,E (TC) 40,E (TC) 100 Time In Seconds 10 1 70,L (B) .1 Current in Amperes 10,000 1,000 100 10 70,L (A) Recloser-Fuse Summary Fuse Total Clearing Faster than Recloser Delay Fuse Minimum Melt Slower than Recloser Fast Pick a Standard – Usually Largest Fuse Possible Fuse-Fuse Coordination 1,000 100 20,T (TC) 25,T (MM) Time In Seconds 10 1 C i A 10,000 1,000 100 10 .1 Fuse-Fuse Coordination (T Type) 1,000 10,T 15,T 25,T 40,T 100 Time In Seconds 10 1 Current in Amperes 10,000 1,000 100 10 .1 Fuse-Fuse Coordination (T Type) 1,000 8,T 12,T 20,T 30,T 100 Time In Seconds 10 1 Current in Amperes 10,000 1,000 100 10 .1 Fuse-Fuse Coordination (TBayonet) 1,000 100 25,T (MM) Time In Seconds 10 C10 (25A.) Bayonet 1 Current in Amperes 10,000 1,000 100 10 .1 Fuse-Fuse Coordination (T-E) 10,000 1,000 1,000 100 100 25,T (MM) Time In Seconds Time In Seconds 10 25,E MM) (Std & Slow) 25,E MM) (Std & Slow) 10 1 25,T (MM) 1 10,000 10,000 Current in Amperes C i A 1,000 1,000 100 100 .1 10 10 .1 Fuse-Fuse Coordination (T-K) 10,000 1,000 25,T (MM) 10 25,K (MM) 1 i 10,000 100 1,000 .1 10 Time In Seconds 100 Fuse-Fuse Coordination (T-CL) 1,000 10,000 25, NX C (MM) 1,000 100 25, NX C (MM) 100 Time In Seconds Time In Seconds 10 25 NXII (MM) 10 25 NXII (MM) 1 1 25,T (MM) 25,T (MM) .1 10,000 10,000 Current in Amperes C i A 1,000 1,000 100 100 10 10 .1 Fuse-Fuse Coordination Summary Total Clearing Faster than Minimum Melt Stick within a Series or Skip a Size Avoid Mixing Different Types Sectionalizing Philosophy Compromise Compromise Compromise Minimum Fault Resistance 40 Ohm Old REA/RUS Standard Based on 1920’s Bell Lab Studies Largest Single Phase Recloser - 70 Amp Smaller Reclosers and Fuses Overall Minimum Fault Resistance 30 Ohm Supported by CRN 96-5 Less Conservative Largest Single Phase Recloser – 100 Amp Larger Reclosers & Fuses Fewer Three Phase Reclosers Minimum Fault Resistance Values Used by IOU’s NSP/Excel – 20 Ohms MP – 0 Ohms or Twice Load Current Sectionalizing Philosophy Recloser Sizing Smallest vs. Largest vs. Hybrid Smallest Smallest Recloser which can carry load Faster Fault Clearing Smaller Load-Side Fuses Recloser Sizing Largest Largest Recloser that Coordinates Larger Load-Side Fuses Fewer Changes in Future Hybrid Same as Largest, but Size Reclosers to Twice Load Level Less Simultaneous Tripping Fast vs. Delay Operations Substation (1) Fast & (3) Delay 85% Faults Temporary Better Coordination with Down-Stream Reclosers Fewer Consumers Affected by Interruption (0) Fast & (3 or 4) Delay Possibly More Outages for Temporary Faults Excellent Coordination with Down-Stream Reclosers No Interruption to Affect Electronic or Commercial Loads Fast vs. Delay Operations Feeder Reclosers (2) Fast & (2) Delay Almost Universal Allows for Temporary Faults to Clear – Fewer Outages Affects Electronic Equipment – Reset Clocks Fast vs. Delay Operations Underground (1) Delay (2) Delay No Temporary Faults on UG Shouldn’t Use If Overhead Beyond Least Amount of Cable Damage Good Coordination if Fuse Used for Overhead Beyond or Fuses on UG Limited Cable Damage (2) Fast & (2) Delay Necessary if Overhead Feeder Beyond Most Cable Damage Recloser Spacing Mileage Between Reclosers on Three Phase 5 Miles 10 Miles Sectionalize Circuit More Shorter Outages Run Out of Sizes on Long Feeders More Line to Patrol for