CSC-101 Line Protection IED Product Guide Version V1.10 Doc. Code: 0SF.492.050(E) Issued Date 2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the instruction. If equipments do not agree with the instruction at anywhere, please contact our company in time. We will provide you with corresponding service. ® is registered trademark of Beijing Sifang Automation Co., Ltd. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result; it is possible that there may be some differences between the hardware/software product and this information product. Manufacturer: Beijing Sifang Automation Co., Ltd. Overview CSC-101 is selective, reliable and high speed comprehensive transmission line protection IED (Intelligent Electronic Device) for overhead lines, cables or combination of them. It is a proper solution for following applications: three pole tripping Communication with station automation system The IED provides a highly sensitive and reliable distance protection with innovative and proven quadrilateral characteristic. In Overhead lines and cables up to 1000kV addition to separated zone extension voltage level functionality, five distance zones have fully All type of station arrangement, such as independent measuring and setting values 1.5 breakers arrangement, double bus which gives high flexibility for all types of arrangement, etc. lines and fault resistances. Many other functions are integrated to provide a Extremely long lines complete backup protection library. Short lines The wide application flexibility makes the Heavily loaded lines IED an excellent choice for both new installations and retrofitting of the existing Satisfy the requirement for single and /or stations . 1 Feature Protection and monitoring IED with extensive functional library, user configuration possibility and expandable hardware design to meet with user’s special requirements Redundant A/D sampling channels and interlocked dual CPU modules guarantee the high security and reliability of the IED Single and/or three tripping/reclosing Highly sensitive startup elements, which enhance the IED sensitivity in all disturbance conditions and avoid maloperation Negative sequence component directional element Impedance directional element Full scheme phase-to-phase and phase-to-earth distance protection with five quadrilateral protection zones and additional extension zone characteristic (21, 21N) Power swing function (68) Proven and reliable principle of power swing logic Unblock elements during power swing Current sudden-change startup element Zero sequence current startup element Permissive Underreach Transfer Trip (PUTT) scheme Over current startup element Undervoltage startup element for weak-infeed end of line Permissive Overreach Transfer Trip (POTT) scheme Blocking scheme Inter-tripping scheme Three kinds of faulty phase selectors are combined to guarantee the correction of phase selection: Current sudden-change phase selector Zero sequence and negative sequence phase selector Under voltage phase selector Four kinds of directional elements cooperate each other so as to determine the fault direction correctly and promptly: Memory voltage directional element Zero sequence component directional element All useful types scheme (85) Phase scheme Particular scheme segregated logic for tele-protection tele-protection tele-protection Current reversal Weak-infeed end Evolving fault logic Sequence tripping logic A complete protection functions library, include: 2 of Distance protection with quadrilateral characteristic (21,21N) Feature Power swing function (68) IED Tele-protection scheme based on distance protection (85-21,21N) Tele-protection scheme based on dedicated earth fault protection (85-67N) Overcurrent protection (50, 51, 67) Earth fault protection (50N, 51N, 67N) Tele-protection contacts for power line carrier protection interface Emergency/backup protection (50, 51) Emergency/backup earth protection (50N, 51N) Switch-onto-fault (50SOTF) Up to two fiber optical remote communication ports for protection function, like tele-protection, used up to 100kM single–mode optical fiber cable External optical/electrical converter, which support communication through SDH or PCM, for G.703 (64kbit/s) and G.703E1 (2048kbit/s) Complete IED information recording: tripping reports, alarm reports, startup reports and general operation reports. Any kinds of reports can be stored up to 2000 and be memorized in case of power disconnection Remote communication overcurrent fault protection Overload protection (50OL) Overvoltage protection (59) Undervoltage protection (27) Circuit breaker failure protection (50BF) Poles discordance protection (50PD) Dead zone protection (50DZ) STUB protection (50STUB) Synchro-check check (25) Auto-reclosing function for singleand/or three-phase reclosing (79) Voltage transformer secondary circuit supervision (97FF) Current transformer circuit supervision and energizing secondary Self-supervision to all modules in the 3 Up to three electric /optical Ethernet ports can be selected to communicate with substation automation system by IEC61850 or IEC60870-5-103 protocols Up to two electric RS-485 ports can be selected to communicate with substation automation system by IEC60870-5-103 protocol Time synchronization via network (SNTP), pulse and IRIG-B mode Configurable LEDs (Light Emitting Diodes) and output relays satisfied users’ requirement Versatile human-machine interface Multifunctional software tool for setting, monitoring, fault recording analysis, configuration, etc. Function Protection functions IEC 61850 Description ANSI Code Logical Node Name IEC 60617 graphical symbol Distance protection Distance protection 21, 21N PDIS Z< Power-swing function 68 RPSB Zpsb Tele-protection Communication scheme for distance protection Communication scheme for earth fault protection 85–21,21N PSCH 85–67N PSCH Current protection 3IINV> Overcurrent protection 50,51,67 PTOC 3I >> 3I >>> I0INV> Earth fault protection 50N, 51N, 67N PTEF I0>> I0>>> Emergency/backup overcurrent protection 50,51 PTOC Emergency/backup earth fault protection 50N,51N PTEF Switch-onto-fault protection 50SOTF PSOF Overload protection 50OL PTOC 3IINV> 3I > I0INV> I0 > 3I >SOTF I0>SOTF 3I >OL Voltage protection Overvoltage protection 59 PTOV Undervoltage protection 27 PTUV 3U> 3U>> 3U< 3U<< Breaker protection and control function 3I> BF Circuit breaker failure protection 50BF RBRF I0>BF I2>BF Dead zone protection 50DZ 4 Function STUB protection 50STUB PTOC 3I>STUB 3I< PD Poles discordance protection 50PD RPLD I0>PD I2>PD Synchro-check and energizing check 25 RSYN Auto-reclosing 79 RREC Single- and/or three-pole tripping 94-1/3 PTRC Secondary system supervision CT secondary circuit supervision VT secondary circuit supervision 97FF Monitoring functions Description Redundant A/D sampling data self-check Phase-sequence of voltage and current supervision 3I0 polarity supervision The third harmonic of voltage supervision Synchro-check reference voltage supervision Auxiliary contacts of circuit breaker supervision Broken conductor check Self-supervision Logicality of setting self-check Fault locator Fault recorder Station communication Description Front communication port 5 O→I Function Isolated RS232 port for maintaining Rear communication port 0-2 isolated electrical RS485 communication ports, support IEC 60870-5-103 protocol 0-3 Ethernet electrical/optical communication ports, support IEC 61850 protocol or IEC 60870-5-103 protocol Time synchronization port, support GPS pulse or IRIG-B code Remote communication Description Communication port Contact(s) interface for power line carrier for tele-protection 0– 2 fiber optical communication port(s) for tele-protection Connection mode Direction fiber cable connection Digital communication network through converter IED software tools Functions Reading measuring value, IED report Setting IED testing Disturbance recording analysis IED configuration Printing 6 Function Remote Communication Ports FO CONNECTION FO CONNECTION 21 Z< 85-21 PDIS 21N Z< PDIS Zpsb 68 PSCH PLC Protection interface 1 85-67N PSCH PLC Protection interface 2 FL RFLO RPSB 50 51/67 3I>>> 3I>>,3I> PTOC PIOC 50N I0>>> PIEF 51N/67N I0>>,I0> 3I>BF 50BF RBRF 50STUB 3I>STUB 50SOTF 50PD MEASUREMENT PTEF PTOC MONITORING PSOF 50PD 59 PD 3U> PTOV RPLD 27 3U< PTUV STATION COMMUNICATION - RS232/485 - RJ45/FO - IEC61850 - IEC60870-5-103 25 RSYN Fault recording 79 O→ I RREC 94 PTRC 7 Protection Δ3i0: Sudden-change zero sequence current Startup elements I_Abrupt: The setting value of current The startup elements basically work as sensitive detector to all types of fault. As soon as fault or disturbance happens, the highly sensitive startup elements will operate immediately and initiate all necessary protection functions for selective clearance of the fault. sudden-change elements Zero sequence current startup element Zero sequence current startup element is applied to improve the fault detection sensitivity at the high resistance earth faults. As an auxiliary startup element, it operates with a short time delay. The control circuit of tripping relays is controlled by the startup elements. Only when one of the startup elements is triggered, the tripping relays can be energized to trip. Thus, the maloperation, due to fatal internal hardware fault, is avoided in this way. Overcurrent startup element If overcurrent protection function is enabled, over current startup element