International District Energy Association’s 24th Annual Campus Energy Conference Presented Presentedby: by: Massachusetts Institute Technology RMFof Engineering, Inc. & RMF Engineering, Inc. 21 MW Cogeneration System 6 Boilers, 556,000 PPH 14 Chillers, 33,800 Tons 2 Satellite Plants Chartered in 1861 168 acres, 100 Buildings Electrical Demand of 27 MW Majority of Campus is Served from the Central Utility Plant Background Information: MIT was informed of a significant reduction in the utility company’s available fault current levels MIT’s electrical system is well maintained and well documented A Campus-Wide Arc Flash Analysis was commissioned to maintain OSHA compliance, update the safety program, and provide warning labels on equipment Air Becomes the Conductor 35,000°F Arc Temperature Molten Metal > 1800°F Hot Air > 500°F Intense Pressure > 2000 lb/psf Sound Waves > 140db Shrapnel > 740 mph Intense Light www.osha.gov - Safety Training for the Focus Four Hazards in the Construction Industry Compliments of Salisbury Electrical Safety L.L.C. Dust, Impurities, Corrosion, Condensation, Animals Spark Discharge from: - Accidental Touching - Dropping Tools Over-voltages Across Narrow Gaps Failure of Insulating Materials Equipment Failure Majority of Electrical Injuries are Burns (~80%), Not Shocks Arc Flash Hazards Must be Identified as Part of the Employer’s Safety Program (OSHA / NFPA 70E) NFPA 70E Currently Allows Two Methods of Arc Flash Hazard Analysis: - Incident Energy Calculations – Recommended Method - Hazard Risk Category (HRC) Tables – Limited Application, Prone to Misinterpretation Site Specific Incident Energy (Arc Flash) Calculations Will Soon Be A Requirement of NFPA 70E IEEE Std 1584-2002 IEEE Guide for Performing Arc-Flash Hazard Calculations Enforced by OSHA Specifies Requirements for Employer’s Safety Program Empirically Derived Model Based on Statistical Analysis and Curve Fitting Programs Extensive Test Data Gathered from Several Laboratories Provides Incident Energy Equations for use by Software Manufacturers Includes Incident Energy Equations for 208V – 15kV, Ibf = 700A – 106kA Includes Incident Energy Equations for 600V and Below (Conservative) References IEEE Std 1584 System Conditions - Available Short-Circuit Current - X/R Ratio - Prefault Voltages - Loading Protective Devices (Time-Current Characteristics) - The First Upstream Device - The Second Upstream Device System Grounding Electrodes and Potential Arc Lengths - Spacing Between Phases - Spacing Between Phases and Ground - Orientation - Insulated Versus Noninsulated Size and Shape of Enclosures Atmosphere Conditions - Ambient Temperature - Barometric Pressure - Humidity Arc Conditions - Randomness of the Arc - Interruption of the Arc - Arc Plasma Characteristics - Other Unidentified Factors Dissipation of Energy - Heat - Latent Heat of Vaporization - Light - Sound - Pressure Wave Other Miscellaneous Factors Electrical Arcing Phenomena – R.A. Ammerman, P.K. Sen, J.P. Nelson 13.8kV 2.4kV 4.16kV 480V Time OC Electromech. Bus Diff. Directional OC Solid State Line Diff. Electronic Fuses Motor Protect. Extensive Equipment Survey (Access Database) Record Nameplate Data Record all Overcurrent Protective Device Types and Settings Build a Power System Software Model Run Baseline System Studies Short Circuit Coordination Load Flow (Voltage Drop, Circuit Capacity) Arc Flash Identify and Analyze Hazards Fault Duty Issues (None Found) Arc Flash Hazards (Several Found) Adjust Overcurrent Devices to Reduce Arc Flash Hazards Incident Energy at Each Bus - Existing Conditions 80 Reactors In Service Reactors Bypassed 70 Incident Energy (cal/cm2) 60 50 40 cal/cm2 (HRC 4) High Risk of Physical Trauma Above This Line 40 30 8 cal/cm2 (HRC 2) Target Conditions Below This Line 20 10 0 13.8kV 4.16kV 2.4kV Bus Name 480V Incident Energy at Each Bus - Recommended Settings 80 Generator Off Generator Running 70 Incident Energy (Cal/cm2) 60 50 40 30 20 10 0 13.8kV 4.16kV 2.4kV