The Webinar will start @ 10 am All participants will be muted upon entry into the session Connecticut Energy Code Administration, General Requirements and Mechanical and Service Water Heating Provisions of 2009 International Energy Conservation Code Connecticut Energy Code 2009 International Energy Conservation Code (IECC) became effective October 6, 2011 Reason for adoption Required by the receipt of ARRA funds Receipt of ARRA funds also required achievement of 90% compliance by December 2017. Information available at www.energycodes.gov/arra/compliance_checklists.stm 2 Administration – Applicability New construction Additions, alterations, renovations or repairs to an existing building, building system or portion thereof Change in occupancy that would result in an increase in energy demand Change in space use from one building type to another building type in the lighting table Change in space conditioning Mixed occupancy 3 Administration & General Requirements Information on construction documents (103.2): Mechanical system design criteria Mechanical and service water heating system and equipment types, sizes and efficiencies Economizer description Equipment and system controls Fan motor horsepower (hp) and controls Duct sealing, duct and pipe insulation and location General requirements Connecticut is in climate zone 5A Interior design conditions Maximum of 72° for heating Minimum of 75° for cooling Maintenance information 4 Residential – Systems Equipment sizing (Mandatory) Heating and cooling loads calculated in accordance with ACCA Manual J (CT Supplement) Heating and cooling equipment sized in accordance with ACCA Manual S (CT Supplement) 5 Residential – Systems Controls (Mandatory) At least 1 thermostat for each separate heating and cooling system At least 1 programmable thermostat for forced- air furnace (55° to 85° capability, 70° & 78° initial settings) 6 Residential – Systems Controls (Mandatory) Heat pumps with electric-resistance supplemental heat controls: Limit supplemental heat operation when heat pump compressor can meet load Snow- and ice-melting system controls: Automatically shut off system when pavement temperature >50° and no precipitation is falling, and Automatic or manual shutoff when outdoor temperature >40° 7 Residential – Systems Ducts (Prescriptive) R-8 minimum insulation on supply ducts in attics R-6 minimum insulation on all ducts elsewhere Minimum duct R-values are installed values (CT Supplement) Exception Insulation not required on ducts located completely inside building thermal envelope 8 Residential – Envelope Thermal Envelope Conditioned Space Conditioned Space 9 Residential – Systems Ducts (Mandatory) Seal joints and seams on: All ducts Air handlers Filter boxes Tightness verification (Not required if the air handler and all ducts are located within conditioned space) Post construction test Rough-in test Building framing cavities not used as supply or return (CT Supplement) ducts 10 Residential – Systems Duct tightness verification: Post construction test ≤8 cfm per 100 ft2 leakage to outdoors or ≤12 cfm per 100 ft2 total leakage Rough-in test ≤6 cfm per 100 ft2 total leakage of complete system ≤4 cfm per 100 ft2 total leakage of system without air handler 11 Residential – Systems Mandatory Systems serving multiple dwelling units shall comply with the commercial requirements. Automatic or readily accessible manual switch on hot water circulating pump when system not in use. Automatic or gravity dampers on outdoor air intake and exhausts to close when the ventilation system not operating. 12 Residential – Systems Pools (Mandatory) Readily accessible switch to allow shutting off heater without adjusting thermostat setting Automatic time switch to turn off and on heaters and pumps Automatic ignition on natural gas or liquefied petroleum (propane) heaters Pool covers: Vapor-retardant on heated pools, and R-12 minimum insulation if pool heated >90° 13 Commercial – General Commercial building project shall comply with: Requirements of Sections 502, 503, 504 and 505 in its entirety or Requirements of ANSI/ASHRAE/IESNA Standard 90.1-2007 with 2008 Supplement (CT Supplement) in its entirety. Exception for projects conforming to Section 506, provided all mandatory sections are each satisfied. 