is used to improve the fault detection sensitivity. As an auxiliary startup element, it operates with short time delay. Based on different principle, there are four kinds of startup elements listed below, which are used to enhance the sensitivity, and to guarantee the security in case of IED’s internal hardware faults. Low-voltage startup element When one end of the protected line is a weak-source system, and the fault sudden-change phase to phase current is too low to startup the IED, low-voltage startup element can be in service to startup the tele-protection scheme with weak-echo logic. Sudden-change current startup element Sudden-change phase to phase or zero sequence current elements are the main startup element that can sensitively detect most of faults. The criteria are as follows: Phase selector The IED applies different phase selectors to determine the faulty phase to make tripping or Auto-reclosing initiation correctly. There are three kinds of phase selectors based on different principle for different fault stages. or where: Δi=|| i (K) - i (K-T) | - |i (K-T) - i Sudden-change current phase selector (K-2T) || : AB,BC or CA, e.g. iAB= iA-iB It operates as soon as the sudden- change current startup element starts up. It makes a phase selection for fast tripping by K: The present sample T: The sample quantity of one power cycle 8 Protection comparison amongst changes of phase-phase currents, iAB, iBC and iCA. the fault. Therefore transient voltage of short circuit conditions doesn’t influence the direction detection. Additionally, it improves the direction detection sensitivity for symmetrical or asymmetrical close-in faults with extremely low voltage. But it should be noted that the memory voltage cannot be effective for a long time. Therefore, the following directional elements work as supplement to detect direction correctly. Symmetrical component phase selector During the whole period of fault, the phase selector checks the angle between negative sequence current and zero sequence current vectors to determine faulty phases. In addition, phase to phase faults will be discriminated through impedance characteristic. Zero sequence component directional element Low voltage phase selector Zero-sequence directional element has efficient features in the solidly grounded system. The directional characteristic only relates to zero sequence impedance angle of the zero sequence network of power system, regardless of the quantity of load current and/or fault resistance throughout the fault. The characteristic of the zero sequence directional element is illustrated in Figure 1 Both current sudden-change phase and symmetric component phase selector are not applicable for weak-infeed end of protected line, so low-voltage phase selector is employed in this condition without VT failure. Theoretically, when one, two or three phase voltages reduce, the relevant phase(s) is selected as faulty phase. 3I 0 Directional elements Four kinds of directional elements are employed for reliable determination of various faults direction. The related protection modules, such as distance protection, tele-protection schemes and overcurrent and earth fault protections, utilize the output of the directional elements as one of their operating condition. All the following directional elements cooperate with the mentioned protection functions. 90° 0° 3 U 0_Ref Φ0_Char Forward -3 I 0 Bisector Figure 1 Characteristic of zero sequence directional element where: Memory voltage directional element Ф0_Char: The settable characteristic angle Negative sequence component directional element The IED uses the memory voltage and fault current to determine the direction of 9 Protection Negative sequence directional element can make an accurate directional discrimination in any asymmetric fault. The directional characteristic only relates to negative sequence impedance angle of the negative sequence network of power system, regardless the quantity of load current and/or fault resistance throughout the fault. The characteristic of the negative sequence directional element is illustrated in Figure 2. 3I2 X_Set X Forward -n∙R_Set R_Set R Reverse 90° -n∙X_Set Figure 3 Direction detection characteristic of impedance directional element 0° where: 3 U 2_ Ref RSET: The resistance setting of relevant zone Φ2_Char of distance protection XSET: The reactance setting of relevant zone Forward of distance protection -3 I 2 Bisector n: Multiplier for reverse directional element, which make the reverse directional Figure 2 Characteristic of negative sequence element more sensitive than forward one directional element where: Distance protection (21, 21N) Ф2_Char: The settable characteristic angle Impedance directional elements The transmission line distance protection provides a five zones full scheme protection with all phase to phase faults and phase to earth fault loops independently for each zones. Zone arrangement illustrated in Figure 4. The characteristic of the impedance directional element (shown in Figure 3) is same with that of distance protection. Additionally, one extension zone is employed to co-operate with Auto-reclosing and tele-protection schemes. 10 Protection R_ZSet: R_ZnPP or R_ZnPE; X Zone 5 X_ZSet: X_ZnPP or X_ZnPE; Zone 4 Zone 3 R_ZnPP: Resistance reach setting for phase Zone 2 to phase fault. Subscript n means the Zone Ext. number of protection zone. Subscript PP Zone 1 means phase to phase fault R R_ZnPE: Resistance reach setting for phase to earth fault. Subscript X means the Zone 4 Reverse (optional) number of protection zone. Subscript PE means phase to earth fault Zone 5 Reverse (optional) X_ZnPP: Reactance reach setting for phase Figure 4 Distance protection zones to phase fault Individual settings of resistive and reactive reach for phase to phase and phase to earth fault of each zone give flexibility for application on overhead lines and cables of different types and lengths, considering different fault resistance for phase to phase and phase to ground short circuits. X_ZnPE: Reactance reach setting for phase to earth fault Φ_ZTop: The upper boundary angle of the characteristic in the first quadrant is designed to avoid distance protection overreaching when a close-in fault happens on the adjacent line Characteristic of distance protection Φ_ZBottom: The bottom boundary angle of the characteristic in the fourth quadrant improves the reliability of the relay to The IED utilizes quadrilateral characteristic as shown in Figure 5. operate reliably for close-in faults with arc resistance Φ_ZRight: The right boundary angle of X characteristic in the first quadrant is used X_ZSet to deal with load encroachment problems Φ_ZTop Φ_ZLeft: The left boundary angle of the characteristic in the second quadrant considers the line impedance angle which generally is not larger than 90°. Thus this Φ_ZLeft Φ_ZRight R_ZSet angle guarantees the correct operation of the relay R Φ_ZBottom Extended operating characteristic Figure 5 Characteristics of distance protection To ensure the correct operation at close-in faults, a rectangle zone covering the where: 11 Protection original point is added to the quadrilateral characteristic. The rectangular offset characteristic (illustrated in Figure 6) is calculated automatically according to the related distance zones settings. Furthermore, the memory voltage direction element, the zero sequence directional element, and the negative sequence direction element are applied to determine the direction together. X -R_ZSet R -X_ZSet X Figure 7 Characteristic distance protection XSet reverse zone ΦTop Switch-onto- fault protection function ΦLeft XOffset Under either auto reclosing or manual closing process, the protection function is able to discriminate these conditions to give an instantaneous tripping once the circuit breaker is closed on permanent faulty line. ΦRight ROffset ΦBottom R RSet Figure 6 Extended polygonal distance protection Power swing (68) zone characteristic Reverse zone characteristic The IED provides a high reliable power swing detector which discriminates between fault and power swing with different algorithm. In addition to the forward characteristic zones mentioned above, the IED provides two optional reverse zone characteristics to protect connected busbar as a backup protection. The reverse zone characteristic can be set for zones 4 and 5 individually. This reverse characteristic has been shown in Figure 7. Power swing blocking logic According to the slow behavior of power swing phenomenon, once one of the two following conditions is met, the protection program will switch to power swing logic process: 12 Without operation of sudden-change current startup element, all phase-to-phase impedances, ZAB, ZBC Protection and ZCA enter into the largest zone of distance protection Based on the experimental results and practical proof, the change rate of measuring resistance and the change vector of measuring impedance are combined to detect the three phase fault during the power swing. Without operation of sudden-change current startup element, all phase currents are bigger than the power swing current setting In addition, according to the experimental results of power swing, it is not possible for impedance vector to come into protected zones in 150 ms after triggering of the current sudden- -change startup element. After 150 ms, the protection program will be switched to power swing logic