Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Refrigerant Leak Detection System Installation Instructions Table of Contents Introduction ......................................................................................1 Hardware Specifications ..................................................................3 Functional Overview ......................................................................10 Panel Installation ............................................................................29 Sensor Installation..........................................................................30 Horn/Strobe installation .................................................................32 Wiring the System..........................................................................33 Checking Installation .....................................................................38 Recommended Gas Alarm Settings ...............................................38 Maintenance ...................................................................................39 Model & Part Numbers ..................................................................41 Introduction Novar Refrigerant Gas Leak Alarm Panel Kits, see Figure 1, are designed to continuously monitor refrigeration racks and walk-in coolers/freezers for the presence of refrigerant gases. Novar’s Refrigerant Gas Leak Alarm Panel Kits provide easily accessible I/O interfaces that allow connection to controllers from multiple manufacturers. Figure 1. Refrigerant Gas Leak Alarm Panel Kit Continuous, remote monitoring can be realized by simply interfacing the RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 1 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Refrigerant Gas Leak Alarm Panel (RGLAP) to any Executive Controller using any standard I/O module supporting a 4-20mA interface. Continuous, off-site monitoring can be realized by simply interfacing the Novar Refrigerant Gas Leak Alarm Panel to an 8IM Module or Rack Input Module and an Executive Controller. The Novar Refrigerant Gas Leak Alarm Panel Kit is a stand-alone, onezone, refrigerant-gas-detection system which consists of the following components: Novar Refrigerant Gas Leak Alarm Panel Figure 2. Novar Refrigerant Gas Leak Alarm Panel Honeywell/Manning AirScanTM IR Refrigerant Sensor Figure 3. Honeywell/Manning AirScanTM IR Refrigerant Sensor RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 2 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT System Sensor Horn/Strobe Audio/Visual Alarm Figure 4. System Sensor Horn/Strobe Audio/Visual Alarm Battery Backup Panel Figure 5. Battery Back-up Panel Hardware Specifications Refrigerant Gas Leak Alarm Panel Enclosed Fuse Holder (600V, 30A) (F1): Indicating: No Poles: One Amperage: 30A Case: Thermoplastic Torque Rating: 17.7in/lbs Wire Range: #8-#14 AWG CU Fuse Size: 13/13"DIA x 1.5" Fuse: ATDR 120VAC-to-24VDC, 2.5A, Class 2 Power Supply Module (PS-1): RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 3 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Type: 24V/2,5A Input Rated Voltage Vin: 100VAC to 240VAC Voltage Range: 85VAC to 264VAC Line Frequency Range: 47Hz to 63 Hz Mains Buffering: > 40 ms Rated Current Iin: 1.22A to0.66A Output Rated Voltage Vout: 24VDC Residual Ripple/Spikes: < 200/300mVpp Setting Range: 22.2VDC to 26.4VDC Rated Current Iout: 2.5A Current Limitation: 3.4A typ. Efficiency at Full Load: 87% typ. Environmental Conditions Transportation and Storage Temperature: -40°C to +70°C Ambient Temperature During Operation:-20°C to +55°C Degree of Protection:IP 20 Pollution Degree Environment:2 Humidity Rating:Climate category 3K3 acc. to EN 60721, relative air humidity 5...95 %, without condensation EMC Interference Emission:EN 50081-1, class B acc. to EN 55022 EMC Interference Immunity:EN 61000-6-2, EN 61000-4-2/-3/-4/-5/-6/-11 Safety Protection Class:Class II (without protective earth PE) Galvanic Isolation Primary/Secondary:SELV output voltage acc. to EN 60950 and EN 50178 AC Fail Relay (RLY-2): Coil Voltage:120VAC Poles:DPDT Contact Amperes:20A Features:Locking Push Button = M4 Bi-Polar LED Relay Module (RLY-1): Coil Voltage:24VDC Poles:3PDT Contact Amperes:15A Features:Locking Push Button = M4 Bi-Polar LED Terminal Block Style Connectors (TB-1): Torque Rating:4.2in/lbs Wire Range:22-12 AWG STR (copper wire 60°C) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 4 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Honeywell Manning Dual Alarm Relay Module Power Supply Requirements: +18 to +26 VDC Power Supply Current: 120 mA Max Operating temperature: -10° F to +120° F Humidity Conditions: 0% to 95% RH non-condensing Relay Contacts: Isolated 5A @ 125 VAC / 100 VDC Set point Adjustment: 33%/100% full-scale (20 mA) and 50%/100% full-scale (20 mA) Built-in hysteresis: 2-second time delay for both On/Off transitions Dimensions: 8.5” high x 8.5” wide x 2.5” deep LED Status Indicators (Internal): Power (green), Low Alarm (yellow), High Alarm (red) Connectors: Screw terminal type 22-gauge to 18-gauge stranded copper Maximum distance from controller: 1000 feet Load Resistor: 50Ω to 400Ω RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 5 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Honeywell Manning AirScanTM iR Refrigerant Sensor Figure 6. Honeywell Manning AirScan iR Specifications RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 6 