14 Sample Compliance Documentation Available at: http://www.aiact.org/about/committees_regulations.php 15 Commercial – Mechanical Mandatory provisions Heating and cooling load calculations In accordance with procedures in ASHRAE/ACCA Standard 183 Adjusted for reductions from energy recovery systems Heating and cooling equipment and systems capacity shall not exceed calculated loads 16 Commercial – Mechanical Mandatory provisions HVAC equipment performance requirements Unitary air conditioners and condensing units Package terminal air conditioners and heat pumps (new construction units and replacement units) Warm air furnaces and unit heaters Gas- and oil-fired boilers Condensing units Water chilling packages (Path A and Path B) 17 Commercial – Mechanical Mandatory HVAC system controls: Thermostatic control for each zone located in zone controlled Heat pump controls to limit electric-resistance supplemental heat operation Humidity control device for each humidity control system (where provided) Automatic off-hour controls for each zone Motorized dampers on outdoor air supply and exhaust ducts Exception: Gravity dampers permitted on buildings <3 stories or intake and exhaust air flows ≤300 cfm 18 Commercial – Mechanical Ventilation Provided in accordance with mechanical code with capability to reduce outdoor air supply to minimum required Demand controlled ventilation for: 2 Spaces >500 ft , and With average occupant load 40 people per 1,000 ft2, and Served by system with one or more of: 1. 2. 3. Air-side economizer Automatic modulating control of outdoor air damper >3,000 cfm design outdoor airflow 19 Commercial – Mechanical Mandatory energy recovery ventilation on fan systems with: ≥5,000 cfm design supply air quantity, and Minimum outside air quantity ≥70% design supply air quantity. Energy recovery system shall: Provide change in enthalpy ≥50% difference between indoor and return air, and Permit cooling with outdoor air where required. 20 Commercial – Mechanical Mandatory duct and plenum insulation ≥R-5 insulation in unconditioned spaces ≥R-8 insulation when outside ≥R-8 insulation separating duct or plenum from exterior or unconditioned or exempt spaces Mandatory duct and plenum sealing All longitudinal and transvers joints, seams and connections shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), masticplus-embedded-fabric systems, or tapes installed per manufacturer’s instructions. High pressure duct testing 21 Commercial – Mechanical Mandatory minimum pipe insulation on heating and cooling systems with fluid temperatures <55° and >105°. Mandatory fan system (nameplate or brake) horsepower limits Mandatory radiant heating system outside building with time limit control 22 Commercial – Mechanical Air-side economizers on systems ≥54,000 Btu/h (total capacity without economizers <480,000 Btu/h per building or 20% of air economizer capacity, whichever is greater) Speed control on VAV fan motors ≥10 hp Static pressure reset on systems with direct digital control of individual zone boxes 23 Commercial – Mechanical Hydronic system controls Limit reheating and recooling of fluids Hydronic part load controls for systems ≥300,000 Btu/h design output Automatic isolation of equipment in central plants with >1 chiller or >1 boiler Automatic sequencing of multiple-package boilers feeding common distribution system Single boiler system >500,000 Btu/h input to have multistaged or modulating burner Speed control on heat rejection fans ≥7.5 hp 24 Commercial – Mechanical Hydronic (water loop) heat pump systems ≥20° dead band between heat rejection and heat addition by central devices Open- or closed-circuit cooling tower: Separate heat exchanger to isolate tower from loop Automatic shutoff of tower loop pump Automatic valve on tower loop to stop flow Two-position valve on each heat pump on system with >10 hp total pump system power 25 Commercial – Mechanical Systems serving multiple zones Variable Air Volume (VAV) systems required Capability to reduce primary air before reheating, recooling or mixing Supply-air temperature reset control Heat recovery for service water heating when: Facility operates 24 hours a day >6,00,00 Btu/h water-cooled heat rejection >1,000,000 Btu/h design service water load Hot gas bypass limitation on systems without multiple steps of unloading or continuous capacity modulation (50% max on systems ≤240k Btu/h, 25% max on systems >240k Btu/h) 26 Commercial – Mechanical Mandatory HVAC system completion Evidence of completion provided by design professional System balancing Operating manual(s) and maintenance manual(s) Equipment capacity and maintenance actions System control maintenance and calibration information Control sequence descriptions Complete written narrative of how each system is intended to operate 27 Commercial – Service Water Heating Mandatory requirements Equipment efficiency Temperature controls to allow 110° to dwelling units and 90° to other occupancies 1” pipe insulation on automatic-circulating systems ½” pipe insulation on first 8 ft. on noncirculating systems Heat traps on supply and discharge piping 28 Commercial – Service Water Heating Pools (Mandatory) Readily accessible switch to allow shutting off heater without adjusting thermostat setting Automatic time switch to turn off and on heaters and pumps Automatic ignition on natural gas or liquefied petroleum (propane) heaters Pool covers: Vapor-retardant on heated pools, and R-12 minimum insulation if pool heated >90° 