FOR N5 EMERGENCY UNITS With Cold Weather and Self

advertisement
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
FOR N5 EMERGENCY UNITS
With Cold Weather and
Self-Diagnostic/Self-Test Option
FOR N5 EMERGENCY UNITS
With Cold Weather and
Self-Diagnostic/Self-Test Option
IMPORTANT SAFEGUARDS:
IMPORTANT SAFEGUARDS:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
INSTRUCTIONS FOR SELF-DIAGNOSTICS/SELF-TESTING FUNCTION
1. To avoid the possibility of electrical shock, turn off power supply before installation or servicing.
2. Review the diagrams thoroughly before installation.
3. All electrical connections must be in accordance with the National Electric and local codes. A qualified electrician should do all the work.
4. Do not let power supply cords touch hot surfaces.
5. Do not mount near gas or electric heaters.
6. Equipment should be mounted in loca
tions where it will not be readily subject to tampering by unauthorized personnel.
7. The use of accessory equipment not recommended by the original manufacturer may cause an unsafe condition.
8. Do not use this equipment for other than intended use.
9. All servicing should be performed by qualified personnel only.
When using electrical equipment, always adhere to basic safety precautions
including the following:
1. Install Emergency Lighting according to Installation Instruction sheet.
2. As soon as AC power is supplied to fixture, the unit will automatically initiate a Self-Test
and Self-Diagnostic test as follows:
(1) Verifies battery disconnection, charger failure, lamp failure and transformer failure at every 5 seconds.
(2) One-minute Self-Testing (battery discharging test) every month.
(3) 30 minutes Self-Testing (battery discharging test) on the 6th month of the year.
(4) 90 minutes Self-Testing (battery discharging test) on the 12th month of the year.
3. Dual color LED lamp shows the following status:
(1) Green color (Operating Status)
ON/Ready
Blinking: Testing
(2) Red color (Service Alert)
(3) Service Alert LED Code (Red color LED lamp)
One blink ON/pause
Two blinks ON/pause (4 seconds)
Battery is shorted or battery voltage drops below the acceptable value
Three blinks ON/pause(4 seconds)
Charger board circuit fault
Four blinks ON/pause (4 seconds)
Power input fault
Five blinks ON/pause (4 seconds)
Emergency lamp fault
(4 seconds)
Battery is not connected
CAUTION:
Press test button once
(within 2 seconds)
1 minute test
Press test button twice
(within 2 seconds)
5 minutes test
Press test button 3 times
(within 2 seconds)
30 minutes test
Press test button 4 times
(within 2 seconds)
90 minutes test
1. Remove the top cover from back plate with a screwdriver. (See Figure 1)
2. Remove the knock out hole in the center of the back plate. Remove knock out slots on the back plate that corresponds to the size of the junction box holes to be used.
3. Feed AC supply leads through the center hole in the back plate, then make the proper electrical connections. See electrical connection section in Figure 2 for electrical connections. Cap off unused hot lead.
4. Mount back plate to junction box with a
#8-32X1” screw provided. (See Figure 2)
5. Attach the battery connector to the circuit
board.
6. Snap top cover to back plate.
7. Restore power and press the test button.
The battery powered bulbs will come on and the AC light will turn off.
MOUNTING WITH SURFACE
CONDUIT FEED
1. Remove the top cover from back plate with a screwdriver. (See Figure 1)
2. Unscrew the plug from top of the back plate.
3. Secure the back plate screw on the conduit. (See Figure 3)
4. Make the proper supply lead connections. See electrical connections section and Figure 2 for electrical connections.
Cap off unused hot lead.
5. Attach the battery connector to the circuit board.
6. Snap top cover to back plate.
7. Restore power and press the test button. The battery powered bulbs will come on and the AC light will turn off.
Figure 1
OPENING TOP COVER
ELECTRICAL CONNECTIONS
4. For manual test, press test button as follows:
WALL MOUNTING
NOTE: Allow battery to charge for 72 hours
before first use.
After solving the fault of emergency equipment, please press test button for 2 seconds without release,
then LED lamp will show green color.
When using electrical equipment, always adhere to basic safety precautions
including the following:
1. Verify the power is off before installation.
2. Connect ground (green) lead to suitable ground.
3. Connect fixture common (white) lead to supply common (white) lead.
4. Determine supply voltage for fixture. Connect hot lead (black for 120V or orange for 277V) to supply hot lead. Cap unused fixture lead with wire nut.
LAMP REPLACEMENT
1.
2.
WARRANTY
Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group’s obligation
is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been
granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty
is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty
of merchantability. Also, there are no warranties which extend beyond the description of the product on the company’s literature setting forth
terms of sale.
Insert screwdriver into the slots between the tip cover and the back plate and then push gently to remove the front cover that contains the lens.
Install new lamp G4 Base 6V-6W Xenon.
Product Services Phone (888) 387-2212
SAVE THESE INSTRUCTIONS
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
Rev 07/08
P2481
pg 4 of 4
©2016 Acuity Brands Lighting, Inc.
Rev 07/08
P2481
pg 1 of 4
INSTALLATION INSTRUCTIONS
FOR N5 EMERGENCY UNITS
With Cold Weather and
Self-Diagnostic/Self-Test Option
INSTALLATION INSTRUCTIONS
FOR N5 EMERGENCY UNITS
With Cold Weather and
Self-Diagnostic/Self-Test Option
IMPORTANT SAFEGUARDS:
Figure 2
WALL MOUNTING
When using electrical equipment, always adhere to basic safety precautions
including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
INSTRUCTION FOR ELECTRICAL
CIRCUIT CONNECTION FOR
HEAT PAD
1. 2. For 120V AC input connection, insert short circuit connector in female connector A marked “120V JP2”. (See Figure 4)
For 277V AC input connection, insert short circuit connector in female connector B marked “277V JP1”. (See Figure 5)
Figure 4
CIRCUIT CONNECTION FOR 120VAC INPUT
Figure 3
CEILING MOUNTING WITH
SURFACE MOUNTED CONDUIT FEED
Figure 5
CIRCUIT CONNECTION FOR 277VAC INPUT
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
Rev 07/08
P2481
pg 2 of 4
©2016 Acuity Brands Lighting, Inc.
Rev 07/08
P2481
pg 3 of 4
Download