process if no tripping is issued. Therefore, according to the above condition, the IED program enters the power swing logic process and the distance protection is blocked until removing of the mentioned conditions or until a fault occurrence in the protected line. Tele-protection scheme for distance protection (85-21) To achieve non-delayed and selective tripping on 100 % of the line length for all faults, the communication scheme logic is provided for distance protection. The communication schemes are as follows: Power swing unblocking logic The unblocking logic provides possibility for selective tripping of faults on transmission lines during system oscillations, when the distance protection function is normally blocked. In order to unblock distance protection and therefore, fast clearing of the faults, the following elements are in service to discriminate between an internal fault and power swing conditions. Three phase fault detection element Permissive Overreach Transfer Trip (POTT) Permissive Underreach Transfer Trip (PUTT) Blocking scheme Following protection logic are used to ensure correct operation under some special fault conditions: Asymmetric faults detection element Current reversal logic Weak-infeed end and echo logic Evolving fault logic Sequence tripping logic Direct Transfer Trip The zero and negative sequence current are always the key features of the asymmetric fault. By comparison amongst the positive, negative and zero sequence component of phase current, the element distinguishes the asymmetric fault from power swing. The function is provided to cooperate with related local protection IED, such as busbar protection, breaker failure protection, etc., to trip the opposite end circuit breaker. 13 Protection Phase segregated communication scheme Phase segregated communication scheme To guarantee correct phase selection at all times for simultaneous faults on the parallel lines, the phase segregated communication scheme logic can be employed to support single-pole tripping for faults occurring anywhere at all times on entire length of the parallel lines. To guarantee correct phase selection at all times for simultaneous faults on the parallel lines, the phase segregated communication scheme logic can be employed to support single-pole tripping for faults occurring anywhere at all times on entire length of the parallel lines. Tele-protection scheme for earth fault protection (85-67N) Overcurrent protection (50, 51, 67) To achieve highly sensitive and selective tripping on 100 % of the line length for all faults, especially at the high resistance earth faults. It always works as complement to tele-protection for distance protection with a short time delay. Permissive transfer trip communication scheme is applied. Two definite time stages One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Settable directional element characteristic angle, to satisfy the different network conditions and applications Each stage can be set individually as directional/non-directional Each stage can be set individually for inrush restraint Cross blocking function for inrush detection The protection provides following features: The protection provides dedicated current and time elements independent of the earth fault protection. Following protection logic are used to ensure correct operation under some special fault conditions. Current reversal logic Weak-infeed end logic Sequence tripping logic Settable maximum inrush current Direct Transfer Trip VT secondary circuit supervision for directional protection. Once VT failure happens, the directional stage can be set to be blocked The function is provided to cooperate with related local protection IED, such as busbar protection, breaker failure protection, etc., to trip the remote end circuit breaker. Inrush restraint function The protection relay may detect large 14 Protection 90° Forward magnetizing inrush currents during transformer energizing. In addition to considerable unbalance fundamental current, inrush current comprises large second harmonic current which does not appear in short circuit current. Therefore, the inrush current may affect the protection functions which operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent overcurrent protection from maloperation. IA Bisector ΦPh_Char 0° U BC_Ref -IA Furthermore, by recognition of the inrush current in one phase, it is possible to set the protection in a way that not only the phase with the considerable inrush current, but also the other phases of the overcurrent protection are blocked for a certain time. This is achieved by cross-blocking feature integrated in the IED. Figure 8 Direction detection characteristic of overcurrent protection directional element where: ФPh_Char: The settable characteristic angle The assignment of the applied measuring values used in direction determination has been shown in Table 1 for different types of faults. The inrush restraint function has a maximum inrush current setting. Once the measuring current exceeds the setting, the overcurrent protection will not be blocked any longer. Table 1 Assignment of applied current and reference voltage for directional element Characteristic of direction element The direction detection is performed by determining the position of current vector in directional characteristic. In other word, it is done by comparing phase angle between the fault current and the reference voltage, Figure 8 illustrates the direction detection characteristic for phase A element. Phase Current Voltage A Ia U bc B Ib U ca C Ic U ab For three-phase short-circuit fault, without any healthy phase, memory voltage values are used to determine direction clearly if the measured voltage values are not sufficient. The detected direction is based on the memory voltage of previous power cycles. 15 Protection Earth fault protection (50N, 51N, 67N) Directional element The earth fault protection adopts zero sequence directional element which compares the zero sequence system quantities: The earth fault protection can be used to clear phase to earth faults as system back-up protection. The protection provides following features: Two definite time stages One inverse time stage 11 kinds of the IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Zero sequence directional element Negative sequence directional element is applied as a complement to zero sequence directional element. It can be enabled/disabled by setting 3I0, current is measured from earth phase CT 3U0, the voltage is used as reference voltage. It is calculated from the sum of the three phase voltages 3I 0 90° 0° 3U 0_Ref Φ0_Char Each stage can be set individually as directional/non-directional Settable directional element characteristic angle, to satisfy the different network conditions and applications Forward Settable maximum inrush current VT secondary circuit supervision for directional protection function. Once VT failure happens, the directional stage can be set to be blocked CT secondary circuit supervision for earth fault protection. Once CT failure happens, all stages will be blocked Zero-sequence current is measured from earth phase CT Bisector Figure 9 Direction detection characteristic of zero sequence directional element Each stage can be set individually for inrush restraint -3 I 0 where: Ф0_Char: The settable characteristic angle For earth fault protection, users can choose negative sequence directional element as the complement of zero sequence directional element. It can be used in case of too low zero sequence voltage due to some fault condition e.g. the unfavorable zero-sequence voltage. The negative sequence directional element characteristic is shown in Figure 10. 16 Protection 3I2 Emergency/backup overcurrent protection (50, 51) 90° In the case of VT fail condition, all distance zones and protection functions related with voltage input are out of service. In this case, an emergency overcurrent protection comes into operation. 0° 3 U 2_ Ref Φ2_Char Forward -3 I 2 Additionally, the protection can be set as backup non directional overcurrent protection according to the user’s requirement. Bisector Figure 10 Direction detection characteristic of The protection provides following features: negative sequence directional element where: One definite time stage One inverse time stage 11 kinds of IEC and ANSI inverse characteristics curve as well as optional user defined characteristic Inrush restraint function can be set for each stage separately Cross blocking of inrush detection Settable maximum inrush current Ф2_Char: The settable characteristic angle Furthermore, under the VT failure situation, it can be set to block directional earth fault protection. Inrush restraint function The protection relay may detect large magnetizing inrush currents during transformer energizing. In addition to considerable unbalance fundamental current, Inrush current comprises large second harmonic current which doesn’t appear in short circuit current. Therefore, the inrush current may affect the protection functions which operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent earth fault protection from mis-tripping. Emergency/backup earth fault protection (50N, 51N) In the case of VT fail condition, all distance zones and protection functions related with voltage input are out of operation. An emergency earth fault protection comes into operation. Since inrush current cannot be more than a