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT System Sensor Horn/Strobe Audio/Visual Alarm Figure 7. System Horn Strobe Specifications RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 7 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Fire-Lite CHG-75 Battery Charger: Primary (AC) Power - TB1, Terminals 1 (Hot), 2 (Neutral) & 3 (Earth) 120VAC, 60Hz, 2.05A maximum 220/240VAC, 50Hz, 1.14A maximum (JP1 cut) Fuse F1 - 6.25A (slow blow 3AG) Wire size: Minimum 14 AWG with 600 volt insulation Secondary Power (Battery) Charging Circuit - TB2, Terminals 1 (+) & 2 (-) Supports lead-acid batteries only Float Charge Voltage: 27.6VDC Maximum Charge Current: 4.5A (peak) Maximum Battery Capacity: 75AH Supervised and Current-limited: F2 – 15A replaceable fuse 24 VDC Secondary (Battery) Input Power The CHG-75 current consumption from the battery is as follows: • During AC Loss: 60mA • With AC Present: 0mA Note: use these values in battery calculations for host FACP Battery Output - TB2, Terminals 3 (+) & 4 (-) Provides battery backup connection to other loads Current-limited: F3 – 15A replaceable fuse SLC (Signal Line Circuit) Connector - TB3, Terminals 1(B+), 2(A+), 3(B-) & 4(A-) Voltage 24VDC nominal, 27.6VDC maximum Maximum Loop Current 400mA (short circuit) or 100mA (normal) Maximum Loop Resistance 40ohms Supervised and Power-limited Trouble Contact Rating - TB4, Terminals 1 (C), 2 (NO) & 3 (NC) Fail-safe Form-C Relay Contacts Rated for 2A @ 30VDC (resistive) BAT-12260 26AHR Lead Acid Battery: Nominal voltage: 12VDC Nominal capacity (20 hr): 26.0AH Dimensions Total height 125 mm (4.92") Container height 125 mm (4.92") Length 166 mm (6.54"); width 175 mm (6.89") Weight Approximately 8.80 kg (19.40 lbs) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 8 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Container material: UL94HB ABS, UL94V-0 ABS. Internal resistance (25°C, 77°F): ~ 10 m. Discharge capacity under different temperatures 40°C: ~ 102% 25°C: ~ 100% 0°C: ~ 85% Capacity 25°C/77°F 20hr @ 1.3A: 26.0AH 5hr @ 4.16A: 20.8AH 1hr @ 15.6A: 15.6AH 1C @ 26.0A: 13.0AH Charging voltage (25°C, 77°F) Standby use: 13.65V ± 0.15V Cycle use: 14.7V ± 0.3V Maximum discharge current: 300A (5 sec) Maximum charging current: 7.8A Self-discharge residual capacity (25°C, 77°F) After 3 months: ~ 90% After 6 months: ~ 82% After 12 months: ~ 70% Piezoelectric Trouble Buzzer: Sound level Category : Medium Sound Level Mode of Operation: Slow Pulse Voltage Rating: 6 to 28VDC Frequency Range: 1900 Hz ±300 Hz Loudness (Min. Voltage): 60 dB(A) min. @ 2 FT and 6VDC Loudness (Max Voltage): 75 dB(A) min. @ 2FT and 28VDC Current Draw 5 mA Max @ 6VDC 23 mA Max @ 28VDC Min Pulse Rate (PPS): 0.5 @ 6VDC Max Pulse Rate (PPS): 2.0 @ 28VDC Duty Cycle (%): 50 (Approx) Storage Temperature: -40°F to 185°F (-40°C to +85°C) Operating Temperature: -22°F to 149°F (-30°C to +65°C) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 9 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Weight (Typical): 2.1 oz (59 g) Housing: 6/6 Nylon, Color Black Functional Overview The Novar Refrigerant Gas Leak Alarm Panel kit consists of a Novar Refrigerant Gas Leak Alarm Panel, a Honeywell/Manning AirScanTM IR infrared refrigerant gas sensor, and a Spectrometry Advance System Sensor horn/strobe audio/visual alarm. An optional 24VDC Battery Backup Panel is also available if required by the customer or local authority. Figure 8. is a block diagram of the system. Continuous, off-site monitoring can be accomplished by simply interfacing the Novar Refrigerant Gas Leak Alarm Panel to either a Novar 8IM or Rack Input Module and an Executive Controller. Interfacing to an 8IM Module is implemented by connecting the 4mA-to20mA current-loop output (CNT-SIG and CNT-GND) to one of the 8IM Module’s current inputs. For Rack Input Module implementation, one of the three normally-open, dry-contact outputs provided (ALARM #1NO / ALARM#1COM, ALARM #2NO / ALARM#2COM, or ALARM #3NO / ALARM#3COM ) should be used. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 10 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 8. System Block Diagram Refrigerant Gas Leak Alarm Panel The Novar Refrigerant Gas Leak Alarm Panel consists of the following components (See Figure 9): Enclosed Fuse Holder (F1) 120VAC-to-24VDC, 2.5A, Class-2 Power Supply Module (PS-1) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 11 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT AC Fail Relay Module (RLY-2) Honeywell/Manning Dual Alarm Relay Module (RDARM) Relay Module of Three Normally-Open, Dry Contacts (RLY-1) Terminal Block Style Connector for Outside Connections (TB-1) Three Status Lamps (located on the center, lower front of the panel) SpectrAlert® Advance System Sensor Horn/Strobe Audio/Visual Alarm Figure 9. RGLAP Inside View Enclosed fuse holder (F1), class-2 power supply module (PS-1), AC fault relay module (RLY-2), relay module (RLY-1), and terminal connectors (TB-1) of the Novar Refrigerant Gas Leak Alarm Panel are all mounted on 1-3/8 inch (35mm) wide DIN rail. The Honeywell/Manning Dual Alarm Relay Module (RDARM) is mounted with threaded standoffs and nuts at each corner of the board. The SpectrAlert® Advance System Sensor Horn/Strobe Audio/Visual Alarm is snap-fitted to a four-screw-mounted base-plate at the top center of the panel door. For ease of installation, all modules and terminals have wire-cage and screw connections (Figure 10). RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 12 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 10. Wire-cage screw connections The enclosed fuse holder F1 (see Figure 11) contains a 600V, 30A fuse which is easily replaceable by use of a fuse lift-handle system. If an overcurrent fault should occur within the system, the fuse will open removing the system from the 120VAC power line. One replacement fuse is mounted inside the panel at the lower right (see Figure 11). Figure 11. Fuse placement The 120VAC-to-24VDC power supply (PS-1 in Figure 12) sources RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 13 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT +24VDC@2.5A to all components of the system. 