São Carlos, 19 de Setembro de 2013 AC grid protection for grids with VSC-HVDC converters Helder Leite INESC TEC/University of Porto Outline Transmission Line Protection Principle Short Lines Medium Lines Long Lines Distance Relays: Step coordination Pilot-Aided Distance-Based Schemes Overreaching Distance Functions The influence of a VSC-based HVDC link on the AC SCR Transmission Line Protection Principle VSC-HVDC converters are going to connect to AC Grid Transmission lines are going to take this bulk of energy and provide the path to transfer power to the load; Transmission lines are : A Vital Part of the Power System • Operate at voltage levels from 69kV to 765kV; • Deregulated markets, economic, environmental requirements have pushed utilities to operate transmission lines close to their limits. Transmission Line Protection Principle Classification of line length depends on: Source-to-line Impedance Ratio (SIR), and Nominal voltage Length considerations: Short Lines: SIR > 4 Medium Lines: 0.5 < SIR < 4 Long Lines: SIR < 0.5 ZS SIR ZL Zs- Source Impedance ZL - Line Impedance (1) Transmission Line Protection Principle • Typical Protection Schemes (Short Lines) Current differential Phase comparison Permissive Overreach Transfer Trip (POTT) Directional Comparison Blocking (DCB) Transmission Line Protection Principle • Typical Protection Schemes (Medium Lines) Phase comparison Directional Comparison Blocking (DCB) Permissive Underreach Transfer Trip (PUTT) Permissive Overreach Transfer Trip (POTT) Unblocking Step Distance Step or coordinated overcurrent Inverse time overcurrent Current Differential Transmission Line Protection Principle • Typical Protection Schemes (Long Lines) Phase comparison Directional Comparison Blocking (DCB) Permissive Underreach Transfer Trip (PUTT) Permissive Overreach Transfer Trip (POTT) Unblocking Step Distance Step or coordinated overcurrent Current Differential Transmission Line Protection Principle Z3 (remote backup) Z2 (time delayed) Z1 Transmission Line Protection Principle • Distance relay Coordination Over Lap Local Relay – Z2 Remote Relay – Z4 Transmission Line Protection Principle • The Impedance Relay Characteristic R 2 X 2 Z r21 X Plain Impedance Relay Operation Zone Z Z r1 Zr1 Radius Zr1 R Transmission Line Protection Principle • Step Distance relays • Zone 1: Trips with no intentional time delay Underreaches to avoid unnecessary operation for faults beyond remote terminal Typical reach setting range 80-90% of ZL • Zone 2: Set to protect remainder of line Overreaches into adjacent line/equipment Minimum reach setting 120% of ZL Typically time delayed by 15-30 cycles • Zone 3: Remote backup for relay/station failures at remote terminal Reaches beyond Z2, load encroachment a consideration Transmission Line Protection Principle • Need directionality F2 1 F1 2 3 4 RELAY 3 Operation Zone 5 6 X F1 F2 Nonselective Relay Operation R Transmission Line Protection Principle • Directionality improvement F1 F2 1 2 3 RELAY 3 Operation Zone 4 6 X F1 F2 The Relay Will Not Operate for This Fault 5 Directional Impedance Relay Characteristic R Transmission Line Protection Principle Mho Element Characteristic (Directional Impedance Relay) Operates when: V I Z M cos MT Z Z M cos MT X ZM Z MT R Transmission Line Protection Principle Distance Relay Characteristics) X PLAIN IMPEDANCE X OFFSET MHO (2) R R X X OHM QUADRILATERAL R R Transmission Line Protection Principle Inverse-Time Relay Coordination I Distance t T T T Distance Transmission Line Protection Principle Inverse-Time Relay Coordination t Relay Operation Time I Radial Line Fault Load Transmission Line Protection Principle Directional Comparison Pilot Protection Systems L IR IL T Relays R Communications Channel Exchange of logic information on relay status R Relays T R Transmission Line Protection Principle Pilot-Aided Distance-Based Schemes DUTT – Direct Under-reaching Transfer Trip PUTT – Permissive Under-reaching Transfer Trip POTT – Permissive Over-reaching Transfer Trip Hybrid POTT – Hybrid Permissive Over-reaching Transfer Trip DCB – Directional Comparison Blocking Scheme DCUB – Directional Comparison Unblocking Scheme Transmission Line Protection Principle Pilot-Aided Distance-Based Schemes –DUTT Scheme Zone 1 Bus Bus Line Zone 1 Transmission Line Protection Principle Pilot-Aided Distance-Based Schemes –DUTT Scheme Zone 2 Zone 1 To protect end of line Bus Bus Line Zone 1 Zone 2 Transmission Line Protection Principle Pilot-Aided Distance-Based Schemes –POTT Scheme Zone 2 Zone 1 Bus Bus Line Zone 1 Zone 2 Key XMTR Zone 2 Elements RCVR AND Trip Transmission Line Protection Principle Directional Comparison Blocking Scheme Bus A 1 RVS 2 Bus B 3 4 5 6 FWD FWD RVS Overreaching Distance Functions Impedance Seen by Distance Relays Power swings can be seen as multi-phase faults by distance relays; Power swing protection monitor the rate of change of the positive-sequence impedance; During a major disturbance, a distance relay may see a power swing as a multiphase fault if the positive sequence impedance trajectory enters the operating characteristic relay; As an example: - Simple two-source system A ES ZS Relay Irelay B ZL ZR ER0 Overreaching Distance Functions Impedance Seen by Distance Relays - Simple two-source system A ES Relay ZS Irelay - The current in Bus A I relay ZT Z S Z L Z R B ZL ZR E S E R ZS ZL ZR ER0 (2) - The impedance measure by the relay at bus A Z seen ( relay ) Vrelay I relay E S I relay Z S I relay E S Z S E S E R Z T (3) Overreaching Distance Functions Impedance Seen by Distance Relays - Let us define - K=1 ES k ER 1 Z seen ( relay ) Z S Z T 1 cos j sin Z Z ZS T j T cot 2 2 2 a cons tan t offset - K≠1 Z seen perpendicu lar line segment k ( k cos ) j sin ZS Z T (5) 2 2 ( k cos ) sin (4) Overreaching Distance Functions