specified value, the inrush restraint provides an upper current limit in which blocking does not occur. Additionally, the protection can be set as backup non directional earth fault protection according to the user’s 17 Protection Overload protection (50OL) requirement. The protection provides following features: One definite time stage One inverse time stage 11 kinds of IEC and ANSI inverse characteristics curve as well as optional user defined characteristic Inrush restraint can be individually for each stage Settable maximum inrush current CT secondary circuit supervision for earth fault protection. Once CT failure happens, all stages will be blocked Zero-sequence current is measured from 3-phase currents summation The IED supervises load flow in real time. If each phase current is greater than the dedicated setting for a set delay time, the protection will issue alarm. Overvoltage protection (59) selected The overvoltage protection detects abnormally network high voltage conditions. Overvoltage conditions may occur possibly in the power system during abnormal conditions such as no-load, lightly load, or open line end on long line. The protection can be used as open line end detector or as system voltage supervision normally. Switch-onto-fault protection (50SOTF) The protection provides following features: The protection gives a trip when the circuit breaker is closed manually onto a short circuited line. Two definite time stages Each stage can be set to alarm or trip Measuring voltage between phase-earth voltage and phase-phase (selectable) Settable dropout ratio The protection provide following features: One definite time overcurrent stage One definite time earth fault protection stage Inrush restraint can be selected Cross blocking for inrush detection Settable maximum inrush current Manual closing binary input detection Undervoltage protection (27) One voltage reduction can occur in the power system during faults or abnormal conditions. The protection provides following features: 18 Two definite time stages Each stage can be set to alarm or trip Protection Measuring voltage between phase-earth voltage and phase-phase selectable Current criteria supervision Circuit breaker supervision VT secondary circuit supervision, the Undervoltage function will be blocked when VT failure happens aux. The function can be set to give single- or three phase re-tripping of the local breaker to avoid unnecessary tripping of surrounding breakers in the case of the circuit breaker with two available trip coils. contact Additionally, during single pole tripping, stage 1 is able to re-tripping three phase with settable delay time after single phase re-tripping failure. Two trip stages (local and surrounding breaker tripping) Transfer trip command to the remote line end in second stage Internal/ external initiation Single/three phase CBF initiation Selectable CB Aux contacts checking Current criteria checking (including phase current, zero and negative sequence current) Settable dropout ratio Breaker failure protection (50BF) The circuit breaker failure protection is designed to detect failure of the circuit breaker during a fault clearance. It ensures fast back-up tripping of surrounding breakers by tripping relevant bus sections. The protection can be single- or three-phase started to allow use with single or three-phase tripping applications. Dead zone protection (50DZ) Once a circuit breaker operating failure occurs on a feeder/transformer, the bus section which the feeder/transformer is connected with can be selectively isolated by the protection. In addition a transfer trip signal is issued to trip the opposite end circuit breaker of the feeder. The IED provides this protection function to protect dead zone, namely the area between circuit breaker and CT in the case that CB is open. Therefore, by occurrence of a fault in dead zone, the short circuit current is measured by protection relay while CB auxiliary contacts indicate the CB is open. In the event of a circuit breaker failure with a busbar fault, a transfer trip signal is issued to trip the remote end circuit breaker of the feeder. The current criteria are in combination with three phase current, zero and negative sequence current to achieve a higher security. Internal/external initiation Self-adaptive for bus side CT or line side CT When one bus side CT of feeder is applied, once a fault occurs in the dead zone, the IED trips the relevant busbar zone. 19 Protection Tripping logic is illustrated in Figure 11. STUB protection (50STUB) The VT is mostly installed at line side of transmission lines. Therefore, for the cases that transmission line is taken out of service and the line disconnector is opened, the distance protection will not be able to operate and must be blocked. Trip Bus IFAULT Line1 Line2 Opened CB The STUB protection protects the zone between the CTs and the open dis-connector. The STUB protection is enabled when the open position of the disconnector is connected to IED binary input. The function supports one definite stage which related concept is shown in Figure 13. LineN Closed CB Figure 11 Tripping logic, applying bus side CT When one line side CT is applied, when a fault occurs in the dead zone, protection relay sends a transfer trip to remote end relay to isolate the fault. Tripping logic is illustrated in Figure 12. Bus A Bus B Delay trip IFAULT IFAULT Bus Inter trip Line A Line B IFAULT Closed CB Line1 Line2 LineN Figure 13 Tripping logic of STUB protection Trip Relay Opened CB Poles discordance protection (50PD) Closed CB The phase segregated operating circuit Figure 12 Tripping logic, applying line side CT 20 Protection breakers can be in different positions (close-open) due to electrical or mechanical failures during the system normal operation. Dead V4 and dead V3Ph Dead V4 and live V3Ph Live V4 and dead V3Ph The protection operates based on information from auxiliary contacts of the circuit breaker with additional criteria. Synchro-check reference voltage supervision The protection performs following features: 3 phase CB Aux contacts supervision Current criteria checking (including phase current, zero and negative sequence current) If the automatic reclosing is set for synchronization check or energizing check, during the automatic reclosing period, the synchronization condition of the voltages between both sides of CB cannot be met, an alarm will be issued after default time delay. Synchro-check and energizing check (25) Auto-reclosing (79) The synchro-check function checks the both side voltages of the circuit breaker for synchronism conditions. For restoration of the normal service after a fault an auto reclosing attempt is mostly made for overhead lines. Experiences show that about 85% of faults have transient nature and will disappear after an auto reclosing attempt is performed. This means that the line can be re-energized in a short period. The reconnection is accomplished after a dead time via the automatic reclosing function. If the fault is permanent or short circuit arc has not been extinguished, the protection will re-trip the breaker. Main features of the Auto-reclosing are as follows: The synchronization function ensures the stability of the network in three phase reclosing condition. To do this, the two side voltages of the circuit breaker are compared in terms of magnitude, phase angle and frequency differences. Additionally, closing can be done safely in conditions that at least one side of the CB has dead voltage. Available for automatic (internally or externally) Based on voltage/ angle/ frequency difference Modes of energizing check: reclosing Up to 4 shots (selectable) Individually settable dead time for three phase and single phase fault and for each shot Internal/external AR initiation Single/three phase AR operation CB status supervision Synchro-check modes: Synch-check Energizing check, and synch-check if energizing check failure Override 21 Protection CB Aux. contact supervision circuit supervision Cooperation with internal synch-check function for reclosing command A measured voltage failure, due to a broken conductor or a short circuit fault in the secondary circuit of voltage transformer, may result in unwanted operation of the protection functions which work based on voltage criteria. VT failure supervision function is provided to block these protection functions and enable the backup protection functions. The features of the function are as follows: Secondary system supervision Current transformer secondary circuit supervision Open or short circuited CT cores can cause unwanted operation of some protection functions such as earth fault current and negative sequence current functions. Interruption of the CT secondary circuit is detected based on zero-sequence current. Once CT failure happens, each stage of earth fault protection is blocked. Voltage transformer secondary 22 Symmetrical/asymmetrical VT failure detection 3-phase AC voltage MCB monitoring 1-phase AC voltage MCB monitoring Zero and negative sequence current monitoring Applicable in solid grounded, compensated or isolated networks Monitoring Phase-sequence of voltage and current supervision and cables. Detection can initiate an alarm or tripping. The phase-sequence of three phase voltage and current are monitored in the normal condition to determine that the secondary circuit of CT or VT is connected with IED correctly. Self-supervision