120VAC line power is supplied to the module through two wire-cage and screw terminals. One terminal (L1) connects to line voltage through fuse module F1; the other (Neutral) through the TB-1 terminal block connector. Figure 12. 24VDC power supply The AC fail relay (RLY-2 in Figure 13) prevents system power failure if a power-line loss should occur by switching from the 120VAC-to24VDC power supply to the optional +24VDC Battery Backup Panel if installed. Battery Backup Panel connections are made at TB-1 BATT(+) and BATT (-). If a power outage should occur, the Battery Backup option will allow the Refrigerant Gas Leak Alarm Panel to continue normal operation for twenty-four hours and then be capable of operating in alarm mode for five minutes if a refrigerant leak should occur during the power outage. The AC fail relay has both mechanical and LED status indicators and a locking push button. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 14 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 13. Power system failure prevention Output from the Honeywell/Manning AirScanTM IR infrared refrigerant gas sensor is input to a Honeywell/Manning Dual Alarm Relay Module (Figure 14). The Dual Alarm Relay Module is a 4mA-to-20mA, feedthrough device designed to provide remote dual stage alarm relay outputs and can be used with any Honeywell/Manning Systems gas sensor. Setpoint adjustment is by a two-position switch, allowing standard trip levels of 33% / 100 % full scale trip levels or 50 % / 100% full scale. The 2A@24VDC SPDT relays are unpowered in normal state. Three LED's located at the center of the module indicate status of power (green), low alarm (yellow), and high alarm (red). Figure 14. Relay module RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 15 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Connections are made to the Dual Alarm Relay Module (RDARM) from panel terminal blocks TB-1 (CNT-SIG, CNT-GND, SEN-GND, SEN24V, and SEN-GND) through two board mounted connector blocks, one providing gas sensor +24V power, ground, and 4mA-to-20mA signal input; the other providing control panel +24V power, ground, and 4mAto-20mA control signal. NOTE! In the event that offsite monitoring will not being utilized (not connected to a Novar 8IM Module), to enable the alarm function of the alarm panel a properly sized (wattage), 50Ω to 400Ω resistor must be connected between terminals CNT-SIG and CNT-GND. If this is not done, the Dual Alarm Relay Module will not alarm in the event of a detected gas leak. The Relay Module (RLY-1 in Figure 15) provides three normally-open, dry contacts which are used for auxiliary monitoring of alarms or external equipment interfacing. The relay has both mechanical and LED status indicators and a locking push button. Figure 15. Relay module Three status lamps are located on the lower front of the panel (Figure 16). After the 120VAC power is applied, the left-side green status lamp will be illuminated. The center blue 24VDC power status lamp is illuminated with the presence of either battery-backup power or the 24VDC power supply. The right-side red alarm status lamp is illuminated only during an alarm. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 16 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 16. Alarm Panel Upon detection of a refrigeration gas leak, the alarm status lamp is illuminated by the Dual Alarm Relay Module’s low-alarm relay, which also activates the SpectrAlert® Horn/Strobe Alarm, causing the strobe to flash at a one-hertz rate and the horn to sound. NOTE! Alarms are automatically silenced when the detected refrigerant has dissipated in the area being monitored and the gas sensor sampling chamber has been cleared. Provision is made for the addition of external strobe/horn devices at connector terminals H/S 24V and H/S GND. Manning AirScanTM IR The Honeywell Manning AirScanTM IR infrared sensor (Figure 17) is a microprocessor-based sensor that is selective to refrigerants and provides years of service at the highest level of accuracy and reliability. This highly versatile sensor features SensorCheckTM, a unique technology that continuously monitors sensor performance that enables it to provide worry-free performance throughout the life of the sensor. A true “diffusion” design sensor, the Honeywell Manning AirScanTM IR sensor does not require pumps or filters and allows all points of gas detection to be monitored perpetually, unlike sample draw systems. