Recloser Catalog-RWK-2RCB

advertisement
RCW
Pole mounted vacuum Recloser
6kV,….38kV, 630A,..800,….1250A
Provided Customized manufacture
Whole solutions for design, assembly, test…
Catalog
Best solution for your power!
1. Summary
Rockwill Electric strives to bring our customers the latest technology and competitive pricing and
best service for distribution automatic.
The RCW series automatic circuit reclosers can use on overhead distribution lines as well as
distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power
system. and its rated current can reach 1250A.
The RCW series automatic circuit reclosers integrates the functions of control, protection,
measurement, communication, fault detection, on-line monitoring of closing or opening.
2. Service environment
a) Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 2500m or more higher.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
3. Offering
With optional classes for rated current range:
For 15kV, with 630A, 20kA Breaking capacity. 800A, 20kA capacity, and 1250A, 20kA.
For 27kV, with 630A, 20kA Breaking capacity. 800A, 16kA capacity, and 1250A, 25kA.
For 38kV, with 800A, 20kA,. and expanding 1250A, .25kA RCW38M type..
With optional classes for installation styles:
Single phase, vacuum recloser and Three phase, vacuum recloser.
With optional relay protection curves for user choice:
Instantaneous over-current protection.
Timing over-current protection.
Negative sequence over-current protection.
Directional over-current protection(*).
Over-voltage protection./Under voltage protection.
More relay functions can be customized.
With optional choice by locally or remotely.
With optional communication protocols & I/O port for user choice:
RS-232 and RS-485 ports supporting.
DNP3.0 communication protocol support(*).
Modbus communication protocol is optional(*).
IEC 60870-5-101 communication protocol support.
IEC 60870-5-104 communication protocol support. (*).
The recloser can communicate through GPRS(Or GSM) modem with English or Chinese languege
(*).With optional functions for user.
Rated currents, System phase current.
Rated voltages, System phase voltage& secondary low voltage power supply voltage.
Frenquency, power(kWh), reactive power(kVarh),power factor .
With optional reclosing interval for user pre-program:
Reclosing times setting support.
Dead time setting support.
With events recording function:
SOE 1000 operations record.
Fault record and normal operation record.
Note: (*) mean should customized by manufacturer if needed.
4. Recloser feature
4.1 Outline of recloser:
The RCW series vacuum recloser is mainly combined
with integration terminal, current transformer, permanent
magnetic actuator and its recloser controller.
4.2 The recloser tank feature:
The Vacuum recloser tanks are manufactured from
304#grade stainless steel and are powder coated
a light grey colour.
Whole recloser IP65 protection class, equipped with
a auxiliary plug to connect with recloser controller by
control cable, Diameter Max22mm, 6 M length(8M for special). .
Its can performance serve more than 20 years long term under heavy duty circumstance.
4.3 The recloser vacuum embedded pole feature:
The recloser’s vacuum interrupter insert in
an epoxy resin solid pole, and external
coated with a high reliable, stable material:
Fluorocarbon silicone rubber
(γ-trifluoro propyl methyl polysiloxane)
With excellent electric insulation,
weather resistance, ozone, biological inertia,
can be stand under the long-term use in -55 ~ +200 ℃.
Creepage Distances of RCW
Description
15kV
BIL 15kV
95/110kV
125kV
BIL 27kV
125kV
T to T*
480/646mm
646mm
796mm
796mm
1145mm
T to G/E*
480/763mm
763mm
763mm
1126mm
1126mm
T to T*
-----Terminal to terminal creepage
T to G/E* -----Terminal to ground/earth creepage
BIL 27kV
150kV
BIL 38kV
BIL
170/185kV
5. Main new advantages of RCW
High reliable manual opening device
Visible ON/OFF indicator
High reliable manual closing device
IP64 class waterproof plug connector
Note:
ROCKWIILL Supply special design manual closing device technology with own patent,It applied for
nomal and abnormal situation closing. Its closing speed(time) comply with IEC62271-100.
This function can offset from magnetic actuator fault which when ctuator can’t work will cause the
major accident..
----------------------------------------------------------------------------------------------------------------------
Primacy incomer
terminal(directly connect to
interrupter reduce power lost)
Current transformer(external
modular design easy for quality
control and maintenance)
Vacuum interrupter(Adopt the
APG technology with external
silicone rubber mold pressure
covering, increasing the whole
insulation and
weathering
performance)
----------------------------------------------------------------------------------------------------------------------
Internal
Voltage
sensors
Shielded 4-conductor cable
incorporated within the
connection
vacuum interrupter module
Magnitude Accuracy: ±2.0%
Source-side or Load side
Phase Accuracy:±1.5 %
connections
Voltage Sensor Ratio:500/1 or
Eliminate
external
1000/1
voltage-sensing PTs
---------------------------------------------------------------------------------------------------------------------Apply ANSOFT design the high performance magnetic actuator,
high reliable and free maintenance. Through 35,000 times opening
reverse excitation test, the demagnetization rate less than 1%.
Note:
ROCKWIILL supply special patent modular design mono-stable
type magnetic actuator with two coils controlling.Its the best design
for vacuum circuit breaker.
6. Main technical data
No.
Item
Unit
data
1
2
Rated voltage
Rated current
kV
A
11/15
630
3
Rated frequency
HZ
50/60
4
Power frequency 1min
kV
Dry
27
630/1250
38
630/1250
49/55
65
85/95*
kV
38/45
95/110
55
150
80
185
kA
20
16/25
20/25
6
Wet
Lightning impulse withstand voltage(peak
value)alternate, opposite/fracture
Rated short circuit breaking current
7
8
Rated short current switching current(peak value)
Rated peak value withstand current
kA
kA
50
50
40/63
40/63
50/63
50/63
9
4S short time withstand current
kA
20
16/25
20
10
11
Rated operating circulate
Breaking current frequency under rated short
circuit
times
O-T1-CO-T2-CO-T3-CO-T4-CO
30
12
13
Mechanism life
Secondary loop 1 min power frequency withstand
voltage
times
kV
10000
2
5
7. Accessories of RCW
Upper voltage shield 3 pcs/set
Lower expaning bushing 3 pcs/set
Note:
all above insulating components for BIL 170kV expanding using. Any question pls contact with
our engineer.
Upper terminal 3 pcs/set
Lower termianl 3 pcs/set
Note:
Standard made of T2 copper material, for 630A rated current using.
With expanding range.
8. Outline &Sizes for RCW
38kV BIL170/185kV Recloser switch dimensional drawing
Installation reference for single pole schema
15/27kV BIL125/150kV Recloser switch dimensional drawing
12/15kV BIL110kV Recloser switch dimensional drawing
9. Technical service
Rockwill,China. Provide with best support, If you have any question pls consult below.
Rockwill, CHINA. Tel: 0086-577-27869968 . Email: rockwill.tech@gmail.com
Download