All modules can perform selfsupervision to its key hardware components and program, as soon as energizing. Parts of the modules are self-supervised in real time. All internal faults or abnormal conditions will initiate an alarm. The fatal faults among them will result in the whole IED blocked The sampled data from the redundant A/D sampling channels compare with each other in real time. If the difference exceeds the specified threshold, it will be considered as analog input channel fault and the protection will be blocked immediately CPU module and communication module perform real time inter-supervision. Therefore communication interruption between them is detected and related alarm will be given CRC checks for the setting, program and configuration, etc. 3I0 polarity supervision The IED compare the magnitude and phase angle of the calculated zero sequence current with the measured one to determine that the polarity is connected in a right way. The third harmonic of voltage supervision If the third harmonic voltage is excessive, the alarm without blocking protection will be given with delay time for checking of the secondary circuit of voltage transformer. Auxiliary contacts of circuit breaker supervision Current flowing through the transmission line and connected CB aux. contacts are monitored in phase segregated. Therefore, the conflict condition is reported as alarm. For example, If CB aux. contacts indicate that CB is open in phase A and at the same time flowing current is measured in this phase, related alarm is reported. Fault locator The built-in fault locator is an impedance measuring function giving the distance from the IED measuring location to the fault position in km. The IED reports fault location after the IED tripping. Broken conductor detection The main purpose of the broken conductor detection function is to detect the broken conductors on protected transmission lines 23 Communication Sifang software tool. Station communication RS485 communication ports Overview Up to 2 isolated electrical RS485 communication ports are provided to connect with substation automation system. These two ports can work in parallel for IEC60870-5-103. The IED is able to connect to one or more substation level systems or equipments simultaneously, through the communication ports with communica-tion protocols supported. (Shown in Figure 14) Ethernet communication ports Front communication port Up to 3 electrical or optical Ethernet communication ports are provided to connect with substation automation system. These two out of three ports can work in parallel for protocol, IEC61850 or IEC60870-5-103. There is a serial RS232 port on the front plate of all the IEDs. Through this port, the IED can be connected to the personal computer for setting, testing, and configuration using the dedicated Server or Work Station 1 Work Station 3 Server or Work Station 2 Switch Work Station 4 Net 1: IEC61850/IEC103,Ethernet Port A Switch Net 2: IEC61850/IEC103,Ethernet Port B Switch Switch Switch Gateway or converter Switch Gateway or converter Net 4: IEC103, RS485 Port B Net 3: IEC103, RS485 Port A Figure 14 Connection example for multi-networks of station automation system Note: All four ports can work in parallel Communication protocol that bay IEDs can exchange information to each other directly, and a simple master-less system can be set up for bay and system interlocking and other interactive function. The IED supports station communication with IEC 61850-8 and IED60870-5-103 protocols. By means of IEC61850, GOOSE peer-to-peer communication make it possible Time synchronization port 24 Communication All IEDs feature a permanently integrated electrical time synchronization port. It can be used to feed timing telegrams in IRIG-B or pulse format into the IEDs via time synchronization receivers. The IED can adapt the second or minute pulse in the pulse mode automatically. The binary signals can be exchanged through remote communication channels between the two IEDs on the two end of the transmission line or cable respectively. This functionality is mainly used for the line Tele-protection schemes, e.g., POTT or PUTT schemes, blocking scheme and inter trip and so on. Meanwhile, SNTP network time synchro-nization can be applied. Remote communication channel The Figure 15 illustrates the optional time synchronization modes. IRIG-B SNTP Ethernet port IRIG-B port The IEDs are able to communicate with each other in two types: Directly fiber-optical cable connection mode at distances up to 100 km (see Figure 16 and Figure 17) Through the communication converter with G.703 or G.703E1 interface through the public digital communica-tion network (see Figure 18 and Figure 19) Pulse Binary input Figure 15 Time synchronizing modes Remote communication Binary signal transfer Because there are up to two selectable fiber-optical remote communication ports, the IED can work in the redundant communication channel mode, with advantage of no time-delay channel switch in case of the primary channel broken (Figure 17, Figure 19 and Figure 20). Overhead Line or Cable Single-mode FO Length: <60kM or 60~100kM Channel A IED IED Figure 16 Single channel, communication through dedicated fiber optical cable 25 Communication Overhead Line or Cable Single-mode FO Length: <60kM or 60~100kM Channel A Channel B IED IED Figure 17 Double channels, communication through dedicated fiber optical cable connectors to the protection IED. The converter can be set to support an electrical G703-64 kbit/s or G703-E1 2Mbit/s interface, according the require-ment of the multiplexed communication network. Communication converter The link between the IED and a multiplexed communication network is made by dedicated communication converters (CSC186). They have a fiber-optic interface with 1310 nm and 2 FC Overhead Line or Cable G703.5(E1: 2048kbit/s) G703.1(64kbit/s) o e IED Digital communication network e o Communication converter Communication converter IED Figure 18 Single Channel, communication through digital communication network 26 Communication Overhead Line or Cable G703.5(E1: 2048kbit/s) G703.1(64kbit/s) Channel A Digital communication network o e o e IED Communication converter Digital communication network e o e o Communication converter IED Channel B Figure 19 Double channels, communication through digital communication network Overhead Line or Cable Single-mode FO Length: <60kM or 60~100kM Channel A o IED e Digital communication network e o IED Channel B G703.5(E1: 2048kbit/s), G703.1(64kbit/s) Figure 20 Double channels, one channel through digital communication network, one channel through dedicated fiber optical cables 27 Software tools A user-friendly software tool is offered for engineering, setting, disturbance analysis and monitoring. It provides versatile functionalities required throughout the life cycle of protection IEDs. Its features are as follows: diagrams, vector diagrams, bar charts and data sheet. Device administration in projects with freely configurable hierarchies for any substation and electrical power station topology Modification, import and export of parameter sets sorted by protection functions, with setting logicality check Precise fault analysis with visualization of fault records in curves, circle 28 Intelligent plausibility checks rule out incorrect input Graphical visualization of charac-teristics and zone diagrams with direct manipulation of the curves Password-protected access for different jobs such as parameter setting, commissioning and controlling (authorized staff only) Testing and diagnostic functions –decisive support in the commissioning phase Hardware Front plate The whole front plate is divided into zones, each of them with a well-defined functionality: 5 1 4 CSC-101 2 3 6 8 7 Figure 21 Front plate 1 Liquid crystal display (LCD) 5 Reset key 2 LEDs 6 Quit key 3 Shortcut function keys 7 Set key 4 Arrow keys 8 RS232 communication port Rear plate Test port X11 For BIM and BOM X10 X9 X8 X7 Ethernet ports X6 X5 PSM X4 X3 COM CPU2 Figure 22 Rear plate of the protection IED 29 Fiber Optical ports X2 CPU1 X1 AIM Hardware optical Ethernet ports and up to 2 channels RS485 serial communication ports can be provided in communication module to meet the communication demands of different substation automation system and RTU at the same time. Modules Analogue Input Module (AIM) The analogue input module is used to galvanically separate and transform the secondary currents and voltages generated by the measuring transformers. The time synchronization port is equipped, which can work in pulse mode or IRIG-B mode. SNTP mode can be applied through communication port. CPU Module (CPU) The CPU module handles all protection functions and logic. There are two CPU modules in the IED, CPU1 and CPU2, with the same software and hardware. They work in parallel and interlock each other to prevent maloperation due to the internal faults of one CPU modules. In addition, a series printer port is also reserved. Binary Input Module (BIM) The binary input module is used to connect the input signals and alarm signals such as the auxiliary contacts of the circuit breaker (CB), etc. Moreover, the redundant A/D sampling channels are equipped. By comparing the data from redundant sampling channels, any sampling data errors and the channel hardware faults can be detected immediately and the proper alarm and blocking is initiated in time. Binary Output