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 17 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 17. Air Scan Gas detection by the infrared method is based on the principle that most gases absorb infrared energy at a characteristic frequency. In this instrument, a broad band infrared source emits energy which is then band-pass filtered to produce a narrow range of frequencies characteristic of the refrigerants’ (CFC/HCFC/HFC) absorption spectra. Any refrigerant in the gas sample cell (Figure 18) selectively absorbs energy reaching the detector. This reduction in energy is detected, amplified and sent to the signal processing portion of the system. The Honeywell Manning AirScanTM IR Sensor line is a three-wire, 4mAto-20mA sensor for two bands of refrigerants available in a range of 0— 3,000ppm, but can be adjusted for lower ranges, if required. The lowband or R-404a infrared sensor reacts to R-123, R-134a, R-404a and R507. The high-band or R-22 Honeywell/Manning AirScanTM IR sensor reacts to R-22. Figure 18. Sample cell RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 18 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Internal compensation for environmental changes allows the sensor to automatically adapt to fluctuating temperature and humidity conditions. Every two seconds SensorCheckTM technology monitors the AirScanTM IR source and ensures that the dual channels are functioning properly. A notification signal will be transmitted if any of several performance parameters are not met. Monitoring equipment must be configured to indicate a fault if the signal is less than 1.5mA. All signals over 20mA must be considered a high gas concentration. Honeywell Manning infrared sensors are normally long-lived (5 years plus), unless physically damaged or wetted with water or other liquid. Power and signal connections for the Honeywell Manning AirScanTM IR are made through a wire-cage and screw connector (see Figure 19). Figure 19. Screw connector Sensor operation status is indicated by the blink pattern of seven LED’s located in a vertical row on the right side of the sensor circuit board (see Figure 20). LED status is differentiated by color and duration/pattern of blink(s). RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 19 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 20 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 20. Sensor circuit board After power-up, the green power LED is continuously on, both fault LED’s are off, and the green source LED is blinking once every 2 seconds. The green power LED is continuously ON once power is applied. The yellow system LED indicates the following: Continuous ON during normal filtered output run mode “dead band” from 4mA to 4.6mA Slow blink during normal non-filtered output run mode Fast blink indicating unit lost calibration data Off during 4mA-to-20mA loop check The yellow calibrate LED indicates the following: Continuous momentary on for auto-zero mode activation Slow blink for 4mA output calibration mode Medium double blink indicates 4mA-to-20mA loop check 0.5mA (low) Fast blink for span calibration mode and 4mA-to-20mA loop check 22mA (high) The red fault LED indicates the following (all scenarios produce a 0.5mA output): RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 21 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Continuous on indicates a failed source, low signal, or circuit failure Slow blink indicates the power supply 24VDC input voltage is too low Medium double blink indicates sensor is outside the operating temperature range Fast blink indicates the signal drifted below 4mA and needs to be re-calibrated, only in non-filtered output run mode (no dead-band) The red mA fault LED attempts to output a 0.5mA. A fast blink indicates 4mA-to-20mA loop failure or load resistance too high. The green source LED blinks once every 2 seconds to indicate when source is energized and also that the source is not short circuited. The green ATMOS LED is continuously on and indicates ATMOS circuitry is active or adjusting the enclosure’s internal environmental conditions for the sensor to function reliably. The above description on LED indicators is very limited; See AirScan IR Manual for full details. Pushbutton S1 (Figure 21) is used to initiate the auto-zero function, program the 4mA output calibration, and initiate the 4mA-to-20mA loop test. Figure 21. Pushbutton S1 RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 22 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT System Sensor SpectrAlert® Horn/Strobe Audio/Visual Alarm The SpectrAlert Advance horns, strobes, and horn/strobes can be used indoors or outdoors in wet or dry applications and can provide reliable operation from −40°F to 151°F. Figure 22. Honeywell Sensor SpectrAlert Horn/Strobe Like the entire SpectrAlert Advance product line, these devices include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, which make installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. All horns, strobes, and horn/strobes use a universal mounting plate with an onboard shorting spring that tests wiring continuity before the device is installed, protecting devices from damage. The SpectrAlert Advance is housed in a NEMA 4X rated, 5.6” x 4.7” x 2.5 deep (without weather-proof back box) enclosure. 