Impedance Seen by Distance Relays - K=1 K≠1 Overreaching Distance Functions Impedance Seen by Distance Relays - The distance relay located at bus 1 will misoperate on load if the magnitude and phase angle result in a measure impedance that falls within the relays characteristic; 2 Z a R jX - Za V V ( P jQ ) P Q 2 2 is the impedance measure by a distance relay is the measure voltage - P and Q is the active and reactive power (6) Overreaching Distance Functions Impedance Seen by Distance Relays - The distance relay located at bus 1 will misoperate on load if the magnitude and phase angle result in a measure impedance that falls within the relays characteristic; 2 Z a R jX - Za V V ( P jQ ) P Q 2 2 is the impedance measure by a distance relay is the measure voltage - P and Q is the active and reactive power (6) Overreaching Distance Functions Impedance Seen by Distance Relays Overreaching Distance Functions Impedance Seen by Distance Relays - The real and imaginary parts of the measured impedance 2 R V 2 P P Q 2 X 2 V Q P Q 2 (7) 2 4 - R and X can be written as R X 2 - Substituting (7)and (8) results in: 2 R X 2 2 RV P 2 R X 2 2 XV Q 2 V P Q 2 2 (8) 2 4 V V 2 R X 2 P 4P2 2 2 4 V V 2 R X 2Q 4Q 2 2 (9) (10) Overreaching Distance Functions Impedance Seen by Distance Relays - The real and imaginary parts of the measured impedance Overreaching Distance Functions Effect of Fault Resistance in Loop System Vm Zm sZ mn R f I mf If I mf Vn Zn (1 s ) Z mn R f I nf If I nf (11) (12) - Vm and Vn are the voltages at the buses; Imf and Inf are the currents flowing in the line; If is the fault current flowing into the fault F Overreaching Distance Functions Effect of Fault Resistance in Loop System - The currents Imf and Inf are usually shifted, - Current in the fault resistance is phase displaced from currents at the line terminals; - Because of these phase displacements, errors can be obtained on fault location estimation; - The fault resistance appears to the fault locator as an impedance that both resistive and reactive components; Overreaching Distance Functions Effect of Fault Resistance in Loop System Impact of VSC-HVDC Links on AC Power System - The VSC-HVDC can practically instantaneous change the active and reactive power within the capability curve of the converter - Can be used to support the grid with the best mixture of active and reactive power during stressed conditions (even if power reversal is necessary). - Why to know the Impact of VSC-HVDC Links on AC Power System? - Voltage and power stability on the AC Network - Rating of circuit breaker - Power system Protection Impact of VSC-HVDC Links on AC Power System - The basics control patterns for VSC-HVDC a) Frequency control; b) AC voltage control; c) Active power d) Reactive power control e) DC voltage control f) AC current control Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS Contribution of the VSC-HVDC Links to short circuit currents may have some significant impact on the ratings for the circuit breakers in the existing AC Active power control (Control of active power and DC voltage reference) Reactive power control (control of reative power and AC voltage control) VSC can be seen as voltage souce control under normal condition and a current source under abnormal condiction The higher the SCR of the AC network the less contribution in current form the VSC- HVDC Different control modes and different operation points may change the short circuit current contribution from the VSC. Limited contribution Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS - E.g. AC Current mode - When the AC voltage lowers the current limit is reached, the active power reduces - the current limitation is implemented by limiting current components (dand q- axis). - The converter closer to the AC side fault is operating under DC voltage control and reactive power - In the sending end of the VSC-HVDC, active and reactive orders are adjusted proportionally, according with the pre-specified power factor, in order to avoid DC overvoltages, assuming also the sources behind the converter can reduce their production. Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS - Working Example - Fault @ bus 3 | VSC –power control Zf (p.u.) Fault @ bus 3 j0.005 7.41% j0.01 7.68% 0.005 11.32% 0.01 15.45% 0.05 15.49% Icc(p.u.A) 10.24<74.2º 9.79<74.7º 11.00<81.5º 10.91<78.4º 9.49<57.2º Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS - Working Example 2 Active power control (Control of active power and DC voltage reference) FRT PROVISION BY HVDC GRIDS HVDC-VSC technology is able to remain connected to the AC grid during low voltage sags. For the converters connected to onshore AC grids, a voltage sag in the AC side will lead to a current increase, since the converters will try to remain transmitting the same amount of power. Nevertheless, power electronic converters have a maximum current limit associated with the characteristics of the power electric switches. Such characteristic results on a significant reduction of power being injected to the faulted AC mainland grid, which leads to a DC power unbalance that results on DC overvoltages Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS - Working Example 2 FRT Ability of remaining connected to the AC network during moments were voltage profile is extremely low (normally due to fault occurrence) Inject reactive current in order to support AC voltage Impact of VSC-HVDC Links on AC Power System’s Protections VSC-HVDC CONTRIBUTION TO SHORT CIRCUIT CURRENTS • • Fault occurrence at onshore AC grid #1 Severe 500 ms 3 - phase fault: • Assessment of the impact in DC voltage. • The non-injected power in the AC grid #1 is partially re-direct to AC grid #2 – influenced by P/V droop and DC grid dynamics • Overvoltage occurrence in the DC grid