Module (BOM) The binary output modules mainly provide tripping output contacts, initiating output contacts and signaling output contacts. All the tripping output relays have contacts with a high switching capacity and are blocked by protection startup elements. Communication Module (COM) The communication module performs communication between the internal protection system and external equipments such as HMI, engineering workstation, substation automation system, RTU, etc., to transmit remote metering, remote signaling, SOE, event reports and record data. Each output relay can be configured to satisfy the demands of users. Power Supply Module (PSM) The power supply module is used to provide the correct internal voltages and full isolation between the terminal and the battery system. Up to 3 channels isolated electrical or 30 Hardware Dimension E C A D B Figure 23 4U, 19” case with rear cover Table 2 Dimension of the IED case Legend A B C D E Dimension (mm) 177 482.6 265 320 437.2 D C E A B Figure 24 Cut-out on the panel Table 3 Dimension of the cutout for IED mounting Legend A B C D E Dimension (mm) 450 465 101.6 178 6.5 31 Connection A. Typical rear terminal diagram X5 X1 a01 b01 a02 b02 a03 b03 a04 b04 a05 b05 a06 b06 a07 b07 a08 b08 a09 b09 a10 b10 a11 b11 a12 b12 BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 BI29 BI30 BI-COM1(-) BI-COM2(-) CSC-101 IA IB IC I0 I4 Null Null Null Null Null Null Null Null U4 UB UC UA UN X2 1) RX connector of optical fiber port 1 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 TX connector of optical fiber port 1 X6 RX connector of optical fiber port 2 Output relay 01 Output relay 02 TX connector of optical fiber port 2 Output relay 03 Output relay 04 X4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Output relay 05 Null Null Null Null RS485 - 2B RS485 - 2A RS485 - 1B RS485 - 1A GPS GPS - GND Null Null Null Null Null Null Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 2) Ethernet Port 1 - RJ45 Ethernet Port 2 - RJ45 Output relay 14 Output relay 15 Output relay 16 32 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Note: 1) The two optical fiber ports are optional for protection remote communication 2) Alternative Ethernet ports for station communication are 2 ST optical fiber ports, shown as following, Ethernet Port 1 - ST Ethernet Port 2 - ST Connection CSC-101 X7 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 X9 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Output relay 01 Output relay 01 Output relay 02 Output relay 02 Output relay 03 Output relay 04 Output relay 03 Output relay 05 Output relay 07 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 08 Output relay 09 Output relay 09 Output relay 10 Output relay 10 Output relay 11 Output relay 11 Output relay 12 Output relay 12 Output relay 13 Output relay 13 Output relay 14 Output relay 14 Output relay 15 Output relay 15 Output relay 16 Output relay 16 Output relay 06 X10 X8 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 1) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 Output relay 10 Output relay 11 Output relay 12 Output relay 13 Output relay 14 Output relay 15 Output relay 16 33 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Note : 1) X10 is optional terminal set, for additional binary output module ordered by user. Connection CSC-101 X11 DC 24V + output Null Null DC 24V - output Power failure alarm relay 1 Power failure alarm relay 2 Null Null AUX DC + input Null Null AUX DC - input Null Null Terminal for earthing Terminal for earthing 34 a02 c02 a04 c04 a06 c06 a08 c08 a10 c10 a12 c12 a14 c14 a16 c16 a18 c18 a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a32 c32 Connection B. Typical analogue inputs connection for one breaker of single or double busbar arrangement A B C Protection IED a01 b01 IA a02 b02 * * * IB a03 b03 IC a04 b04 a12 a11 b11 b12 IN UA UB UC UN a10 b10 35 U4 Connection C. Typical analogue inputs connection for one and half breaker arrangement A B C * * * * * * Protection IED a01 b01 IA a02 b02 IB a03 b03 IC a04 b04 a12 a11 b11 b12 IN UA UB UC UN a10 b10 A B C 36 U4 Connection D. Typical analogue inputs connection for parallel lines A B C Protection IED a01 b01 IA a02 b02 * * * IB * a03 b03 IC a04 b04 a12 a11 b11 b12 IN UA UB UC UN a10 b10 U4 a05 b05 37 INM * * Technical data Frequency Item Standard Rated system frequency IEC 60255-1 Data 50 Hz or 60Hz Internal current transformer Item Standard Rated current Ir IEC 60255-1 Data 1 or 5 A Nominal current range 0.05 Ir to 30 Ir Nominal current range of sensitive 0.005 to 1 A CT ≤ 0.1 VA at Ir = 1 A; Power consumption (per phase) ≤ 0.5 VA at Ir = 5 A ≤ 0.5 VA for sensitive CT Thermal overload capability IEC 60255-1 100 Ir for 1 s IEC 60255-27 4 Ir continuous Internal voltage transformer Item Standard Rated voltage Vr (ph-ph) IEC 60255-1 Data 100 V /110 V Nominal range (ph-e) 0.4 V to 120 V Power consumption at Vr = 110 V IEC 60255-27 ≤ 0.1 VA per phase DL/T 478-2001 Thermal overload capability (phase-neutral voltage) IEC 60255-27 2 Vr, for 10s DL/T 478-2001 1.5 Vr, continuous Auxiliary voltage Item Standard Data Rated auxiliary voltage Uaux IEC60255-1 110 to 250V Permissible tolerance IEC60255-1 ±%20 Uaux Power consumption at quiescent IEC60255-1 ≤ 50 W per power supply module IEC60255-1 ≤ 60 W per power supply module state Power consumption at maximum load 38 Technical data Inrush Current T ≤ 10 ms/I≤ 25 A per power supply IEC60255-1 module, Binary inputs Item Input voltage range Standard IEC60255-1 Data 110/125 V 220/250 V Threshold1: guarantee IEC60255-1 154V, for 220/250V operation 77V, for 110V/125V Threshold2: uncertain operation IEC60255-1 132V, for 220/250V ; 66V, for 110V/125V Response time/reset time IEC60255-1 Software provides de-bounce time Power consumption, energized IEC60255-1 Max. 0.5 W/input, 110V Max. 1 W/input, 220V Binary outputs Item Standard Data Max. system voltage IEC60255-1 250V /~ Current carrying capacity IEC60255-1 5 A continuous, 30A,200ms ON, 15s OFF Making capacity IEC60255-1 1100 W( ) at inductive load with L/R>40 ms 1000 VA(AC) Breaking capacity Mechanical endurance, Unloaded IEC60255-1 IEC60255-1 220V , 0.15A, at L/R≤40 ms 110V , 0.30A, at L/R≤40 ms 50,000,000 cycles (3 Hz switching frequency) Mechanical endurance, making IEC60255-1 ≥1000 cycles Mechanical endurance, breaking IEC60255-1 ≥1000 cycles Specification state verification IEC60255-1 UL/CSA、TŰV IEC60255-23 IEC61810-1 39 Technical data Contact circuit resistance IEC60255-1 measurement IEC60255-23 30mΩ IEC61810-1 Open Contact insulation test (AC IEC60255-1 Dielectric strength) IEC60255-27 Maximum temperature of parts and IEC60255-1 AC1000V 1min 55℃ materials Front communication port Item Data Number 1 Connection Isolated, RS232; front panel, 9-pin subminiature connector, for software tools Communication speed 9600 baud Max. length of communication cable 15 m RS485 communication port Item Data Number 0 to 2 Connection 2-wire connector Rear port in communication module Max. length of communication cable 1.0 km Test voltage 500 V AC against earth For IEC 60870-5-103 protocol Communication speed Factory setting 9600 baud, Min. 1200 baud, Max. 19200 baud Ethernet communication port Item Data Electrical communication port Number 0 to 3 Connection RJ45 connector Rear port in communication module Max. length of communication cable 100m For IEC 61850 protocol 40 Technical data Communication speed 100 Mbit/s For IEC 60870-5-103 protocol Communication speed 100 Mbit/s Optical communication port ( optional ) Number 0 to 2 Connection SC connector Rear port in communication module Optical cable type Multi-mode Max. length of communication cable 2.0km IEC 61850 protocol Communication speed 100 Mbit/s IEC 60870-5-103 protocol Communication speed 100 Mbit/s Time synchronization Item Data Mode Pulse mode IRIG-B signal format IRIG-B000 Connection 2-wire connector Rear port in communication module Voltage levels differential input Fiber optic communication ports for remote communication Item Data Number 1 to 2 Fiber optic cable type Single-mode Optic wavelength 1310nm, when the transmission distance <60km; 1550nm, when the transmission distance >60km Optic received sensitivity -38dBm Emitter electric level >-8dBm; (the transmission distance <40km) >-4dBm; (the transmission distance 40~60km) >-3dBm; (the transmission distance >60km) Fiber optic connector type FC, when the transmission distance <60km) SC, when the transmission distance >60km Data transmission rate 64 kbit/s, G703; 2,048 kbit/s, G703-E1 Max. transmission distance 100kM 41 Technical data Environmental influence Item Recommended permanent operating temperature Data -10 °C to +55°C (Legibility of display may be impaired above +55 °C /+131 °F) Storage and transport temperature limit -25°C to +70°C Permissible humidity 95 % of relative humidity IED design Item Data Case size 4U×19inch Weight ≤ 10kg 42 Technical Data Product safety-related Tests Item Standard Data Over voltage category IEC60255-27 Category III Pollution degree IEC60255-27 Degree 2 Insulation IEC60255-27 Basic insulation Degree of protection (IP) IEC60255-27 Front plate: IP40 IEC 60529 Rear, side, top and bottom: IP 30 IEC 60255-5 2KV, 50Hz EN 60255-5 2.8kV ANSI C37.90 between the following circuits: GB/T 15145-2001 auxiliary power supply DL/T 478-2001 CT / VT inputs Power frequency withstand test high voltage binary inputs binary outputs case earth 500V, 50Hz between the