24VDC Battery Backup Panel The Battery Backup Panel (Figure 23) allows the Refrigerant Leak Detection Panel to continue with normal operation for twenty-four hours and then be capable of operating in alarm mode for at least five minutes. The Refrigerant Leak Detection Panel transfers to the Battery Backup Panel when 120VAC power is lost. The Refrigerant Leak Detection Panel automatically returns to primary power when the 120VAC power has been restored. Simultaneously, when 120VAC power is lost, a 24VDC trouble audible will sound (pulses on/off for one second) until the primary power has RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 23 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT been restored. The audible buzzer cannot be manually silenced. Battery Backup Panel dimensions are 15.6” x 15.5” x 5.13”; weight is approximately 60lbs with batteries. The Battery Backup Panel consists of the following components: Fire-Lite CHG-75 Battery Charger Fire-Lite BB-26 Battery Box Fire-Lite BAT-12260 26AH, Lead-Acid, Sealed Battery (2 required). Piezoelectric Buzzer with Bracket Assembly Figure 23. Battery Backup Panel CHG-75 Battery Charger The CHG-75 battery charger (Figure 24) is designed to charge lead-acid batteries that provide emergency standby power. Two 12V batteries (BAT-12260) are used in series to supply a nominal 24VDC. The battery charger is compatible with any lead-acid batteries with a rating of 25AH to 75AH. The CHG-75 can be configured for 120VAC operation or 220/240VAC operation via jumper selection. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 24 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 24. Battery Charger Two screw terminal blocks, one insulated located at the lower-left-side of the module and one non-insulated located at the right-hand side of the module, provide connection points for line power, battery, and RGLAP +24VDC power out (see Figure 24 and Figure 25). Figure 25. Wiring Board RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 25 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Line power connections Line, Neutral, and Ground enter the CHG-75 through the insulated, screw-terminal block located at the lower-left side of the module. BAT-12260 + and - connections are made at the lower two screw terminals located on the right-hand side of the module. RGLAP +24VDC power out connections are made at the upper two screw terminals located on the right-hand side of the module. Status indication LEDs are provided on the CHG-75 circuit board to monitor various charger conditions: AC LED – green LED indicates AC power is present Trouble LED – yellow LED turns on for charger troubles or trouble indication from the Master Trouble Input Low Battery LED – yellow LED turns on when the battery voltage drops too low Charging LED – yellow LED indicates battery is being charged, turns off when the CHG-75 is trickle charging Ground Fault LED – yellow LED turns on to indicate ground fault on the charger BB-26 Battery Box The battery box is designed to contain two BAT-12260 12V, 26AH, lead-acid, sealed batteries; a CHG-75 battery charger; and a piezoelectric alarm buzzer with bracket assembly. The CHG-75 module is located and mounted on four #4-40 threaded studs. One #4-40 stud, located at the left side of the CHG-75 module, is provided for battery box grounding. The BB-26 box dimensions are 15.6" (39.62cm) wide, 15.5" (39.37cm) high, and 5.125" (13.02cm) deep. For installation wiring, the box is designed with one 1.125” diameter (2.857cm) knockout located on the left-side top of the box; four identical knockouts are located in both sides and the rear of the box. Two mounting holes are provided at the top of the battery box for installation of optional AM-1and VM-1 meters. For installation mounting, the BB-26 battery box has two mounting holes located in the back of the box (see Figure 26) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 26 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 26. Battery Box RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 27 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 27. Mounting Diagram Optional Ammeter (AM-1) or Voltmeter (VM-1) Optional ammeter (AM-1) and voltmeter (VM-1) are available for the CHG-75 battery charger. Meter ranges are 0A-to-10A and 0V-to-50V respectfully. The meters indicate charge voltage and charge current. Both meters are wired to the CHG-75 and mounted in mounting holes provided in the BB-26 battery box. BAT-12260 The BAT 12260 battery is a 12V, 26AH, lead-acid, sealed battery. Two are required and are serially configured for a nominal output voltage of 24VDC. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 28 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Piezoelectric Trouble Buzzer with Custom Bracket Assembly A piezoelectric buzzer (Figure 28) is employed to sound a one-second pulse rate, 70dB(A)@2Ft audible alarm when primary line power to the Battery Backup and RGLP is lost. The alarm will sound until primary power is restored and cannot be manually silenced. Figure 28. Piezoelectric buzzer The piezoelectric buzzer is mounted on a custom bracket which is mounted to the CHG-75 module. The buzzer is powered by the +24VDC battery source and is operated by the CHG-75 module Form-C, trouble-relay contacts. Panel Installation This section covers the mounting of the Refrigerant Gas leak Alarm Panel (RGLAP). It assumes that the work is being completed by an engineer, technician, or service person that is performing control systems installation. Mounting and Orientation The Panel is to be mounted per the requirements of the Customer or Authority having jurisdiction. The panel is to be mounted at a height which allows appropriate access to the interior of the panel. When