29 Total Building Performance Performance-base compliance: Energy cost of proposed design ≤ energy cost of standard reference design Simulations include all building systems and all internal and process loads All mandatory criteria are met Complete freedom for trade offs Criteria for components, assemblies and systems will be different than prescriptive criteria, especially for mechanical 30 Connecticut Energy Efficiency Fund Programs for C/I Projects Energy Conscious Blueprint Incentives for new construction and major renovation Energy Opportunities Incentives for retrofit of existing systems Rebates Rebates or replacement of equipment and controls 31 CT Energy Efficiency Fund Programs Presentation by: The Conservation and Load Management Departments of Connecticut Light & Power and United Illuminating 32 COMMERCIAL & INDUSTRIAL PROGRAMS 33 Energy Conscious Blueprint Program (EB) New Construction Major Renovation Equipment Replacement 75% End of Life Project Track (Incentive requires pre-approval) Prescriptive Rebate Energy Opportunities (EO) Encourages customers to replace functioning equipment with more energy-efficient options Project Track (Incentive requires pre-approval) Prescriptive Rebate 34 Energy Conscious Blueprint (EB) Energy Opportunities (EO) Incentives for installing: HVAC equipment VFDs Refrigeration Motors Process equipment Gas boilers Energy-efficient lighting* Lighting controls 35 Mechanical Upgrades (EO) Incentive is the lesser of: 40% installed cost The greater of: CL&P $0.35/kWh UI $0.30/kWh $1,000/summer peak kW $800/summer peak kW 36 Energy Conscious Blueprint (ECB) HVAC Unitary/splits/ductless units (≤ 30 Tons) $50 to $120 / ton Unitary/splits/ductless units (>30 Tons) Custom Chillers & VFDs Custom Air Compressors (lesser of) Incremental Cost 75% Measure Cap (greater of) $0.30 / kWh OR $1,000 / summer peak kW Prescriptive VFD’s 0 – 5 hp $0 ≥ 5 hp < 40 hp $310 / hp ≥ 40 hp > 50 hp $240 / hp ≥ 50 hp ≤ 100 hp $205 / hp > 100 hp See Process Equipment 37 Gas Measures – Retrofit (EO) Space Heating and Non-Space Heating (lesser of) EO RCx / O&M % of Installed Cost 40% 40% Measure Cap $3.50/ccf $3.50/ccf Prescriptive Values – if applicable $$/unit $$/unit Gas Food Service Rebates EO and ECB ENERGY STAR® Gas Fryers $750/unit ENERGY STAR Gas Steamers $750/unit ENERGY STAR Gas Convection Ovens $500/unit ENERGY STAR Gas Griddles $450/unit 39 Gas Measures – Other Other Prescriptive Caps EO Pool Covers (automated) $12.00/sf Window Film $2.00/sf EMS Systems $500/pt ECB $500/pt High Performance Glazing $2.00/sf Gas Boilers (non-condensing) $4.00/input MBH Gas Boilers (condensing) $8.00/input MBH Gas Storage Water Heaters Varies by input MBH Gas IR Heater Fixed Rebates (Low & High Intensity) Varies by input BTU Up to 50,000 BTU/hr $500/unit ≥ 50,000 BTU/hr < 150,000 BTU/hr $550/unit ≥ 150,000 BTU/hr < 175,000 BTU/hr $650/unit ≥ 175,000 BTU/hr $850/unit 41 HVAC – Cool Choice Rebate $ per ton for exceeding code Unitary / splits / ductless units (units ≤ 30 tons) $50 - $120 / ton (see rebate) Unitary / splits / ductless units (> 30 tons) Custom Incentives Chillers & VFDs Rooftop Units 42 43 44 C&I Loan Program 4.99% for all single measure projects Through 3rd party lenders Loan limits: $2,000 to $1M with interest subsidies on the first $100,000 Maximum loan term not to exceed 5 years Potential cash positive scenarios created 2.99% For projects addressing multiple measures and two or more end uses 45 RESIDENTIAL PROGRAMS 46 Rebates for ENERGY STAR® Certified Equipment HVAC $150 to $250/ system Electric Central A/C Electric Heat Pump Systems Ductless Split Heat Pump Geothermal Heat Pump $500/ton $250/unit $1,500/ dwelling $1,000/ dwelling Additional information on these and all Energy Efficiency Fund rebates can be found at: www.CTEnergyInfo.com 47 Residential New Construction Program Incentives Available for Building Energy Efficient Homes! Single Family Homes, Multifamily Homes, and Gut Rehabs of Existing Homes Qualify For more information contact: Michael Chesney UIL Holdings Corporation 180 Marsh Hill Road MS AD-2A Orange, CT 06477 Enoch Lenge CL&P/Yankee Gas 107 Selden St. Berlin, CT 06037 Tel: 860.665.5369 Tel: 203.499.5935 Fax: 860.665.3030 Fax: 203.499.2800 Email: Michael.Chesney@uinet.com Email: Enoch.Lenge@nu.com 48 Contacts United Illuminating • • • • • Commercial Programs: Residential Programs: Natural Gas Programs: Rebates: Financing: Roy W. Haller (203) 499-2025 Chris Ehlert (203) 499-2965 Roy W. Haller (203) 499-2025 Roy W. Haller (203) 499-2025 Roy W. Haller (203) 499-2025 Connecticut Light & Power • Commercial Programs: • • • • Residential Programs: Commercial Rebates: Natural Gas Programs: Financing: Rich Asselin (860) 665-3292 Glen Eigo (860) 665-5084 Lomont White (860) 665-3790 Dave Hayward (860) 665-3386 Matt Fox (860) 665-3749 Gentiana Darragjati (860) 665-4757 49 Questions? Thank you! 50