following circuits: Communication ports to case earth time synchronization terminals to case earth Impulse voltage test IEC60255-5 5kV (1.2/50μs, 0.5J) IEC 60255-27 If Ui≥63V EN 60255-5 1kV if Ui<63V ANSI C37.90 Tested between the following GB/T 15145-2001 circuits: DL/T 478-2001 auxiliary power supply CT / VT inputs binary inputs binary outputs case earth Note: Ui: Rated voltage Insulation resistance IEC60255-5 IEC 60255-27 EN 60255-5 ANSI C37.90 GB/T 15145-2001 43 ≥ 100 MΩ at 500 V Technical Data DL/T 478-2001 Protective bonding resistance IEC60255-27 ≤ 0.1Ω Fire withstand/flammability IEC60255-27 Class V2 Electromagnetic immunity tests Item 1 MHz burst immunity test Standard Data IEC60255-22-1 Class III IEC60255-26 2.5 kV CM ; 1 kV DM IEC61000-4-18 Tested on the following circuits: EN 60255-22-1 auxiliary power supply ANSI/IEEE C37.90.1 CT / VT inputs binary inputs binary outputs 1 kV CM ; 0 kV DM Tested on the following circuits: communication ports Electrostatic discharge IEC 60255-22-2 Level 4 IEC 61000-4-2 8 kV contact discharge; EN 60255-22-2 15 kV air gap discharge; both polarities; 150 pF; Ri = 330 Ω Radiated electromagnetic field IEC 60255-22-3 Frequency sweep: disturbance test EN 60255-22-3 80 MHz – 1 GHz; 1.4 GHz – 2.7 GHz spot frequencies: 80 MHz; 160 MHz; 380 MHz; 450 MHz; 900 MHz; 1850 MHz; 2150 MHz 10 V/m AM, 80%, 1 kHz Radiated electromagnetic field IEC 60255-22-3 Pulse-modulated disturbance test EN 60255-22-3 10 V/m, 900 MHz; repetition rate 200 Hz, on duration 50 % Electric fast transient/burst immunity IEC 60255-22-4, Class A, 4KV test IEC 61000-4-4 Tested on the following circuits: EN 60255-22-4 auxiliary power supply ANSI/IEEE C37.90.1 CT / VT inputs binary inputs binary outputs 44 Technical Data Class A, 1KV Tested on the following circuits: communication ports Surge immunity test IEC 60255-22-5 4.0kV L-E IEC 61000-4-5 2.0kV L-L Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 500V L-E Tested on the following circuits: communication ports Conduct immunity test IEC 60255-22-6 Frequency sweep: 150 kHz – 80 IEC 61000-4-6 MHz spot frequencies: 27 MHz and 68 MHz 10 V AM, 80%, 1 kHz Power frequency immunity test IEC60255-22-7 Class A 300 V CM 150 V DM Power frequency magnetic field test IEC 61000-4-8 Level 4 30 A/m cont. / 300 A/m 1 s to 3 s 100 kHz burst immunity test IEC61000-4-18 2.5 kV CM ; 1 kV DM Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 1 kV CM ; 0 kV DM Tested on the following circuits: communication ports DC voltage interruption test Item DC voltage dips Standard IEC 60255-11 45 Data 100% reduction 20 ms Technical Data 60% reduction 200 ms 30% reduction 500 ms DC voltage interruptions IEC 60255-11 100% reduction 5 s DC voltage ripple IEC 60255-11 15%, twice rated frequency DC voltage gradual shut–down IEC 60255-11 60 s shut down ramp /start-up 5 min power off 60 s start-up ramp DC voltage reverse polarity IEC 60255-11 1 min Electromagnetic emission test Item Standard Radiated emission Data IEC60255-25 30MHz to 1GHz ( IT device may up EN60255-25 to 5 GHz) CISPR22 Conducted emission IEC60255-25 0.15MHz to 30MHz EN60255-25 CISPR22 Mechanical tests Item Sinusoidal Vibration Standard response test Data IEC60255-21-1 Class 1 EN 60255-21-1 10 Hz to 60 Hz: 0.075 mm 60 Hz to 150 Hz: 1 g 1 sweep cycle in each axis Relay energized Sinusoidal Vibration endurance IEC60255-21-1 Class 1 test EN 60255-21-1 10 Hz to 150 Hz: 1 g 20 sweep cycle in each axis Relay non-energized Shock response test IEC60255-21-2 Class 1 EN 60255-21-2 5 g, 11 ms duration 3 shocks in both directions of 3 axes Relay energized Shock withstand test IEC60255-21-2 Class 1 EN 60255-21-2 15 g, 11 ms duration 3 shocks in both directions of 3 axes 46 Technical Data Relay non-energized Bump test IEC60255-21-2 Class 1 10 g, 16 ms duration 1000 shocks in both directions of 3 axes Relay non-energized Seismic test IEC60255-21-3 Class 1 X-axis 1 Hz to 8/9 Hz: 7.5 mm X-axis 8/9 Hz to 35 Hz :2 g Y-axis 1 Hz to 8/9 Hz: 3.75 mm Y-axis 8/9 Hz to 35 Hz :1 g 1 sweep cycle in each axis, Relay energized Climatic tests Item Standard Cold test - Operation IEC60255-27 Data -10°C, 16 hours, rated load IEC60068-2-1 Cold test – Storage IEC60255-27 IEC60068-2-1 -25°C, 16 hours Dry heat test – Operation [IEC60255-27 +55°C, 16 hours, rated load IEC60068-2-2 Dry heat test – Storage IEC60255-27 +70°C, 16 hours IEC60068-2-2 Change of temperature Damp heat static test IEC60255-27 Test Nb, figure 2, 5 cycles IEC60068-2-14 -10°C / +55°C IEC60255-27 +40°C, 93% r.h. 10 days, rated load IEC60068-2-78 Damp heat cyclic test IEC60255-27 +55°C, 93% r.h. 6 cycles, rated load IEC60068-2-30 CE Certificate Item EMC Directive Low voltage directive Data EN 61000-6-2 and EN61000-6-4 (EMC Council Directive 2004/108/EC) EN 60255-27 (Low-voltage directive 2006/95 EC). 47 Technical Data Functions NOTE: Ir: CT rated secondary current, 1A or 5A; Distance protection (ANSI 21, 21N) Item Number of settable zone Rang or Value 5 zones , with Tolerance additional extended zone Distance characteristic Polygonal Resistance setting range 0.01Ω~120Ω, step 0.01Ω, when ≤± 5.0% static accuracy Ir=5A; Conditions: 0.05Ω~600Ω, step 0.01Ω, when Voltage range: 0.01 Ur to 1.2 Ur Current range: 0.12 Ir to 20 Ir Ir=1A; Reactance setting range 0.01Ω~120Ω, step 0.01Ω, when Ir=5A; 0.05Ω~600Ω, step 0.01Ω, when Ir=1A; Time delay of distance zones 0.00 to 60.00s, step 0.01s ≤±1% or +20 ms, at 70% operating setting and setting time > 60ms Operation time 22ms typically at 70% setting of zone 1 Dynamic overreaching for zone 1 ≤±5%, at 0.5<SIR<30 Tele-protection (ANSI 85 – 21, 21N, 67N) Item Operating time Rang or Value Tolerance 25ms typically in permission mode for 21/21N, at 70% setting Overcurrent protection (ANSI 50, 51, 67) Item Rang or Value Tolerance Definite time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200% operating setting 48 Technical Data Inverse time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir IEC standard Normal inverse; ≤ ±5% setting + 40ms, at 2 Very inverse; <I/ISETTING < 20, in accordance Extremely inverse; with IEC60255-151 Long inverse ANSI Inverse; ≤ ±5% setting + 40ms, at 2 Short inverse; <I/ISETTING < 20, in Long inverse; accordance with ANSI/IEEE C37.112, Moderately inverse; Very inverse; Extremely inverse; Definite inverse user-defined characteristic ≤ ±5% setting + 40ms, at 2 T= <I/ISETTING < 20, in accordance with IEC60255-151 Time factor of inverse time, A 0.005 to 200.0s, step 0.001s Delay of inverse time, B 0.000 to 60.00s, step 0.01s Index of inverse time, P 0.005 to 10.00, step 0.005 set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s Reset mode instantaneous Directional element Operating area range Characteristic angle ≤ ±3°, at phase to phase voltage >1V 0°to 90°, step 1° Earth fault protection (ANSI 50N, 51N, 67N) Item Rang or value Tolerance Definite time characteristic Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200% operating setting Inverse time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir IEC standard Normal inverse; IEC60255-151 Very inverse; ≤ ±5% setting + 40ms, at 2 Extremely inverse; <I/ISETTING < 20 49 Technical Data Long inverse ANSI Inverse; ANSI/IEEE C37.112, Short inverse; ≤ ±5% setting + 40ms, at 2 Long inverse; <I/ISETTING < 20 Moderately inverse; Very inverse; Extremely inverse; Definite inverse user-defined characteristic IEC60255-151 T= ≤ ±5% setting + 40ms, at 2 <I/ISETTING < 20 Time factor of inverse time, A 0.005 to 200.0s, step 0.001s Delay of inverse time, B 0.000 to 60.00s, step 0.01s Index of inverse time, P 0.005 to 10.00, step 0.005 set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s Reset mode instantaneous Directional element ≤ ±3°, at 3U0≥1V Operating area range of zero sequence directional element Characteristic angle 0°to 90°, step 1° ≤ ±3°, at 3U2≥2V Operating area range of negative sequence directional element Characteristic angle 50°to 90°, step 1° Emergency/backup overcurrent protection (ANSI 50, 51) Item Rang or Value Tolerance Definite time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200% operating setting Inverse time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir IEC standard Normal inverse; ≤ ±5% setting + 40ms, at 2 Very inverse; <I/ISETTING < 20, in accordance Extremely inverse; with IEC60255-151 Long inverse 50 Technical Data ANSI Inverse; ≤ ±5% setting + 40ms, at 2 Short inverse; <I/ISETTING < 20, in Long inverse; accordance with ANSI/IEEE Moderately inverse; C37.112, Very inverse; Extremely inverse; Definite inverse user-defined characteristic ≤ ±5% setting + 40ms, at 2 T= <I/ISETTING < 20, in accordance with IEC60255-151 Time factor of inverse time, A 0.005 to 200.0s, step 0.001s Delay of inverse time, B 0.000 to 60.00s, step 0.01s Index of inverse time, P 0.005 to 10.00, step 0.005 set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s Reset mode instantaneous Emergency/backup earth fault protection (ANSI 50N, 51N) Item Rang or value Tolerance Definite time characteristic Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200% operating setting Inverse time characteristics Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir IEC standard Normal inverse; ≤ ±5% setting + 40ms, at 2 Very inverse; <I/ISETTING < 20, in accordance with Extremely inverse; IEC60255-151 Long inverse ANSI Inverse; ≤ ±5% setting + 40ms, at 2 Short inverse; <I/ISETTING < 20, in accordance Long inverse; with ANSI/IEEE C37.112, Moderately inverse; Very