mounting the panel to paneling or drywall, use hollow-wall anchors or appropriate fasteners to insure that the assembly remains secure. The panel should be on the outside of the space being monitored near the entrance of that space. Screw Locations The RGLAP should be installed plumb and level and securely fastened to RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 29 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT a rigid mounting surface. The enclosure utilizes four mounting holes on the back of the box (see Figure 29 below). Figure 29. Mounting hole locations Sensor Installation This section covers the mounting of the Manning AirScanTM IR. Mounting and Orientation Because each sensor can only “report” what it is seeing at the moment, it is very important that the sensor be located where leaks are most likely to occur. CFC/ HCFC/HFC vapor is heavier than ambient air, so in a room with no air movement it will tend to settle. For quickest detection, mount the sensor about one to two feet from the floor, close to the potential leak source. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 30 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT If the primary application is the fastest possible leak detection, mount the sensor near the potential leak sources. In doing this, be aware that the indicated concentration may not be representative of personnel exposure and easy access for the required calibration and maintenance could be compromised. General Considerations: Very Important: Must be easily accessible for calibration and maintenance. Always mount the sensor vertically. Mount the sensor close to the potential leak source for fastest possible leak detection. Protect sensor from water, excessive humidity, and washdown. Take air movement and ventilation patterns into account. To prevent electrical interference, keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters. Protect sensor from physical damage (fork lifts, etc.). Do not mount the sensor over a door in a refrigerated area. Sensor must be mounted vertically. Never mount sensor flat on a ceiling. Enter enclosure only through existing hole in bottom of enclosure. Always make a drip loop in the conduit. Never mount sensor on a vibrating surface. NOTE! Mount sensor enclosures through the flange holes as shown in Figure 30 and always mount vertically. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 31 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 30. Sensor Dimensions Horn/Strobe installation This section covers the mounting of the Remote Horn and Strobe. The Horn/Strobe is to be mounted per the requirements of the Customer or Authority having jurisdiction. An installed weatherproof back box should not be left without an installed unit for extended periods of time to avoid water accumulation. Mounting and Orientation The wall-mount back box shipped with these products must be mounted with the internal post (Figure 31A) in the lower left corner.*Attach the device mounting plate (Figure 31B) to the weatherproof back box (Figure 31C) using the four non-painted screws (Figure 31D) included with the product. Hook the tabs on the product housing into the grooves on the mounting plate. Then, swing the product into position to engage the pins on the device with the terminals on the mounting plate. Verify that the tabs on the back of the device are fully engaged with the mounting plate. Finally, secure the device to the mounting plate by tightening the single screw attached to the front of the housing (Figure 31E). For tamper resistance, the captured screw may be replaced with the Torx screw supplied with the device. For conduit installation refer to the Proper Installation of SpectrAlert® Advance Outdoor Audible Visible Appliances guide. Screw Locations The Horn and Strobe should be installed plumb and level and securely fastened to a rigid mounting surface. The enclosure utilizes two flange holes on the either side of the box (see Figure 31 below). RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 32 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 31. Horn Strobe details Wiring the System CAUTION! All wiring must comply with local and national electrical codes. CAUTION! Disconnect power before beginning installation. Failure to do so can cause electrical shock or equipment damage. NOTE! This product should be installed by a trained and experienced technician. Failure to follow these instructions carefully could damage the product or cause unexpected system operation. Refrigerant Gas Leak Alarm Panel The 120VAC-to-24VDC power supply (PS-1) sources +24VDC@2.5A RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 33 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT to all components of the Novar Refrigerant Leak Detection System through Terminal Block 1 (TB1). 