Outage – Longer Outages Not as Likely to Run Out of Sizes Except at 24.9kV Longer Distance Difficulty Finding Fault Mostly Easily to Backfeed Tap Protection w/ Recloser vs. Fuse Recloser Smaller Reclosers or Lightly Loaded Reclosers More Expensive if have to Purchases Reclosers One More Operation for Temporary Fault –Fewer Outages Smaller Fuses on Taps Beyond Recloser Fuse Larger Fuses and on Tap Replace Fuse for Outage Possibly More Outages Feeder Protection Reclosers Substation Taps with Load Larger than 20 amps or Longer than 5 Miles Every 10 Miles Along Three Phase Every 10 Miles Along Taps Where Load Larger than 20 Amps Beyond Special Loads Feeder Protection Fuses All Taps or All Taps Longer than Three Spans Divide Taps Longer than 10 Miles Sectionalizers All Taps that Could be Fuses, But Would Overload Fuse Minimum Line Recloser & Fuse Size What Size Transformer Fuse Do You Want to Coordinate? Minimum Recloser & Fuse Size What Size Transformer Fuse Do You Want to Coordinate? 25 kVA – 6,T Minimum Recloser & Fuse Size 1,000 1,000 10,T 10,T 6,T6,T (TC ) ) (TC 100 100 Time In Seconds Time In Seconds 1010 1 1 Current Current in Amperes in Amperes 10,000 10,000 1,000 1,000 100 100 10 10 .1 .1 Minimum Recloser & Fuse Size What Size Transformer Fuse Do You Want to Coordinate? 25 kVA – 6,T Line Fuse – 10,T Minimum Recloser & Fuse Size 1,000 1,000 6,T 6,T ) (TC (TC) 10,T 10,T 10 10 1 1 25,4H 25,4H (B ) (B) 10,000 10,000 Current in Amperes C i A 1,000 1,000 100 100 .1 .1 1010 Time Time In Seconds In Seconds 100 100 Minimum Recloser & Fuse Size What Size Transformer Fuse Do You Want to Coordinate? 25 kVA – 6,T Line Fuse – 10,T Recloser – 25 amp Fuses in Series Considerations Damage to Upstream Fuses Minimum Fuse Size Coordination Limitations Avoid as Much as Possible Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications Three Phase Reclosers Hydraulic Reclosers Recloser with CT’s & Solenoids Electronic Control Triple-Single Option 1Ø Trip, 1Ø L.O. 1Ø Trip, 3Ø L.O. 3Ø Trip, 3Ø L.O. Time Dial Settings 1,000 100 A PU, T D=2 U4-US Ext Inv 100 200 A PU, T D=2 U4-US Ext Inv 10 Time In Seconds 300 A PU, T D=2 U4-US Ext Inv 1 Current in Amperes 100,000 10,000 1,000 .01 100 .1 Pickup Settings 1,000 100 200 A PU, T D=1 U4-US Ext Inv 200 A PU, T D=2 U4-US Ext Inv 10 Time In Seconds 200 A PU, T D=4 U4-US Ext Inv 1 Current in Amperes 100,000 10,000 1,000 .01 100 .1 Phase – Ground Coordination 1,000 100 A PU, T D = 4 U2-US Inverse 100 300 A PU, T D = 2 U4-US Ext Inv Time In Seconds 10 1 Current in Amperes 100,000 10,000 1,000 .01 100 .1 ANSI Standard Device Designation Numbers 25) Synchronizing or Synchronism-Check Device 27) Undervoltage Relay Is a device that functions on a desired value of power flow in a given direction or upon reverse power resulting from arcback in the anode or cathode circuits of a power rectifier. 50) Instantaneous Overcurrent or Rate-of-Rise Relay Is a relay that functions on a given value of under-voltage. 32) Directional Power Relay Is a device that operates when two a-c circuits are within the desired limits of frequency, phase angle, or voltage, to permit or to cause the paralleling of these two circuits. Is a relay that functions instantaneously on an excessive value of current or on an excessive rate of current rise, thus indicating a fault in the apparatus or circuit being protected. 