inverse; Extremely inverse; Definite inverse user-defined characteristic ≤ ±5% setting + 40ms, at 2 T= <I/ISETTING < 20, in accordance with 51 Technical Data IEC60255-151 Time factor of inverse time, A 0.005 to 200.0s, step 0.001s Delay of inverse time, B 0.000 to 60.00s, step 0.01s Index of inverse time, P 0.005 to 10.00, step 0.005 set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s Reset mode instantaneous Inrush restraint function Item Upper function limit Range or value 0.25 Ir to 20.00 Ir Tolerance ≤ ±3% setting value or ±0.02Ir Max current for inrush restraint Ratio of 2 nd harmonic current to 0.10 to 0.45, step 0.01 fundamental component current Cross-block (IL1, IL2, IL3) 0.00s to 60.00 s, step 0.01s ≤ ±1% setting or +40ms (settable time) Switch-onto-fault protection (ANSI 50SOTF) Item Rang or Value Tolerance Phase current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Zero-sequence current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay of phase overcurrent 0.00s to 60.00s, step 0.01s ≤ ±1% setting or +40ms, at 200% operating setting Time delay of zero sequence 0.00s to 60.00s, step 0.01s current ≤ ±1% setting or +40ms, at 200% operating setting Breaker failure protection (ANSI 50 BF) Item Rang or Value Tolerance 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay of stage 1 0.00s to 32.00 s, step 0.01s ≤ ±1% setting or +25 ms, at Time delay of stage 2 0.00s to 32.00 s, step 0.01s 200% operating setting phase current Negative sequence current zero sequence current 52 Technical Data Reset time of stage 1 < 20ms Dead zone protection (ANSI 50DZ) Item Rang or Value Tolerance Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00s to 32.00s, step 0.01s ≤ ±1% setting or +40 ms, at 200% operating setting Pole discordance protection (ANSI 50PD) Item Rang or Value Tolerance Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00s to 60.00s, step 0.01s ≤ ±1% setting or +40 ms, at 200% operating setting STUB protection (ANSI 50STUB) Item Rang or Value Tolerance Current 0.08 Ir to 20.00 Ir ≤ ±3% setting or ±0.02Ir Time delay 0.00s to 60.00s, step 0.01s ≤ ±1% setting or +40 ms, at 200% operating setting Undervoltage protection (ANSI 27) Item Voltage connection Rang or Value Phase-to-phase voltages or Tolerance ≤ ±3 % setting or ±1 V phase-to-earth voltages Phase to earth voltage 5 to 75 V , step 1 V ≤ ±3 % setting or ±1 V Phase to phase voltage 10 to 150 V, step 1 V ≤ ±3 % setting or ±1 V Reset ratio 1.01 to 2.00, step 0.01 ≤ ±3 % setting Time delay 0.00 to 120.00 s, step 0.01 s ≤ ±1 % setting or +50 ms, at 80% operating setting Current criteria 0.08 to 2.00 Ir Reset time ≤ 50 ms ≤ ±3% setting or ±0.02Ir 53 Technical Data Overvoltage protection (ANSI 59) Item Rang or Value Voltage connection Phase-to-phase voltages or Tolerance ≤ ±3 % setting or ±1 V phase-to-earth voltages Phase to earth voltage 40 to 100 V, step 1 V ≤ ±3 % setting or ±1 V Phase to phase voltage 80 to 200 V, step 1 V ≤ ±3 % setting or ±1 V Reset ratio 0.90 to 0.99, step 0.01 ≤ ±3 % setting Time delay 0.00 to 60.00 s, step 0.01s ≤ ±1 % setting or +50 ms, at 120% operating setting Reset time <40ms Synchro-check and voltage check (ANSI 25) Item Rang or Value Tolerance Synchronization check: Operating mode Synch-check Energizing check, and synch-check if energizing check failure Override Energizing check: Dead V4 and dead V3Ph Dead V4 and live V3Ph Live V4 and dead V3Ph Voltage threshold of dead line or 10 to 50 V (phase to earth), step bus 1V Voltage threshold of live line or 30 to 65 V (phase to earth), step bus 1V ∆V-measurement Voltage difference Δf-measurement 1 to 40 V (phase-to-earth), steps ≤ ± 3 % setting or 1 V ≤ ± 3 % setting or 1 V ≤ ± 1V 1V (f2>f1; f2<f1) Δα-measurement (α2>α1; 0.02 to 2.00 Hz, step, 0.01 Hz, ≤ ± 20 mHz 1 °to 80 °, step, 1 ° ≤ ± 3° 0.05 to 60.00 s, step,0.01 s, ≤ ± 1.5 % setting value or +60 α2<α1) Minimum measuring time ms Maximum synch-check 0.05 to 60.00 s, step,0.01 s, extension time 54 ≤ ± 1 % setting value or +50 ms Technical Data Auto-Reclosing (ANSI 79) Item Number of reclosing shots Rang or Value Tolerance Up to 4 Shot 1 to 4 is individually selectable AR initiating functions Internal protection functions External binary input Dead time, separated setting for 0.05 s to 60.00 s, step 0.01 s ≤ ± 1 % setting value or +50 ms shots 1 to 4 Reclaim time 0.50 s to 60.00s, step 0.01 s Blocking duration time (AR reset 0.05 s to 60.00s, step 0.01 s time) Circuit breaker ready supervision 0.50 s to 60.00 s, step 0.01 s time Dead time extension for 0.05 s to 60.00 s, step 0.01 s synch-check (Max. SYNT EXT) VT secondary circuit supervision (97FF) Item Range or value Tolerances Minimum current 0.08Ir to 0.20Ir, step 0.01A ≤ ±3% setting or ±0.02Ir Minimum zero or negative 0.08Ir to 0.20Ir, step 0.01A ≤ ±5% setting or ±0.02Ir Maximum phase to earth voltage 7.0V to 20.0V, step 0.01V ≤ ±3% setting or ±1 V Maximum phase to phase 10.0V to 30.0V, step 0.01V ≤ ±3% setting or ±1 V 40.0V to 65.0V, step 0.01V ≤ ±3% setting or ±1 V sequence current voltage Normal phase to earth voltage 55 Ordering Pre-configure schemes Pre-configure scheme M01 M02 Full function single busbar Double or Application arrangement M03 breaker arrangement Distance protection (21, 21N) 1 1 1 Power-swing function (68) 1 1 1 1 1 1 1 1 1 (1) (1) (1) Communication scheme for distance protection (85–21,21N) Communication scheme for earth fault protection (85–67N) Phase segregated scheme communication logic Overcurrent protection (50, 51, 67) 1 Earth fault protection (50N, 51N, 67N) 1 1 1 Emergency/backup overcurrent protection (50, 51) 1 1 1 Emergency/backup earth fault protection (50N, 51N) 1 1 1 Switch-onto-fault protection (50SOTF) 1 1 1 Overload protection (50OL) 1 1 1 Overvoltage protection (59) 1 1 1 Undervoltage protection (27) 1 1 1 Breaker failure protection (50BF) 1 Dead zone protection (50DZ) 1 STUB protection (50STUB) 1 Poles discordance protection (50PD) 1 1 Synchro-check and energizing check (25) 1 1 Auto-reclosing (79) 1 1 Single and/or three pole tripping (94) 1 1 1 CT secondary circuit supervision 1 1 1 VT secondary circuit supervision (97FF) 1 1 1 Analogue input module (5I + 4U) 1 1 1 CPU modules 2 2 2 1 1 1 1 1 1 2 2 2 2 2 2 1 1 Communication module(with Ethernet interfaces, RS485 interfaces and time synchronizing interface) Binary input module (30 BI) Binary output modules (16 relays for tripping and initiation) Binary output modules (16 relays for signal) 56 Ordering Power supply module 1 1 1 Programmable LEDs 18 18 18 Case, 4U,19” 1 1 1 Note: n : Quantity of standard function or standard hardware, n= 1, 2, ….; (n) : Quantity of optional function or optional hardware, n= 1, 2, ….; 57 Ordering Ordering code No.1~16 C S C 1 0 1 - No.17~37 L F T Pre-configure scheme Pre-configure scheme code M Pre-configure scheme number 1 0~9 Pre-configure scheme number 2 0~9 HMI Language (L) note English 1 Russian 2 French Portuguese 3 Spanish 5 4 Rated Frequency (F) 50 Hz 5 60 Hz 6 Station Communication Protocols (T) Ethernet interface:IEC61850-8; RS485 interface: IEC60870-5-103 1 Ethernet interface:IEC60870-5-103; RS485 interface: IEC60870-5-103 2 Note: Chinese is always offered as default HMI language. 58 Ordering No.17~23 No.1~16 C S C 1 0 1 - A M No.24~37 C Slot 1 Analogue Input Module (A) 5I (1A)+4U 5 5I (5A)+4U 6 Slot 2 CPU Module 1 (M) without FDDI 4 1 FDDI, 2Mbps, single mode, SC type, transmission distance <40 kM 5 1 FDDI, 2Mbps, single mode, SC type, transmission distance 40~60kM 6 1 FDDI, 2Mbps, single mode, SC type, transmission distance 60~100kM 7 2 FDDIs, 2Mbps, SC type, Channel A: transmission distance 40~60 kM; Channel B: transmission distance <40 kM 8 2 FDDIs, 2Mbps, SC type, Channel A: transmission distance 60~100 kM; Channel B: transmission distance <40 kM 9 2 FDDIs, 2Mbps, SC type, Channel A: transmission distance <40 kM; Channel B: transmission distance <40 kM e 2 FDDIs, 2Mbps, SC type, Channel A: transmission distance 60~100 kM; Channel B: transmission distance 60~100 kM f Slot 3 CPU Module 2 (M) without FDDI 4 Slot 4 Communication module (C) 3 electrical Ethernet ports, 1 RS485 ports, IRIG-B 1 3 electrical Ethernet ports, 1 RS485 ports, Pulse 2 electrical Ethernet ports, 2 RS485 ports, IRIG-B 2 2 electrical Ethernet ports, 2 RS485 ports, Pulse 2 optical Ethernet ports, 2 RS485 ports, IRIG-B 4 5 2 optical Ethernet ports, 2 RS485 ports, Pulse 6 3 59 Ordering No.24~31 No.1~23 C S C 1 0 1 - I No.32~37 O Slot 5 Binary Input Module (I) 30BI (220V DC), with startup blocking relay 1 30BI (110V DC), with startup blocking relay 2 Slot 6 Binary Output Module (O) 16 relays for tripping 1 Slot 7 Binary Output Module (O) 16 relays for tripping 1 16 relays (with 19 contacts) for signalling 3 Null x Slot 8 Binary Output Module (O) 16 relays for tripping 1 16 relays (with 19 contacts) for signalling 3 Null x Slot 9 Binary Output Module (O) 16 relays for tripping 1 16 relays (with 19 contacts) for signalling 3 Null x Slot 10 Binary Output Module (O) 16 relays for tripping 1 16 relays (with 19 contacts) for signalling 3 Null x 60 Ordering No.1~31 C S C 1 0 1 - No.32~37 P K Z Slot 11 Power Supply Module (P) 1 110V - 250V DC Case and Front Plate (K) Case: 4U, 19' Front plate: Medium size LCD; 20 LEDs 3 Accessories (Z) Null x 61 Address: No.9 Shangdi 4th Street, Haidian District, Beijing, P.R.C. 100085 Tel: +86 10 62962554, +86 10 62961515 ext.8998 Fax: +86 10 82783625 Email:sf_sales@sf-auto.com Website: http://www.sf-auto.com