120VAC line power is supplied to the module through two wire cage and screw terminals using 18 AWG. One terminal (L1) connects to terminal 1 (on TB1) line voltage through the fuse module; the other (Neutral) through the terminal block connector terminal 2 (TB1). Connect the Earth Ground to terminal 3. NOTE! Refer to the wire diagram in the panel door pocket for further detail. NOTE! In the event that offsite monitoring will not being utilized (not connected to an Input/Output Module), to enable the alarm function of the alarm panel a properly sized (wattage), 50Ω to 400Ω resistor must be connected between terminals CNT-SIG and CNT-GND. If this is not done, the Dual Alarm Relay Module will not alarm in the event of a detected gas leak. Connecting to a Novar system The RGLAP is typically connected to a Novar 8IM Module, or other input/output module. Connect TB1 terminals 6 (Signal), and 7 (Ground) in the RGLAP (see Figure 32) to the 8IM module sensor input field termination block. There are 8 screw terminals; the signal wire is to be connected to the positive terminal and ground to the negative terminal on the 8IM module. Connecting to a third party system The RGLAP may be connected to an input/output device from other third party suppliers designed to accept a 4mA-20mA signal. Connect TB1 terminals 6 (Signal) and 7 (Ground) in the RGLAP connect to the Third party input/output module as specified by the manufacture. The Novar Refrigerant Leak Detection System can be monitored by any other manufacturer’s control equipment using the normally open dry relay contacts provided in the RGLAP. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 34 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT NOTE! In the event that offsite monitoring will not being utilized (not connected to an Input/Output Module), to enable the alarm function of the alarm panel a properly sized (wattage), 50Ω to 400Ω resistor must be connected between terminals CNT-SIG and CNT-GND. If this is not done, the Dual Alarm Relay Module will not alarm in the event of a detected gas leak. Figure 32. Contactor Panel Manning AirScan™IR NOTE! Nearly all start-up problems are due to improper wiring or monitor configuration. Please follow these guide-lines carefully. Always use three conductors, insulated, stranded, shielded copper cable. Use only three conductor cable, not two cables of two conductor wire. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 35 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Do not pull sensor wiring with AC power cables. This will cause electrical interference. Be sure there are no breaks or splices in sensor wiring runs. If cable runs cannot be made without a splice, all connections must be soldered. Soldering should be done using a rosin flux to tie the connecting ends of sensor wires to ensure a positive and long-lasting contact. Ground the shield at the main control panel. Connect the shield wire in the sensor terminal block labeled shield. Tape all exposed shield wire at the sensor to insulate it from the enclosure. All penetrations into a refrigerated room should be sealed to prevent condensate from forming in the conduit and dripping into the sensor enclosure. Make drip loops for cables going into sensor housings. Follow the special mounting instructions on the enclosure (…This End Up). NOTE! Circuit board mounted sensor provides a linear 4/20 mA output. Monitoring equipment may have a maximum input impedance of 500 ohms. Cable Recommendation: Use #18/3 (Belden #8770) for cable runs up to 200 feet. Use #16/3 (Belden #8618) for cable runs up to 1,000 feet. Use only the existing punched holes for connections to the sensor. Connection to RGLAP: The sensor wires are connected to terminal block 1 (TB-1 Figure 33) on terminals 8 (signal), 9 (24V) and 10 (Ground) NOTE! Allow the sensor to operate for 12 hours with the enclosure sealed prior to testing the sensors. This will give the sensor time to reach thermal equilibrium to the external and internal temperatures while in operation. Because sensors are normally located at a distance from the main unit, the test time required and accuracy of the response checks will be improved if two people perform the start-up procedures and use radio contact. To avoid possible activation of the H/S both internal and remote do not connect the signal wire during this period. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 36 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Figure 33. Wiring Remote Horn/Strobe The Horn/strobe can be wired (Figure 34) using #12 to #18 AWG. The remote horn/strobe is connected to the RGLAP on terminal block 1 (TB1) on terminals 11 (24V), 12 (Ground). Figure 34. Terminals RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 37 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Checking Installation Manning AirScan™ IR NOTE! Before applying power, make a final check of all wiring for continuity, shorts, grounds, etc. It is usually best to disconnect external alarms and other equipment from the sensor until the initial start-up procedures are completed. For detail in verifying proper operation of the Manning AirScan™ IR sensor please reference section 3 of the Honeywell Installation and Instruction manual Manning AirScan™IR Refrigerant Sensor 19546 AirScan™-IR-com RGLAP HORN/STROBE 1. 2. 3. 4. Apply 120 VAC Verify the 120 VAC lamp is lit. Verify the 24 VDC lamp is lit Exposes the sensor to the recommended about of gas that is being monitored per the Calibration manual (Refer to the AirScan Calibration manual) 5. Verify that the RGLAP responses causing appropriate alarm function (Horn/Strobe active and front panel alarm lamp is lit). 