51) A-C Time Overcurrent Relay Is a relay with either a definite or inverse time characteristic that functions when the current in an a-c circuit exceed a predetermined value. ANSI Standard Device Designation Numbers 52) A-C Circuit Breaker 59) Overvoltage Relay Is a relay that controls the automatic reclosing and locking out of an a-c circuit interrupter. 81) Frequency Relay Is a relay that functions on a desired value of a-c overcurrent flowing in a predetermined direction. 79) A-C Reclosing Relay Is a relay that functions on a given value of over-voltage. 67) A-C Directional Overcurrent Relay Is a device that is used to close and interrupt an a-c power circuit under normal conditions or to interrupt this circuit under fault of emergency conditions. Is a relay that functions on a predetermined value of frequency (either under or over or on normal system frequency) or rate of change of frequency. 89) Line Switch Is a switch used as a disconnecting, load-interrupter, or isolating switch in an a-c or d-c power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc. One-line Diagram Conductor Arcing through Asphalt Conductor Breakage / Glassification Steady State Harmonic Energy Arcing Fault Harmonic Energy Substation Protection Substation Transformer 10,000 65E SMD-Standard -T otal Clear A0.87 Low-Side Line to Line Fault 65E SMD-Standard -T otal Clear Low-Side Three Phase Fault 1,000 65E SMD-Standard -T otal Clear A1.73 Low-Side Single Line to Ground Fault 5,000 kVA, 69-12.47 kV Transformer Mechanical Damage 10 T hermal Damage 1 .1 Current in Amperes 100,000 10,000 .01 1,000 Inrush 100 Time In Seconds 100 Large Substation Transformers 10,000 150E SMD-Standard -T otal Clear Low-Side Three Phase Fault 150E SMD-Standard -T otal Clear A1.73 1,000 Low-Side Single Line to Ground Fault 12/16/20 MVA, 69-12.47 kV Transformer Mechanical Damage 10 T hermal Damage 1 .1 Current in Amperes 100,000 10,000 .01 1,000 Inrush 100 Time In Seconds 100 Zones of Protection Differential Relays C.T. Curves Transformer Protection One-line Diagram Specific Applications Capacitor Protection 1,000 GE 10% Probability Case Rupture 100 kVAr Units 100 10 1 15 T -Minimum Melt .1 Current in Amperes 10,000 1,000 .001 100 .01 10 Time In Seconds 15 T -T otal Clear Parallel Capacitors 1,000 GE 10% Probability Case Rupture 100 kVAr Units 100 10 25 T -T otal Clear 1 15 T -Minimum Melt .1 25 T -Minimum Melt Current in Amperes 10,000 1,000 .001 100 .01 10 Time In Seconds 15 T -T otal Clear Capacitor with C.L. Fuse 1,000 100 GE 10% Probability Case Rupture 100 kVAr Units 10 25 T -Minimum Melt 1 25K NX Companion Fuses -T otal Clear .1 25K NX Companion Fuses -Minimum Melt Current in Amperes 10,000 100 .001 1,000 .01 10 Time In Seconds 25 T -T otal Clear Current Limiting Fuses Partial range C.L. fuses Pad/Pole Transformer Overhead capacitors Underground applications Power quality Hard to coordinate areas Step Down Transformer Protection Automatic Loop Restoration - 5 Reclosers Substation 1 3.3 miles 3.3 miles 3.3 miles R R N.C. Recloser N.C. Recloser R R N.C. Recloser N.C. Recloser Substation 2 N.C. - Normally-Closed N.O. - Normally-Open R N.O. Recloser Loop Coordination Loss of V By # of recloses & loss of V Normal O.C. & comm. Current diff & comm. Control Logic Questions & comments