Bus Name 480V 480V Switchgear Available Primary Fault Current =12,000A Available Primary Fault Current = 13,700A %Z = 6.36 %Z = 6.21 Identical Settings Secondary Fault Current = 22,700A Incident Energy = 580 cal/cm2 Extremely Dangerous Motor Contribution = 3,300A Motor Contribution = 3,000A Secondary Fault Current = 24,400a Incident Energy = 16 cal/cm2 Workable with Adequate PPE CURRENT IN AMPERES CURRENT IN AMPERES 1000 1000 85% Arcing Current 11,030 Amps 85% Arcing Current 11,739 Amps 100% Arcing Current 12,976 Amps 100 100% Arcing Current 13,810 Ampus 100 Breaker Trips in 15.9s IE = 580 cal/cm2 48XAM - Phase NOT WORKABLE EXTREMELY DANGEROUS 1 10 48XBM - Phase Breaker Trips in 0.33s IE = 16 cal/cm2 WORKABLE USING ADEQUATE PPE 1 0.10 0.10 27484 A 26031 A 0.01 0.01 1K 10K 48XAM.tcc Ref. Voltage: 480V Current in Amps x 1 100K 1K 10K 48XBM.tcc Ref. Voltage: 480V Current in Amps x 1 100K TIME IN SECONDS TIME IN SECONDS 10 Design Factors - Divide and Conquer (Modular Design) – Use multiple, smaller - - transformers/substations instead of one big one. Segregate “process” loads into modular units to facilitate shutdowns. Electric Room Design – Provide ample space in front and in back of switchgear. Equipment – Use metal-clad switchgear, specify insulated bus, and utilize remote racking mechanisms. Provide infra-red windows for “closed door” thermo scans. Arc resistant switchgear is an option. Overcurrent Protection - Apply differential relaying schemes (for MV) and zone-interlocking (for LV). Provide arc flash maintenance settings inside protective relays (for MV), and arc flash maintenance switches (for LV). Apply Impedance-Grounding Techniques – Stop the arc before it starts Operations & Maintenance Considerations - Update arc flash studies and warning labels every 5 years (NFPA 70E requirement) - Provide a comprehensive safety program (employer) Expected Phase – Ground Fault Current Flow Central Utility Plant Cogen Plant 13.8kV, 30MVA 791Ω, 10A 10 Sec, Neutral Grounding Resistor 10A Utility Distribution Substation Intertie Breaker XFMR Secondary Breaker Closed Closed Closed Closed Closed Closed Closed Closed 10,000A Closed Ground Fault Current Contribution = 10A 10A Substation XFMR 115kV – 13.8kV, 34MVA 10,000A Ground Fault Current Contribution = 10,000A XFMR Primary Breaker Actual Phase – Ground Fault Current Flow Central Utility Plant Intertie Cogen Plant Breaker 13.8kV, 30MVA 850A 850A 1700A 791Ω, 10A 10 Sec, Neutral Grounding Resistor Utility Distribution Substation XFMR Secondary Breaker Closed Closed Closed Closed Substation XFMR 115kV – 13.8kV, 34MVA 850A 850A XFMR Primary Breaker Closed Closed 10,000A Closed 1700A Ground Fault Current Contribution = 1700A Closed 10,000A 11,700A 11,700A Ground Fault Current Contribution = 10,000A Closed Actual Phase – Ground Fault Current Flow Central Utility Plant Intertie Cogen Plant Breaker 13.8kV, 30MVA 1,500A 3,000A 791Ω, 10A 10 Sec, Neutral Grounding Resistor Utility Distribution Substation XFMR Secondary Breaker 1,500A Closed Closed Closed Closed Substation XFMR 115kV – 13.8kV, 34MVA 1,500A 1,500A 3,000A Closed 1,500A 4,500A Open Open 1,500A Closed XFMR Primary Breaker 4,500A Open Actual Phase – Ground Fault Current Flow Central Utility Plant Cogen Plant 13.8kV, 30MVA Utility Distribution Substation XFMR Secondary Breaker Intertie Breaker Substation XFMR 115kV – 13.8kV, 34MVA XFMR Primary Breaker Open Open 10A Open Open 791Ω, 10A 10 Sec, Neutral Grounding Resistor Open Open 10A 10A Flash Protection Boundary - Limited Approach Boundary - Minimum Distance from Live Parts for “Unqualified Persons” Restricted Approach Boundary - Incident Energy ≤ 1.2 cal/cm2 outside this boundary To be Entered by “Qualified Persons with Documented Plan and Appropriate PPE Prohibited Approach Boundary - Considered the Same as Making Contact with Live Parts Presented By: Richard Lucas Ben Standish MIT - Utilities (617) 324-6801 rlucas@plant.mit.edu RMF Engineering, Inc. (800) 938-5760 bstandis@rmf.com