6. Allow alarm to clear before leaving Recommended Gas Alarm Settings User Configuration Settings Only the Dual Relay Module is capable of configuration. The user can select one of two set point adjustments (left position: 33%/100% full scale, right position: 50%/100% full scale). Factory Defaults The Dual Relay Module is factory pre-set for 33%/100% set point trip levels. The gas sensor has been calibrated at an altitude of 1,000 ft. above sea level. For installations where the altitude is greater than 3,500 ft. above RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 38 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT sea level, it is necessary to recalibrate the sensor “span” during the initial setup for more accuracy and reliability. Calibration is accomplished by using a Manning “CK” Calibration Kit for the specific gas to be detected. For information on Calibration kits please refer to the Manning Calibration Kit Instruction and Calibration Manual. Maintenance Manning AirScan™ IR Expose each sensor to test gases monthly to verify that the sensor has a normal response. This will also check the alarm lights and relay action of the monitoring equipment. NOTE! It is essential that signal voltages be taken and logged on a consistent basis at least monthly. Periodically, sensors should be exposed to refrigerant sample and the results logged. For proper operation it is essential that the test and calibration schedule be adhered to. Honeywell Analytics recommends the following maintenance schedule: Calibration should be performed with certified calibration gas every six months. Calibration kits are available from Honeywell Analytics. All tests and calibrations must be logged. It is highly recommended that certified calibration gas be used every six months. NOTE: For information on Calibration kits please refer to the Manning Calibration Kit Instruction and Calibration Manual. Interchangeability The 404a and 407a gas sensors are interchangeable with any RGLAP, provided it is used for monitoring the appropriate refrigerant gas. Refrigerant Gas Leak Alarm Panel RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 39 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Only the AC fuse is serviceable. A Replacement fuse will be included with each panel. The Dual Relay Module and Indoor Horn/Strobe is also field replaceable. All other hardware failures will require panel replacement. Outdoor Horn/Strobe No user serviceable parts. Failures will require Horn/Strobe replacement. RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 40 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Model & Part Numbers The part numbers below should be used to order Novar parts. OS/ Part No. LKDT-404A-KIT-1 LKDT-407A-KIT-1 LKDT-PNL-1 815003000 M-700071 P2WHK-P LKDT-BATT-BCKP-KIT P2WH-P BAT-12260-M M-700124 Product 404a Refrigeration Leak Detector Panel Kit 407a Refrigeration Leak Detector Panel Kit Refrigeration Leak Alarm Panel (no sensor-spare part) 404A Refrigerant Sensor 407A Refrigerant Sensor Horn/Strobe, 24 VDC, Outdoor w/Back Box, White Battery Back-up Unit w/Power Supply, Battery Cabinet, Trouble Buzzer Assembly and (2) BAT-12260 Sealed Lead-Acid Batteries Horn/Strobe, 24 VDC, Indoor w/o Back Box, White (spare part) Battery, 12 VDC, 26 AHR, Sealed Lead Acid (spare part) Dual Relay Module (spare part) RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 41 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT Regulatory Compliance Refrigerant Gas Leak Alarm Panel: UL/ULC: UL-508A CE CE CE marking acc. to 2004/108/EG and 2006/95/EG UL UL 508 (Listed, File E197259), UL 60950 (Recognized, File E151273), NEC Class 2 for 6EP13321SH42 FM Class I, Division 2, Groups A,B,C,D, T4 GL Approval for shipbuilding to Germanischer Lloyd ABS Approval for shipbuilding to American Bureau of Shipping for 6EP1322-1SH02 und 6EP1332-1SH42 ATEX ATEX94/9/EC Kat.3;Ex, nA IIC T3 UL 1638 (strobe) and UL 464 (horn) UL Listed: 1638 (strobe) 464 (horn) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) FM Approved: 3023572 MEA Approved: MEA452-05-E State of California State Fire Marshall: 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) N/A UL 1638 (strobe) and UL 464 (horn) UL Listed: 1638 (strobe) 464 (horn) 24VDC Supply Horn/Strobe Alarm: Manning AirScanTM IR Refrigerant Sensor System Sensor Outdoor Horn/Strobe RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 42 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) FM Approved: 3023572 MEA Approved: MEA452-05-E State of California State Fire Marshall: 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) UL Recognized Components: files MH19884 (B & B Battery), MH20567 (UPG, previously Jolt), MH20845 (Power-Sonic). Battery Backup Panel: BAT-12260 Note: The listings and approvals below apply to BAT Series Batteries. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. CHG-75 Battery Charger UL Listed S1287 MEA 297-01-E California State Fire Marshal 7315-0075:201 (power units) UL Listed Piezoelectric Buzzer RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 43 Part # LKDT-PNL-1; LKDT-BATT-BCKP-KIT The material in this document is for information purposes only. The content and the product it describes are subject to change without notice. Novar makes no representations or warranties with respect to this document. In no event shall Novar be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document. No part of this document may be reproduced in any form or by any means without prior written permission from Novar. Copyright © 2011 by Honeywell International, Inc.. All Rights Reserved. Novar 6060 Rockside Woods Blvd., Cleveland, OH 44131 Phone: 1.800.348.1235 www.novar.com RLDPK_INS 08/10/2011 For the latest technical documentation, visit www.novar.com/manuals 44